Evaporative humidifier · BACnet points list

Neptronic SKV BACnet points list

Updated 28 October 2026

Short answer

The SKV is a multi-module evaporative humidifier. Its controller speaks BACnet MS/TP and exposes control mode and source selection, network setpoints and readings, a network fallback timeout, and per-module (1-4) demand, state, valve, float and fault objects.

This page lists 277 BACnet objects for the Neptronic SKV — 242 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
SKV
Equipment
Evaporative humidifier
Equipment type
Humidifiers
BACnet objects
277 (242 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
153000 by default
Also known as
SKV evaporative humidifier, SKV BACnet
Source document
SKV Evaporative Humidifier BACnet User Guide · rev. 2018-09-05
Download CSV 277 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Neptronic SKV

Integration in brief

Set MSV 4 ControlMode to Network (or an internal mode with network sources) and write demand to AV 5, or feed room RH via MSV 3 = Network. Turn the system on with BV 116 SystemPower and keep network values fresh inside the fallback timeout (AV 38).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 116SystemPowerSystem power on/offWrite
MV 4ControlModeControl mode (6 = Network)Write
AV 5SystDemandDemand from the BMS, % (when MSV 4 = Network)Write
AV 16SetpointRHBMS RH setpoint (when MSV 5 = Network)Write
AV 13RoomRHBMS room RH (when MSV 3 = Network)Write
MV 16Module1StateStand-by/drain/fill/ready/alarm state of module 1Write
AV 1SystOutputActual system output %Write
BV 118AlarmRelayClosed on any alarm but airflow cutout/service warningWrite
BV 121NetworkFallbackAlarmOn when network values time out (AV 38)Write

Enable & remote start

BV 116 SystemPower: ON = normal operation, OFF = demand inhibited. MSV 4 ControlMode selects an analog input, internal temperature/RH control or Network.

Heartbeat & communication loss

AV 38 NetworkFallbackTimeout (1-15 min) applies whenever at least one control input uses Network as its source; AV 39 counts down and BV 121 NetworkFallbackAlarm turns on when it expires.

Sensors & values from the BMS

Set MSV 3 RoomRHSource or MSV 2 RoomTempSource to Network and write the values from the BMS; MSV 5 SetpointSource = Network uses the external setpoints AV 16 (RH) and AV 17 (temperature).

