High-pressure atomizing humidifier / cooler · BACnet points list

Neptronic SKH4 BACnet points list

Updated 28 October 2026

Short answer

The SKH4 pumps treated water to high-pressure nozzles for humidification or adiabatic cooling, serving up to six zones. BACnet MS/TP and BACnet IP are built in; besides system control sources and network RH/temperature inputs the guide lists per-zone control, occupancy, demand, readings, stage and communication objects.

This page lists 325 BACnet objects for the Neptronic SKH4 — 238 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
SKH4
Equipment
High-pressure atomizing humidifier / cooler
Equipment type
Humidifiers
BACnet objects
325 (238 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
153000 + MAC address (153001 by default)
Also known as
SKH4 high-pressure atomizer, SKH4 BACnet
Source document
SKH4 High-Pressure Atomizer BACnet Communication Module User Guide · SKH4-BACnet Guide-240126 (V1.00) · rev. 2024-01-26
Download CSV 325 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Neptronic SKH4

Integration in brief

Choose a Network control profile (MSV 28) or demand source (MSV 43 = Network) and write demand to AV 138, or feed room RH/temperature readings (AV 106 / AV 155) for internal control. Per-zone control and occupancy are set with the Zone MSVs; watch BV 44 and the zone communication timeout BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 95Zone A ControlZone A on/off: 1 = Off, 2 = NormalWrite
MV 96Zone A Occupancy1 = occupied, 2 = unoccupied, 3 = offWrite
MV 28Control ProfileControl profile: choose a Network profileWrite
AV 138Control Network DemandDirect demand written by the BMS, %Command
AV 107Room RH SetpointOccupied room RH setpoint (internal control)Write
AV 106Room RH Network ReadingNetwork room RH reading for internal controlCommand
MV 83System Power StateSystem on/off statusRead
AV 143User DemandCurrent humidity demand %Read
BV 68Drive StateDrive status: 0 = Ok, 1 = FaultRead
BV 44Network Control State1 = fault: network control lost (AV 223 timeout)Write

Enable & remote start

No writable system on/off object is listed (MSV 83 System Power State is read-only in this guide). Zones are switched with the Zone x Control MSVs (1 = Off, 2 = Normal...) and Zone x Occupancy; the demand source comes from MSV 28 / MSV 43.

Heartbeat & communication loss

AV 223 Network Timeout (1-900 s) is how long the unit tries to reach the BACnet or Modbus network before it stops operating; BV 44 Network Control State shows 1 = Fault. AV 441 sets the internal zone communication timeout, with per-zone alarms BV 86-91.

Sensors & values from the BMS

Network room RH to AV 106 (MSV 33 = Network) with setpoints AV 107-109; room temperature to AV 155 for cooling profiles; supply high limit RH to AV 122 (MSV 38 = Network) and temperature to AV 175 (MSV 71 = Network). Direct demand goes to AV 138 and high limit to AV 139.

