Make-up air unit (electric heat) · BACnet points list

Neptronic CMU Compact Make-up Air Unit BACnet points list

Updated 28 October 2026

Short answer

The CMU is a packaged make-up air heater with its own controller that exposes a fixed BACnet MS/TP object table. Objects are grouped into Integrator, Advanced and Factory lists, and MSV.2 Cfg_ObjectListMode selects which group the controller shows on the network. Points cover supply, room and outdoor air readings, airflow and temperature setpoints, damper and exhaust fan settings, and a long set of heater and sensor alarms.

This page lists 130 BACnet objects for the Neptronic CMU Compact Make-up Air Unit — 76 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
CMU Compact Make-up Air Unit
Equipment
Make-up air unit (electric heat)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
130 (76 writable)
Transport
BACnet MS/TP
Firmware
1.02 (as printed)
Default device instance
153000 + MAC address
Also known as
CMU, Neptronic CMU
Source document
Compact Make-up Air Unit BACnet Communication Module User Guide · CMU-BACnet Guide-211201 · rev. 2021-12-01
Download CSV 130 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Neptronic CMU Compact Make-up Air Unit

Integration in brief

Start/stop the unit with BV.18 SystemOnOff, choose where the temperature setpoint comes from with MSV.17 (set Network to use AV.10), and command the fan through AV.7 CurrentAirflowSetpoint. Monitor supply air temperature, occupancy state and the alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 18SystemOnOffTurns the unit on or offWrite
MV 17Cfg_TempSetpointSourceSelect OnBoard, Tstat or Network setpoint sourceWrite
AV 10NetworkTempSetpointTemperature setpoint written by the BMSWrite
AV 7CurrentAirflowSetpointFan speed / airflow setpoint % (commandable)Command
MV 1OccupancyStateOccupied, unoccupied or offRead
BV 4CMUFanEnableShows whether the supply fan is enabledRead
AV 1SATSupply air temperatureRead
BV 19HostThermalCutoutAlarmHeater thermal cutout alarmRead
BV 28HostAirFlowDetectAlarmAirflow sensor alarmRead

Enable & remote start

BV.18 SystemOnOff turns the system on or off from the network. Occupancy can come from inputs (BV.13 enables them, BV.17 picks Unoccupied or Off when inactive) or from the internal schedule enabled by BV.11; without a schedule the unit stays occupied.

Sensors & values from the BMS

Set MSV.17 Cfg_TempSetpointSource to Network and write AV.10 NetworkTempSetpoint. MSV.16 selects whether control is on supply (SAT) or room (RAT) temperature; the doc lists no BMS-written temperature input.

Network setup

Watch out for

Neptronic CMU Compact Make-up Air Unit BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