Network setup

Watch out for

Neptronic SKV BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

277 of 277 shown
Type
Multi-state
Access
Show
Neptronic SKV BACnet Points List
DescriptionStates
AI1ExternalDemandExternal demand signal measurementmVRead
AI2ExternalSetpointExternal setpoint signal measurementmVRead
AI3RoomTempSensorRoom temperature sensor signal measurementmVRead
AI4RoomRHSensorRoom relative humidity sensor signal measurementmVRead
AI5DuctSensorDuct relative humidity sensor signal measurementmVRead
AI6Module1WaterLevelSensorModule 1 water level sensor signal measurementHzRead
AI7Module2WaterLevelSensorModule 2 water level sensor signal measurementHzRead
AI8Module3WaterLevelSensorModule 3 water level sensor signal measurementHzRead
AI9Module4WaterLevelSensorModule 4 water level sensor signal measurementHzRead
AI10Module1WaterTempSensorModule 1 water temperature sensor signal measurementmVRead
AI11Module2WaterTempSensorModule 2 water temperature sensor signal measurementmVRead
AI12Module3WaterTempSensorModule 3 water temperature sensor signal measurementmVRead
AI13Module4WaterTempSensorModule 4 water temperature sensor signal measurementmVRead
AVmin1SystOutputSystem output in percent%Write
AV2SystOutputSystem output in Mass Flow unitsWrite
AV3SystCapacityTotal system output capacityWrite
AV4NumOfModulesNumber of humidifier modulesWrite
AVmin5SystDemandSystem demand%Write
AV6SystLimitSystem output limit as per high limit signals%Write
AV7SystOutputLockOnSystem output lock or limit for load shedding%Write
AV8SystFeedbackSystem output feedback signalmVWrite
AV9SimDemandSimulation mode demand%Write
AV10SimDurationSimulation mode durationminWrite
AV11SimCountdownSimulation mode countdownsWrite
AV12AnalogDemandAnalog system demand%Write
AVmin13RoomRHRoom relative humidity%RHWrite
AV14RoomTempRoom temperatureWrite
AV15DuctRHDuct relative humidity%RHWrite
AVmin16SetpointRHExternal relative humidity setpoint%RHWrite
AV17SetpointTempExternal temperature setpointWrite
AV18InternalSetpointOccupiedInternal %RH setpoint during occupancy%Write
AV19InternalSetpointOccupiedInternal temperature setpoint during occupancy°F or °CWrite
AV20InternalSetpointUnoccupiedInternal %RH setpoint during occupancy%Write
AV21InternalSetpointUnoccupiedInternal temperature setpoint during occupancy°F or °CWrite
AV22InternalSetpointVacantInternal %RH setpoint during vacancy%Write
AV23InternalSetpointVacantInternal temperature setpoint during vacancy°F or °CWrite
AV24ProportionalRampProportional ramp for %RH%RHWrite
AV25ProportionalRampProportional ramp for temperature°F or °CWrite
AV26IntegralRampIntegral ramp for %RH%RHWrite
AV27IntegralRampIntegral ramp for temperature°F or °CWrite
AV28DeadbandDeadband for %RH%RHWrite
AV29DeadbandDeadband for temperature°F or °CWrite
AV30HighLimitSetpointAnalog high limit setpoint value%RHWrite
AV31HighLimitProportionalRampAnalog high limit proportional ramp%RHWrite
AV32DilutionIntervalWater dilution intervalminWrite
AV33DilutionCyclesNumber of water dilution cyclesWrite
AV34CleaningIntervalCleaning intervalmonthsWrite
AV35AutoDrainIntervalAutomatic drain intervalhWrite
AV36UVLampIntervalUV lamp replacement intervalhWrite
AV37InactivityDelaySystem inactivity delayhWrite
AV38NetworkFallbackTimeoutNetwork fallback timeoutminWrite
AV39NetworkTimeoutCountdownNetwork fallback timeout countdownsWrite
AV40InactivityCounterSystem inactivity downcountersWrite
AV41Module1DrainTimeoutCountdownModule 1 drain timeout countdownsWrite
AV42Module2DrainTimeoutCountdownModule 2 drain timeout countdownsWrite
AV43Module3DrainTimeoutCountdownModule 3 drain timeout countdownsWrite
AV44Module4DrainTimeoutCountdownModule 4 drain timeout countdownsWrite
AV45Module1FillTimeoutCountdownModule 1 fill timeout countdownsWrite