Network setup

Watch out for

Neptronic SKH4 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

325 of 325 shown
Type
Multi-state
Access
Show
Neptronic SKH4 BACnet Points List
DescriptionStates
AI5Control SignalControl demand analog input signalVRead
AI6Room RH SignalRoom humidity analog input signalVRead
AI7Supply RH SignalDuct or supply high limit humidity analog input signalVRead
AI15Water Temperature SignalWater temperature sensor signalVRead
AI16Pressure Sensor SignalPressure sensor signalVRead
AI24Board Temperature SignalBoard temperature sensor signalVRead
AI25Main Power SupplyMeasured voltage in the power supplyVRead
AI28Room Temperature SignalRoom temperature sensor signalVRead
AI29Supply Temperature SignalRoom temperature sensor signalVRead
AI30Control SignalControl signalVRead
AO1Power Output Feedback SignalPower output feedback signalVRead
AO16Drive SignalDrive signalVCommand
AV10MCU LoadCurrent microcontroller load%Read
AV11Memory LoadCurrent memory load%Read
AV21DemandDemand%Read
AV41Control InputCurrent control input reading%Read
AV42Control MinMinimum value of the control demand analog input%Write
AV43Control MaxMaximum value of the control demand analog input%Write
AV44Control BiasBias value for the control demand analog input%Write
AV49Room RHRoom humidity reading%RHRead
AV50Room RH MinMinimum value of the room humidity analog input%Write
AV51Room RH MaxMaximum value of the room humidity analog input%Write
AV52Room RH BiasBias value of the room humidity analog input%RHWrite
AV57Supply High Limit RHDuct or supply high limit humidity analog input%RHRead
AV58Supply High Limit RH MinMinimum value of the duct or supply high limit humidity analog input%RHWrite
AV59Supply High Limit RH MaxMaximum value of the duct or supply high limit humidity analog input%RHWrite
AV60Supply High Limit RH BiasBias value of the duct or supply high limit humidity analog input%RHWrite
AV69Run TimeNumber of seconds that the system has been powered onhCommand
AV70On TimeTotal operating time of the humidifierhCommand
AV72Service On TimeOperating time of the humidifier since the last servicinghCommand
AV75Water TemperatureTemperature of water in the evaporation chamber°F or °CRead
AV82Service IntervalSystem service intervalhRead
AV85Power Output Feedback BiasBias value for the power output feedback signalVWrite
AV86Power Output Feedback MinMinimum value of the power output feedback signalVWrite
AV87Power Output Feedback MaxMaximum value of the power output feedback signalVWrite
AV88Power Output FeedbackFeedback value of the power output analog output%Command
AV94Motor SpeedMotor speed%Write
AVmin106Room RH Network ReadingRoom relative humidity reading received from the network%RHCommand
AVmin107Room RH SetpointRoom relative humidity setpoint received from the network%RHWrite
AV108Room RH Unoccupied SetpointRoom relative humidity reading received from the network during no occupancy state%RHWrite
AV109Room RH Vacant SetpointRoom relative humidity reading received from the network during vacancy%RHWrite
AV110Room RH Demand Proportional GainRoom demand proportional gainWrite
AV111Room RH Demand Integral TimeRoom demand integral timesWrite
AV112Room RH Demand Derivative TimeRoom demand derivative timesWrite
AV120Room RH DemandHumidity demand within the room%Command
AV122RH Supply High Limit Network ReadingSupply high limit reading received from the network%RHCommand
AV123RH Supply High Limit SetpointSupply high limit setpoint received from the network%RHWrite
AV124RH Supply High Limit Unoccupied SetpointSupply high limit setpoint during the unoccupied mode%RHWrite
AV125RH Supply High Limit Vacant SetpointSupply high limit setpoint during the occupied mode%RHWrite
AV126RH Supply High Limit Proportional GainSupply high limit demand proportional gainWrite
AV127RH Supply High Limit Integral TimeSupply high limit demand integral timesWrite
AV128RH Supply High Limit Derivative TimeSupply high limit demand derivative timesWrite
AV136RH Supply High Limit DemandSupply high limit humidity demand value%Command