130 of 130 shown
Type
Multi-state
Access
Show
Neptronic CMU Compact Make-up Air Unit BACnet Points List
DescriptionStates
AI1AI1_VoltageActual voltage of analog input 1 in VdcVRead
AI2AI2_VoltageActual voltage of analog input 2 in VdcVRead
AI3AI3_TemperatureActual temperature read by the sensor on analog input 3°F/°CRead
AI4AI4_TemperatureActual temperature read by the sensor on analog input 4°F/°CRead
AI5Room Air TemperatureRoom temperature reading value°F/°CRead
AI6Room Air Relative HumidityRoom relative humidity reading value%RHRead
AI7CO2LevelReading of the CO sensorppmRead
AI8VOCIndexReading of the VOC sensorRead
AI9LuminousFluxReading of the light sensorluxRead
AI10CMUOnBoardTempSetpointTemperature setpoint value from the CMU on-board potentiometer°F/°CRead
AI11CMUIntakeCMU air intake temperature°F/°CRead
AI12CMUOuttakeCMU air outtake temperature°F/°CRead
AI13CMUBoardTempeatureTemperature value of the CMU main printed circuit board°F/°CRead
AI14CMUSSRTempTemperature value measured on the solid-state relay°F/°CRead
AO1AO1_VoltageVoltage on analog output 1 in VdcVCommand
AO2AO2_VoltageVoltage on analog output 2 in VdcVCommand
AVmin1SATSupply Air Temperature (SAT) reading°F/°CRead
AV2SARHSupply Air Relative Humidity (SARH) reading%RHRead
AV3OATOutside Air Temperature (OAT) reading°F/°CRead
AV4OARHOutside Air Relative Humidity (OARH) reading%RHRead
AV5DuctStaticPressureStatic pressure value in the ductPaRead
AV6ModulatingDamperFeedbackFeedback value corresponding to the modulating damper position%Read
AVmin7CurrentAirflowSetpointAirflow setpoint value as a percentage of the maximum capacity (fan speed%Command
AV8CMUFanRPMECM fan speed RPM valueppmRead
AV9CMUHeaterStage1DutyCycleDuty cycle of the heater vernier stage 1 when there is a%Read
AVmin10NetworkTempSetpointTemperature setpoint set over the network°F/°CWrite
AV11TstatTempSetpointTemperature setpoint set using the TDF°F/°CWrite
AV12Cfg_CMUAntiFreezeSetpointCMU anti-freeze temperature setpoint (Advanced list)°F/°CCommand
AV13Cfg_OccAirflowSetpointAirflow setpoint in percentage of the maximum capacity when in Occupied mode (Advanced list)%Write
AV14Cfg_UnoccAirflowSetpointAirflow setpoint in percentage of the maximum capacity when in Unoccupied mode (Advanced list)%Write
AV15Cfg_BI3_StageWeightSignal stage weight for binary input 3 in percentage of the full (Advanced list)%Write
AV16Cfg_BI4_StageWeightSignal stage weight for binary input 4 in percentage of the full (Advanced list)%Write
AV17Cfg_ExhaustFanDelayExhaust fan start time delay (Advanced list)sWrite
AV18Cfg_ExhaustFanMinRangeMinimum value of the exhaust fan control signal (Advanced list)VWrite
AV19Cfg_ExhaustFanMaxRangeMaximum value of the exhaust fan control signal (Advanced list)VWrite
AV20Cfg_DamperDelayDamper stroke time delay (Advanced list)sWrite
AV21Cfg_OccupanyInputMinTimeOccupancy input minimum time (Advanced list)minWrite
AV22Cfg_TstatTempSetpointMinMinimum value of the temperature setpoint set using the TDF (Advanced list)°F/°CWrite
AV23Cfg_TstatTempSetpointMaxMaximum value of the temperature setpoint set using the TDF (Advanced list)°F/°CWrite
AV24Cfg_DryModeSetpointRelative humidity setpoint in dry mode (Advanced list)%RHWrite
AV25Cfg_DryModeDeadBandDeadband for the relative humidity setpoint in dry mode (Advanced list)%RHWrite
AV26Cfg_DryModeAntiCycleDelayAnti-cycle time delay in dry mode (Advanced list)minWrite
AV27Cfg_DuctOccStaticPressureSetpointStatic pressure control loop setpoint in the duct when in occupied mode (Advanced list)PaWrite
AV28Cfg_DuctUnoccStaticPressureSetPointStatic pressure control loop setpoint in the duct when in unoccupied mode (Advanced list)PaWrite
AV29Cfg_CO2SetpointMaximum limit of CO concentration before the unit sends 2 an alarm (Advanced list)ppmWrite
AV30Cfg_CO2DeadBandDeadband for the maximum limit of CO concentration (Advanced list)ppmWrite
AV31Cfg_SATOffsetSupply Air Temperature offset (Advanced list)°F/°CWrite
AV32Cfg_SARHOffsetSupply Air Relative Humidity offset (Advanced list)%RHWrite
AV33Cfg_OATOffsetOutside Air Temperature offset (Advanced list)°F/°CWrite
AV34Cfg_OARHOffsetOutside Air Relative Humidity offset (Advanced list)%RHWrite
AV35Cfg_RATOffsetRoom Air Temperature offset (Advanced list)°F/°CWrite
AV36Cfg_RARHOffsetRoom Air Relative Humidity offset (Advanced list)%RHWrite
AV37Cfg_DuctStaticPressureOffsetDuct static pressure offset (Advanced list)PaWrite
AV38Cfg_FactoryMinFanSpeedMinimum fan speed (Factory list)%Write
AV39Cfg_TempControlPropBandTemperature control proportional band (Factory list)°F/°CWrite
AV40Cfg_TempControlIntTimeTemperature control integral time (Factory list)sWrite
AV41Cfg_TempControlDerivTimeTemperature control derivative time (Factory list)sWrite
AV42Cfg_StaticPressurePropBandStatic pressure control proportional band (Factory list)PaWrite
AV43Cfg_StaticPressureIntTimeStatic pressure control integral time (Factory list)sWrite
AV44Cfg_StaticPressureDerivTimeStatic pressure control derivative time (Factory list)sWrite