AV46Module2FillTimeoutCountdownModule 2 fill timeout countdownsWrite
AV47Module3FillTimeoutCountdownModule 3 fill timeout countdownsWrite
AV48Module4FillTimeoutCountdownModule 4 fill timeout countdownsWrite
AV49Module1InactivityCountdownModule 1 inactivity countdownsWrite
AV50Module2InactivityCountdownModule 2 inactivity countdownsWrite
AV51Module3InactivityCountdownModule 3 inactivity countdownsWrite
AV52Module4InactivityCountdownModule 4 inactivity countdownsWrite
AV53Module1StateCountdownModule 1 state countdownWrite
AV54Module2StateCountdownModule 2 state countdownWrite
AV55Module3StateCountdownModule 3 state countdownWrite
AV56Module4StateCountdownModule 4 state countdownWrite
AV57Module1DemandModule 1 demand%Write
AV58Module2DemandModule 2 demand%Write
AV59Module3DemandModule 3 demand%Write
AV60Module4DemandModule 4 demand%Write
AV61Module1OutputModule 1 output%Write
AV62Module2OutputModule 2 output%Write
AV63Module3OutputModule 3 output%Write
AV64Module4OutputModule 4 output%Write
AV65Module1CapacityModule 1 total capacityWrite
AV66Module2CapacityModule 2 total capacityWrite
AV67Module3CapacityModule 3 total capacityWrite
AV68Module4CapacityModule 4 total capacityWrite
AV69Module1WaterLevelModule 1 water level%Write
AV70Module2WaterLevelModule 2 water level%Write
AV71Module3WaterLevelModule 3 water level%Write
AV72Module4WaterLevelModule 4 water level%Write
AV73Module1WaterTempModule 1 water temperature°F or °CWrite
AV74Module2WaterTempModule 2 water temperature°F or °CWrite
AV75Module3WaterTempModule 3 water temperature°F or °CWrite
AV76Module4WaterTempModule 4 water temperature°F or °CWrite
AV77Module1PumpStageWeightModule 1 pump's stage weight relative to module's full capacity%Write
AV78Module2PumpStageWeightModule 2 pump's stage weight relative to module's full capacity%Write
AV79Module3PumpStageWeightModule 3 pump's stage weight relative to module's full capacity%Write
AV80Module4PumpStageWeightModule 4 pump's stage weight relative to module's full capacity%Write
AV81Module1Valve1StageWeightStage weight of Module 1, valve 1 relative to module's full capacity%Write
AV82Module2Valve1StageWeightStage weight of Module 2, valve 1 relative to module's full capacity%Write
AV83Module3Valve1StageWeightStage weight of Module 3, valve 1 relative to module's full capacity%Write
AV84Module4Valve1StageWeightStage weight of Module 4, valve 1 relative to module's full capacity%Write
AV85Module1Valve2StageWeightStage weight of Module 1, valve 2 relative to module's full capacity%Write
AV86Module2Valve2StageWeightStage weight of Module 2, valve 2 relative to module's full capacity%Write
AV87Module3Valve2StageWeightStage weight of Module 3, valve 2 relative to module's full capacity%Write
AV88Module4Valve2StageWeightStage weight of Module 4, valve 2 relative to module's full capacity%Write
AV89Module1Valve3StageWeightStage weight of Module 1, valve 3 relative to module's full capacity%Write
AV90Module2Valve3StageWeightStage weight of Module 2, valve 3 relative to module's full capacity%Write
AV91Module3Valve3StageWeightStage weight of Module 3, valve 3 relative to module's full capacity%Write
AV92Module4Valve3StageWeightStage weight of Module 4, valve 3 relative to module's full capacity%Write
AV93Module1Valve4StageWeightStage weight of Module 1, valve 4 relative to module's full capacity%Write
AV94Module2Valve4StageWeightStage weight of Module 2, valve 4 relative to module's full capacity%Write
AV95Module3Valve4StageWeightStage weight of Module 3, valve 4 relative to module's full capacity%Write
AV96Module4Valve4StageWeightStage weight of Module 4, valve 4 relative to module's full capacity%Write
AV97Module1TotalDutyTotal duty of Module 1 (in hours) at 100% outputhWrite
