Steam-to-steam humidifier · BACnet points list

Neptronic SKS4 BACnet points list

Updated 28 October 2026

Short answer

The SKS4 makes clean steam from a building boiler steam supply through a heat exchanger. Its controller exposes BACnet MS/TP and BACnet IP with the same control structure as the SKE4: selectable demand sources, network demand and RH inputs, operating state, alarms and service counters.

This page lists 180 BACnet objects for the Neptronic SKS4 — 122 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
SKS4
Equipment
Steam-to-steam humidifier
Equipment type
Humidifiers
BACnet objects
180 (122 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
153000 + MAC address (153001 by default)
Also known as
SKS4 steam to steam humidifier, SKS4 BACnet
Source document
SKS4 Steam to Steam Humidifier BACnet Communication Module User Guide · SKS4-BACnet Guide-220509 (V2.03) · rev. 2022-05-09
Download CSV 180 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Neptronic SKS4

Integration in brief

Choose a network control profile (MSV 28) or set MSV 43 to Network, then write demand to AV 138 (or room RH to AV 106 with setpoint AV 107). Turn the unit on/off with MSV 83 and alarm on MSV 64 and BV 44.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 83System Power StateSystem on/off from the BMSWrite
MV 28Control ProfileControl profile: choose a Network profileWrite
AV 138Humidity Control Network DemandNetwork humidity demand written by the BMSCommand
AV 107Room RH SetpointOccupied room RH setpoint (internal control)Write
AV 106Room RH Network ReadingNetwork room RH reading for internal controlCommand
MV 60Boiler StateHumidifier operating stateRead
AV 149Boiler Power OutputActual steam output of the humidifier %Read
MV 64Boiler AlarmActive alarmRead
BV 44Network Control State1 = fault: network control lost (AV 223 timeout)Write

Enable & remote start

MSV 83 System Power State is writable (1 = Off, 2 = On); the control source follows MSV 28 Control Profile or MSV 43 with the Custom profile.

Heartbeat & communication loss

AV 223 Network Timeout (1-900 s) sets how long the humidifier tolerates loss of BACnet control communication before it stops; BV 44 Network Control State shows 1 = Fault.

Sensors & values from the BMS

Room RH from the BMS goes to AV 106 when MSV 33 = Network; setpoints AV 107-109; supply high limit reading AV 122 (MSV 38 = Network) and setpoint AV 123; direct demand AV 138 and high limit AV 139.