AVmin138Control Network DemandHumidity control demand received from the network%Command
AV139Control Network High LimitHumidity control high limit received from the network%Command
AVmin143User DemandMeasured humidity demand of the humidifier%Read
AV151Room Temperature MinMinimum value of the room temperature signal°F or °CCommand
AV152Room Temperature MaxMaximum value of the room temperature signal°F or °CCommand
AV153Room Temperature BiasBias value of the room temperature signal°F or °CCommand
AV155Room Temperature Network ReadingRoom temperature network°F or °CCommand
AV156Room Temperature SetpointRoom temperature setpoint°F or °CCommand
AV157Room Temperature Unoccupied SetpointRoom temperature setpoint value used during unoccupied state°F or °CCommand
AV158Room Temperature Vacant SetpointRoom temperature setpoint value used during occupied state°F or °CCommand
AV159Room Temperature Demand Proportional GainRoom demand proportional gainCommand
AV160Room Temperature Demand Integral TimeRoom demand integral timesCommand
AV161Room Temperature Demand Derivative TimeRoom demand derivative timesCommand
AV169Room Temperature DemandRoom demand temperature%Read
AV170HRL TemperatureRoom temperature value measured by the HRL24 controller°F or °CRead
AV171HRL HumidityRoom humidity value measured by the HRL24 controller%Read
AV174Room Temp Demand Proportional BandRoom demand proportional band%Command
AV175Temp Supply High Limit Network ReadingTemperature supply high limit network reading°F or °CCommand
AV176Temp Supply High Limit SetpointSupply high limit temperature setpoint value°F or °CCommand
AV177Temp Supply High Limit Unoccupied SetpointSupply high limit temperature setpoint value used during unoccupied state°F or °CCommand
AV178Temp Supply High Limit Vacant SetpointSupply high limit temperature setpoint value used during occupied state°F or °CCommand
AV179Temp Supply High Limit Proportional GainSupply high limit temperature proportional gainCommand
AV180Temp Supply High Limit Integral TimeSupply high limit demand integral timesCommand
AV181Modbus TCP IP Keep Alive Time OutAmount of time the communication stays open before connection is cut out...minCommand
AV182Temp Supply High Limit Derivative TimeSupply high limit temperature derivative timesCommand
AV190Temp Supply High Limit DemandThe supply high limit demand temperature%Read
AV193Temp Supply High Limit Proportional BandThe supply high limit demand proportional band%Read
AV196Supply High Limit TemperatureThe supply high limit temperature°F or °CRead
AV197Supply High Limit Temperature MinConfiguration minimum value of the supply high limit temperature°F or °CCommand
AV198Supply High Limit Temperature MaxConfiguration maximum value of the supply high limit temperature°F or °CCommand
AV199Supply High Limit Temperature BiasConfiguration bias value of the supply high limit temperature°F or °CCommand
AV220Demand Low Dead BandLower limit dead band value for the humidity demand%Command
AV223Network TimeoutAmount of time the humidifier may attempt to connect to the BACnet...sCommand
AV230Room RH Demand Proportional BandRoom demand humidity proportional band%Command
AV231RH Supply High Limit Proportional BandThe supply high limit humidity proportional band%Read
AV234Control TimerControl timersCommand
AV235Zone A DemandThe demand for Zone A%Read
AV236Zone A TemperatureTemperature for Zone A°F or °CCommand
AV237Zone A HumidityHumidity for Zone A%RHCommand
AV240Zone B DemandThe demand for Zone B%Read
AV241Zone B TemperatureTemperature for Zone B°F or °CCommand
AV242Zone B HumidityHumidity for Zone B%RHCommand
AV245Zone C DemandThe demand for Zone C%Read
AV246Zone C TemperatureTemperature for Zone C°F or °CCommand
AV247Zone C HumidityHumidity for Zone C%RHCommand
AV250Zone D DemandThe demand for Zone D%Read
AV251Zone D TemperatureTemperature for Zone D°F or °CCommand
AV252Zone D HumidityHumidity for Zone D%RHCommand
AV255Zone E DemandThe demand for Zone E%Read
AV256Zone E TemperatureTemperature for Zone E°F or °CCommand
