Dual duct VAV terminal controller · BACnet points list

Neptronic EVCBM Dual Duct VAV Controller BACnet points list

Updated 28 October 2026

Short answer

The EVCBM Dual Duct controller manages both hot and cold decks of a dual duct box, with separate airflow K-factor, setpoint and balancing objects for the master and slave sides. It talks BACnet MS/TP with a fixed object table. Points cover zone temperature and setpoints, demands, both airflow channels and output configuration.

This page lists 136 BACnet objects for the Neptronic EVCBM Dual Duct VAV Controller — 109 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
EVCBM Dual Duct VAV Controller
Equipment
Dual duct VAV terminal controller
Equipment type
VAV boxes & fan coils
BACnet objects
136 (109 writable)
Transport
BACnet MS/TP
Firmware
4.09 (as printed)
Default device instance
153000 + MAC address
Also known as
EVCBM, EVCBM Dual Duct, EVCB dual duct
Source document
EVCBM Dual Duct BACnet Communication Module User Guide · EVCBM Dual Duct-V500-BACnet Guide-EUA-180927 · rev. 2018-09-27
Download CSV 136 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Neptronic EVCBM Dual Duct VAV Controller

Integration in brief

Read the zone temperature, setpoint, demands and airflow, and drive occupancy with MSV.11. To control from a BMS space temperature, set MSV.4 to Network Sensor and keep writing AV.1 ControlTemp faster than the Cfg_NetworkTimeOut period (AV.145).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 11NsbOccCommandBMS occupancy / night setback / off commandWrite
AV 15TempSetPointOccupied/day zone setpointWrite
MV 4Cfg_TempControlSourceSelect internal, external or network temperatureWrite
AV 1ControlTempControl temp; BMS writes it when MSV.4 = Network SensorWrite
MV 12OccupancyStatusActual occupancy stateRead
AV 110ActualAirFlow1Measured airflowRead
AV 111AirFlowSetPoint1Airflow setpoint calculated from demandRead
AV 121ActualAirFlow2Measured airflow of the slave (second) ductRead
AV 20HeatingDemand1Heating ramp demand, %Read
AV 40CoolingDemand1Cooling ramp demand, %Read

Enable & remote start

Occupancy and off are commanded with MSV.11 NsbOccCommand: Locally (wired input/sensor decides), Occupancy, No Occupancy (night setback) or OFF.

Heartbeat & communication loss

AV.145 Cfg_NetworkTimeOut (0-60 min): when the temperature source is Network/Remote and the BMS has not written a temperature within this time, the EVC goes to OFF and AV.1 shows 999°C in fault. Setting it to 0 makes AV.1 fall back to the AV.15 setpoint value instead.

Sensors & values from the BMS

Set MSV.4 Cfg_TempControlSource to Network Sensor; AV.1 ControlTemp then becomes writable and must be refreshed by the BMS (see AV.145).

Network setup

Watch out for

Neptronic EVCBM Dual Duct VAV Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

