Steam humidifier valve controller · BACnet points list

Neptronic SKDESC-xB BACnet points list

Updated 28 October 2026

Short answer

The SKDESC-xB is the electronic controller used on Neptronic steam injection humidifier valves. It communicates over BACnet MS/TP only and exposes setpoints, room and duct RH, PI tuning, high limit, network fallback settings, inputs and relay states.

This page lists 87 BACnet objects for the Neptronic SKDESC-xB — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
SKDESC-xB
Equipment
Steam humidifier valve controller
Equipment type
Humidifiers
BACnet objects
87 (30 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
153000 + MAC address (153000 by default, MAC 0)
Also known as
SKDESC, SKDESCxB, ESCJx, ESCMx, Electronic Steam Controller
Source document
SKDESC-xB Series Electronic Steam Controller BACnet Communication Module User Guide · SKDESCXB-BACnet-250905-EUA · rev. 2025-09-05
Download CSV 87 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Neptronic SKDESC-xB

Integration in brief

Set MSV 2 Control Mode to Network to drive the valve from the BMS, or feed room RH to AV 2 (after turning on BV 14 NetworkRoomRH) with the internal setpoint AV 1. Configure the network fallback timeout and fallback setpoint, and switch the system with BV 1.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1PowerStatusSystem power on/offWrite
MV 2ControlModeControl mode: External, Internal or NetworkWrite
AV 1InternalStpntInternal RH setpointWrite
AV 2RoomRHRoom RH (writable when BV 14 = On)Write
AV 4SystemDemandHumidity demand the controller is acting onRead
BV 20AlarmRelayStateAlarm relay output; on when the controller signals an alarmRead

Enable & remote start

BV 1 PowerStatus (0 = Off, 1 = On) is writable; MSV 2 ControlMode selects External, Internal or Network control.

Heartbeat & communication loss

Network fallback is configured with AV 30 FallbackTimeout (0-900 s), AV 31 FallbackStpnt (0-100 %) and the AV 32 FallbackDownCntr countdown; the guide lists these objects but does not spell out the fallback sequence, so test it on site.

Sensors & values from the BMS

Room RH is written to AV 2 only while BV 14 NetworkRoomRH = On; duct RH is written to AV 3 only while MSV 3 HiLimitSensorSrc = Network. BV 15 enables an external RH setpoint.