AV257Zone E HumidityHumidity for Zone E%RHCommand
AV260Zone F DemandThe demand for Zone F%Read
AV261Zone F TemperatureTemperature for Zone F°F or °CCommand
AV262Zone F HumidityHumidity for Zone F%RHCommand
AV263Stage 1 CapacityCapacity for stage 1L/hCommand
AV264Stage 1 Drain VolumeDrain volume for stage 1Command
AV265Stage 2 CapacityCapacity for stage 2L/hCommand
AV266Stage 2 Drain VolumeDrain volume for stage 2Command
AV267Stage 3 CapacityCapacity for stage 3L/hCommand
AV268Stage 3 Drain VolumeDrain volume for stage 3Command
AV269Stage 4 CapacityCapacity for stage 4L/hCommand
AV270Stage 4 Drain VolumeDrain volume for stage 4Command
AV271Stage 5 CapacityCapacity for stage 5L/hCommand
AV272Stage 5 Drain VolumeDrain volume for stage 5Command
AV273Stage 6 CapacityCapacity for stage 6L/hCommand
AV278Stage 6 Drain VolumeDrain volume for stage 6Command
AV279Stage 1 Drain TimeThe drain time for stage 1sRead
AV280Stage 2 Drain TimeDrain time for stage 2sCommand
AV281Stage 3 Drain TimeDrain time for stage 3sCommand
AV282Stage 4 Drain TimeDrain time for stage 4sCommand
AV283Stage 5 Drain TimeDrain time for stage 5sCommand
AV284Stage 6 Drain TimeDrain time for stage 6sCommand
AV307Stage 1 Idle TimeThe idle time for stage 1sRead
AV308Stage 2 Idle TimeThe idle time for stage 2sRead
AV309Stage 3 Idle TimeThe idle time for stage 3sRead
AV310Stage 4 Idle TimeThe idle time for stage 4sRead
AV311Stage 5 Idle TimeThe idle time for stage 5sRead
AV312Stage 6 Idle TimeThe idle time for stage 6sRead
AV313Stage 1 Run TimeThe run time for stage 1sRead
AV314Stage 2 Run TimeThe run time for stage 2sRead
AV315Stage 3 Run TimeThe run time for stage 3sRead
AV316Stage 4 Run TimeThe run time for stage 4sRead
AV317Stage 5 Run TimeThe run time for stage 5sRead
AV318Stage 6 Run TimeThe run time for stage 6sRead
AV319Stage 1 Cycle CountThe cycle count for stage 1Read
AV320Stage 2 Cycle CountThe cycle count for stage 2Read
AV321Stage 3 Cycle CountThe cycle count for stage 3Read
AV322Stage 4 Cycle CountThe cycle count for stage 4Read
AV323Stage 5 Cycle CountThe cycle count for stage 5Read
AV324Stage 6 Cycle CountThe cycle count for stage 6Read
AV325Cool Drain TimerCool drain timerminCommand
AV382Stage 1 Max On TimeMaximum on time for stage 1sCommand
AV383Stage 2 Max On TimeMaximum on time for stage 2sCommand
AV384Stage 3 Max On TimeMaximum on time for stage 3sCommand
AV385Stage 4 Max On TimeMaximum on time for stage 4sCommand
AV386Stage 5 MaxOn TimeMaximum on time for stage 5sCommand
AV387Stage 6 Max On TimeMaximum on time for stage 6sCommand
AV388Stage 1 Pause TimePause time for stage 1sCommand
AV389Stage 2 Pause TimePause time for stage 2sCommand
AV390Stage 3 Pause TimePause time for stage 3sCommand
AV391Stage 4 Pause TimePause time for stage 4sCommand
AV392Stage 5 Pause TimePause time for stage 5sCommand
AV393Stage 6 Pause TimePause time for stage 6sCommand
AV394Zone A Stage Opening DelayStage opening delay for zone AsCommand
AV395Zone B Stage Opening DelayStage opening delay for zone BsCommand
AV396Zone C Stage Opening DelayStage opening delay for zone CsCommand
AV397Zone D Stage Opening DelayStage opening delay for zone DsCommand
AV398Zone E Stage Opening DelayStage opening delay for zone EsCommand
AV399Zone F Stage Opening DelayStage opening delay for zone FsCommand
AV400Drain 1 Cycle CountThe drain cycle count for stage 1Read
AV401Drain 2 Cycle CountThe drain cycle count for stage 2Read
AV402Drain 3 Cycle CountThe drain cycle count for stage 3Read
AV403Drain 4 Cycle CountThe drain cycle count for stage 4Read
AV404Drain 5 Cycle CountThe drain cycle count for stage 5Read
AV405Drain 6 Cycle CountThe drain cycle count for stage 6Read
AV406Stage 1 On TimeThe operating time of the humidifier since the last servicing for stage...hRead
AV407Stage 2 On TimeThe operating time of the humidifier since the last servicing for stage...hRead
AV408Stage 3 On TimeThe operating time of the humidifier since the last servicing for stage...hRead
AV409Stage 4 On TimeThe operating time of the humidifier since the last servicing for stage...hRead
