Gas-fired steam humidifier · BACnet points list

Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module BACnet points list

Updated 12 November 2026

Short answer

The NEPICSKG module gives the older SKG gas-fired humidifier a BACnet MS/TP interface (B-ASC). A common block (instances 1-99) carries humidity output, demand, room and duct humidity, setpoints, delays, PID settings, status and alarm flags and the control, operation and source selectors; each tank adds its own block (101-199 for tank 1 up to 401-499 for tank 4) with water and chimney temperatures, water level, burner demand and fan speed, timers, status flags and alarms.

This page lists 199 BACnet objects for the Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module — 115 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module
Equipment
Gas-fired steam humidifier
Equipment type
Humidifiers
BACnet objects
199 (115 writable)
Transport
BACnet MS/TP
Firmware
1.00
Default device instance
153000
Also known as
SKG, SKG3, Neptronic SKG, NEPICSKG, SKG-BACNET, SKG gas fired humidifier
Source document
Gas Fired Humidifier SKG Series - BACnet Communication Module User Guide · SKG-BACNET · rev. Rev 060803
Download CSV 199 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.

BMS integration notes: Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module

Integration in brief

For BMS demand control set MSV 1 Ctl_Mode to 3 and write AV 1 Humidity_Demand; for the internal PID set MSV 1 to 2, choose the setpoint and humidity sources (MSV 4-6) and write AV 16 and AV 2. MSV 2 turns the unit off, on or to drain. Read BI 1, AI 1 and the two summary alarms BI 4 and BI 5.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 2Operation_ModeUnit off, on or drainWrite
MV 1Ctl_ModeControl mode; 3 = demand from BACnetWrite
AV 1Humidity_DemandHumidity demand from the BMS, %Write
AV 16Ctl_SPHumidity setpoint for internal PID, %RHWrite
AV 2Room_HumidityRoom RH from the BMS (remote source)Write
BI 1Power_StatusUnit power onRead
AI 1Humidity_OutHumidifier output, %Read
BI 4Alrm_Not_CriticalNon-critical alarm, unit still runningRead
BI 5Alarm_CriticalCritical alarm, unit stoppedRead

Enable & remote start

MSV 2 Operation_Mode sets the unit off (1), on (2) or to drain (3). MSV 1 Ctl_Mode picks the demand source: 1 = analog input 1, 2 = internal PID, 3 = remote demand over BACnet.

Sensors & values from the BMS

With MSV 5 Room_Hum_Source = 2 and MSV 6 Duct_Hum_Source = 3 (remote) the BMS writes AV 2 Room_Humidity and AV 4 Duct_Humidity; MSV 4 SP_Source = 3 takes the setpoint from BACnet.

Network setup

Watch out for

Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

199 of 199 shown
Type
Access
Show
Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module BACnet Points List
DescriptionStates
AImin1Humidity_OutHumidity Output (0-100 %RH)%RHRead
AVmin1Humidity_DemandHumidity Demand (0-100 %RH)%RHWrite
AVmin2Room_HumidityRoom Humidity (0-100 %RH)%RHWrite
AV3Room_Humidity_OffRoom Humidity offset (±0-10.0 %RH)%RHWrite
AV4Duct_HumidityDuct Humidity (0-100 %RH)%RHWrite
AV5Duct_Humidity_OffDuct Humidity offset (±0-10.0 %RH)%RHWrite
AV6Outside_TempOutside Temperature (-40 - 40 °C or -40 - 104 °F)°C/°FWrite
AV7Lock_On_CapacityLock On capacity (10-100%)%Write
AV8Max_Output_LimitMaximum output limit (10-100%)%Write
AV9Drain_DelayDrain Delay (1-100Hrs)hWrite
AV10Service_DelayService Delay (1-5000Hrs)hWrite
AV11End_Season_DelayEnd of season delay (1-250Hrs)hWrite
AV12PID_Loop_KPPID Loop gain KP (0-255)Write
AV13PID_Loop_KIPID Loop gain KI (0-255)Write
AV14PID_Loop_KDPID Loop gain KD (0-255)Write
AV15Ctl_BandControl band (0-20.0% (0..200))%Write
AVmin16Ctl_SPControl set point (0-100%RH)%RHWrite
AV17Extern_SP_MinExternal setpoint minimum (0-100%RH)%RHWrite
AV18Extern_SP_MaxExternal setpoint maximum (0-100%RH)%RHWrite
AV19Duct_Hum_HiLim_SPDuct hum. high limit set point (50-100%RH)%RHWrite
AV20Min_ON_Time_FanMinimum ON time for fan (2-20 minutes)minWrite
AV21Min_H2O_TempMin. water temp. in ON mode (50-90 °C or 122-194 °F (0°C/°FWrite
AV22Antifreeze_TempAnti-freeze mode temperature (7-12 °C or 44-54 °F (0 -> Mode is°C/°FWrite
AV23Analog_Ctl_In_LoAnalog Control input Lo Limit (0-10.00VDC)VWrite
AV24Analog_Ctl_In_HiAnalog Control input Hi Limit (0-10.00VDC)VWrite
AV25Analog_Hum_In_LoAnalog Humidity input Lo Limit (0-10.00VDC)VWrite
AV26Analog_Hum_In_HiAnalog Humidity input Hi Limit (0-10.00VDC)VWrite
AV27Analog_Duct_In_LoAnalog Duct input Lo Limit (0-10.00VDC)VWrite
AV28Analog_Duct_In_HiAnalog Duct input Hi Limit (0-10.00VDC)VWrite
BImin1Power_StatusPower StatusRead0=OFF, 1=ON
BI2Humidity_DemandHumidity DemandRead0=NO, 1=YES
BI3Manual_DrainManual DrainRead0=NO, 1=YES
BImin4Alrm_Not_CriticalAlarm not critical (unit running)Read0=NO, 1=YES
BImin5Alarm_CriticalAlarm critical (unit not running)Read0=NO, 1=YES
BI6End_of_Season_DlyEnd of Season DelayRead0=NO, 1=YES
BI7Fan_Proof_StatusFan proof StatusRead0=OFF, 1=ON
BI8HiLimit_StatusHi-Limit StatusRead0=OFF, 1=ON
BI9InterlockInterlockRead0=OFF, 1=ON
BI10Thermal_Fuse_ExtThermal fuse (external 24VAC)Read0=OFF, 1=ON
BI11Thermal_Fuse_IntThermal fuse (internal 24VDC)Read0=OFF, 1=ON
BI12Interlock_In_OpenInterlock input openRead0=Normal, 1=Alarm
BI13High_Hum_In_DuctHigh humidity level in the ductRead0=Normal, 1=Alarm
BI14Input_Voltage_LowInput voltage too lowRead0=Normal, 1=Alarm
BI15Thermal_Fuse_OpenThermal Fuse open (24VAC)Read0=Normal, 1=Alarm
BI16Slave_Comm_LostComm lost with slave boardRead0=Normal, 1=Alarm
BI17Hum_Clean_StartHumidifier started cleaning periodRead0=Normal, 1=Alarm
BI18Hum_Ex_Svc_TimeHumidifier exceeded service timeRead0=Normal, 1=Alarm
BV1Temperature_UnitTemperature UnitWrite0=Celcius, 1=Fahrenheit
BV2Outside_Temp_CompOutside Temp. CompensationWrite0=OFF, 1=ON
BV3Alarm_BeepAlarm BeepWrite0=OFF, 1=ON
BV4Demand_SP_TypeDemand/Set point typeWrite0=Voltage, 1=Current