Network setup

Watch out for

Neptronic SKS4 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

180 of 180 shown
Type
Multi-state
Access
Show
Neptronic SKS4 BACnet Points List
DescriptionStates
AI1Cabinet Temperature SignalMeasured input voltage of the weatherproof enclosure temperature sensorVRead
AI5Control SignalControl demand analog input signalVRead
AI6Room RH SignalRoom humidity analog input signalVRead
AI7Supply RH SignalDuct or supply high limit humidity analog input signalVRead
AI9Water Level SignalMeasured input frequency of the water level sensorRead
AI10Water Level Low SignalResistive low water level sensor signalVRead
AI11Water Level High SignalResistive high water level sensor signalVRead
AI12Water Temperature SignalWater temperature sensor signalVRead
AI13Foam SignalFoam sensor signalVRead
AI25Main Power SupplyMeasured voltage in the power supplyVRead
AO1Steam Output Feedback SignalSteam output feedback signalVRead
AO9Steam Valve SignalSteam valve signalVRead
AV10MCU LoadCurrent microcontroller load%Read
AV11Memory LoadCurrent memory load%Read
AV31Water Level Replace IntervalAmount of time the humidifier may run using only the resistive water...daysWrite
AV41Control InputCurrent control input reading%Read
AV42Control MinMinimum value of the control demand analog input%Write
AV43Control MaxMaximum value of the control demand analog input%Write
AV44Control BiasBias value for the control demand analog input%Write
AV49Room RHRoom humidity reading%RHRead
AV50Room RH MinMinimum value of the room humidity analog input%RHWrite
AV51Room RH MaxMaximum value of the room humidity analog input%RHWrite
AV52Room RH BiasBias value of the room humidity analog input%RHWrite
AV57Supply High Limit RHDuct or supply high limit humidity analog input%RHRead
AV58Supply High Limit RH MinMinimum value of the duct or supply high limit humidity analog input%RHWrite
AV59Supply High Limit RH MaxMaximum value of the duct or supply high limit humidity analog input%RHWrite
AV60Supply High Limit RH BiasBias value of the duct or supply high limit humidity analog input%RHWrite
AV69Water TemperatureTemperature of water in the evaporation chamber°F or °CRead
AV72Water Temperature BiasBias value of temperature of water in the evaporation chamber°F or °CWrite
AV79RuntimeNumber of seconds that the system has been powered onsRead
AV81Cabinet TemperatureTemperature inside of the weather proof enclosure°F or °CWrite
AV85Power Output Feedback BiasBias value for the power output feedback signalVWrite
AV86Power Output Feedback MinMinimum value of the power output feedback signalVWrite
AV87Power Output Feedback MaxMaximum value of the power output feedback signalVWrite
AV88Power Output FeedbackFeedback value of the power output analog output%Command
AV94Steam Valve ControlControl signal coming from the actuated steam valve%Read
AV97Water LevelPercentage of water remaining in the evaporation chamber%Read
AV100Water Probe Low Pos ReadingLow position value of the water level sensorHzRead
AV101Water Probe High Pos ReadingHigh position value of the water level sensorHzRead
AV104Water Probe Abs Low Pos ReadingAbsolute low position value of the water level sensorHzRead
AV105Water Prob Abs High Pos ReadingAbsolute high position value of the water level sensorHzRead
AVmin106Room RH Network ReadingRoom relative humidity reading received from the network%RHCommand
AVmin107Room RH SetpointRoom relative humidity setpoint received from the network%RHWrite
AV108Room RH Unoccupied SetpointRoom relative humidity reading received from the network during no occupancy state%RHWrite
AV109Room RH Vacant SetpointRoom relative humidity reading received from the network during vacancy%RHWrite
AV110Room Demand Proportional GainRoom demand proportional gainWrite
AV111Room Demand Integral TimeRoom demand integral timesWrite
AV112Room Demand Derivative TimeRoom demand derivative timesWrite
AV120Room DemandHumidity demand within the room%Command
AV122Supply High Limit Network ReadingSupply high limit reading received from the network%RHCommand
AV123Supply High Limit SetpointSupply high limit setpoint received from the network%RHWrite
AV126Supply High Limit Proportional GainSupply high limit demand proportional gainWrite
AV127Supply High Limit Integral TimeSupply high limit demand integral timesWrite
AV128Supply High Limit Derivative TimeSupply high limit demand derivative timesWrite
AV136Supply High Limit DemandSupply high limit humidity demand value%Command
AVmin138Humidity Control Network DemandHumidity control demand received from the network%Command
AV139Humidity Control Network High LimitHumidity control high limit received from the network%Command
AV143Humidity DemandCurrent humidity demand%Read
AV145System Power OutputMeasured power output of the system%Read
AV147Boiler DemandMeasured humidity demand of the humidifier%Command
AVmin149Boiler Power OutputMeasured power output of the humidifier%Read
AV150Boiler Run TimeTotal runtime of the humidifierhRead
AV151Boiler On TimeTotal operating time of the humidifierhRead
AV152Boiler Service Run TimeRun time of the humidifier since the last servicinghRead
AV153Boiler Service On TimeOperating time of the humidifier since the last servicinghRead