136 of 136 shown
Type
Multi-state
Access
Show
Neptronic EVCBM Dual Duct VAV Controller BACnet Points List
DescriptionStates
AI2AnalogInput2CO2Sensor: Input set to 0-10Vdc CO2 sensorVRead
AI3InternTempIntern temperature sensor (ITS)°F/°CRead
AI5InternHumidityHumidity reading of on board humidity sensor of TRLH or TRLGH24 unit%RHRead
AI6TrlgCO2CO reading of on-board sensor of TRLG24 or TRLGH24 thermostat unitppmRead
AO2AnalogOutput2Modulation percentage of analog output 2 based on demand%Write
AVmin1ControlTempControl temperature; writable when MSV.4 is Network Sensor°F/°CWrite
AV2ExternTempExtern temperature sensor (ETS)°F/°CRead
AV4AirSupplyTempAir supply temperature sensor (AST)°F/°CRead
AV5CO2SensorCarbon dioxide sensor (CO2)ppmRead
AV10Cfg_InternTempOffsetTo calibrate the integrated temperature sensor of the TRL (ITS)°F/°CWrite
AV11Cfg_ExternTempOffsetTo calibrate the external temperature sensor (ETS)°F/°CWrite
AVmin15TempSetPointActual user setpoint of the zone in occupied/day mode°F/°CWrite
AV16Cfg_MinpSetPointUser minimum permitted setpoint of the zone in occupied/day mode°F/°CWrite
AV17Cfg_MaxpSetPointUser maximum permitted setpoint of the zone in occupied/day mode°F/°CWrite
AV18SetPointCoolNoOccNSBCooling setpoint when in night setback or unoccupied°F/°CWrite
AV19SetPointHeatNoOccNSBHeating setpoint when in night setback or unoccupied°F/°CWrite
AVmin20HeatingDemand1Heating demand in percentage for the Heating Ramp 1. This value is%Read
AV21Cfg_HeatingPropBand1Range through which the controller will modulate the heating output from 0-100%°F/°CWrite
AV22Cfg_HeatingDeadBandRange where the controller will not take action when below the zone°F/°CWrite
AV23HeatingDemand2Heating demand in percentage for the Heating Ramp 2. This value is%Read
AV24Cfg_HeatingPropBand2Range through which the controller will modulate the heating output from 0-100%°F/°CWrite
AV25Cfg_HeatingDeadBand2Range where the controller will not take action when below the zone°F/°CWrite
AV30Cfg_IntegralTimeHeatingReciprocal of the integral time in seconds (1/I or repeats per second)sWrite
AVmin40CoolingDemand1Cooling demand for the Cooling Ramp 1. This value is based on%Read
AV41Cfg_CoolingPropBand1Range through which the controller will modulate the cooling output from 0-100%°F/°CWrite
AV42Cfg_CoolingDeadBand1Range at which the controller will not take action when above the°F/°CWrite
AV45CoolingDemand2Cooling demand for the Cooling Ramp 2. This value is based on%Read
AV46Cfg_CoolingPropBand2Range through which the controller will modulate the cooling output from 0-100%°F/°CWrite
AV47Cfg_CoolingDeadBand2Range at which the controller will not take action when above the°F/°CWrite
AV50Cfg_IntegralTimeCoolingReciprocal of the integral time in seconds (1/I or repeats per second)sWrite
AV51Cfg_CoolingAntiCycleDelayIn minutes to prevent the cooling outputs to cycle on and offminWrite
AV60Cfg_NSBSetBackOverrideDelayTime in minutes when in night setback and an override has beenminWrite
AV61Cfg_NoOccOverrideDelayTime in minutes when unoccupied and an override has been activated onminWrite
AV62Cfg_OccupancyMinTimeTime in minutes for minimum time to maintain occupancy mode after aminWrite
AV64Cfg_DigitalInput2DelayTime in secondssWrite
AV72Cfg_AnalogOutput2MinMinimum control signal of the controlled elementVWrite
AV73Cfg_AnalogOutput2MaxMaximum control signal of the controlled elementVWrite
AV75FloatingTO1/TO2TimerTime required by the valve actuator to complete a 90° runsWrite
AV77Cfg_TO1ClosePosThat indicates at what percentage of the demand the contact closes to%Write
AV78Cfg_TO1OpenPosThat indicates at what percentage of the demand the contact opens to%Write
AV79Cfg_TO2ClosePos%Write
AV80Cfg_TO2OpenPos%Write
AV93Motor1PositionDamper actuator position of the master unit%Read
AV94Motor2PositionDamper actuator position of the slave unit%Read
AV100Cfg_PressureNumFilterTo stabilize the reading of the differential pressure transducer when balancingsWrite
AV101Cfg_AirFlowKFactor1Maximum airflow of the Master VAV box at 1" w.cWrite
AV102Cfg_AirFlowCoolMinMinimum cooling airflow when system is in cooling modeWrite
AV103Cfg_AirFlowCoolMaxMaximum cooling airflow when system is in cooling mode%Write
AV104Cfg_AirFlowHeatMinMinimum heating airflow when system is in heating modeWrite
AV105Cfg_AirFlowHeatMaxMaximum cooling airflow when system is in heating mode%Write
AVmin110ActualAirFlow1Actual converted airflow measured by the differential pressure transducer on the masterRead
AVmin111AirFlowSetPoint1Airflow calculated by demand for the master unitRead