AV410Stage 5 On TimeThe operating time of the humidifier since the last servicing for stage...hRead
AV411Stage 6 On TimeThe operating time of the humidifier since the last servicing for stage...hRead
AV412Diagnostic PeriodValue of the diagnostic periodminCommand
AV414Zone A MACValue of the MAC address for Zone ACommand
AV415Zone B MACValue of the MAC address for Zone BCommand
AV416Zone C MACValue of the MAC address for Zone CCommand
AV417Zone D MACValue of the MAC address for Zone DCommand
AV418Zone E MACValue of the MAC address for Zone ECommand
AV419Zone F MACValue of the MAC address for Zone FCommand
AV420Control InputValue of the control input°F or °CCommand
AV423Control MinMinimum value of the control input°F or °CCommand
AV424Control MaxMaximum value of the control input°F or °CCommand
AV425Control BiasBias value of the control input°F or °CCommand
AV441Zone Communication Timeout DelayZone communication timeout delaysCommand
BI1Air FlowStatus of the airflow switchRead0=Closed, 1=Open
BI2Supply High LimitStatus of the high limit contactRead0=Closed, 1=Open
BI3InterlockStatus of the interlockRead0=Closed, 1=Open
BI4Binary External DemandStatus of the binary external demandRead0=0%, 1=100%
BI8Water Leak DetectionWhether a water leak has been detectedRead0=OK, 1=Leak
BI14Drive StatusStatus of the driveRead0=Ok, 1=Fault
BI19Inlet Pressure SwitchWhether the inlet pressure switch is available or notRead0=Low, 1=Ok
BI20RS485 InterfaceWhether the RS485 interface is available or notRead0=No, 1=Yes
BI21Ethernet InterfaceWhether the Ethernet interface is available or notRead0=No, 1=Yes
BI22Relay FuseStatus of the relay fuseRead0=Normal, 1=Open Fuse
BI23Control PCB FuseStatus of the control PCB fuseRead0=Normal, 1=Open Fuse
BO2Alarm Warning RelayAlarm warning relayCommand0=Off, 1=On
BO3Service Warning RelayService warning relayCommand0=Off, 1=On
BO4Valve 1Valve 1Command0=Off, 1=On
BO5Valve 2Valve 2Command0=Off, 1=On
BO6Valve 3Valve 3Command0=Off, 1=On
BO7Valve 4Valve 4Command0=Off, 1=On
BO8Valve 5Valve 5Command0=Off, 1=On
BO10Valve 6Valve 6Command0=Off, 1=On
BO11Valve 7Valve 7Command0=Off, 1=On
BO12Valve 8Valve 8Command0=Off, 1=On
BO13Valve 9Valve 9Command0=Off, 1=On
BO14Valve 10Valve 10Command0=Off, 1=On
BO15Valve 11Valve 11Command0=Off, 1=On
BO16Valve 12Valve 12Command0=Off, 1=On
BO18Alarm LEDAlarm LEDCommand0=Off, 1=On
BO19Power LEDPower LEDCommand0=Off, 1=On
BO20BuzzerBuzzerCommand0=Off, 1=On
BO21Contactor PumpContactor pumpCommand0=Off, 1=On
BO22Drive EnableDrive enableCommand0=Off, 1=On
BV3Alarm BuzzerConfiguration value that enables or disables the alarm buzzer sound when there...Write0=Normal, 1=Disabled
BV17Service DueWhether the humidifier is due for servicingRead0=No, 1=Yes
BV30Startup Line RinsePerform an automatic tank rinse cycle upon each start-up of the humidifierWrite0=Off, 1=On
BV32Run While Service AlarmStatus of the run while service alarmWrite0=Not Allowed, 1=Allowed
BV38HRL Lock SetpointWhether the setpoint obtained from the HRL24 controller can be modifiedCommand0=Unlock, 1=Lock
BVmin44Network Control StateState of the control communication between the device and the BACnet networkWrite0=Normal, 1=Fault
BV52SMTP SSLUse a secure socket layer encrypt the communication between the device and...Write0=Off, 1=On
BV53SMTP PortPort number to be used for email transferWrite0=25, 1=587
BV54Notify AlarmGet notified of all humidifier alarm messages by emailWrite0=Off, 1=On
BV55Notify WarningGet notified of all humidifier warning messages by emailWrite0=Off, 1=On
BV56Notify App MsgGet notified of all humidifier event messages by emailWrite0=Off, 1=On
BVmin68Drive StateStatus of the driveRead0=Ok, 1=Fault
BV70Stage 1 Diagnostic EnableStatus of the diagnostic enable for stage 1Write0=No, 1=Yes
BV71Stage 2 Diagnostic EnableStatus of the diagnostic enable for stage 2Write0=No, 1=Yes
BV72Stage 3 Diagnostic EnableStatus of the diagnostic enable for stage 3Write0=No, 1=Yes
BV73Stage 4 Diagnostic EnableStatus of the diagnostic enable for stage 4Write0=No, 1=Yes
BV74Stage 5 Diagnostic EnableStatus of the diagnostic enable for stage 5Write0=No, 1=Yes
BV75Stage 6 Diagnostic EnableStatus of the diagnostic enable for stage 6Write0=No, 1=Yes
BV86Zone A Communication TimeoutStatus of the communication timeout for zone ARead0=Ok, 1=Timeout
BV87Zone B Communication TimeoutStatus of the communication timeout for zone BRead0=Ok, 1=Timeout
BV88Zone C Communication TimeoutStatus of the communication timeout for zone CRead0=Ok, 1=Timeout
BV89Zone D Communication TimeoutStatus of the communication timeout for zone DRead0=Ok, 1=Timeout
BV90Zone E Communication TimeoutStatus of the communication timeout for zone ERead0=Ok, 1=Timeout
BV91Zone F Communication TimeoutStatus of the communication timeout for zone FRead0=Ok, 1=Timeout
BV98Low Water Temperature WarningStatus of the low water temperature warningRead0=Ok, 1=Timeout
CSV10HMI OverwriteOverwrite the value displayed on the local display menuWrite
CSV22SMTP Server IP AddressServer IP address for the email accountWrite
CSV24SMTP Mail FromEmail address that will be sending the humidifier notification messagesWrite
CSV25SMTP Mail ToEmail address that will be receiving the humidifier notification messagesWrite
CSV26SMTP UsernameLogin username for the email accountWrite
CSV37SMTP PasswordLogin password for the email accountWrite
CSV62EthernetMacAddMAC address of the Ethernet interfaceWrite
MV5System Log Verbose LevelType of information to be stored on the log fileWrite1=None, 2=Emergency, 3=Alert, 4=Critical, 5=Error, 6=Warning, 7=Notice, 8=Info, 9=Debug
MV9BACnet Server LanguageBACnet server languageWrite1=English
MV10BACnet Server List ModeCategory of BACnet objects to displayWrite1=Integrator, 2=Advanced, 3=Factory
MV11BACnet Server UnitsDisplay units for the BACnet serverWrite1=Metric, 2=Imperial
MV24Control Signal TypeSignal type for the control demand analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV25Room RH Signal TypeSignal type for the room humidity analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV26Supply RH Signal TypeSignal type for the duct or supply high limit humidity analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV27RequestRequest for the humidifierWrite1=None, 2=ResetAlarms, 3=Drain, 4=ResetServCnt
MVmin28Control ProfileControl profileWrite1=ExternAnalog, 2=ExternNetwork, 3=InternHumAnalog, 4=InternHumNetwork, 5=InternCoolAnalog, 6=InternCoolNetwork, 7=HRL Hum, 8=HRL Cool
MV29Modulating High Limit ProfileA preconfigured control mode profile for the modulating high limit demandRead1=Disabled, 2=ExternAnalog, 3=ExternNetwork, 4=InternHumAnalog, 5=InternHumNetwork, 6=InternCoolAnalog, 7=InternCoolNetwork, 8=Custom
MV32Occupancy StateOccupancy stateRead1=Occupied, 2=Unoccupied, 3=Vacant, 4=Off
MV33Room RH SourceReading source for the room demandWrite1=None, 2=RoomRH, 3=Network, 4=HRL
MV34Room RH Setpoint SourceRoom demand setpoint sourceWrite1=None, 2=Internal, 3=ControlInput
MV38RH Supply High Limit Reading SourceReading source for the supply high limit demandWrite1=None, 2=SupplyHLRH, 3=Network
MV39RH Supply High Limit Setpoint SourceSupply high limit demand setpoint sourceWrite1=None, 2=Internal, 3=ControlInput
MV43Control Demand SourceHumidity control demand sourceWrite1=None, 2=ControlInput, 3=HumRoomDemand, 4=Network, 5=TempRoomDemand
MV44Control High Limit SourceCurrent state of the safety control circuit and whether the circuit has...Write1=None, 2=ControlInput, 3=RHSupplyHLDemand, 4=Network, 5=TempSupplyHLDemand
MV46Control Binary Demand SourceBinary demand sourceWrite1=None, 2=BinaryExtDemand
MV67Room Temperature Setpoint SourceRoom temperature setpoint sourceWrite1=None, 2=Internal, 3=ControlInput
MV71Temp Supply High Limit Reading SourceTemperature supply high limit reading sourceWrite1=None, 2=SupplyHLTemp, 3=Network
MV72Temp Supply High Limit Setpoint SourceTemperature supply high limit setpoint sourceWrite1=None, 2=Internal, 3=ControlInput
MV76Room Temperature SourceRoom temperature sourceWrite1=None, 2=RoomTemp, 3=Network, 4=HRL
MV77Room Temperature Signal TypeRoom temperature signal typeWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV78Supply Temperature Signal TypeSupply temperature signal typeWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MVmin83System Power StateWhether the system is powered on or offRead1=Off, 2=On
MVmin95Zone A ControlControl mode for zone AWrite1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock
MVmin96Zone A OccupancyOccupied status for zone AWrite1=Occupied, 2=Unoccupied, 3=Off
MV97Zone B ControlControl mode for zone BWrite1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock
MV98Zone B OccupancyOccupied status for zone BWrite1=Occupied, 2=Unoccupied, 3=Off
MV99Zone C ControlControl mode for zone CWrite1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock
MV100Zone C OccupancyOccupied status for zone CWrite1=Occupied, 2=Unoccupied, 3=Off
MV101Zone D ControlControl mode for zone D (printed as MAV.101)Write1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock
MV102Zone D OccupancyOccupied status for zone DWrite1=Occupied, 2=Unoccupied, 3=Off
MV103Zone E ControlControl mode for zone EWrite1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock
MV104Zone E OccupancyOccupied status for zone EWrite1=Occupied, 2=Unoccupied, 3=Off
MV105Zone F ControlControl mode for zone FWrite1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock
MV106Zone F OccupancyOccupied status for zone FWrite1=Occupied, 2=Unoccupied, 3=Off
MV107Stage 1 ZoneStage 1 zoneWrite1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF
MV108Stage1 DrainStage 1 drainWrite1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12
MV109Stage 2 ZoneStage 2 zoneWrite1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF
MV110Stage 2 DrainStage 2 drainWrite1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12
MV111Stage 3 ZoneStage 3 zoneWrite1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF
MV112Stage 3 DrainStage 3 drainWrite1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12
MV113Stage 4 ZoneStage 4 zoneWrite1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF
MV114Stage 4 DrainStage 4 drainWrite1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12
MV115Stage 5 ZoneStage 5 zoneWrite1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF
MV116Stage 5 DrainStage 5 drainWrite1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12
MV117Stage 6 ZoneStage 6 zoneWrite1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF
MV118Stage 6 DrainStage 6 drainWrite1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12
MV120Cooling Drain Control ModeCooling drain control modeWrite1=Off, 2=TimeLatch
MV135Low Water Temperature AlarmStatus of the low water temperature alarmWrite1=Alarm, 2=Warning
MV160Diagnostic StateStatus of the diagnostic stateWrite1=Off, 2=On
MV161Diagnostic CommandStatus of the diagnostic commandWrite1=Spray, 2=Drain
MV162Control Signal TypeControl signal typeWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
Other1NSDF Core ProgramNSDF Core ProgramWrite
Other2Module 1Module 1Write
Other3Module 2Module 2Write
Other4Module 3Module 3Write
Other5Module 4Module 4Write
Other6Module 5Module 5Write
Other7Module 6Module 6Write
Other8Module 7Module 7Write
Other9Module 8Module 8Write
Other10Module 9Module 9Write
Other11Module 10Module 10Write
Other12Module 11Module 11Write
Other13Module 12Module 12Write
Other14Module 13Module 13Write
Other15NSDF DatabaseNSDF DatabaseWrite
FILE1Core File.Core FileWrite
FILE2SysLogAlarmSystem Log AlarmWrite
FILE7USB System Log FileUSB System Log fileWrite
FILE8USB System Alarm Log FileUSB System Alarm Log fileWrite
FILE16System Log FileSystem Log fileWrite
FILE19UpdatePackageFileUpdate Package fileWrite
SCH1Occupancy ScheduleWeekly occupancy schedule to specify which occupancy state is active during specific...Write
SCH2Drain ScheduleCustomized draining schedule with up to six events per dayWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKH4 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic SKH4