AV162Boiler Minimum Steam OutputMinimum steam production demand value, below which no steam will be produced%Write
AV163Boiler Drain IntervalDrain cyclehWrite
AV164Boiler Drain VolumeVolume of water that is drained from the chamber, relative to the...%Write
AV165Boiler Max Steam OutputMaximum steam output of a modulating humidifier relative to its total capacity%Write
AV166Boiler Idle Time DrainAmount of time the humidifier can remain in standby mode until an...hWrite
AV167Boiler Idle Temperature SetpointIdle temperature setpoint for the evaporation chamber when there is no demand°F or °CWrite
AV170HRL TemperatureRoom temperature measured by the HRL24 controller°F or °CCommand
AV171HRL HumidityRoom humidity measured by the HRL24 controller%RHCommand
AV173Boiler Blowdown RateRate of boiler blowdown or water dilution in order to minimize water...%Write
AV174Boiler Service IntervalTime of operation before the humidifier calls for servicinghWrite
AV181Modbus TCP IP Keep Alive Time OutAmount of time the communication to the Modbus TCP/IP server stays open...minWrite
AV182Boiler Idle Tank Rinse IntervalAmount of time the humidifier stays in “Idle” or “Off” mode, before...daysWrite
AV208Steam Valve FeedbackFeedback signal coming from the actuated steam valve%Read
AV219Actuator DeadbandDeadband of the actuated steam valve%Write
AV220Humidity Demand Low Dead BandLower limit deadband for the humidity demand%RHWrite
AV223Network TimeoutAmount of time the humidifier may attempt to connect to the BACnet...sWrite
AV230Room Demand Proportional BandRoom demand proportional band%Write
AV231Supply High Limit Proportional BandSupply high limit proportional band%Write
AV233Boiler Manual Calibration TimeAmount of time that has been elapsed since the last manual calibration...hRead
AV236HRL Temperature BiasBias value of the temperature measured on the HRL controller°F or °CWrite
AV237HRL Humidity BiasBias value of the humidity measured on the HRL controller%RHWrite
BI1Air FlowStatus of the airflow switchRead0=Closed, 1=Open
BI2Supply High LimitStatus of the high limit contactRead0=Closed, 1=Open
BI3InterlockStatus of the interlockRead0=Closed, 1=Open
BI4Binary External DemandWhether there is currently a humidity demand, when an On/Off humidifier is...Read0=0%, 1=100%
BI8Water Leak DetectionWhether a water leak has been detectedRead0=Ok, 1=Leak
BI14Thermal CutoutStatus of the high temperature switchRead0=Closed, 1=Open
BI20RS485 InterfaceWhether the RS485 interface is available or notRead0=No, 1=Yes
BI21Ethernet InterfaceWhether the Ethernet interface is available or notRead0=No, 1=Yes
BI22Contactors PCB FuseStatus of the contactors PCB fuseRead0=Normal, 1=Blown Fuse
BI23Control PCB FuseStatus of the control PCB fuseRead0=Normal, 1=Open Fuse
BO2Alarm Warning RelayAlarm warning relayCommand0=Off, 1=On
BO3Service Warning RelayService warning relayCommand0=Off, 1=On
BO4Water Level ValveWater level sensor supply valveCommand0=Off, 1=On
BO5Tank Water ValveEvaporation chamber water supply valveCommand0=Off, 1=On
BO6Drain Cooler ValveInternal drain cooler valveCommand0=Off, 1=On
BO7Drain PumpFirst drain pumpCommand0=Off, 1=On
BO8Drain ValveNormally open drain valveCommand0=Off, 1=On
BO12Drain Pump 2Second drain pumpCommand0=Off, 1=On
BO13Drain Pump 3Third drain pumpCommand0=Off, 1=On
BO18Alarm LEDAlarm LEDCommand0=Off, 1=On
BO19Power LEDPower LEDCommand0=Off, 1=On
BO20BuzzerBuzzerCommand0=Off, 1=On
BV3Alarm BuzzerConfiguration value that enables or disables the alarm buzzer sound when there...Write0=Normal, 1=Disabled
BV14Water Level LowResistive low water level sensorRead0=Inactive, 1=Active
BV15Water Level HighResistive high water level sensorRead0=Inactive, 1=Active
BV16Foam SensorWhether foam has been detected within the evaporation chamberRead0=No Foam, 1=Foam
BV30Boiler Service OperationEnable the humidifier to continue producing steam, even when it is due...Write0=Not Allowed, 1=Allowed
BV32Boiler Service DueStatus value that indicates whether the humidifier is due for servicingRead0=Off, 1=On
BV34FoamWhether the humidifier has currently detected foam or notRead0=Ok, 1=Detected
BV36Boiler Line RinsePerform an automatic pipe line rinse cycle upon each start-up of the...Write0=Off, 1=On
BV38HRL Lock SetpointWhether the setpoint obtained from the HRL24 controller can be modifiedCommand0=Unlock, 1=Lock
BVmin44Network Control StateState of the control communication between the device and the BACnet networkWrite0=Normal, 1=Fault
BV48Inhibit Resistive ProbeDisable the resistive water level sensor probesWrite0=No, 1=Yes
BV52SMTP SSLUse a secure socket layer encrypt the communication between the device and...Write0=Off, 1=On
BV53SMTP PortPort number to be used for email transferWrite0=25, 1=587
BV54Notify AlarmGet notified of all humidifier alarm messages by emailWrite0=Off, 1=On
BV55Notify WarningGet notified of all humidifier warning messages by emailWrite0=Off, 1=On
BV56Notify App MsgGet notified of all humidifier event messages by emailWrite0=Off, 1=On
BV58Power Up DrainEnable an automatic draining cycle each time the humidifier is powered onWrite0=Off, 1=On
BV62Manual Water Calibration StateThat the water level sensor must be manually calibratedRead0=Ok, 1=Required
BV152AntiFreeze WarningStatus of the anti freeze warning indicating if the drain valve is...Read0=Inactive, 1=Drain
CSV10HMI OverwriteOverwrite the value displayed on the local display menuWrite
CSV22SMTP Server IP AddressServer IP address for the email accountWrite
CSV24SMTP Mail FromEmail address that will be sending the humidifier notification messagesWrite
CSV25SMTP Mail ToEmail address that will be receiving the humidifier notification messagesWrite
CSV26SMTP UsernameLogin username for the email accountWrite
CSV37EthernetMacAddMAC address of the Ethernet interfaceWrite
CSV62SMTP PasswordLogin password for the email accountWrite
MV9BACnet Server LanguageBACnet server languageWrite1=English
MV10BACnet Server List ModeCategory of BACnet objects to displayWrite1=Integrator, 2=Advanced, 3=Factory
MV11BACnet Server UnitsDisplay units for the BACnet serverWrite1=Metric, 2=Imperial
MV24Control Signal TypeSignal type for the control demand analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV25Room RH Signal TypeSignal type for the room humidity analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV26Supply RH Signal TypeSignal type for the duct or supply high limit humidity analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MVmin28Control ProfileA preconfigured control mode profile for the modulating humidity demandWrite1=ExternAnalog, 2=ExternNetwork, 3=InternAnalog, 4=InternNetwork, 5=HRL, 6=Custom
MV29Modulating High Limit ProfileA preconfigured control mode profile for the modulating high limit demandWrite1=Disabled, 2=ExternAnalog, 3=ExternNetwork, 4=InternAnalog, 5=InternNetwork, 6=Custom
MV32Occupancy StateOccupancy stateRead1=Occupied, 2=Unoccupied, 3=Vacant, 4=Off
MV33Room RH SourceReading source for the room demandWrite1=None, 2=RoomRH, 3=Network
MV34Room RH Setpoint SourceRoom demand setpoint sourceWrite1=None, 2=Internal, 3=ControlInput
MV38Supply High Limit Reading SourceReading source for the supply high limit demandWrite1=None, 2=SupplyHLRH, 3=Network
MV39Supply High Limit Setpoint SourceSupply high limit demand setpoint sourceWrite1=None, 2=Internal, 3=ControlInput
MV43Humidity Control Demand SourceHumidity control demand sourceWrite1=None, 2=ControlInput, 3=RoomDemand, 4=Network
MV44Humidity Control High Limit SourceHumidity control high limit sourceWrite1=None, 2=ControlInput, 3=SupplyHLDemand, 4=Network
MV51Humidity Control Cutout StateState of the safety control circuit and whether the circuit has been...Read1=Off, 2=Normal, 3=LowLimit, 4=HighLimit, 5=NoAirFlow, 6=Interlock
MV59Boiler RequestPerform one of the following actions for the humidifier: reset service counters...Write1=None, 2=Reset Alarms, 3=Drain, 4=Reset Counters, 5=Filling, 6=WaterCalib
MVmin60Boiler StateState of operation of the humidifierRead1=Off, 2=Idle, 3=LineRinse, 4=TankRinse, 5=Filling, 6=Draining, 7=Heating, 8=Boiling, 9=Alarm
MV63Boiler Fill ModeWater filling method for the fill valve: When set to OneShot, water...Write1=OneShot, 2=Pulsed
MVmin64Boiler AlarmStatus of the humidifier alarmRead1=Normal, 2=FailedPump, 3=FillTimeout, 4=BlockedPiping, 5=HeatTimeout, 6=Overheat, 7=WaterLeak, 8=Service, 9=Reserved, 10=TankBlocked, 11=RefillDelay
MV65Boiler Idle Tank Rinse OnWhether to enable automatic rinse cycles while the humidifier is turned on...Write1=Off, 2=On
MV66Boiler Idle Tank Rinse OffWhether to enable automatic rinse cycles while the humidifier is turned off...Write1=Off, 2=On
MV67Water Probe Auto CalibWhether to enable or disable the automatic calibration of the water level...Write1=Off, 2=On
MVmin83System Power StateWhether the system is powered on or offWrite1=Off, 2=On
MV95Boiler Startup Tank RinseWhether to enable an automatic rinse cycle upon each start-up of the...Write1=Off, 2=On
MV96Water Level Probe WarningWhether there is currently a warning message associated with the water level...Read1=Ok, 2=Replace
MV97Water Level Probe FailureWhich one of the water level sensor’s probes is currently not functioning...Read1=None, 2=Capacitive, 3=Resistive, 4=Both
MV98Water Level Probe AlarmWhether there is currently an alarm message to indicate that the water...Read0=Ok, 1=Defect, 2=NoCalib
Other1NSDF Core ProgramNSDF Core ProgramWrite
Other2BACnet Server ProgramBACnet Server ProgramWrite
Other3LCD_Display ProgramLCD_Display ProgramWrite
Other4Modbus Server ProgramModbus Server ProgramWrite
Other5RMHI ProgramRHMI ProgramWrite
Other6SKS ProgramSKS ProgramWrite
Other7Universal Humidifier Manager ProgramUniversal Humidifier Manager ProgramWrite
Other8Universal User Control ProgramUniversal User Control ProgramWrite
Other9Web Server ProgramWeb Server ProgramWrite
Other10Water Level Probe ProgramWater Level Probe ProgramWrite
Other15Database ProgramDatabase ProgramWrite
FILE2SysLogAlarmSystem Log AlarmWrite
FILE7USB System Log FileUSB System Log fileWrite
FILE8USB System Alarm Log FileUSB System Alarm Log fileWrite
FILE16System Log FileSystem Log fileWrite
FILE19UpdatePackageFileUpdate Package fileWrite
SCH1Occupancy ScheduleWeekly occupancy schedule to specify which occupancy state is active during specific...Write
SCH2Boiler Drain ScheduleCustomized draining schedule with up to six events per dayWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKS4 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic SKS4

How many BACnet points does the Neptronic SKS4 have?

This list has 180 BACnet objects: 10 analog inputs, 2 analog outputs, 74 analog values, 10 binary inputs, 12 binary outputs, 19 binary values, 5 files, 2 schedules, 28 multi-state values, 7 characterstring values, 11 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic SKS4 BACnet points are writable?

122 of the 180 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic SKS4 BACnet documentation?

The source is SKS4 Steam to Steam Humidifier BACnet Communication Module User Guide (SKS4-BACnet Guide-220509 (V2.03)), revision 2022-05-09, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/SKS4/20230525/SKS4-BACnet%20Guide-220509%20(V2.03).pdf.

What are the minimum BACnet points to integrate the Neptronic SKS4?

Start with MV 83 System Power State (System on/off from the BMS); MV 28 Control Profile (Control profile: choose a Network profile); AV 138 Humidity Control Network Demand (Network humidity demand written by the BMS); AV 107 Room RH Setpoint (Occupied room RH setpoint (internal control)); AV 106 Room RH Network Reading (Network room RH reading for internal control); MV 60 Boiler State (Humidifier operating state); AV 149 Boiler Power Output (Actual steam output of the humidifier %); MV 64 Boiler Alarm (Active alarm); BV 44 Network Control State (1 = fault: network control lost (AV 223 timeout)).

How do I enable BMS control of the Neptronic SKS4?

MSV 83 System Power State is writable (1 = Off, 2 = On); the control source follows MSV 28 Control Profile or MSV 43 with the Custom profile.

Does the Neptronic SKS4 need a BACnet heartbeat or have a communication timeout?

AV 223 Network Timeout (1-900 s) sets how long the humidifier tolerates loss of BACnet control communication before it stops; BV 44 Network Control State shows 1 = Fault.

Can the BMS supply sensor values to the Neptronic SKS4?

Room RH from the BMS goes to AV 106 when MSV 33 = Network; setpoints AV 107-109; supply high limit reading AV 122 (MSV 38 = Network) and setpoint AV 123; direct demand AV 138 and high limit AV 139.

How do I check these points on the real SKS4?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: SKS4 Steam to Steam Humidifier BACnet Communication Module User Guide · SKS4-BACnet Guide-220509 (V2.03) · rev. 2022-05-09. Object names, instances and units are reproduced as published; descriptions are our own.