Reverse osmosis water treatment unit · BACnet points list

Neptronic SKRO BACnet points list

Updated 28 October 2026

Short answer

The SKRO produces purified water for humidifiers. Its controller offers BACnet MS/TP and BACnet IP, mostly for monitoring: state, system alarm, pressures and conductivity, valves and motor, service counters, plus a request object and email notification settings.

This page lists 87 BACnet objects for the Neptronic SKRO — 50 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
SKRO
Equipment
Reverse osmosis water treatment unit
Equipment type
Humidifiers
BACnet objects
87 (50 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
153000 + MAC address (153001 by default)
Also known as
SKRO reverse osmosis, SKRO BACnet
Source document
SKRO Reverse Osmosis Water Treatment Unit BACnet Communication Module User Guide · SKRO-BACnet Guide-250913 (V1.0) · rev. 2025-09-13
Download CSV 87 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Neptronic SKRO

Integration in brief

Mostly a monitoring integration: read the SKRO state (MSV 141), system alarm (MSV 142), interlock and network timeout status. Few control writes are exposed; most objects are read-only in this guide.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 5System Power StateSystem on (1) or off (0)Read
MV 141StateOperating stateRead
BV 19InterlockInterlock open (1) or closed (0)Read
MV 142System AlarmActive alarm (0 = Normal)Read
BV 68Network Timeout Failsafe1 = BACnet network timeout activeWrite

Heartbeat & communication loss

The guide lists BV 71 BACnet Network Timeout (Off/On) and BV 68 Network Timeout Failsafe (0 = Ok, 1 = Timeout) but does not describe the timeout length or the resulting action.