BV5Humidity_In_TypeHumidity input typeWrite0=Voltage, 1=Current
BV6HiLim_Hum_In_TypeHi-limit humidity input typeWrite0=Voltage, 1=Current
MVmin1Ctl_ModeControl ModeWrite1=Demand from analog input 1 (default), 2=Internal PID loop calculation, 3=Demand from remote communication port (e.g. BACnet)
MVmin2Operation_ModeOperation ModeWrite1=Set unit Off, 2=Set unit On, 3=Set unit in drain mode
MV3Unit_Display_LangUnit Display LanguageWrite1=English (Default), 2=French, 3=Spanish
MV4SP_SourceSetpoint SourceWrite1=Local analog input 1, 2=Local Internal digital value, 3=Remote from communication port (e.g. BACnet)
MV5Room_Hum_SourceRoom Humidity SourceRead1=Local analog input 2 (default), 2=Remote from communication port (e.g. BACnet)
MV6Duct_Hum_SourceDuct Humidity SourceWrite1=Not used, 2=Local analog input 3, 3=Remote from communication port (e.g. BACnet)
AI101Water_Temp1Water Temperature 1 (0-260 °C or 32-500 °F)°C/°FRead
AI102Chimney_Temp1Chimney Temperature 1 (0-260 °C or 32-500 °F)°C/°FRead
AI103Water_Level1Water level 1 (0-120%)%Read
AI104Burner_Demand1Burner Demand 1 (0.0 - 100.0%)%Read
AI105Op_Timer_Total1Operation Timer 1 (Total time) (1-1677215Hrs)hRead
AI106Op_Timer1Operation Timer 1 (1-5000Hrs)hRead
AI107Delay_Autodrain1Delay until Auto-drain 1 (1-100Hrs)hRead
AI108Foam_Probe_Sensr1Foam Probe Sensor 1 (0-255)Read
AI109Burner_Fan_Speed1Burner Fan Speed 1 (0-1000Hz)HzRead
AV101Water_Temp_Off1Water Temperature offset 1 (±0-20 °C or ±0-40 °F)°C/°FWrite
AV102Chimney_Temp_Off1Chimney Temperature offset 1 (±0-20 °C or ±0-40 °F)°C/°FWrite
AV103Water_Level_Off1Water Level offset 1 (±0-20%)%Write
BV101OverTemp_Cont_ON1Over temperature contact ON 1Write0=Normal, 1=Alarm
BV102Bad_Fill_Tank1Defective filling tank 1Write0=Normal, 1=Alarm
BV103Bad_Refill_Tank1Defective refill tank 1(too long)Write0=Normal, 1=Alarm
BV104Bad_Drain_Tank1Defective draining tank 1Write0=Normal, 1=Alarm
BV105Bad_Burner_Fan1Defective Burner Fan 1Write0=Normal, 1=Alarm
BV106Bad_Burner_Gas1Defective Burner Gas 1(Locked)Write0=Normal, 1=Alarm
BV107Input_Volt_Low1Input voltage 1 too lowWrite0=Normal, 1=Alarm
BV108Power_Fuse_Open1Power Fuse 1 open (24VAC)Write0=Normal, 1=Alarm
BV109Tank_Sens_Bad1Tank sensor 1 defectiveWrite0=Normal, 1=Alarm
BV110Chim_Sens_Bad1Chimney sensor 1 defectiveWrite0=Normal, 1=Alarm
BV111H2OLvl_Prb_Bad1Water level probe 1 defectWrite0=Normal, 1=Alarm
BV112Foam_Sens_ON1Foam Sensor 1 ONWrite0=Normal, 1=Alarm
BV113OverFlow_DripPan1Over Flow, Drip Pan 1Write0=Normal, 1=Alarm
BV114Tank_Temp_Low1Tank temper. 1 Too low (freeze)Write0=Normal, 1=Alarm
BV115Tank_Temp_Hi1Tank temperature 1 too highWrite0=Normal, 1=Alarm
BV116Chimney_Temp_Hi1Chimney temperature 1 too highWrite0=Normal, 1=Alarm
BI101Burner_Valve1Burner Valve 1Read0=OFF, 1=ON
BI102Burner_Fan1Burner Fan 1Read0=OFF, 1=ON
BI103Fill_Tank1Fill Tank 1Read0=OFF, 1=ON
BI104Drain_Tank1Drain Tank 1Read0=OFF, 1=ON
BI105Water_Level_OK1Water Level 1 OkayRead0=OFF, 1=ON
BI106Modulation Stat1Modulation Status 1Read0=OFF, 1=ON
MI101Unit_Size1Unit Size 1Read1=100Lbs/Hr, 2=150Lbs/Hr, 3=175Lbs/Hr, 4=200Lbs/Hr
AI201Water_Temp2Water Temperature 2 (0-260 °C or 32-500 °F)°C/°FRead
AI202Chimney_Temp2Chimney Temperature 2 (0-260 °C or 32-500 °F)°C/°FRead
AI203Water_Level2Water level 2 (0-120%)%Read
AI204Burner_Demand2Burner Demand 2 (0.0 - 100.0%)%Read
AI205Op_Timer_Total2Operation Timer 2 (Total time) (1-1677215Hrs)hRead
AI206Op_Timer2Operation Timer 2 (1-5000Hrs)hRead
AI207Delay_Autodrain2Delay until Auto-drain 2 (1-100Hrs)hRead
AI208Foam_Probe_Sensr2Foam Probe Sensor 2 (0-255)Read
AI209Burner_Fan_Speed2Burner Fan Speed 2 (0-1000Hz)HzRead
AV201Water_Temp_Off2Water Temperature offset 2 (±0-20 °C or ±0-40 °F)°C/°FWrite
AV202Chimney_Temp_Off2Chimney Temperature offset 2 (±0-20 °C or ±0-40 °F)°C/°FWrite
AV203Water_Level_Off2Water Level offset 2 (±0-20%)%Write
BV201OverTemp_Cont_ON2Over temperature contact ON 2Write0=Normal, 1=Alarm
BV202Bad_Fill_Tank2Defective filling tank 2Write0=Normal, 1=Alarm
BV203Bad_Refill_Tank2Defective refill tank 2(too long)Write0=Normal, 1=Alarm
BV204Bad_Drain_Tank2Defective draining tank 2Write0=Normal, 1=Alarm
BV205Bad_Burner_Fan2Defective Burner Fan 2Write0=Normal, 1=Alarm
BV206Bad_Burner_Gas2Defective Burner Gas 2(Locked)Write0=Normal, 1=Alarm
BV207Input_Volt_Low2Input voltage 2 too lowWrite0=Normal, 1=Alarm
BV208Power_Fuse_Open2Power Fuse 2 open (24VAC)Write0=Normal, 1=Alarm
BV209Tank_Sens_Bad2Tank sensor 2 defectiveWrite0=Normal, 1=Alarm
BV210Chim_Sens_Bad2Chimney sensor 2 defectiveWrite0=Normal, 1=Alarm
BV211H2OLvl_Prb_Bad2Water level probe 2 defectWrite0=Normal, 1=Alarm
BV212Foam_Sens_ON2Foam Sensor 2 ONWrite0=Normal, 1=Alarm
BV213OverFlow_DripPan2Over Flow, Drip Pan 2Write0=Normal, 1=Alarm
BV214Tank_Temp_Low2Tank temper. 2 Too low (freeze)Write0=Normal, 1=Alarm
BV215Tank_Temp_Hi2Tank temperature 2 too highWrite0=Normal, 1=Alarm
BV216Chimney_Temp_Hi2Chimney temperature 2 too highWrite0=Normal, 1=Alarm
BI201Burner_Valve2Burner Valve 2Read0=OFF, 1=ON
BI202Burner_Fan2Burner Fan 2Read0=OFF, 1=ON
BI203Fill_Tank2Fill Tank 2Read0=OFF, 1=ON
BI204Drain_Tank2Drain Tank 2Read0=OFF, 1=ON
BI205Water_Level_OK2Water Level 2 OkayRead0=OFF, 1=ON
BI206Modulation Stat2Modulation Status 2Read0=OFF, 1=ON
MI201Unit_Size2Unit Size 2Read1=100Lbs/Hr, 2=150Lbs/Hr, 3=175Lbs/Hr, 4=200Lbs/Hr
AI301Water_Temp3Water Temperature 3 (0-260 °C or 32-500 °F)°C/°FRead
AI302Chimney_Temp3Chimney Temperature 3 (0-260 °C or 32-500 °F)°C/°FRead
AI303Water_Level3Water level 3 (0-120%)%Read
AI304Burner_Demand3Burner Demand 3 (0.0 - 100.0%)%Read
AI305Op_Timer_Total3Operation Timer 3 (Total time) (1-1677215Hrs)hRead
AI306Op_Timer3Operation Timer 3 (1-5000Hrs)hRead
AI307Delay_Autodrain3Delay until Auto-drain 3 (1-100Hrs)hRead
AI308Foam_Probe_Sensr3Foam Probe Sensor 3 (0-255)Read
AI309Burner_Fan_Speed3Burner Fan Speed 3 (0-1000Hz)HzRead
AV301Water_Temp_Off3Water Temperature offset 3 (±0-20 °C or ±0-40 °F)°C/°FWrite
AV302Chimney_Temp_Off3Chimney Temperature offset 3 (±0-20 °C or ±0-40 °F)°C/°FWrite
AV303Water_Level_Off3Water Level offset 3 (±0-20%)%Write
BV301OverTemp_Cont_ON3Over temperature contact ON 3Write0=Normal, 1=Alarm
BV302Bad_Fill_Tank3Defective filling tank 3Write0=Normal, 1=Alarm
BV303Bad_Refill_Tank3Defective refill tank 3(too long)Write0=Normal, 1=Alarm
BV304Bad_Drain_Tank3Defective draining tank 3Write0=Normal, 1=Alarm
BV305Bad_Burner_Fan3Defective Burner Fan 3Write0=Normal, 1=Alarm
BV306Bad_Burner_Gas3Defective Burner Gas 3(Locked)Write0=Normal, 1=Alarm
BV307Input_Volt_Low3Input voltage 3 too lowWrite0=Normal, 1=Alarm
BV308Power_Fuse_Open3Power Fuse 3 open (34VAC)Write0=Normal, 1=Alarm