AV98Module2TotalDutyTotal duty of Module 2 (in hours) at 100% outputhWrite
AV99Module3TotalDutyTotal duty of Module 3 (in hours) at 100% outputhWrite
AV100Module4TotalDutyTotal duty of Module 4 (in hours) at 100% outputhWrite
BV1Module1DrainRequestDrain request for Module 1Write0=OFF, 1=ON
BV2Module2DrainRequestDrain request for Module 2Write0=OFF, 1=ON
BV3Module3DrainRequestDrain request for Module 3Write0=OFF, 1=ON
BV4Module4DrainRequestDrain request for Module 4Write0=OFF, 1=ON
BV5Module1InactivityInactivity state for Module 1Write0=True, 1=False
BV6Module2InactivityInactivity state for Module 2Write0=True, 1=False
BV7Module3InactivityInactivity state for Module 3Write0=True, 1=False
BV8Module4InactivityInactivity state for Module 4Write0=True, 1=False
BV9Module1SilverIonChangeDueDate on which Silver Ion cartridge change is due for Module 1Write0=True, 1=False
BV10Module2SilverIonChangeDueDate on which Silver Ion cartridge change is due for Module 2Write0=True, 1=False
BV11Module3SilverIonChangeDueDate on which Silver Ion cartridge change is due for Module 3Write0=True, 1=False
BV12Module4SilverIonChangeDueDate on which Silver Ion cartridge change is due for Module 4Write0=True, 1=False
BV13Module1UVLampChangeDueDate on which UV lamp change is due for Module 1Write0=True, 1=False
BV14Module2UVLampChangeDueDate on which UV lamp change is due for Module 2Write0=True, 1=False
BV15Module3UVLampChangeDueDate on which UV lamp change is due for Module 3Write0=True, 1=False
BV16Module4UVLampChangeDueDate on which UV lamp change is due for Module 4Write0=True, 1=False
BV17Module1CleaningChangeDueDate on which cleaning is due for Module 1Write0=True, 1=False
BV18Module2CleaningChangeDueDate on which cleaning is due for Module 2Write0=True, 1=False
BV19Module3CleaningChangeDueDate on which cleaning is due for Module 3Write0=True, 1=False
BV20Module4CleaningChangeDueDate on which cleaning is due for Module 4Write0=True, 1=False
BV21Module1DilutionWater dilution cycle for Module 1Write0=Waiting, 1=In Progress
BV22Module2DilutionWater dilution cycle for Module 2Write0=Waiting, 1=In Progress
BV23Module3DilutionWater dilution cycle for Module 3Write0=Waiting, 1=In Progress
BV24Module4DilutionWater dilution cycle for Module 4Write0=Waiting, 1=In Progress
BV25Module1ServiceWarningUpcoming cleaning for Module 1Write0=OFF, 1=ON
BV26Module2ServiceWarningUpcoming cleaning for Module 2Write0=OFF, 1=ON
BV27Module3ServiceWarningUpcoming cleaning for Module 3Write0=OFF, 1=ON
BV28Module4ServiceWarningUpcoming cleaning for Module 4Write0=OFF, 1=ON
BV29Module1ServiceAlarmAlarm for Module 1 when cleaning, UV lamp change or Silver Ion...Write0=OFF, 1=ON
BV30Module2ServiceAlarmAlarm for Module 2 when cleaning, UV lamp change or Silver Ion...Write0=OFF, 1=ON
BV31Module3ServiceAlarmAlarm for Module 3 when cleaning, UV lamp change or Silver Ion...Write0=OFF, 1=ON
BV32Module4ServiceAlarmAlarm for Module 4 when cleaning, UV lamp change or Silver Ion...Write0=OFF, 1=ON
BV33Module1DrainFaultDrain fault alarm for Module 1 when drain countdown reaches 0Write0=OFF, 1=ON
BV34Module2DrainFaultDrain fault alarm for Module 2 when drain countdown reaches 0Write0=OFF, 1=ON
BV35Module3DrainFaultDrain fault alarm for Module 3 when drain countdown reaches 0Write0=OFF, 1=ON
BV36Module4DrainFaultDrain fault alarm for Module 4 when drain countdown reaches 0Write0=OFF, 1=ON
BV37Module1WaterInletFaultInlet fault for Module 1 when fill countdown reaches 0Write0=OFF, 1=ON
BV38Module2WaterInletFaultInlet fault for Module 2 when fill countdown reaches 0Write0=OFF, 1=ON
BV39Module3WaterInletFaultInlet fault for Module 3 when fill countdown reaches 0Write0=OFF, 1=ON
BV40Module4WaterInletFaultInlet fault for Module 4 when fill countdown reaches 0Write0=OFF, 1=ON