Network setup

Watch out for

Neptronic SKRO BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

87 of 87 shown
Type
Multi-state
Access
Show
Neptronic SKRO BACnet Points List
DescriptionStates
AI1Inlet SignalReading value at the inlet of the signalVRead
AI2Permeate SignalReading value of the permeate line signalVRead
AI3Concentrate SignalReading value of the concentrate line signalVRead
AI9Permeate PulseRaw pulse value of the flow meter for permeateRead
AI10Concentrate PulseRaw pulse value of the flow meter for concentrateRead
AV10MCU LoadCurrent microcontroller load%Read
AV11Memory LoadCurrent memory load%Read
AV43Inlet PressurePressure at the inlet of the unitpsiCommand
AV53Permeate PressurePressure of the permeate tankpsiWrite
AV63Concentrate PressureOsmotic pressure on the concentrate sidepsiWrite
AV73TDS SensorValue read by the TDS sensorWrite
AV150RuntimeActual run time since the last power up in secondsRead
AV151HALTicksNumber of Hardware ticksRead
AV158Modbus TCP IP Keep Alive Time OutAmount of time the Modbus communication stays open before connection is cut...minWrite
AV399Run TimeTotal run time of the unithRead
AV400On TimeTotal operating time of the unithRead
AV401Regulator PressureParameter of the pressure of the regulatorpsiWrite
AV402Pump On Fast Flush DelayDelay after which the pump is turned on during fast flush routinesWrite
AV442Idle Drain TimeDrain time intervalhWrite
AV443Damaged Membrane DelayTime delay before the damaged membranes alarm is activatedsWrite
AV444Permeate FlowFlow of the permeate water in liter per minuteminWrite
AV445Concentrate FlowFlow of the concentrate water in liter per minuteminWrite
BO1MotorStatus of the motorRead0=Off, 1=On
BO2Inlet ValveStatus of the inlet valveRead0=Closed, 1=Open
BO3Fast Flush ValveStatus of the fast flush (drain) valveRead0=Closed, 1=Open
BO5AlarmStatus of the alarm contactCommand0=Off, 1=On
BO6Work SignalStatus of the work signal contactRead0=Off, 1=On
BO10Alarm LEDStatus of the alarm LEDRead0=Off, 1=On
BO11Power LEDStatus of the power LEDRead0=Off, 1=On
BV16High Level FloatHigh level float sensorRead0=Off, 1=On
BV17Low Level FloatLow level float sensorRead0=Off, 1=On
BV18Alarm Level FloatAlarm level float sensorRead0=Off, 1=On
BVmin19InterlockStatus of the interlockRead0=Closed, 1=Open
BV26Ethernet enableWhether the Ethernet interface is enabled or notWrite0=Disable, 1=Enable
BV53AI8 PolarityPolarity of the analog inputCommand0=Direct, 1=Reverse
BV58SMTP SSLUse a secure socket layer encrypt the communication between the device and...Write0=Off, 1=On
BV59SMTP PortPort number to be used for email transferWrite0=Off, 1=On
BV60Notify AlarmGet notified of all alarm messages by emailWrite0=Off, 1=On
BV61Notify WarningGet notified of all warning messages by emailWrite0=Off, 1=On
BV62Notify App MsgGet notified of all event messages by emailWrite0=Off, 1=On
BVmin68Network Timeout FailsafeNetwork timeout fail-safe stateWrite0=Ok, 1=Timeout
BV71BACnet Network TimeoutBACnet Network Timeout valueWrite0=Off, 1=On
BV113Memory StatusMemory statusRead0=Ok, 1=Fail
BV116Inlet Low Pressure WarningAlarm to indicate that the pressure is insufficient at the inlet to...Read0=Off, 1=On
BV117Fast Flush Blocked WarningWarning to indicate that the fast flush valve has failed to closeRead0=Off, 1=On
BV118Inlet Valve Open WarningWarning to indicate that the inlet valve has failed to openRead0=Off, 1=On
BV119Insufficient Osmosis WarningWarning to indicate that the water is not being replenished in the...Read0=Off, 1=On
BV120Clogged Membrane Service WarningWarning to indicate that the water in the tank is falling to...Read0=Off, 1=On
BV121TDS Sensor Fail WarningWarning to indicate that the TDS sensor is not workingRead0=Off, 1=On
BV122Over Usage WarningWarning to indicate that the purifying state has been active for more...Read0=Off, 1=On
BV140RO Tank ProfileStatus of the RO tank profileWrite0=Atmospheric, 1=Pressurized
CSV20SMTP Server IP AddressServer IP address for the email accountWrite
CSV21SMTP Mail FromEmail address that will be sending the SKRO notification messagesWrite
CSV22SMTP Mail ToEmail address that will be receiving the SKRO notification messagesWrite
CSV23SMTP UsernameLogin username for the email accountWrite
CSV25SMTP PasswordLogin password for the email accountWrite
CSV35EthernetMacAddMAC address of the Ethernet interfaceWrite
CSV75Database VersionDatabase versionWrite
MVmin5System Power StateWhether the system is powered on or offRead0=Off, 1=On
MV6System Log Verbose LevelType of information to be stored on the log fileWrite0=None, 1=Emergency, 2=Alert, 3=Critical, 4=Error, 5=Warning, 6=Notice, 7=Info, 8=Debug
MV8BACnet Server LanguageBACnet server languageRead1=English
MV9BACnet Server List ModeCategory of BACnet objects to displayRead1=Integrator, 2=Advanced, 3=Factory
MV10BACnet Server UnitsDisplay units for the BACnet serverRead1=Metric, 2=Imperial
MV139Update Process StatusProcess statusRead0=Ok, 1=CRC, 2=Device, 3=Failed
MV140RequestRequest for the SKRORead0=None, 1=ResetAlarms, 2=FastFlush, 3=ResetService
MVmin141StateState of the operation of the SKRORead0=Off, 1=Idle, 2=Purifying, 3=FastFlush, 4=Alarm
MVmin142System AlarmSet the system alarmsRead0=Normal, 1=InHiPress, 2=DmgMembrane, 3=BlocMembrane, 4=ConcOpen, 5=LoPumpPress, 6=InletClog, 7=PressReg, 8=NoPureWater, 9=TankClosed, 10=FloatOff, 11=InletSensor, 12=PermeatSensor, 13=ConcentSensor
Other1NSDF Core ProgramNSDF Core ProgramWrite
Other2Module 1Module 1Write
Other3Module 2Module 2Write
Other4Module 3Module 3Write
Other5Module 4Module 4Write
Other6Module 5Module 5Write
Other7Module 6Module 6Write
Other8Module 7Module 7Write
Other9Module 8Module 8Write
Other10Module 9Module 9Write
Other11Module 10Module 10Write
Other12Module 11Module 11Write
Other13Module 12Module 12Write
Other14Module 13Module 13Write
Other15NSDF DatabaseNSDF DatabaseWrite
FILE2UpdatePackageFileUpdate Package fileWrite
FILE4SysLogAlarmSystem Log AlarmWrite
FILE5USB System Log FileUSB System Log fileWrite
FILE6USB System Alarm Log FileUSB System Alarm Log fileWrite
FILE16System Log FileSystem Log fileWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKRO and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic SKRO

How many BACnet points does the Neptronic SKRO have?

This list has 87 BACnet objects: 5 analog inputs, 17 analog values, 7 binary outputs, 22 binary values, 5 files, 9 multi-state values, 7 characterstring values, 15 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic SKRO BACnet points are writable?

50 of the 87 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic SKRO BACnet documentation?

The source is SKRO Reverse Osmosis Water Treatment Unit BACnet Communication Module User Guide (SKRO-BACnet Guide-250913 (V1.0)), revision 2025-09-13, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/2025/SKRO-BACnet%20Guide-250913%20(V1.0).pdf.

What are the minimum BACnet points to integrate the Neptronic SKRO?

Start with MV 5 System Power State (System on (1) or off (0)); MV 141 State (Operating state); BV 19 Interlock (Interlock open (1) or closed (0)); MV 142 System Alarm (Active alarm (0 = Normal)); BV 68 Network Timeout Failsafe (1 = BACnet network timeout active).

Does the Neptronic SKRO need a BACnet heartbeat or have a communication timeout?

The guide lists BV 71 BACnet Network Timeout (Off/On) and BV 68 Network Timeout Failsafe (0 = Ok, 1 = Timeout) but does not describe the timeout length or the resulting action.

How do I check these points on the real SKRO?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: SKRO Reverse Osmosis Water Treatment Unit BACnet Communication Module User Guide · SKRO-BACnet Guide-250913 (V1.0) · rev. 2025-09-13. Object names, instances and units are reproduced as published; descriptions are our own.