  4. CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects

VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Mitsubishi Electric City Multi PUHV-P CM-E outdoor units over BACnet: type, control and operation mode, compressor and fan frequencies, total cooling and heating capacity, LEV positions, compressor currents and bus voltage, 63HS/63LS pressures, thermistor, condensing and evaporating temperatures, operation status and OC/OS attribute, plus subcooling and superheat values and box temperature (54 objects). Monitoring only.

This page lists 54 BACnet objects for the CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
54 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PUHV-P CM-E
Brands covered
Mitsubishi Electric
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 54 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Mitsubishi Electric equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operation mode, compressor frequency and pressures.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
PIV 258OpeMOperation mode codeRead
PIV 280OpeSOperation status codeRead
BI 306CompOnCompressor onRead
PIV 260F1Compressor 1 frequency, HzRead
AI 27163HS1High pressure, kg/cm2Read
AI 27263LSLow pressure, kg/cm2Read
AI 287TcCondensing temperature, °CRead
AI 288TeEvaporating temperature, °CRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

54 of 54 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
PIV257CtrlMControl ModeRead
PIVmin258OpeMOperation ModeRead
IV259F(Hz)All temporary frequenciesHzRead
PIVmin260F1Temporary frequency of No.1 COMPHzRead
PIV261FocTemporary frequencyHzRead
PIV262FANFan outputHzRead
IV263QjCTotal capacity CoolRead
IV264QjHTotal capacity HeatRead
PIV265LEV1LEV1 Linear expansion valveplsRead
AI266IdcDirect currentARead
AI267IuU-Phase current effective valueARead
AI268IwW-Phase current effective valueARead
PIV269ALALRead
AI270VdcCOMP bus voltageVRead
AImin27163HS163HS1 Pressure sensorkg/cm2Read
AImin27263LS63LS Pressure sensorkg/cm2Read
AI273TH2Thermistor 2°CRead
AI274TH3Thermistor 3°CRead
AI275TH4Thermistor 4°CRead
AI276TH6Inlet pipe temperature of the heat exchanger°CRead
AI277TH7Thermistor 7°CRead
AI278FAN-VerFan1 SW versionRead
PIV279SaveCapacity save signal%Read
PIVmin280OpeSOperation StatusRead
PIV281AttrAttribute (OC/OS identification)Read
PIV282M-NetSupUnM-NET supply unitRead
PIV283StrtUpUnStart-up unitRead
AI284SCoHeat exchanger outlet subcooling°CRead
AI285SCcCoil outlet subcooling°CRead
AI286SHbCoil bypass outlet superheat°CRead
AImin287TcCondensing temperature°CRead
AImin288TeEvaporating temperature°CRead
AI289THHSThermistor 9°CRead
AI290THBOXThermistor in box°CRead
IV291AKHeat exchanger capacityRead
AI292RotTmRotation timerRead
BI293SV1aSV1(A)/SV1aRead
BI294DmndDemandRead
BI295Dmnd2Demand2Read
BI296NgtNightRead
BI297Ngt2Night2Read
BI298SnowSnowRead
BI29921S4a21S4aRead
BI30021S4b21S4bRead
BI301SV5bSV5bRead
BI302PwrPower source frequencyRead
BI303WMWMRead
BI304RepRepeater outputRead
BI30572C72CRead
BImin306CompOnComp ONRead
BI307M-NetSupM-NET supplyRead
BI308CH11CH11Read
BI309INV-FAN1INV-FAN1Read
Object ID lookup: CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects have?

This list has 54 BACnet objects: 20 analog inputs, 17 binary inputs, 1 characterstring value, 4 integer values, 12 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects?

Start with PIV 258 OpeM (Operation mode code); PIV 280 OpeS (Operation status code); BI 306 CompOn (Compressor on); PIV 260 F1 (Compressor 1 frequency, Hz); AI 271 63HS1 (High pressure, kg/cm2); AI 272 63LS (Low pressure, kg/cm2); AI 287 Tc (Condensing temperature, °C); AI 288 Te (Evaporating temperature, °C).

How do I enable BMS control of the CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.