AV112Cfg_AdjustAirFlow1MaxDuring airflow balancing sequence of the master unitWrite
AV113Cfg_AdjustAirFlow1MinDuring airflow balancing sequence of the master unitWrite
AV114Cfg_AirFlow1OffsetTo adjust the calibration of the differential pressure transducer of the masterWrite
AV116Cfg_AirFlowHysteresisStopAirflow setpoint percentage used to prevent damper actuator oscillations%Write
AV117Cfg_AirFlowHysteresisStartAirflow setpoint percentage used to prevent actuator from oscillations%Write
AV120Cfg_AirFlowKFactor2Maximum airflow of the slave VAV box at 1" w.cWrite
AVmin121ActualAirFlow2Actual converted airflow measured by the differential pressure transducer on the slaveRead
AV122AirFlowSetPoint2Airflow calculated by demand for the slave unitRead
AV123Cfg_AdjustAirFlow2MaxDuring airflow balancing sequence of the slave unitWrite
AV124Cfg_AdjustAirFlow2MinDuring airflow balancing sequence of the slave unitWrite
AV125Cfg_AirFlow2OffsetTo adjust the calibration of the differential pressure transducer of the slaveWrite
AV126PressureInput2Voltage output value in mV of the pressure sensor on the slaveRead
AV127Cfg_Pressure2NumFilterTo stabilize the reading of the differential pressure transducer when balancing thesWrite
AV128Cfg_MixAirDeadBandFor snap acting, set to deadband mix to 0°C or 0°F. For°F/°CWrite
AV132Cfg_Input3 Minimum ReadingThis setting represents the deadband of the pressure sensor in mV. ForWrite
AV133Cfg_Input3 ReadingVoltage output value in mV of the pressure sensor on the masterRead
AV140Cfg_CO2RangeMaximum range of the CO2 sensor (PPM) or the external sensor ifppmWrite
AV141CO2SetpointMaximum limit of CO2 concentration before the EVC sends an alarmppmWrite
AV145Cfg_NetworkTimeOutBMS temperature timeout when control source is networkminWrite
AV165CopyCfgStartAddressWhen using copy config, this value represents the first address in theWrite
AV166CopyCfgEndAddressWhen using copy config, this value represents the last address in theWrite
AV167CopyCfgResultWhen using copy config, this value is used to verify that theWrite
AV170CL_HT_SwitchTimerTime required before the changeover is permitted to take place (time inminWrite
AV171CL_HT_SwitchTimerCountRemaining time before the changeover is authorisedsRead
AV180FloatingTO1/TO2Status value to show the floating signal demand%Write
AV182TO1PulsingTR Status value to show the pulse signal demand%Write
AV183TO2PulsingStatus value to show the pulse signal demand%Write
BI1DigitalInput1Contact status of the inputRead0 = Open 1 = Close
BI2DigitalInput2Contact status of the inputRead0 = Open 1 = Close
BO1TO1OnOffStatus value to show if TO1 is active or notWrite0 = Off 1 = On
BO2TO2OnOffStatus value to show if TO2 is active or notWrite0 = Off 1 = On
BV1Cfg_TempUnitBACnetTemperature units used in BACnetWrite0 = Celsius, 1 = Fahrenheit
BV2Cfg_TempSetPointLockLock the zone setpoint and prevent users to change the valueWrite0 = Disable, 1 = Enable
BV3UserSysOffModeAllow users to turn off the EVC. (0) Enable user to turnWrite0 = Enable, 1 = Disable
BV4Cfg_TempUnitTstatUser temperature units used on TRL. If set to (0), the temperatureWrite0 = Celsius, 1 = Fahrenheit
BV6Cfg_FreezeProtectionPrevent a zone from falling below 4°C (39.2°F)Write0 = Off , 1 = On
BV7Cfg_KeyPadUpperLeftLockLock the Cool/Heat buttonWrite0 = Off, 1 = On (If set to “On”, functionality of these buttons will not be available.)
BV8Cfg_KeyPadBottomLeftLockLock the °C/°F buttonWrite0 = Off, 1 = On If set to “On”, functionality of these buttons will not be available.
BV9Cfg_KeyPadArrowsLockLock the arrow buttonsWrite0 = Off, 1 = On If set to “On”, functionality of these buttons will not be available.
BV10Cfg_ProgramLockLock the all TRL buttonsWrite0 = Off, 1 = On If set to “On”, functionality of these buttons will not be available.
BV20Cfg_NightSetBackModeDetermine the action of the EVC when in night setbackWrite0 = Setpoint, 1 = OFF
BV26Cfg_AnalogOutput2DirectionAnalog output directionWrite0 = Direct, 1 = Reverse
BV30Cfg_FloatingTO1/TO2DirectionTRIAC contact normal state (Normally Open, Normally Close) when MSV.26 TO1 SignalWrite0 = Direct, 1 = Reverse
BV32Cfg_TO1 DirectionTRIAC contact normal state value of the rotation when MSV.26 TO1 SignalWrite0 = Direct, 1 = Reverse
BV33Cfg_TO2 DirectionTRIAC contact normal state value of the rotation when MSV.28 TO2 SignalWrite0 = Direct, 1 = Reverse
BV36Cfg_Digital Input 2 ContactChange the contact's normal positionWrite0 = Norm Open, 1 = Norm Close
BV40Cfg_Motor1DirectionChange the rotation direction of the damper actuator of the Master unitWrite0 = Direct, 1 = Reverse
