VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Samsung DVM S Water HR outdoor units over BACnet: type, operation mode and status, error code, capacity, compressor target, order and current frequencies, temperatures, compressor current, EEV positions and compressor and valve states, plus water temperature, flow control and flow switch (54 objects). Monitoring only.

This page lists 54 BACnet objects for the CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
54 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Samsung DVM S Water BACnet, CoolMasterNet Samsung, DVM-S Water HR
Brands covered
Samsung
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 54 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Samsung outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the outdoor block's VA and trend water temperature, pressures, compressor frequency and error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
PIV 257OpModeOperation mode codeRead
PIV 258OpStatOperation status codeRead
PIV 263CurFreq1Compressor 1 current frequency, HzRead
AI 276WtrTWater temperature, °CRead
AI 267HiPrsHigh pressure, kg/cm2Read
AI 269LoPrsLow pressure, kg/cm2Read
AI 271DisT1Compressor 1 discharge temperature, °CRead
PIV 259ErrCodeError codeRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

54 of 54 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
PIVmin257OpModeOperation ModeRead
PIVmin258OpStatOperation StatusRead
PIVmin259ErrCodeError CodeRead
PIV260CapCapacityhpRead
PIV261TrgFreq1Target Frequency1HzRead
PIV262OrdFreq1Order Frequency1HzRead
PIVmin263CurFreq1Current Frequency1HzRead
PIV264TrgFreq2Target Frequency2HzRead
PIV265OrdFreq2Order Frequency2HzRead
PIV266CurFreq2Current Frequency2HzRead
AImin267HiPrsHigh Pressurekg/cm2Read
IV268SatTPdSaturated T_Pd°CRead
AImin269LoPrsLow Pressurekg/cm2Read
IV270SatTPsSaturated T_Ps°CRead
AImin271DisT1Discharge1°CRead
AI272DisT2Discharge2°CRead
PIV273TstOpTest Operation(UP)Read
AI274CompTop1Comp Top1°CRead
AI275CompTop2Comp Top2°CRead
AImin276WtrTWater temperature°CRead
AI277CompCur1Compressor current1ARead
AI278CompCur2Compressor current2ARead
AI279IPM1TIPM1 temperature°CRead
AI280IPM2TIPM2 temperature°CRead
AI281CondOutTCondOut temperature°CRead
AI282LiqTubTLiquid tube temperature°CRead
AI283Suct1TSuction1 temperature°CRead
AI284Suct2TSuction2 temperature°CRead
PIV285MainEEVMain EEVRead
PIV286EviEEVEVI EEVRead
AI287EviInEVI IN°CRead
AI288EviOutEVI OUT°CRead
AI289CtrlBxTControl Box Temperature°CRead
AI290FlwCtrlFlow ControlRead
BI291Comp1Comp1Read
BI292Comp2Comp2Read
BI2934Way4Way valveRead
BI294HotGas1Hot Gas Bypass1Read
BI295HotGas2Hot Gas Bypass2Read
BI296MainCoolMain CoolingRead
BI297EEVVlvEEV ValveRead
BI298EviSol1EVI Solenoid Valve1Read
BI299EviSol2EVI Solenoid Valve2Read
BI300EviBpsEVI BypassRead
BI301CCH1Comp Coil Heater1Read
BI302CCH2Comp Coil Heater2Read
BI303LiqTubLiquid tubeRead
BI304HotGasChrgHot Gas ChargingRead
BI305FlwSwFlow SwitchRead
BI3062Way2WayRead
BI307PumpOutPump OutRead
BI308DcFanDC FanRead
CSV309SNSerial NumberRead
Object ID lookup: CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects have?

This list has 54 BACnet objects: 19 analog inputs, 18 binary inputs, 2 characterstring values, 2 integer values, 13 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects?

Start with PIV 257 OpMode (Operation mode code); PIV 258 OpStat (Operation status code); PIV 263 CurFreq1 (Compressor 1 current frequency, Hz); AI 276 WtrT (Water temperature, °C); AI 267 HiPrs (High pressure, kg/cm2); AI 269 LoPrs (Low pressure, kg/cm2); AI 271 DisT1 (Compressor 1 discharge temperature, °C); PIV 259 ErrCode (Error code).

How do I enable BMS control of the CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.