How many BACnet points does the Neptronic SKH4 have?

This list has 325 BACnet objects: 10 analog inputs, 2 analog outputs, 174 analog values, 11 binary inputs, 19 binary outputs, 25 binary values, 6 files, 2 schedules, 54 multi-state values, 7 characterstring values, 15 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic SKH4 BACnet points are writable?

238 of the 325 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic SKH4 BACnet documentation?

The source is SKH4 High-Pressure Atomizer BACnet Communication Module User Guide (SKH4-BACnet Guide-240126 (V1.00)), revision 2024-01-26, published free by Neptronic at https://www.neptronic.com/Humidifiers/pdf/2024/SKH4-BACnet%20Guide-240126%20(V1.00).pdf.

What are the minimum BACnet points to integrate the Neptronic SKH4?

Start with MV 95 Zone A Control (Zone A on/off: 1 = Off, 2 = Normal); MV 96 Zone A Occupancy (1 = occupied, 2 = unoccupied, 3 = off); MV 28 Control Profile (Control profile: choose a Network profile); AV 138 Control Network Demand (Direct demand written by the BMS, %); AV 107 Room RH Setpoint (Occupied room RH setpoint (internal control)); AV 106 Room RH Network Reading (Network room RH reading for internal control); MV 83 System Power State (System on/off status); AV 143 User Demand (Current humidity demand %); BV 68 Drive State (Drive status: 0 = Ok, 1 = Fault); BV 44 Network Control State (1 = fault: network control lost (AV 223 timeout)).

How do I enable BMS control of the Neptronic SKH4?

No writable system on/off object is listed (MSV 83 System Power State is read-only in this guide). Zones are switched with the Zone x Control MSVs (1 = Off, 2 = Normal...) and Zone x Occupancy; the demand source comes from MSV 28 / MSV 43.

Does the Neptronic SKH4 need a BACnet heartbeat or have a communication timeout?

AV 223 Network Timeout (1-900 s) is how long the unit tries to reach the BACnet or Modbus network before it stops operating; BV 44 Network Control State shows 1 = Fault. AV 441 sets the internal zone communication timeout, with per-zone alarms BV 86-91.

Can the BMS supply sensor values to the Neptronic SKH4?

Network room RH to AV 106 (MSV 33 = Network) with setpoints AV 107-109; room temperature to AV 155 for cooling profiles; supply high limit RH to AV 122 (MSV 38 = Network) and temperature to AV 175 (MSV 71 = Network). Direct demand goes to AV 138 and high limit to AV 139.

How do I check these points on the real SKH4?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: SKH4 High-Pressure Atomizer BACnet Communication Module User Guide · SKH4-BACnet Guide-240126 (V1.00) · rev. 2024-01-26. Object names, instances and units are reproduced as published; descriptions are our own.