BV41Cfg_Motor2DirectionChange the rotation direction of the damper actuator of the Slave unitWrite0 = Direct, 1 = Reverse
BV45AirFlowBalancing1Enable and disable the airflow balancing for the Master unitWrite0= Disable, 1= Enable
BV46AirFlowBalancing2To enable and disable the airflow balancing for the Slave unitWrite0= Disable, 1= Enable
BV48Cfg_ConstantFlowOptionIf set to "no", the controller can perform snap acting or performWrite0= No, 1= Yes
BV49Cfg_Pressure2OptionSelect Local or Total based on location of crossflow sensorWrite0= Local, 1= Total
BV55AL_HighCO2LevelIndicates that the CO2 concentration is above setpointRead0= No, 1= Yes
BV56AL_OverrideStatus to inform if an override is activeRead0= No, 1= Yes
BV60Cfg_DisplayRHDetermines if the thermostat displays the %RH valueWrite0= Off, 1= On
BV65Cfg_DisplayCO2Determines if the thermostat displays the CO2 valueWrite0= Off, 1= On
BV66Cfg_CO2ControlSourceDetermines the source of the CO2 readingWrite0= Analog Input, 1= TRLG
BV70Cfg_ActiveScheduleActivate the scheduleWrite0= No, 1= Yes
BV90CopyCfgExecuteWhen using copy config, this value is used to start the copyWrite0= No, 1= Yes
BV91Cfg_Pressure1CalibrationTo recalibrate the differential pressure transducer of the Master unitWrite0= No, 1= Yes
BV92Cfg_Pressure1Calibration LockTo unlock the calibration process of BV.91 of the Master unitWrite0 = Lock, 1 = Unlock
MV2Cfg_UniversalInputAI2TypeInputWriteOff Extern Sensor CO2 Sensor Air Supply Temp
MVmin4Cfg_TempControlSourceControl temperature to be used by the EVC. Intern Temp, the controlWriteIntern Sensor Extern Sensor Network Sensor
MV10Cfg_NsbOccContactDI1 modeWriteOff Occ Norm Open Occ Norm Close NSB Norm Open NSB Norm Close
MVmin11NsbOccCommandSet the occupancy or night setback modeWriteOFF/Locally/Locally Occupancy/OFF/OFF No Occupancy/Occupancy/Day -- /No Occupancy/Night
MVmin12OccupancyStatusStatus that indicates the actual occupancy when occupancy is usedReadNoOccupancy Occupancy Override
MV13NightSetBackStatusStatus that indicates the actual mode of the zone when night setbackReadDay Night Override
MV14Cfg_DigitalInput2TypeDI2 modeWriteOff Override Over Heat1 Over Heat2 Over Heat All
MV15OverHeatStatusStatus to inform if a heat override is activeReadOverHeatNormal Over Heat1 Over Heat2 Over Heat All
MV16UserSystemModeZone mode the user has set on the TRL. Not to beWriteAuto Heating Cooling Off
MV17UserSysModeSelectSet the permissions or restrictions to change the zone mode by theWriteAuto Heating Cooling Heating or Cooling Auto Lock
MV22Cfg_AnalogOutput2RampRamp used to modulate AO1 based on demandWriteOff Cooling Ramp1 Cooling Ramp2 Heating Ramp1 Heating Ramp2 CO2 Alarm | CO2 Alarm (CO2): This ramp is used to activate or deactivate controlled elements based on CO2 levels. The ramp is configured with "AV.140 CO2 Range" and "AV.141 CO2 Setpoint". When "BV.55 CO2 Alarm" is activated, AO1 will activate as well. With this option, AO1 becomes a binary output (0 or 10Vdc).
MV25Cfg_TO1RampRamp used to modulate (pulse or floating) or activate/deactivate (On/Off) TO1 basedWriteOff Cooling Ramp1 Cooling Ramp2 Heating Ramp1 Heating Ramp2 CO2 Alarm
MV26Cfg_TO1SignalTypeOutput signal typeWritePulsing (If Hr1 or Hr2 is selected)  On_Off  Floating
MV27Cfg_TO2RampWriteOff Cooling Ramp1 Cooling Ramp2 Heating Ramp1 Heating Ramp2 CO2 Alarm
MV28Cfg_TO2SignalTypeOutput signal typeWritePulsing (If Hr1 or Hr2 is selected) 2On_Off 3Floating
MV35Cfg_Motor1RampRamp used to modulate the damper actuator of the Master unit basedWriteCooling Ramp1 Heating Ramp1
MV36Cfg_NSBMotorModeSet the motor position while in night setbackWriteAuto Open
MV37Motor1PositionOverrideTo override the motor position of the Master unitWriteAuto Open Close Air Flow Min (heat/cool as per current mode) Air Flow Max (heat/cool as per current mode)
MV38Motor2PositionOverrideTo override the motor position of the Slave unitWriteAuto Open Close Air Flow Min (heat/cool as per current mode) Air Flow Max (heat/cool as per current mode)
MV41Cfg_AirFlowScaleAirflow scale used to get a better resolution when small airflows areWriteScale1 | Scale10 | Scale100
MV42AirFlowBal1_ModePosition the damper actuator of the Master unit to preset positionsWriteClosed | Min Flow | Max Flow | Full Open
MV43AirFlowBal2_ModePosition the damper actuator of the Slave unit to preset positionsWriteClosed | Min Flow | Max Flow | Full Open
MV95Cfg_DisplayInfoInformation displayed on the TRL. Display Temp Demand: the TRL will displayWriteTemp and Demand | Setpoint and Demand Temp only | Setpoint only | Off