BV41Module1WaterLevelDefectWater level defect for Module 1 when both capacitive sensor and float...Write0=OFF, 1=ON
BV42Module2WaterLevelDefectWater level defect for Module 2 when both capacitive sensor and float...Write0=OFF, 1=ON
BV43Module3WateLevelDefectWater level defect for Module 3 when both capacitive sensor and float...Write0=OFF, 1=ON
BV44Module4WaterLevelDefectWater level defect for Module 4 when both capacitive sensor and float...Write0=OFF, 1=ON
BV45Module1WaterTempDefectWater temperature sensor defect for Module 1Write0=OFF, 1=ON
BV46Module2WaterTempDefectWater temperature sensor defect for Module 2.Module stops operationWrite0=OFF, 1=ON
BV47Module3WaterTempDefectWater temperature sensor defect for Module 3Write0=OFF, 1=ON
BV48Module4WaterTempDefectWater temperature sensor defect for Module 4Write0=OFF, 1=ON
BV49Module1WaterLevelFaultWater level fault for Module 1 when capacitive level sensor is not...Write0=OFF, 1=ON
BV50Module2WaterLevelFaultWater level fault for Module 2 when capacitive level sensor is not...Write0=OFF, 1=ON
BV51Module3WateLevelFaultWater level fault for Module 3 when capacitive level sensor is not...Write0=OFF, 1=ON
BV52Module4WaterLevelFaultWater level fault for Module 4 when capacitive level sensor is not...Write0=OFF, 1=ON
BV53Module1HighWaterTempHigh water temperature for Module 1 when water temperature equals 25°C (77°F)...Write0=OFF, 1=ON
BV54Module2HighWaterTempHigh water temperature for Module 2 when water temperature equals 25°C (77°F)...Write0=OFF, 1=ON
BV55Module3HighWaterTempHigh water temperature for Module 3 when water temperature equals 25°C (77°F)...Write0=OFF, 1=ON
BV56Module4HighWaterTempHigh water temperature for Module 4 when water temperature equals 25°C (77°F)...Write0=OFF, 1=ON
BV57Module1HighWaterTempFaultHigh water temperature fault for Module 1 when Water temperature keeps at...Write0=OFF, 1=ON
BV58Module2HighWaterTempFaultHigh water temperature fault for Module 2 when Water temperature keeps at...Write0=OFF, 1=ON
BV59Module3HighWaterTempFaultHigh water temperature fault for Module 3 when Water temperature keeps at...Write0=OFF, 1=ON
BV60Module4HighWaterTempFaultHigh water temperature fault for Module 4 when Water temperature keeps at...Write0=OFF, 1=ON
BV61Module1FloatFaultWater float of Module 1 is in a fault conditionWrite0=OFF, 1=ON
BV62Module2FloatFaultWater float of Module 2 is in a fault conditionWrite0=OFF, 1=ON
BV63Module3FloatFaultWater float of Module 3 is in a fault conditionWrite0=OFF, 1=ON
BV64Module4FloatFaultWater float of Module 4 is in a fault conditionWrite0=OFF, 1=ON
BV65Module1CirculationPumpCirculation pump status of Module 1Write0=OFF, 1=ON
BV66Module2CirculationPumpCirculation pump status of Module 2Write0=OFF, 1=ON
BV67Module3CirculationPumpCirculation pump status of Module 3Write0=OFF, 1=ON
BV68Module4CirculationPumpCirculation pump status of Module 4Write0=OFF, 1=ON
BV69Module1FillValveFill valve status of Module 1Write0=OFF, 1=ON
BV70Module2FillValveFill valve status of Module 2Write0=OFF, 1=ON
BV71Module3FillValveFill valve status of Module 3Write0=OFF, 1=ON
BV72Module4FillValveFill valve status of Module 4Write0=OFF, 1=ON
BV73Module1DrainDrain status of Module 1Write0=OFF, 1=ON
BV74Module2DrainDrain status of Module 2Write0=OFF, 1=ON
BV75Module3DrainDrain status of Module 3Write0=OFF, 1=ON
BV76Module4DrainDrain status of Module 4Write0=OFF, 1=ON
BV77Module1StageValve1Status of Module 1's stage valve 1Write0=OFF, 1=ON
BV78Module2StageValve1Status of Module 2's stage valve 1Write0=OFF, 1=ON
BV79Module3StageValve1Status of Module 3's stage valve 1Write0=OFF, 1=ON
BV80Module4StageValve1Status of Module 4's stage valve 1Write0=OFF, 1=ON
BV81Module1StageValve2Status of Module 1's stage valve 2Write0=OFF, 1=ON
BV82Module2StageValve2Status of Module 2's stage valve 2Write0=OFF, 1=ON
BV83Module3StageValve2Status of Module 3's stage valve 2Write0=OFF, 1=ON
BV84Module4StageValve2Status of Module 4's stage valve 2Write0=OFF, 1=ON
BV85Module1StageValve3Status of Module 1's stage valve 3Write0=OFF, 1=ON
BV86Module2StageValve3Status of Module 2's stage valve 3Write0=OFF, 1=ON
BV87Module3StageValve3Status of Module 3's stage valve 3Write0=OFF, 1=ON
BV88Module4StageValve3Status of Module 4's stage valve 3Write0=OFF, 1=ON
BV89Module1StageValve4Status of Module 1's stage valve 4Write0=OFF, 1=ON
BV90Module2StageValve4Status of Module 2's stage valve 4Write0=OFF, 1=ON
BV91Module3StageValve4Status of Module 3's stage valve 4Write0=OFF, 1=ON
BV92Module4StageValve4Status of Module 4's stage valve 4Write0=OFF, 1=ON
BV93SimModeSimulation mode stateWrite0=OFF, 1=ON
BV94SystInactivitySystem inactivity stateWrite0=True, 1=False
BV95SystResetAlarmsManual system reset alarm requestWrite0=OFF, 1=ON
BV96AirFlowCutoutStatus is On when no air flow (AirFlowInput = opened)Write0=OFF, 1=ON
BV97HighLimitCutoutStatus is On when too much humidity is present inside duct (HighLimitInput...Write0=OFF, 1=ON
BV98InterlockCutoutStatus is On when InterlockInput = openedWrite0=OFF, 1=ON
BV99RoomTempSensorDefectStatus is On when room temperature sensor is defectiveWrite0=OFF, 1=ON
BV100RoomRHSensorDefectStatus is On when room relative humidity sensor is defectiveWrite0=OFF, 1=ON
BV101DuctSensorDefectStatus is On when duct's relative humidity is defectiveWrite0=OFF, 1=ON
BV102Module1CommTimeoutStatus is On when communication is lost with Module 1Write0=OFF, 1=ON
BV103Module2CommTimeoutStatus is On when communication is lost with Module 2Write0=OFF, 1=ON
BV104Module3CommTimeoutStatus is On when communication is lost with Module 3Write0=OFF, 1=ON
BV105Module4CommTimeoutStatus is On when communication is lost with Module 4Write0=OFF, 1=ON
BV106SystOutputLimitedStatus is On when output is limited by any high limit signalsWrite0=OFF, 1=ON
BV107RunWhileServiceAlarmWhen ON, modules will continue demand output even when their service alarm...Write0=OFF, 1=ON
BV108TempUnitsAvailable temperature unit options, °C and °FWrite0=°C, 1=°F
BV109MassflowUnitsAvailable mass flow units, percent and mass flowWrite0=kg/h, 1=lb/h
BV110OutputDisplayDisplay of output in percent or mass flow unitsWrite0=Percent, 1=MassFlow
BV111AlarmBeepWhen the alarm beep is ON, any alarm sets the buzzer output...Write0=OFF, 1=ON
BV112KeyBeepWhen the key beep is ON, the buzzer will beep to confirm...Write0=OFF, 1=ON
BV113OccupancyScheduleWhen the Occupancy Schedule status is ON and is in any internal...Write0=OFF, 1=ON
BV114TimeFormatAvailable time format, 12 and 24 hoursWrite0=24hr, 1=12hr
BV115SilverIonNotifWhen ON, the modules will notify when Silver Ion cartridge is due...Write0=OFF, 1=ON
BVmin116SystemPowerSystem normal operation when ON, produces humidity as per demandWrite0=OFF, 1=ON
BV117WaterLevelCalibrationWhen ON, water level capacitive sensor will be automatically calibrated each time...Write0=OFF, 1=ON
BVmin118AlarmRelayClosed when any alarm is on but AirFlowCutout and ServiceWarningWrite0=Opened, 1=Closed
BV119MaitenanceRelayClosed when ServiceAlarm or ServiceWarning is onWrite0=Opened, 1=Closed
BV120BuzzerON when a key push event is acknowledge and KeyBeep is on...Write0=OFF, 1=ON
BVmin121NetworkFallbackAlarmON during a network fallback alarmWrite0=OFF, 1=ON
BI1AirflowInputAir flow switch inputRead0=Opened, 1=Closed
BI2HighLimitInputHigh limit switch inputRead0=Opened, 1=Closed
BI3InterlockInputInterlock cutout inputRead0=Opened, 1=Closed
BI4DemandInputBinary demand (all or nothing) inputRead0=Opened, 1=Closed
BI5MemoryCardMounted when card is physically detectedRead0=Unmounted, 1=Mounted
