VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Toshiba SMMSe header outdoor units over BACnet: unit HP, compressor speeds, fan mode, high and low pressure, discharge, heat exchanger, liquid, suction, outdoor and oil temperatures, check codes, compressor currents, PMV positions and valve states, plus IGBT temperatures, heaters and forced-stop flags (57 objects). Monitoring only.

This page lists 57 BACnet objects for the CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
57 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Toshiba SMMSe BACnet, Toshiba VRF BACnet, CoolMasterNet Toshiba, SMMSe Header
Brands covered
Toshiba
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 57 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Toshiba outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the header unit's VA and trend pressures, compressor speed and check codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 259Comp(1)Compressor 1 speed, HzRead
AI 278TOOutdoor air temperature, °CRead
AI 263Pd[psi]High pressure, psiRead
AI 264Ps[psi]Low pressure, psiRead
AI 265TD1Discharge temperature 1, °CRead
PIV 287CheckCd1Check (error) code 1Read

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

57 of 57 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
PIV257StPriStarting PriorityRead
PIV258HPOutdoor Unit HPRead
AImin259Comp(1)Comp(1) HzHzRead
AI260Comp(2)Comp(2) HzHzRead
IV261FanModeOutdoor Unit FanModeRead
BI2624wayVlv4way ValveRead
AImin263Pd[psi]Pd:High PressurepsiRead
AImin264Ps[psi]Ps:Low PressurepsiRead
AImin265TD1TD1 Discharge Temp°CRead
AI266TD2TD2 Discharge Temp°CRead
AI267TE1TE1:Heat Exchanger Temp°CRead
AI268TE2TE2:Heat Exchanger Temp°CRead
AI269TL1TL1:Liquid Pipe Temp°CRead
AI270TL2TL2:Liquid Pipe Temp°CRead
AI271TL3TL3:Liquid Pipe Temp°CRead
AI272TS1TS1:Suction Temp°CRead
AI273TS3TS3:Suction Temp°CRead
AI274TG1TG1:Gas.Temp°CRead
AI275TG2TG2:Gas.Temp°CRead
AI276TGTG:High Pressure Temp°CRead
AI277TUTU Low Pressure Temp°CRead
AImin278TOTO Outdoor Air Temp°CRead
AI279TK1TK1:Oil Temp1°CRead
AI280TK2TK2:Oil Temp2°CRead
AI281TK4TK4:Oil Temp4°CRead
AI282TK5TK5:Oil Temp5°CRead
AI283TH1TH1:Comp1 IGBT Temp°CRead
AI284TH2TH2:Comp2 IGBT Temp°CRead
AI285THF1THF1:Fan Motor1 IGBT Temp°CRead
AI286THF2THF2:Fan Motor1 IGBT Temp°CRead
PIVmin287CheckCd1Check Code1Read
PIV288CheckCd2Check Code2Read
PIV289OilLvCk1Oil Level Check1Read
PIV290OilLvCk2Oil Level Check2Read
BI291CompBUp1Comp BackUp1Read
BI292CompBUp2Comp BackUp2Read
AI293I1I1ARead
AI294I2I2ARead
IV295PMV1Pulse Motor Valve1plsRead
IV296PMV3Pulse Motor Valve3plsRead
IV297PMV4Pulse Motor Valve4plsRead
BI298SV2SV2:Hot Gas BypassRead
BI299SV3ASV3A:Oil Supply ON/OFFRead
BI300SV3BSV3B:Oil Return ON/OFFRead
BI301SV3CSV3C:Gas Pressure ON/OFFRead
BI302SV3DSV3D:Separator OpenRead
BI303SV3ESV3E:Oil Balance ON/OFFRead
BI304SV41SV41:Comp Start AssistRead
BI305SV42SV42:Comp Start AssistRead
BI306AccHeatAccumulator HeaterRead
BI307Co1HeatComp1 HeaterRead
BI308Co2HeatComp2 HeaterRead
BI309SV51SV51Read
BI310SV52SV52Read
BI311CFoStop1Comp Forced Stop1Read
BI312CFoStop2Comp Forced Stop2Read
Object ID lookup: CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects have?

This list has 57 BACnet objects: 28 analog inputs, 18 binary inputs, 1 characterstring value, 4 integer values, 6 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects?

Start with AI 259 Comp(1) (Compressor 1 speed, Hz); AI 278 TO (Outdoor air temperature, °C); AI 263 Pd[psi] (High pressure, psi); AI 264 Ps[psi] (Low pressure, psi); AI 265 TD1 (Discharge temperature 1, °C); PIV 287 CheckCd1 (Check (error) code 1).

How do I enable BMS control of the CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists