Gas-fired steam humidifier · BACnet points list

Neptronic SKG4 BACnet points list

Updated 28 October 2026

Short answer

The SKG4 is a natural gas or propane fired steam humidifier with BACnet MS/TP and BACnet IP on its controller. The object list covers system control sources and network inputs plus per-module (1-4) state, request, alarm, burner, service and water level objects.

This page lists 303 BACnet objects for the Neptronic SKG4 — 175 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
SKG4
Equipment
Gas-fired steam humidifier
Equipment type
Humidifiers
BACnet objects
303 (175 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
153000 + MAC address (153001 by default)
Also known as
SKG4 gas fired humidifier, SKG4-N, SKG4-E, SKG4 BACnet
Source document
SKG4 Gas Fired Humidifier BACnet Communication Module User Guide · SKG4-BACnet Guide-250609 (V2.06) · rev. 2025-06-09
Download CSV 303 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Neptronic SKG4

Integration in brief

Select a network control profile (MSV 33) or demand source, write the demand to AV 141 or a room RH reading to AV 109 with setpoint AV 110, and switch the system with MSV 60. Monitor per-module state and alarm MSVs plus BV 104 for network control health.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 60System Power StateSystem on/off from the BMSWrite
MV 33Control ProfileControl profile: choose a Network profileWrite
AV 141Humidity Control Network DemandNetwork humidity demand written by the BMSCommand
AV 110Room RH SetpointOccupied room RH setpoint (internal control)Write
AV 109Room RH Network ReadingNetwork room RH reading for internal controlCommand
MV 63Module 1 StateModule 1 operating stateRead
AV 148System Power OutputActual output of the whole system %Read
MV 65Module 1 AlarmModule 1 active alarm (1 = Normal)Read
BV 104Network Control State1 = fault: network control lost (AV 248 timeout)Write

Enable & remote start

MSV 60 System Power State is writable (1 = Off, 2 = On). The control source follows MSV 33 Control Profile (ExternNetwork / InternNetwork for BMS control) or the individual source MSVs with the Custom profile.

Heartbeat & communication loss

AV 248 Network Timeout (1-900 s) sets how long the humidifier tolerates loss of BACnet control communication before stopping; BV 104 Network Control State reports 1 = Fault.

Sensors & values from the BMS

With the room RH source on Network write room RH to AV 109 and setpoints to AV 110-112 (occupied/unoccupied/vacant); write the supply high limit reading to AV 125 and setpoint AV 126. A direct network demand goes to AV 141 and a network high limit to AV 142.

Network setup

Watch out for

Neptronic SKG4 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

303 of 303 shown
Type
Multi-state
Access
Show
Neptronic SKG4 BACnet Points List
DescriptionStates
AI2Supply RH SignalDuct or supply high limit humidity analog input signalVRead
AI3Room RH SignalRoom humidity analog input signalVRead
AI4Control SignalCurrent demand analog input signalVRead
AO3Power Output Feedback SignalPower output feedback signalVRead
AV10MCU LoadCurrent microcontroller load%Read
AV11Memory LoadCurrent memory load%Read
AV37Water Level Replace IntervalAmount of time the humidifier may run using only the resistive water...daysWrite
AV48Supply High Limit RHDuct or supply high limit humidity analog input%RHWrite
AV49Supply High Limit RH MinMinimum value of the duct or supply high limit humidity analog input%RHWrite
AV50Supply High Limit RH MaxMaximum value of the duct or supply high limit humidity analog input%RHWrite
AV51Supply High Limit RH BiasBias value of the duct or supply high limit humidity analog input%RHWrite
AV54Room RHRoom humidity reading%RHWrite
AV55Room RH MinMinimum value of the room humidity analog input%RHWrite
AV56Room RH MaxMaximum value of the room humidity analog input%RHWrite
AV57Room RH BiasBias value of the room humidity analog input%RHWrite
AV60Control InputCurrent control input reading%Write
AV61Control MinMinimum value of the control demand analog input%RHWrite
AV62Control MaxMaximum value of the control demand analog input%RHWrite
AV63Control BiasBias value of the control demand analog input%Write
AV64Board TemperatureThe board temperature°F or °CWrite
AV67Power Output Feedback BiasBias value for the power output feedback signalVWrite
AV68Power Output Feedback MinMinimum value of the power output feedback signalVWrite
AV69Power Output Feedback MaxMaximum value of the current steam output feedbackVWrite
AV70Power Output FeedbackFeedback value of the power output analog output%Command
AV73Module 1 Water LevelPercentage of water remaining in the evaporation chamber%Read
AV76Module 1 Water Probe Low Pos ReadingLow position value of the water level sensor of the first humidifier...Read
AV77Module 1 Water Probe High Pos ReadingHigh position value of the water level sensor of the first humidifier...Read
AV80Module 1 Water Probe Abs Low Pos ReadingAbsolute low position value of the water level sensor of the first...Read
AV81Module 1 Water Probe Abs High Pos ReadingAbsolute high position value of the water level sensor of the first...Read
AV82Module 2 Water LevelPercentage of water remaining in the evaporation chamber%Read
AV85Module 2 Water Probe Low Pos ReadingLow position value of the water level sensor of the second humidifier...Read
AV86Module 2 Water Probe High Pos ReadingHigh position value of the water level sensor of the second humidifier...Read
AV89Module 2 Water Probe Abs Low ReadingAbsolute low position value of the water level sensor of the second...Read
AV90Module 2 Water Probe Abs High Pos ReadingAbsolute high position value of the water level sensor of the second...Read
AV91Module 3 Water LevelPercentage of water remaining in the evaporation chamber%Read
AV94Module 3 Water Probe Low Pos ReadingLow position value of the water level sensor of the third humidifier...Read
AV95Module 3 Water Probe High Pos ReadingHigh position value of the water level sensor of the third humidifier...Read
AV98Module 3 Water Probe Abs Low Pos ReadingAbsolute low position value of the water level sensor of the third...Read
AV99Module 3 Water Probe Abs High Pos ReadingAbsolute high position value of the water level sensor of the third...Read
AV100Module 4 Water LevelPercentage of water remaining in the evaporation chamber%Read
AV103Module 4 Water Probe Low Pos ReadingLow position value of the water level sensor of the fourth humidifier...Read
AV104Module 4 Water Probe High Pos ReadingHigh position value of the water level sensor of the first humidifier...Read
AV107Module 4 Water Probe Abs Low Pos ReadingAbsolute low position value of the water level sensor of the first...Read
AV108Module 4 Water Probe Abs High Pos ReadingAbsolute high position value of the water level sensor of the first...Read
AVmin109Room RH Network ReadingRoom relative humidity reading received from the network%Command
AVmin110Room RH SetpointRoom relative humidity setpoint received from the network%RHWrite
AV111Room RH Unoccupied SetpointRoom relative humidity reading received from the network during no occupancy state%RHWrite
AV112Room RH Vacant SetpointRoom relative humidity reading received from the network during vacancy%RHWrite
AV113Room Demand Proportional GainRoom demand proportional gainWrite
AV114Room Demand Integral TimeRoom demand integral timesWrite
AV115Room Demand Derivative TimeRoom demand derivative timesWrite
AV123Room DemandHumidity demand within the room%Command
AV125Supply High Limit Network ReadingSupply high limit reading received from the network%Command
AV126Supply High Limit SetpointSupply high limit setpoint received from the network%RHWrite
AV129Supply High Limit Proportional GainSupply high limit demand proportional gainWrite
AV130Supply High Limit Integral TimeSupply high limit demand integral timesWrite
AV131Supply High Limit Derivative TimeSupply high limit demand derivative timesWrite
AV139Supply High Limit DemandSupply high limit humidity demand value%Command
AVmin141Humidity Control Network DemandHumidity control demand received from the network%Command
AV142Humidity Control Network High LimitHumidity control high limit received from the network%Command
AV146Humidity DemandCurrent humidity demand%Read
AVmin148System Power OutputMeasured power output of the system as a percentage of the total...%Read
AV150Module 1 Chimney TempFlue gas temperature value of the first humidifier module°F or °CWrite
AV151Module 1 Water TempTemperature of water in the evaporation chamber of the first humidifier module°F or °CRead
AV152Module 1 Water FrequencyInput frequency of the water level sensor of the first humidifier moduleWrite
AV154Module 1 Ambient TempTemperature inside of the weather proof enclosure of the first humidifier module°F or °CWrite
AV155Module 1 Fan FeedbackValue from the burner fan feedback of the first humidifier moduleHzWrite
AV156Module 1 Fan PWMPWM control signal from the burner fan of the first humidifier module%Read
AV158Module 1 Run TimeTotal runtime of the first humidifier modulehRead
AV159Module 1 Service On TimeOperating time of the first humidifier module, since the last servicinghRead
AV160Module 1 Service Run TimeRuntime of the first humidifier module, since the last servicinghRead
AV161Module 1 On TimeTotal operating time for the first humidifier modulehRead
AV162Module 1 DemandMeasured humidity demand of the first humidifier module%Command
AV166Module 1 Max Steam OutputMaximum steam output of the first modulating humidifier relative to its total...%Write
AV170Module 2 Chimney TempFlue gas temperature value of the second humidifier module°F or °CWrite
AV171Module 2 Water TempTemperature of water in the evaporation chamber of the second humidifier module°F or °CRead
AV172Module 2 Water FrequencyInput frequency of the water level sensor of the second humidifier moduleWrite
AV174Module 2 Ambient TempTemperature inside of the weather proof enclosure of the second humidifier module°F or °CWrite
AV175Module 2 Fan FeedbackValue from the burner fan feedback of the second humidifier moduleHzWrite
AV176Module 2 Fan PWMPWM control signal from the burner fan of the second humidifier module%Read
AV178Module 2 Run TimeTotal runtime of the second humidifier modulehRead
AV179Module 2 Service On TimeOperating time of the second humidifier module, since the last servicinghRead
AV180Module 2 Service Run TimeRuntime of the second humidifier module, since the last servicinghRead
AV181Module 2 On TimeTotal operating time for the second humidifier modulehRead
AV182Module 2 DemandMeasured humidity demand of the second humidifier module%Command
AV186Module 2 Max Steam OutputMaximum steam output of the second modulating humidifier relative to its total...%Write
AV190Module 3 Chimney TempFlue gas temperature value of the third humidifier module°F or °CWrite
AV191Module 3 Water TempTemperature of water in the evaporation chamber of the third humidifier module°F or °CRead
AV192Module 3 Water FrequencyInput frequency of the water level sensor of the third humidifier moduleWrite
AV194Module 3 Ambient TempTemperature inside of the weather proof enclosure of the third humidifier module°F or °CWrite
AV195Module 3 Fan FeedbackValue from the burner fan feedback of the third humidifier moduleHzWrite
AV196Module 3 Fan PWMPWM control signal from the burner fan of the third humidifier module%Read
AV198Module 3 Run TimeTotal runtime of the third humidifier modulehRead
AV199Module 3 Service On TimeOperating time of the third humidifier module, since the last servicinghRead
AV200Module 3 Service Run TimeRuntime of the third humidifier module, since the last servicinghRead
AV201Module 3 On TimeTotal operating time for the third humidifier modulehRead
AV202Module 3 DemandMeasured humidity demand of the third humidifier module%Command
AV206Module 3 Max Steam OutputMaximum steam output of the third modulating humidifier relative to its total...%Write
AV210Module 4 Chimney TempFlue gas temperature value of the fourth humidifier module°F or °CWrite
AV211Module 4 Water TempTemperature of water in the evaporation chamber of the fourth humidifier module°F or °CRead
AV212Module 4 Water FrequencyInput frequency of the water level sensor of the fourth humidifier moduleWrite
AV214Module 4 Ambient TempTemperature inside of the weather proof enclosure of the fourth humidifier module°F or °CWrite
AV215Module 4 Fan FeedbackValue from the burner fan feedback of the fourth humidifier moduleHzWrite
AV216Module 4 Fan PWMPWM control signal from the burner fan of the fourth humidifier module%Read
AV218Module 4 Run TimeTotal runtime of the fourth humidifier modulehRead
AV219Module 4 Service On TimeOperating time of the fourth humidifier module, since the last servicinghRead
AV220Module 4 Service Run TimeRuntime of the fourth humidifier module, since the last servicinghRead
AV221Module 4 On TimeTotal operating time for the fourth humidifier modulehRead
AV222Module 4 DemandMeasured humidity demand of the fourth humidifier module%Command
AV226Module 4 Max Steam OutputMaximum steam output of the fourth modulating humidifier relative to its total...%Write
AV231Boiler Blowdown RateRate of boiler blowdown or water dilution in order to minimize water...%Write
AV234Boiler Drain IntervalDrain cyclehWrite
AV235Boiler Idle Temperature SetpointIdle temperature setpoint for the evaporation chamber when there is no demand°F or °CWrite
AV236Boiler Idle Time DrainAmount of time the humidifier can remain in standby mode until an...hWrite
AV241Boiler Service IntervalTime of operation before the humidifier calls for servicinghWrite
AV248Network TimeoutAmount of time the humidifier may attempt to connect to the BACnet...sWrite
AV254Boiler Idle Tank Rinse IntervalAmount of time the humidifier stays in “Idle” or “Off” mode, before...daysWrite
AV256Boiler Drain VolumeVolume of water that is drained from the chamber, relative to the...%Write
AV270Humidity Demand Low Dead BandLower limit deadband for the humidity demand%RHWrite
AV273Module 1 Ignition CountNumber of times that the first humidifier module has completed an ignition...Write
AV274Module 2 Ignition CountNumber of times that the second humidifier module has completed an ignition...Write
AV275Module 3 Ignition CountNumber of times that the third humidifier module has completed an ignition...Write
AV276Module 4 Ignition CountNumber of times that the fourth humidifier module has completed an ignition...Write
AV281HRL TemperatureRoom temperature measured by the HRL24 controller°F or °CCommand
AV282HRL HumidityRoom humidity measured by the HRL24 controller%RHCommand
AV285RuntimeThe number of seconds that the system has been powered onsCommand
AV286HALTicksHaltickssRead
AV291Room Demand Proportional BandRoom demand proportional band%Write
AV292Supply High Limit Proportional BandSupply high limit proportional band%Write
AV303Module 1 Water Temperature OffsetSet the temperature offset for the first evaporation chamber water temperature value...°F or °CWrite
AV304Module 2 Water Temperature OffsetSet the temperature offset for the second evaporation chamber water temperature value...°F or °CWrite
AV305Module 3 Water Temperature OffsetSet the temperature offset for the third evaporation chamber water temperature value...°F or °CWrite
AV306Module 4 Water Temperature OffsetSet the temperature offset for the fourth evaporation chamber water temperature value...°F or °CWrite
AV309Modbus TCP IP Keep Alive Time OutAmount of time the communication to the Modbus TCP/IP server stays open...minWrite
AV323Module 2 Manual Calibration TimeAmount of time that has been elapsed since the last manual calibration...hRead
AV324Module 3 Manual Calibration TimeAmount of time that has been elapsed since the last manual calibration...hRead
AV325Module 4 Manual Calibration TimeAmount of time that has been elapsed since the last manual calibration...hRead
AV327Module 1 Manual Calibration TimeAmount of time that has been elapsed since the last manual calibration...hRead
AV329HRL Temperature BiasBias value of the temperature measured on the HRL controller°F or °CWrite
AV330HRL Humidity BiasBias value of the humidity measured on the HRL controller%RHWrite
AV335Module 1 Clean Valve DelayThe total drain duration for which the clean valve of module 1...%Write
AV336Module 2 Clean Valve DelayThe total drain duration for which the clean valve of module 2...%Write
AV337Module 3 Clean Valve DelayThe total drain duration for which the clean valve of module 3...%Write
AV338Module 4 Clean Valve DelayThe total drain duration for which the clean valve of module 4...%Write
AV448Module 1 Heating Max OutputMaximum steam output of module 1 relative to its total capacity during...%Write
AV449Module 2 Heating Max OutputMaximum steam output of the module 2 relative to its total capacity...%Write
AV450Module 3 Heating Max OutputMaximum steam output of the module 3 relative to its total capacity...%Write
AV451Module 4 Heating Max OutputMaximum steam output of module 4 relative to its total capacity during...%Write
BI1Water Leak DetectionWhether a water leak has been detectedRead0=OK, 1=Leak
BI5Binary External DemandWhether there is currently a humidity demand, when an On/Off humidifier is...Read0=0%, 1=100%
BI6InterlockStatus of the interlockRead0=Closed, 1=Open
BI7Supply High LimitStatus of the high limit contactRead0=Closed, 1=Open
BI8Air FlowStatus of the airflow switchRead0=Closed, 1=Open
BI9RS485 InterfaceWhether the RS485 interface is available or notRead0=No, 1=Yes
BI10Ethernet InterfaceWhether the Ethernet interface is available or notRead0=No, 1=Yes
BO1Service Warning RelayService warning relayCommand0=Off, 1=On
BO2Alarm Warning RelayAlarm warning relayCommand0=Off, 1=On
BO5Alarm LEDAlarm LEDCommand0=Off, 1=On
BO6Power LEDPower LEDCommand0=Off, 1=On
BO7BuzzerBuzzerCommand0=Off, 1=On
BV2Alarm BuzzerConfiguration value that enables or disables the alarm buzzer sound when there...Write0=Normal, 1=Disabled
BV33Module 1 Burner Inlet PressureBurner inlet air pressure switch of the first humidifier moduleWrite0=Normal, 1=Blocked
BV34Module 1 Water Level LowResistive low water level sensor of the first humidifier moduleRead0=Inactive, 1=Active
BV35Module 1 Water Level HighResistive high water level sensor of the first humidifier moduleRead0=Inactive, 1=Active
BV36Module 1 Foam SensorWhether foam has been detected within the first evaporation chamberRead0=NoFoam, 1=Foam
BV39Module 1 Gas ValveGas valve of the first humidifier moduleWrite0=Off, 1=On
BV40Module 1 Tank Water ValveEvaporation chamber water supply valve of the first humidifier moduleCommand0=Off, 1=On
BV41Module 1 Water Level ValveWater level sensor supply valve of the first humidifier moduleCommand0=Off, 1=On
BV42Module 1 Drain Cooler ValveInternal drain cooler valve of the first humidifier moduleCommand0=Off, 1=On
BV43Module 1 Drain PumpDrain pump of the first humidifier moduleCommand0=Off, 1=On
BV45Module 1 Ignition ControlIgnition control module of the first humidifier moduleRead0=Off, 1=On
BV47Module 1 Alarm LEDAlarm LED of the first humidifier moduleCommand0=Off, 1=On
BV48Module 2 Burner Inlet PressureBurner inlet air pressure switch of the second humidifier moduleWrite0=Normal, 1=Blocked
BV49Module 2 Water Level LowResistive low water level sensor of the second humidifier moduleRead0=Inactive, 1=Active
BV50Module 2 Water Level HighResistive high water level sensor of the second humidifier moduleRead0=Inactive, 1=Active
BV51Module 2 Foam SensorWhether foam has been detected within the second evaporation chamberRead0=NoFoam, 1=Foam
BV54Module 2 Gas ValveGas valve of the second humidifier moduleWrite0=Off, 1=On
BV55Module 2 Tank Water ValveEvaporation chamber water supply valve of the second humidifier moduleCommand0=Off, 1=On
BV56Module 2 Water Level ValveWater level sensor supply valve of the second humidifier moduleCommand0=Off, 1=On
BV57Module 2 Drain Cooler ValveInternal drain cooler valve of the second humidifier moduleCommand0=Off, 1=On
BV58Module 2 Drain PumpDrain pump of the second humidifier moduleCommand0=Off, 1=On
BV59Boiler Line RinsePerform an automatic pipe line rinse cycle upon each start-up of the...Write0=Off, 1=On
BV60Module 2 Ignition ControlIgnition control module of the second humidifier moduleRead0=Off, 1=On
BV62Module 2 Alarm LEDAlarm LED of the second humidifier moduleCommand0=Off, 1=On
BV63Module 3 Burner Inlet PressureBurner inlet air pressure switch of the third humidifier moduleWrite0=Normal, 1=Blocked
BV64Module 3 Water Level LowResistive low water level sensor of the third humidifier moduleRead0=Inactive, 1=Active
BV65Module 3 Water Level HighResistive high water level sensor of the third humidifier moduleRead0=Inactive, 1=Active
BV66Module 3 Foam SensorWhether foam has been detected within the third evaporation chamberRead0=NoFoam, 1=Foam
BV69Module 3 Gas ValveGas valve of the third humidifier moduleWrite0=Off, 1=On
BV70Module 3 Tank Water ValveEvaporation chamber water supply valve of the third humidifier moduleCommand0=Off, 1=On
BV71Module 3 Water Level ValveWater level sensor supply valve of the third humidifier moduleCommand0=Off, 1=On
BV72Module 3 Drain Cooler ValveInternal drain cooler valve of the third humidifier moduleCommand0=Off, 1=On
BV73Module 3 Drain PumpDrain pump of the third humidifier moduleCommand0=Off, 1=On
BV75Module 3 Ignition ControlIgnition control module of the third humidifier moduleRead0=Off, 1=On
BV77Module 3 Alarm LEDAlarm LED of the third humidifier moduleCommand0=Off, 1=On
BV78Module 4 Burner Inlet PressureBurner inlet air pressure switch of the third humidifier moduleWrite0=Normal, 1=Blocked
BV79Module 4 Water Level LowResistive low water level sensor of the fourth humidifier moduleRead0=Inactive, 1=Active
BV80Module 4 Water Level HighResistive high water level sensor of the fourth humidifier moduleRead0=Inactive, 1=Active
BV81Module 4 Foam SensorWhether foam has been detected within the fourth evaporation chamberRead0=NoFoam, 1=Foam
BV84Module 4 Gas ValveGas valve of the fourth humidifier moduleWrite0=Off, 1=On
BV85Module 4 Tank Water ValveEvaporation chamber water supply valve of the fourth humidifier moduleCommand0=Off, 1=On
BV86Module 4 Water Level ValveWater level sensor supply valve of the fourth humidifier moduleCommand0=Off, 1=On
BV87Module 4 Drain Cooler ValveInternal drain cooler valve of the fourth humidifier moduleCommand0=Off, 1=On
BV88Module 4 Drain PumpDrain pump of the fourth humidifier moduleCommand0=Off, 1=On
BV90Module 4 Ignition ControlIgnition control module of the fourth humidifier moduleRead0=Off, 1=On
BV92Module 4 Alarm LEDAlarm LED of the fourth humidifier moduleCommand0=Off, 1=On
BV94Boiler Service OperationEnable the humidifier to continue producing steam, even when it is due...Write0=Not Allowed, 1=Allowed
BV95Module 1 Foam StateWhether the first humidifier module has currently detected foam or notRead0=Ok, 1=Detected
BV97Module 1 Service DueStatus value that indicates whether the first humidifier module is due for...Read0=No, 1=Yes
BV98Module 2 Service DueStatus value that indicates whether the second humidifier module is due for...Read0=No, 1=Yes
BV99Module 3 Service DueStatus value that indicates whether the third humidifier module is due for...Read0=No, 1=Yes
BV100Module 4 Service DueStatus value that indicates whether the fourth humidifier module is due for...Read0=No, 1=Yes
BVmin104Network Control StateState of the control communication between the device and the BACnet networkWrite0=Normal, 1=Fault
BV105Module 2 Foam StateWhether the second humidifier module has currently detected foam or notRead0=Ok, 1=Detected
BV106Module 3 Foam StateWhether the third humidifier module has currently detected foam or notRead0=Ok, 1=Detected
BV107Module 4 Foam StateWhether the fourth humidifier module has currently detected foam or notRead0=Ok, 1=Detected
BV109HRL Lock SetpointWhether the setpoint obtained from the HRL24 controller can be modifiedCommand0=Unlock, 1=Lock
BV111Module 1 Drain ValveNormally open drain valve of the first humidifier moduleCommand0=On, 1=Off
BV112Module 2 Drain ValveNormally open drain valve of the second humidifier moduleCommand0=On, 1=Off
BV113Module 3 Drain ValveNormally open drain valve of the third humidifier moduleCommand0=On, 1=Off
BV114Module 4 Drain ValveNormally open drain valve fourth humidifier moduleCommand0=On, 1=Off
BV143Module 1 Manual Water Calibration StateThat the water level sensor must be manually calibratedRead0=Ok, 1=Required
BV144Module 2 Manual Water Calibration StateThat the water level sensor must be manually calibratedRead0=Ok, 1=Required
BV145Module 3 Manual Water Calibration StateThat the water level sensor must be manually calibratedRead0=Ok, 1=Required
BV146Module 4 Manual Water Calibration StateThat the water level sensor must be manually calibratedRead0=Ok, 1=Required
BV151Module1 AntiFreeze WarningStatus of the anti freeze warning indicating if the drain valve is...Read0=Inactive, 1=Drain
BV152Module2 AntiFreeze WarningStatus of the anti freeze warning indicating if the drain valve is...Read0=Inactive, 1=Drain
BV153Module3 AntiFreeze WarningStatus of the anti freeze warning indicating if the drain valve is...Read0=Inactive, 1=Drain
BV154Module4 AntiFreeze WarningStatus of the anti freeze warning indicating if the drain valve is...Read0=Inactive, 1=Drain
BV156Memory StatusStatus of the NVMRead0=Ok, 1=Fail
CSV38EthernetMacAddMAC address of the Ethernet interfaceWrite
MV9BACnet Server List ModeCategory of BACnet objects to displayWrite1=Integrator, 2=Advanced, 3=Factory
MV10BACnet Server UnitsDisplay units for the BACnet serverWrite1=Metric, 2=Imperial
MV26Supply RH Signal TypeSignal type for the duct or supply high limit humidity analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV27Room RH Signal TypeSignal type for the room humidity analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV28Control Signal TypeSignal type for the control demand analog inputWrite1=0-10Vdc, 2=2-10mA, 3=4-30mA, 4=0-20mA
MVmin33Control ProfileA preconfigured control mode profile for the modulating humidity demandWrite1=ExternAnalog, 2=ExternNetwork, 3=InternAnalog, 4=InternNetwork, 5=HRL, 6=Custom
MV34Modulating High Limit ProfileA preconfigured control mode profile for the modulating high limit demandWrite1=Disabled, 2=ExternAnalog, 3=ExternNetwork, 4=InternAnalog, 5=InternNetwork, 6=Custom
MV37Occupancy StateOccupancy stateRead1=Occupied, 2=Unoccupied, 3=Vacant, 4=Off
MV56Humidity Control Cutout StateState of the safety control circuit and whether the circuit has been...Read1=Off, 2=Normal, 3=LowLimit, 4=HighLimit, 5=AirFlow, 6=Interlock
MVmin60System Power StateWhether the system is powered on or offWrite1=Off, 2=On
MV61System RequestPerform one of the following actions for the system: reset service counters...Write1=None, 2=Reset Alarms, 3=Drain, 4=Reset Counters, 5=Filling, 6=WaterCalib, 7=PurgeAir
MVmin63Module 1 StateState of operation of the first humidifier moduleRead1=Off, 2=Idle, 3=LineRinse, 4=TankRinse, 5=Filling, 6=Draining, 7=Heating, 8=Boiling, 9=Alarm, 10=PurgeAir
MV64Module 1 RequestPerform one of the following actions for the first humidifier module: reset...Write1=None, 2=Reset Alarms, 3=Drain, 4=Reset Counters, 5=Filling, 6=WaterCalib, 7=PurgeAir
MVmin65Module 1 AlarmStatus of the first humidifier’s alarmRead1=Normal, 2=FailedPump, 3=FillTimeout, 4=Blocked Piping, 5=HeatTimeout, 6=Overheat, 7=WaterLeak, 8=Service, 9=Reserved, 10=BurnerLocked, 11=FanDefect, 12=FailedComm, 13=ChimTempHi, 14=RefillTimeout, 15=FanBlocked, 16=SystBlck, 17=TankBlocked, 18=RefillDelay
MV66Module 2 StateState of operation of the second humidifier moduleRead1=Off, 2=Idle, 3=LineRinse, 4=TankRinse, 5=Filling, 6=Draining, 7=Heating, 8=Boiling, 9=Alarm, 10=PurgeAir
MV67Module 2 RequestPerform one of the following actions for the second humidifier module: reset...Write1=None, 2=Reset Alarms, 3=Drain, 4=Reset Counters, 5=Filling, 6=WaterCalib, 7=PurgeAir
MV68Module 2 AlarmStatus of the second humidifier’s alarmRead1=Normal, 2=FailedPump, 3=FillTimeout, 4=Blocked Piping, 5=HeatTimeout, 6=Overheat, 7=WaterLeak, 8=Service, 9=Reserved, 10=BurnerLocked, 11=FanDefect, 12=FailedComm, 13=ChimTempHi, 14=RefillTimeout, 15=FanBlocked, 16=SystBlck, 17=TankBlocked, 18=RefillDelay
MV69Module 3 StateState of operation of the third humidifier moduleRead1=Off, 2=Idle, 3=LineRinse, 4=TankRinse, 5=Filling, 6=Draining, 7=Heating, 8=Boiling, 9=Alarm, 10=PurgeAir
MV70Module 3 RequestPerform one of the following actions for the third humidifier module: reset...Write1=None, 2=Reset Alarms, 3=Drain, 4=Reset Counters, 5=Filling, 6=WaterCalib, 7=PurgeAir
MV71Module 3 AlarmStatus of the third humidifier’s alarmRead1=Normal, 2=FailedPump, 3=FillTimeout, 4=Blocked Piping, 5=HeatTimeout, 6=Overheat, 7=WaterLeak, 8=Service, 9=Reserved, 10=BurnerLocked, 11=FanDefect, 12=FailedComm, 13=ChimTempHi, 14=RefillTimeout, 15=FanBlocked, 16=SystBlck, 17=TankBlocked, 18=RefillDelay
MV72Module 4 StateState of operation of the fourth humidifier moduleRead1=Off, 2=Idle, 3=LineRinse, 4=TankRinse, 5=Filling, 6=Draining, 7=Heating, 8=Boiling, 9=Alarm, 10=PurgeAir
MV73Module 4 RequestPerform one of the following actions for the fourth humidifier module: reset...Write1=None, 2=Reset Alarms, 3=Drain, 4=Reset Counters, 5=Filling, 6=WaterCalib, 7=PurgeAir
MV74Module 4 AlarmStatus of the fourth humidifier’s alarmRead1=Normal, 2=FailedPump, 3=FillTimeout, 4=Blocked Piping, 5=HeatTimeout, 6=Overheat, 7=WaterLeak, 8=Service, 9=Reserved, 10=BurnerLocked, 11=FanDefect, 12=FailedComm, 13=ChimTempHi, 14=RefillTimeout, 15=FanBlocked, 16=SystBlck, 17=TankBlocked, 18=RefillDelay
MV77Boiler Fill ModeWater filling method for the fill valve: When set to OneShot, water...Write1=OneShot, 2=Pulsed
MV78SKG ConfigurationThis object id is used for internal communication between the modulesRead1=RetroInside, 2=RetroOutside, 3=NewInside, 4=NewOutside
MV79Boiler Idle Tank Rinse OffWhether to enable automatic rinse cycles while the humidifier is turned off...Write1=Off, 2=On
MV80Boiler Idle Tank Rinse OnWhether to enable automatic rinse cycles while the humidifier is turned on...Write1=Off, 2=On
MV93Water Probe 1 Auto CalibWhether to enable or disable the automatic calibration of the water level...Write1=Off, 2=On
MV94Water Probe 2 Auto CalibWhether to enable or disable the automatic calibration of the water level...Write1=Off, 2=On
MV95Water Probe 3 Auto CalibWhether to enable or disable the automatic calibration of the water level...Write1=Off, 2=On
MV96Water Probe 4 Auto CalibWhether to enable or disable the automatic calibration of the water level...Write1=Off, 2=On
MV99System ModeSet under which system operation mode the different modules will operateWrite1=Parallel, 2=Sequential, 3=Hybrid
MV104BACnet Server LanguageBACnet server languageWrite1=English, 2=French, 3=Spanish
MV105SKG ConfigurationThis object id is used for internal communication between the modulesRead1=RetroInside, 2=RetroOutside, 3=NewInside, 4=NewOutside
MV106SKG ConfigurationThis object id is used for internal communication between the modulesRead1=RetroInside, 2=RetroOutside, 3=NewInside, 4=NewOutside
MV107SKG ConfigurationThis object id is used for internal communication between the modulesRead1=RetroInside, 2=RetroOutside, 3=NewInside, 4=NewOutside
MV115Boiler Startup Tank RinseWhether to perform an automatic tank rinse cycle upon each start-up of...Write1=Off, 2=On
MV116Module 1 Water Level Probe WarningWhether there is currently a warning message associated with the water level...Read1=Ok, 2=Replace
MV117Module 2 Water Level Probe WarningWhether there is currently a warning message associated with the water level...Read1=Ok, 2=Replace
MV118Module 3 Water Level Probe WarningWhether there is currently a warning message associated with the water level...Read1=Ok, 2=Replace
MV119Module 4 Water Level Probe WarningWhether there is currently a warning message associated with the water level...Read1=Ok, 2=Replace
MV121Water Level 1 Probe FailureWhich one of the water level sensor’s probes that are currently not...Read1=None, 2=Capacitive, 3=Resistive, 4=Both
MV122Water Level 2 Probe FailureWhich one of the water level sensor’s probes that are currently not...Read1=None, 2=Capacitive, 3=Resistive, 4=Both
MV123Water Level 3 Probe FailureWhich one of the water level sensor’s probes that are currently not...Read1=None, 2=Capacitive, 3=Resistive, 4=Both
MV124Water Level 4 Probe FailureWhich one of the water level sensor’s probes that are currently not...Read1=None, 2=Capacitive, 3=Resistive, 4=Both
MV125Module 1 Bacnet UnitsBACnet units for module 1Read0=Metric, 1=Imperial
MV126Module 2 Bacnet UnitsBACnet units for module 2Read0=Metric, 1=Imperial
MV127Module 3 Bacnet UnitsBACnet units for module 3 (printed as NSV.127)Read0=Metric, 1=Imperial
MV128Module 4 Bacnet UnitsBACnet units for module 4Read0=Metric, 1=Imperial
MV129Module 1 Water Level Probe AlarmWhether there is currently an alarm message to indicate that the water...Read0=Ok, 1=Defect, 2=NoCalib
MV130Module 2 Water Level Probe AlarmWhether there is currently an alarm message to indicate that the water...Read0=Ok, 1=Defect, 2=NoCalib
MV131Module 3 Water Level Probe AlarmWhether there is currently an alarm message to indicate that the water...Read0=Ok, 1=Defect, 2=NoCalib
MV132Module 4 Water Level Probe AlarmWhether there is currently an alarm message to indicate that the water...Read0=Ok, 1=Defect, 2=NoCalib
MV135Update Process StatusStatus of the Firmware update processRead0=Ok, 1=CRC, 2=Device, 3=Failed
Other1NSDF Core ProgramNSDF Core ProgramWrite
Other2BACnet Server ProgramBACnet Server ProgramWrite
Other3LCD_Display ProgramLCD_Display ProgramWrite
Other4Modbus Server ProgramModbus Server ProgramWrite
Other5RMHI ProgramRHMI ProgramWrite
Other6SKG ProgramSKG ProgramWrite
Other7Universal Humidifier Manager ProgramUniversal Humidifier Manager ProgramWrite
Other8Universal User Control ProgramUniversal User Control ProgramWrite
Other9Web Server ProgramWeb Server ProgramWrite
Other10Water Level Probe ProgramWater Level Probe ProgramWrite
Other16NSDF DatabaseDatabase ProgramWrite
FILE2UpdatePackageFileUpdate Package fileWrite
FILE4SysLogAlarmSystem Log AlarmWrite
FILE9USB System Log FileUSB System Log fileWrite
FILE10USB System Alarm Log FileUSB System Alarm Log fileWrite
FILE16System Log FileSystem Log fileWrite
SCH1Occupancy ScheduleWeekly occupancy schedule to specify which occupancy state is active during specific...Write
SCH2Drain ScheduleCustomized draining schedule with up to six events per dayWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKG4 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic SKG4