BI6Module1LowFloatLow water level float state input for Module 1, closed when the...Read0=Opened, 1=Closed
BI7Module2LowFloatLow water level float state input for Module 2, closed when the...Read0=Opened, 1=Closed
BI8Module3LowFloatLow water level float state input for Module 3, closed when the...Read0=Opened, 1=Closed
BI9Module4LowFloatLow water level float state input for Module 4, closed when the...Read0=Opened, 1=Closed
BI10Module1HighFloatHigh water level float state input for Module 1, closed when the...Read0=Opened, 1=Closed
BI11Module2HighFloatHigh water level float state input for Module 2, closed when the...Read0=Opened, 1=Closed
BI12Module3HighFloatHigh water level float state input for Module 3, closed when the...Read0=Opened, 1=Closed
BI13Module4HighFloatHigh water level float state input for Module 4, closed when the...Read0=Opened, 1=Closed
MV1HighLimitSourceAnalog high limit sourceWrite1=None, 2=Analog Input 1, 3=Analog Input 2, 4=Analog Input 3, 5=Network
MV2RoomTempSourceRoom temperature sourceWrite1=None, 2=Analog Input 1, 3=Analog Input 2, 4=Analog Input 3, 5=Network
MV3RoomRHSourceRoom relative humidity sourceWrite1=None, 2=Analog Input 1, 3=Analog Input 2, 4=Analog Input 3, 5=Network
MVmin4ControlModeControl modeWrite1=Analog Input 1, 2=Analog Input 2, 3=Analog Input 3, 4=Internal Temperature, 5=Internal %RH, 6=Network
MV5SetpointSourceSetpoint sourceWrite1=None, 2=Analog Input 1, 3=Analog Input 2, 4=Analog Input 3, 5=Internal, 6=Network
MV6RoomTempSignalAnalog room temperature signal configurationWrite1=0-10Vdc, 2=2-10Vdc, 3=0-20mA, 4=4-20mA
MV7RoomRHSignalAnalog room relative humidity signal configurationWrite1=0-10Vdc, 2=2-10Vdc, 3=0-20mA, 4=4-20mA
MV8HighLimitSignalAnalog high limit signal configurationWrite1=0-10Vdc, 2=2-10Vdc, 3=0-20mA, 4=4-20mA
MV9ControlSignalExternal control signal configurationWrite1=0-10Vdc, 2=2-10Vdc, 3=0-20mA, 4=4-20mA
MV10SetpointSignalExternal setpoint signal configurationWrite1=0-10Vdc, 2=2-10Vdc, 3=0-20mA, 4=4-20mA
MV11FeedbackSignalOutput feedback signal configurationWrite1=0-10Vdc, 2=2-10Vdc, 3=0-20mA, 4=4-20mA
MV12SystemLanguageAvailable language options, English and FrancaisWrite1=English, 2=Français
MV13OccupancyStateStatus of the Occupancy ScheduleWrite1=Occupied, 2=Unoccupied, 3=Vacancy, 4=Off
MV14AutoDrainStateStatus of Auto Drain functionWrite1=Wait, 2=Start, 3=Stop
MV15AutoDrainConfigStatus of Auto Drain configurationWrite1=Interval, 2=Schedule
MVmin16Module1StateStatus of Module 1Write1=Stand-by, 2=Drain Cycle, 3=Disinfection Cycle, 4=Filling, 5=Ready, 6=Alarm
MV17Module2StateStatus of Module 2Write1=Stand-by, 2=Drain Cycle, 3=Disinfection Cycle, 4=Filling, 5=Ready, 6=Alarm
MV18Module3StateStatus of Module 3Write1=Stand-by, 2=Drain Cycle, 3=Disinfection Cycle, 4=Filling, 5=Ready, 6=alarm
MV19Module4StateStatus of Module 4Write1=Stand-by, 2=Drain Cycle, 3=Disinfection Cycle, 4=Filling, 5=Ready, 6=Alarm
Other1ControllerUpdateFirmware upgrade process available for the controllerRead
Other2Module1UpdateFirmware upgrade process available for Module 1Read
Other3Module2UpdateFirmware upgrade process available for Module 2Read
Other4Module3UpdateFirmware upgrade process available for module 3Read
Other5Module4UpdateFirmware upgrade process available for module 4Read
FILE1ControllerUpdateFile object of the controller firmware upgradeRead
FILE2ControllerBootloaderUpdateFile object of the controller bootloader firmware upgradeRead
FILE3ModuleUpdateFile object of the modules firmware upgradeRead
FILE4ModuleBootloaderUpdateFile object of the modules bootloader firmware upgradeRead
SCH1DrainScheduleWeekly auto-drain schedule to specify when to manage auto-drain cyclesWrite
SCH2OccupancyScheduleWeekly occupancy schedule to specify which occupancy state is active during specific...Write

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKV and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic SKV

How many BACnet points does the Neptronic SKV have?

This list has 277 BACnet objects: 13 analog inputs, 100 analog values, 13 binary inputs, 121 binary values, 4 files, 2 schedules, 19 multi-state values, 5 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic SKV BACnet points are writable?

242 of the 277 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Neptronic SKV BACnet documentation?

The source is SKV Evaporative Humidifier BACnet User Guide, revision 2018-09-05, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/skv/20180905/SKV-BACnet-180905.pdf.

What are the minimum BACnet points to integrate the Neptronic SKV?

Start with BV 116 SystemPower (System power on/off); MV 4 ControlMode (Control mode (6 = Network)); AV 5 SystDemand (Demand from the BMS, % (when MSV 4 = Network)); AV 16 SetpointRH (BMS RH setpoint (when MSV 5 = Network)); AV 13 RoomRH (BMS room RH (when MSV 3 = Network)); MV 16 Module1State (Stand-by/drain/fill/ready/alarm state of module 1); AV 1 SystOutput (Actual system output %); BV 118 AlarmRelay (Closed on any alarm but airflow cutout/service warning); BV 121 NetworkFallbackAlarm (On when network values time out (AV 38)).

How do I enable BMS control of the Neptronic SKV?

BV 116 SystemPower: ON = normal operation, OFF = demand inhibited. MSV 4 ControlMode selects an analog input, internal temperature/RH control or Network.

Does the Neptronic SKV need a BACnet heartbeat or have a communication timeout?

AV 38 NetworkFallbackTimeout (1-15 min) applies whenever at least one control input uses Network as its source; AV 39 counts down and BV 121 NetworkFallbackAlarm turns on when it expires.

Can the BMS supply sensor values to the Neptronic SKV?

Set MSV 3 RoomRHSource or MSV 2 RoomTempSource to Network and write the values from the BMS; MSV 5 SetpointSource = Network uses the external setpoints AV 16 (RH) and AV 17 (temperature).

How do I check these points on the real SKV?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.