BV309Tank_Sens_Bad3Tank sensor 3 defectiveWrite0=Normal, 1=Alarm
BV310Chim_Sens_Bad3Chimney sensor 3 defectiveWrite0=Normal, 1=Alarm
BV311H3OLvl_Prb_Bad3Water level probe 3 defectWrite0=Normal, 1=Alarm
BV312Foam_Sens_ON3Foam Sensor 3 ONWrite0=Normal, 1=Alarm
BV313OverFlow_DripPan3Over Flow, Drip Pan 3Write0=Normal, 1=Alarm
BV314Tank_Temp_Low3Tank temper. 3 Too low (freeze)Write0=Normal, 1=Alarm
BV315Tank_Temp_Hi3Tank temperature 3 too highWrite0=Normal, 1=Alarm
BV316Chimney_Temp_Hi3Chimney temperature 3 too highWrite0=Normal, 1=Alarm
BI301Burner_Valve3Burner Valve 3Read0=OFF, 1=ON
BI302Burner_Fan3Burner Fan 3Read0=OFF, 1=ON
BI303Fill_Tank3Fill Tank 3Read0=OFF, 1=ON
BI304Drain_Tank3Drain Tank 3Read0=OFF, 1=ON
BI305Water_Level_OK3Water Level 3 OkayRead0=OFF, 1=ON
BI306Modulation Stat3Modulation Status 3Read0=OFF, 1=ON
MI301Unit_Size3Unit Size 3Read1=100Lbs/Hr, 2=150Lbs/Hr, 3=175Lbs/Hr, 4=200Lbs/Hr
AI401Water_Temp4Water Temperature 4 (0-260 °C or 32-500 °F)°C/°FRead
AI402Chimney_Temp4Chimney Temperature 4 (0-260 °C or 32-500 °F)°C/°FRead
AI403Water_Level4Water level 4 (0-120%)%Read
AI404Burner_Demand4Burner Demand 4 (0.0 - 100.0%)%Read
AI405Op_Timer_Total4Operation Timer 4 (Total time) (1-1677215Hrs)hRead
AI406Op_Timer4Operation Timer 4 (1-5000Hrs)hRead
AI407Delay_Autodrain4Delay until Auto-drain 4 (1-100Hrs)hRead
AI408Foam_Probe_Sensr4Foam Probe Sensor 4 (0-255)Read
AI409Burner_Fan_Speed4Burner Fan Speed 4 (0-1000Hz)HzRead
AV401Water_Temp_Off4Water Temperature offset 4 (±0-20 °C or ±0-40 °F)°C/°FWrite
AV402Chimney_Temp_Off4Chimney Temperature offset 4 (±0-20 °C or ±0-40 °F)°C/°FWrite
AV403Water_Level_Off4Water Level offset 4 (±0-20%)%Write
BV401OverTemp_Cont_ON4Over temperature contact ON 4Write0=Normal, 1=Alarm
BV402Bad_Fill_Tank4Defective filling tank 4Write0=Normal, 1=Alarm
BV403Bad_Refill_Tank4Defective refill tank 4(too long)Write0=Normal, 1=Alarm
BV404Bad_Drain_Tank4Defective draining tank 4Write0=Normal, 1=Alarm
BV405Bad_Burner_Fan4Defective Burner Fan 4Write0=Normal, 1=Alarm
BV406Bad_Burner_Gas4Defective Burner Gas 4(Locked)Write0=Normal, 1=Alarm
BV407Input_Volt_Low4Input voltage 4 too lowWrite0=Normal, 1=Alarm
BV408Power_Fuse_Open4Power Fuse 4 open (44VAC)Write0=Normal, 1=Alarm
BV409Tank_Sens_Bad4Tank sensor 4 defectiveWrite0=Normal, 1=Alarm
BV410Chim_Sens_Bad4Chimney sensor 4 defectiveWrite0=Normal, 1=Alarm
BV411H4OLvl_Prb_Bad4Water level probe 4 defectWrite0=Normal, 1=Alarm
BV412Foam_Sens_ON4Foam Sensor 4 ONWrite0=Normal, 1=Alarm
BV414OverFlow_DripPan4Over Flow, Drip Pan 4Write0=Normal, 1=Alarm
BV414Tank_Temp_Low4Tank temper. 4 Too low (freeze)Write0=Normal, 1=Alarm
BV415Tank_Temp_Hi4Tank temperature 4 too highWrite0=Normal, 1=Alarm
BV416Chimney_Temp_Hi4Chimney temperature 4 too highWrite0=Normal, 1=Alarm
BI401Burner_Valve4Burner Valve 4Read0=OFF, 1=ON
BI402Burner_Fan4Burner Fan 4Read0=OFF, 1=ON
BI403Fill_Tank4Fill Tank 4Read0=OFF, 1=ON
BI404Drain_Tank4Drain Tank 4Read0=OFF, 1=ON
BI405Water_Level_OK4Water Level 4 OkayRead0=OFF, 1=ON
BI406Modulation Stat4Modulation Status 4Read0=OFF, 1=ON
MI401Unit_Size4Unit Size 4Read1=100Lbs/Hr, 2=150Lbs/Hr, 3=175Lbs/Hr, 4=200Lbs/Hr
Object ID lookup: Neptronic SKG gas-fired humidifier with NEPICSKG point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module