Network setup

Watch out for

Neptronic SKDESC-xB BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

87 of 87 shown
Type
Multi-state
Access
Show
Neptronic SKDESC-xB BACnet Points List
DescriptionStates
AI1SeparatorTempSig (ESCJx, ESCMx)Separator temperature sensor signal (TS1) valuemVRead
AI2Jacket1TempSig (ESCJx)Temperature sensor signal (TS2) value of jacket 1mVRead
AI3Jacket2TempSig (ESCJx)Temperature sensor signal (TS3) value of jacket 2mVRead
AI4Jacket3TempSig (ESCJx)Temperature sensor signal (TS4) value of jacket 3mVRead
AI5Jacket4TempSig (ESCJx)Temperature sensor signal (TS5) value of jacket 4mVRead
AI6PCRTempSig (PCR Option)Temperature sensor signal of PCRRead
AI7ExternalSigExternal input signal (AI1)mVRead
AI8RoomRHSigRoom's relative humidity sensor signal (AI2)mVRead
AI9DuctRHSigDuct's relative humidity sensor signalmVRead
AI10PCRWaterLevelSigWater level signal of PCRRead
AVmin1InternalStpntInternal setpoint value%Write
AVmin2RoomRHRelative humidity reading value of the room%Write
AV3DuctRHRelative humidity reading value of the duct%Write
AVmin4SystemDemandSystem demand valueRead
AV5SystemOutputSystem output valueRead
AV6SeparatorTemp (ESCJx, ESCMx)Separator temperature reading°F or °CRead
AV7Jacket1Temp (ESCJx)Temperature reading of jacket 1°F or °CRead
AV8Jacket2Temp (ESCJx)Temperature reading of jacket 2°F or °CRead
AV9Jacket3Temp (ESCJx)Temperature reading of jacket 3°F or °CRead
AV10Jacket4Temp (ESCJx)Temperature reading of jacket 4Read
AV11PCRTemp (PCR Option)Temperature reading of PCRRead
AV12WorkingCapacityPercentage value in full capacity%Write
AV13SeparatorTempOffset (ESCJx, ESCMx)Temperature sensor offset value of separator°F or °CWrite
AV14Jacket1TempOffset (ESCJx)Temperature sensor offset value of jacket 1°F or °CWrite
AV15Jacket2TempOffset (ESCJx)Temperature sensor offset value of jacket 2°F or °CWrite
AV16Jacket3TempOffset (ESCJx)Temperature sensor offset value of jacket 3°F or °CWrite
AV17Jacket4TempOffset (ESCJx)Temperature sensor offset value of jacket 4°F or °CWrite
AV18PCRTempOffset (PCR Option)Temperature sensor offset value of PCRRead
AV19RoomRHOffsetRelative humidity sensor offset value of the room%RHWrite
AV20CntrlDeadBandControl deadband value%RHWrite
AV21CntrlPropRampControl proportional ramp value%RHWrite
AV22CntrlIntgrlTimeControl integral ramp value%RHWrite
AV23HiLimitStpntHigh limit setpoint value%RHWrite
AV24HiLimitPropRampHigh limit proportional ramp value%RHWrite
AV25DuctRHOffsetRelative humidity offset value of the ductRead
AV26HiLimitMaxDemandHigh limit maximum demand value%Read
AV27EndOfSeasonDelayEnd of season delayhWrite
AV28ServiceDelayDelay in hours before a Service has to be performedhWrite
AV29ServiceRunTimeService runtime counterhRead
AV30FallbackTimeoutNetwork fallback timeoutsWrite
AV31FallbackStpntNetwork fallback setpoint%Write
AV32FallbackDownCntrNetwork fallback downcountersWrite
AV33TotalRunTimeTotal system runtimehRead
AV34CntrlOutputSigControl valve output signalmVRead
AV35MicroCntrlTempMicrocontroller temperature reading°F or °CRead
AV36BoardTempTemperature reading of the PC board°F or °CRead
AV37CntrlDerivativeTimeControl derivative timeRead
AV38DuctStpntMinMinimum setpoint value of ductRead
AV39DuctStpntMaxMaximum setpoint value of ductRead
AV41DuctPropRampProportional ramp value of ductRead
AV42DuctIntgrlTimeIntegral time value of ductRead
AV43DuctDerivativeTimeDerivative time value of ductRead
AV44ControlDemandControl demand valueRead
AV45DynamicDuctStpntDynamic duct setpoint valueRead
AV46DuctDemandDuct demand valueRead
AV47PCRSupplySig (PCR Option)Supply signal value of PCRRead
AV48PCRSupply (PCR Option)Supply value of PCRRead
BI1ExternalDemandInputStateDigital external demand input stateRead0=OFF, 1=ON
BI2AirflowInputStateAirflow input stateRead0=OFF, 1=ON
BI3HiLimitInputStateHigh limit input stateRead0=OFF, 1=ON
BI4InterlockInputStateInterlock input stateRead0=OFF, 1=ON
BVmin1PowerStatusSystem's power statusWrite0=OFF, 1=ON
BV2ServiceWarningService warningRead0=OFF, 1=ON
BV3ServiceAlarmService alarmRead0=OFF, 1=ON
BV4AirFlowCutoutAir flow cutout stateRead0=OFF, 1=ON
BV5HiLimitCutoutHigh limit cutout stateRead0=OFF, 1=ON
BV6InterlockCutoutInterlock cutout stateRead0=OFF, 1=ON
BV7TempSensorDefectTemperature sensor defectRead0=OFF, 1=ON
BV8RoomRHSensorDefectRoom relative humidity sensor defectRead0=OFF, 1=ON
BV9DuctRHSensorDefectDuct relative humidity sensor defectRead0=OFF, 1=ON
BV10FloodedSteamTrapFlooded steam trapRead0=OFF, 1=ON
BV11DisplayUnitsDisplay unitsWrite0=Metric, 1=Imperial
BV12EconoModeEconomic modeWrite0=OFF, 1=ON
BV13ExternalSigRangeExternal input signal rangeWrite0=2 to 10V, 1=0 to 10V
BV14NetworkRoomRHNetwork room relative humidityWrite0=OFF, 1=ON
BV15ExternalRHStpntExternal relative humidity setpointWrite0=OFF, 1=ON
BV16ExternalRHStpntRead
BV17HiLimitRHSigRangeHigh limit relative humidity signal rangeWrite0=OFF, 1=ON
BV18RunsWhenServiceAlarmRuns when service alarm is activeWrite0=OFF, 1=ON
BV19IsoValveOutStateIsolating valve output stateRead0=OFF, 1=ON
BVmin20AlarmRelayStateAlarm relay output stateRead0=OFF, 1=ON
BV21SteamRelayStateSteam relay output stateRead0=OFF, 1=ON
BV22PCRReliefValveOutState (PCR Option)Relief valve output state of PCR optionRead
MV1LanguageSytem languageWrite1=ENG
MVmin2ControlModeControl modeWrite1=External, 2=Internal, 3=Network
MV3DuctSensorSrcDuct sensor sourceRead
MV4PCRWaterLevel (PCR Option)PCR water levelRead1=Above High, 2=Above Low, 3=Below Low, 4=Error

