VRF outdoor system monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L) BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish system-level service data for Daikin VRV-L (RSXYP5-10L) outdoor systems over BACnet: type, AirNet address, error code, ambient, heat exchanger, discharge, suction, evaporating, condensing and receiver temperatures, inverter frequency, current and temperature, EV opening, operating states, compressor, heater and valve states, retry, drooping-control and protection flags, HP and fan step (47 objects). Monitoring only.

This page lists 47 BACnet objects for the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L)
Equipment
VRF outdoor system monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
47 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-L, RSXYP5-10L
Brands covered
Daikin
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 47 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L)

Integration in brief

Use these objects to monitor Daikin outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operating states, temperatures, compressor data and the error state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 270CoolCoolingRead
BI 271HeatHeatingRead
BI 273TstatOnThermostat onRead
BI 275DfrstDefrost activeRead
PIV 266InvFrqInverter frequency, HzRead
IV 259AmbTAmbient temperature, °CRead
IV 264EvTEvaporating temperature, °CRead
IV 265CndTCondensing temperature, °CRead
CSV 258ErrCodeSystem error codeRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

47 of 47 shown
Type
Binary
Show
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L) BACnet Points List
DescriptionStates
CSV256TypeOutdoor System Type NameRead
PIV257AirNetAirNet Addr.Read
CSVmin258ErrCodeError codeRead
IVmin259AmbTAmbient temperature°CRead
IV260HexTHeat exchanger temp.°CRead
PIV261DschTInvDisch. temp.(INV)°CRead
PIV262DschTStdDisch. temp.(STD)°CRead
IV263SuctTSuction Temperature°CRead
IVmin264EvTEvaporating Temperature°CRead
IVmin265CndTCondensing Temperature°CRead
PIVmin266InvFrqInverter frequencyHzRead
PIV267InvCurInverter currentARead
PIV268InvTInverter temp.°CRead
PIV269EVOpEV openingplsRead
BImin270CoolCoolingRead
BImin271HeatHeatingRead
BI272VentVentilationRead
BImin273TstatOnThermostat ONRead
BI274ResrtStbyRestart stand-byRead
BImin275DfrstDefrostRead
BI276StrtOpStartup operationRead
BI277OiRtrnOil returnRead
BI278OiEqOpOil equalizing ope.Read
BI279CcH1CH1:Crankcase HeaterRead
BI280CcH2CH2:Crankcase HeaterRead
BI281RcvrReceiversRead
BI282Comp1InvCompressor1(INV)Read
BI283Comp2StdCompressor2(STD)Read
BI284HotGasBypHot gas bypassRead
BI2854WayVlv4-way valveRead
BI286HiPRtryHigh pressure retryRead
BI287LoPRtryLow pressure retryRead
BI288DschPipRtryDisch. pipe retryRead
BI289InvStbyINV stand-byRead
BI290HiPDroCtlHigh pres. drooping cntl.Read
BI291LoPDroCtlLow pres. drooping cntl.Read
BI292DschDroCtlDisch. pipe drooping cntl.Read
BI293InvCurDroCtlINV current drooping cntl.Read
BI294ProtHt1Protect (Heating) 1Read
BI295ProtHt2Protect (Heating) 2Read
BI296ProtHt3Protect (Heating) 3Read
BI297ProtCl1Protect (Cooling) 1Read
BI298ProtCl2Protect (Cooling) 2Read
BI299ProtCl3Protect (Cooling) 3Read
PIV300HPHPhpRead
IV301RcvrTReceiver temp°CRead
PIV302FanStpFan stepRead
Object ID lookup: CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L) point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L)

How many BACnet points does the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L) have?

This list has 47 BACnet objects: 30 binary inputs, 2 characterstring values, 6 integer values, 9 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L) BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L)?

Start with BI 270 Cool (Cooling); BI 271 Heat (Heating); BI 273 TstatOn (Thermostat on); BI 275 Dfrst (Defrost active); PIV 266 InvFrq (Inverter frequency, Hz); IV 259 AmbT (Ambient temperature, °C); IV 264 EvT (Evaporating temperature, °C); IV 265 CndT (Condensing temperature, °C); CSV 258 ErrCode (System error code).

How do I enable BMS control of the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L)?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.