How many BACnet points does the Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module have?

This list has 199 BACnet objects: 37 analog inputs, 40 analog values, 42 binary inputs, 70 binary values, 4 multi-state inputs, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module BACnet points are writable?

115 of the 199 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module BACnet documentation?

The source is Gas Fired Humidifier SKG Series - BACnet Communication Module User Guide (SKG-BACNET), revision Rev 060803, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/SKG3000/SKG-bacnet-user-guide.pdf.

What are the minimum BACnet points to integrate the Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module?

Start with MV 2 Operation_Mode (Unit off, on or drain); MV 1 Ctl_Mode (Control mode; 3 = demand from BACnet); AV 1 Humidity_Demand (Humidity demand from the BMS, %); AV 16 Ctl_SP (Humidity setpoint for internal PID, %RH); AV 2 Room_Humidity (Room RH from the BMS (remote source)); BI 1 Power_Status (Unit power on); AI 1 Humidity_Out (Humidifier output, %); BI 4 Alrm_Not_Critical (Non-critical alarm, unit still running); BI 5 Alarm_Critical (Critical alarm, unit stopped).

How do I enable BMS control of the Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module?

MSV 2 Operation_Mode sets the unit off (1), on (2) or to drain (3). MSV 1 Ctl_Mode picks the demand source: 1 = analog input 1, 2 = internal PID, 3 = remote demand over BACnet.

Can the BMS supply sensor values to the Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module?

With MSV 5 Room_Hum_Source = 2 and MSV 6 Duct_Hum_Source = 3 (remote) the BMS writes AV 2 Room_Humidity and AV 4 Duct_Humidity; MSV 4 SP_Source = 3 takes the setpoint from BACnet.

How do I check these points on the real SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: Gas Fired Humidifier SKG Series - BACnet Communication Module User Guide · SKG-BACNET · rev. Rev 060803. Object names, instances and units are reproduced as published; descriptions are our own.