How many BACnet points does the Neptronic SKG4 have?

This list has 303 BACnet objects: 3 analog inputs, 1 analog output, 144 analog values, 7 binary inputs, 5 binary outputs, 70 binary values, 5 files, 2 schedules, 54 multi-state values, 1 characterstring value, 11 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic SKG4 BACnet points are writable?

175 of the 303 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic SKG4 BACnet documentation?

The source is SKG4 Gas Fired Humidifier BACnet Communication Module User Guide (SKG4-BACnet Guide-250609 (V2.06)), revision 2025-06-09, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/2025/SKG4-BACnet%20Guide-250609%20(V2.06).pdf.

What are the minimum BACnet points to integrate the Neptronic SKG4?

Start with MV 60 System Power State (System on/off from the BMS); MV 33 Control Profile (Control profile: choose a Network profile); AV 141 Humidity Control Network Demand (Network humidity demand written by the BMS); AV 110 Room RH Setpoint (Occupied room RH setpoint (internal control)); AV 109 Room RH Network Reading (Network room RH reading for internal control); MV 63 Module 1 State (Module 1 operating state); AV 148 System Power Output (Actual output of the whole system %); MV 65 Module 1 Alarm (Module 1 active alarm (1 = Normal)); BV 104 Network Control State (1 = fault: network control lost (AV 248 timeout)).

How do I enable BMS control of the Neptronic SKG4?

MSV 60 System Power State is writable (1 = Off, 2 = On). The control source follows MSV 33 Control Profile (ExternNetwork / InternNetwork for BMS control) or the individual source MSVs with the Custom profile.

Does the Neptronic SKG4 need a BACnet heartbeat or have a communication timeout?

AV 248 Network Timeout (1-900 s) sets how long the humidifier tolerates loss of BACnet control communication before stopping; BV 104 Network Control State reports 1 = Fault.

Can the BMS supply sensor values to the Neptronic SKG4?

With the room RH source on Network write room RH to AV 109 and setpoints to AV 110-112 (occupied/unoccupied/vacant); write the supply high limit reading to AV 125 and setpoint AV 126. A direct network demand goes to AV 141 and a network high limit to AV 142.

How do I check these points on the real SKG4?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: SKG4 Gas Fired Humidifier BACnet Communication Module User Guide · SKG4-BACnet Guide-250609 (V2.06) · rev. 2025-06-09. Object names, instances and units are reproduced as published; descriptions are our own.