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EVCBM Dual Duct VAV Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic EVCBM Dual Duct VAV Controller

How many BACnet points does the Neptronic EVCBM Dual Duct VAV Controller have?

This list has 136 BACnet objects: 4 analog inputs, 1 analog output, 74 analog values, 2 binary inputs, 2 binary outputs, 30 binary values, 23 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic EVCBM Dual Duct VAV Controller BACnet points are writable?

109 of the 136 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic EVCBM Dual Duct VAV Controller BACnet documentation?

The source is EVCBM Dual Duct BACnet Communication Module User Guide (EVCBM Dual Duct-V500-BACnet Guide-EUA-180927), revision 2018-09-27, published free by Neptronic at https://www.neptronic.com/Controls/PDF/EVC/BACnetModbus/20181001/EVCBM%20Dual%20Duct-V500-BACnet%20Guide-EUA-180927.pdf.

What are the minimum BACnet points to integrate the Neptronic EVCBM Dual Duct VAV Controller?

Start with MV 11 NsbOccCommand (BMS occupancy / night setback / off command); AV 15 TempSetPoint (Occupied/day zone setpoint); MV 4 Cfg_TempControlSource (Select internal, external or network temperature); AV 1 ControlTemp (Control temp; BMS writes it when MSV.4 = Network Sensor); MV 12 OccupancyStatus (Actual occupancy state); AV 110 ActualAirFlow1 (Measured airflow); AV 111 AirFlowSetPoint1 (Airflow setpoint calculated from demand); AV 121 ActualAirFlow2 (Measured airflow of the slave (second) duct); AV 20 HeatingDemand1 (Heating ramp demand, %); AV 40 CoolingDemand1 (Cooling ramp demand, %).

How do I enable BMS control of the Neptronic EVCBM Dual Duct VAV Controller?

Occupancy and off are commanded with MSV.11 NsbOccCommand: Locally (wired input/sensor decides), Occupancy, No Occupancy (night setback) or OFF.

Does the Neptronic EVCBM Dual Duct VAV Controller need a BACnet heartbeat or have a communication timeout?

AV.145 Cfg_NetworkTimeOut (0-60 min): when the temperature source is Network/Remote and the BMS has not written a temperature within this time, the EVC goes to OFF and AV.1 shows 999°C in fault. Setting it to 0 makes AV.1 fall back to the AV.15 setpoint value instead.

Can the BMS supply sensor values to the Neptronic EVCBM Dual Duct VAV Controller?

Set MSV.4 Cfg_TempControlSource to Network Sensor; AV.1 ControlTemp then becomes writable and must be refreshed by the BMS (see AV.145).

How do I check these points on the real EVCBM Dual Duct VAV Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: EVCBM Dual Duct BACnet Communication Module User Guide · EVCBM Dual Duct-V500-BACnet Guide-EUA-180927 · rev. 2018-09-27. Object names, instances and units are reproduced as published; descriptions are our own.