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKDESC-xB and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic SKDESC-xB

How many BACnet points does the Neptronic SKDESC-xB have?

This list has 87 BACnet objects: 10 analog inputs, 47 analog values, 4 binary inputs, 22 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic SKDESC-xB BACnet points are writable?

30 of the 87 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic SKDESC-xB BACnet documentation?

The source is SKDESC-xB Series Electronic Steam Controller BACnet Communication Module User Guide (SKDESCXB-BACnet-250905-EUA), revision 2025-09-05, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/2025/SKDESCXB-BACnet-250905-EUA.pdf.

What are the minimum BACnet points to integrate the Neptronic SKDESC-xB?

Start with BV 1 PowerStatus (System power on/off); MV 2 ControlMode (Control mode: External, Internal or Network); AV 1 InternalStpnt (Internal RH setpoint); AV 2 RoomRH (Room RH (writable when BV 14 = On)); AV 4 SystemDemand (Humidity demand the controller is acting on); BV 20 AlarmRelayState (Alarm relay output; on when the controller signals an alarm).

How do I enable BMS control of the Neptronic SKDESC-xB?

BV 1 PowerStatus (0 = Off, 1 = On) is writable; MSV 2 ControlMode selects External, Internal or Network control.

Does the Neptronic SKDESC-xB need a BACnet heartbeat or have a communication timeout?

Network fallback is configured with AV 30 FallbackTimeout (0-900 s), AV 31 FallbackStpnt (0-100 %) and the AV 32 FallbackDownCntr countdown; the guide lists these objects but does not spell out the fallback sequence, so test it on site.

Can the BMS supply sensor values to the Neptronic SKDESC-xB?

Room RH is written to AV 2 only while BV 14 NetworkRoomRH = On; duct RH is written to AV 3 only while MSV 3 HiLimitSensorSrc = Network. BV 15 enables an external RH setpoint.

How do I check these points on the real SKDESC-xB?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: SKDESC-xB Series Electronic Steam Controller BACnet Communication Module User Guide · SKDESCXB-BACnet-250905-EUA · rev. 2025-09-05. Object names, instances and units are reproduced as published; descriptions are our own.