AV45Cfg_SATControlBandSupply Air Temperature control band°F/°CWrite
AV46SynchroTimeoutCountSynchronization timeout counter (Factory list)Write
AV47NoHeatDetectionDeadbandNo Heat Detection deadband°F/°CWrite
AV48NoHeatDetectionDelayNo Heat Detection time delaysWrite
BI1BI3_StateContact status of analog input 3/binary input 3: (0) Open, (1) CloseRead0 = Open, 1 = Close
BI2BI4_StateContact status of analog input 4/binary input 4: (0) Open, (1) CloseRead0 = Open, 1 = Close
BI3OccupancySensorStatus value on whether the occupancy sensor has detected movementRead0 = No, 1 = Yes
BI4CMUOnOffInputState of the CMU on/off input contactRead0 = Off, 1 = On
BO1BO1_StateContact status of binary output 1: (0) Open, (1) CloseCommand0 = Open, 1 = Close
BO2BO2_StateContact status of binary output 2: (0) Open, (1) CloseCommand0 = Open, 1 = Close
BV1ExhaustFanStateStatus value for the state of the exhaust fanRead0 = Off, 1 = On
BV2OnOffDamperStateStatus value for the state of the on/off damperRead0 = Closed, 1 = Open
BV3OnOffDamperFeedbackStatus value for the state of the on/off damper feedbackRead0 = Closed, 1 = Open
BVmin4CMUFanEnableStatus value to indicate whether the CMU fan has been enabledRead0 = No, 1 = Yes
BV5CMUHeaterStage2StateStatus value for the state of the second heater stageRead0 = Off, 1 = On
BV6Cfg_BI3ContactTypeChange the contact's normal position for binary input 3. Input can be (Advanced list)Write0 = NO, 1 = NC
BV7Cfg_BI4ContactTypeChange the contact's normal position for binary input 4. Input can be (Advanced list)Write0 = NO, 1 = NC
BV8Cfg_BO1ContactTypeChange the contact's normal position for binary output 1. Output can be (Advanced list)Write0 = NO, 1 = NC
BV9Cfg_BO2ContactTypeChange the contact's normal position for binary output 2. Output can be (Advanced list)Write0 = NO, 1 = NC
BV10Cfg_TstatTempSetpointLockTo lock the temperature setpoint on the TDF (Advanced list)Write0 = No, 1 = Yes
BV11Cfg_ScheduleEnableActivate the schedule (Advanced list)Write0 = No, 1 = Yes
BV12Cfg_UnitSelectionTo select between the metric and imperial unit system (Advanced list)Write0 = Metric, 1 = Imperial
BV13Cfg_OccupancyInputsEnableTo enable or disable the occupancy inputs (Advanced list)Write0 = No, 1 = Yes
BV14Cfg_DryModeTo enable or disable the dry mode (Advanced list)Write0 = Disable, 1 = Enable
BV15Cfg_CO2ExtractModeTo enable or disable the CO extract mode (Advanced list)Write0 = Disable, 1 = Enable
BV16Cfg_StaticPressureLoopTo enable or disable the static pressure loop (Advanced list)Write0 = Disable, 1 = Enable
BV17Cfg_OccupanyInputsInactiveModeOccupancy mode when inactive to either the (0) Unoccupied or (1) Off (Advanced list)Write0 = Unoccupied, 1 = Off
BVmin18SystemOnOffTo turn the system on or offWrite0 = Off, 1 = On
BVmin19HostThermalCutoutAlarmStatus value to indicate whether the Thermal Cutout alarm has been triggeredRead0 = Off, 1 = On
BV20HostCommTimeoutAlarmStatus value to indicate whether the Communication Timeout alarm has been triggeredRead0 = Off, 1 = On
BV21HostSSRCutoutAlarmStatus value to indicate whether the SSR Cutout alarm has been triggeredRead0 = Off, 1 = On
BV22HostBoardCutoutAlarmStatus value to indicate whether the Board Cutout alarm has been triggeredRead0 = Off, 1 = On
BV23HostSSOR1AlarmStatus value to indicate whether the SSOR1 Sensor alarm has been triggeredRead0 = Off, 1 = On
BV24HostSSOR2AlarmStatus value to indicate whether the SSOR2 Sensor alarm has been triggeredRead0 = Off, 1 = On
BV25HostBoardTempAlarmStatus value to indicate whether the Board Temperature Sensor alarm has beenRead0 = Off, 1 = On
BV26HostSSRTempAlarmStatus value to indicate whether the SSR Temperature Sensor alarm has beenRead0 = Off, 1 = On
BV27HostFanTempAlarmStatus value to indicate whether the Fan Temperature Sensor alarm has beenRead0 = Off, 1 = On
BVmin28HostAirFlowDetectAlarmStatus value to indicate whether the Airflow Sensor alarm has been triggeredRead0 = Off, 1 = On
BV29HostInvalidConfigAlarmStatus value to indicate whether the Invalid Board Configuration alarm has beenRead0 = Off, 1 = On
BV30HostNoHeatDetectionAlarmStatus value to indicate whether the No Heat Detection alarm has beenRead0 = Off, 1 = On
BV31HostFrequencySynchronisationErrorStatus value to indicate whether there is a frequency synchronisation error, indicatingRead0 = Off, 1 = On
BV32DamperBlockedAlarmStatus value to indicate whether the Damper Blocked alarm has been triggeredRead0 = Off, 1 = On
BV33SATNotDetectedAlarmStatus value to indicate whether the No Supply Air Temperature Input alarmRead0 = Off, 1 = On
BV34RATNotDetectedAlarmStatus value to indicate whether the No Room Air Temperature Input alarmRead0 = Off, 1 = On
BV35TimeoutCommAlarmStatus value to indicate whether the Timeout Communication alarm has been triggeredRead0 = Off, 1 = On
BV36AI1NotConnectedStatus value to indicate whether analog input 1 is connected or notRead0 = Off, 1 = On
BV37AI2NotConnectedStatus value to indicate whether analog input 2 is connected or notRead0 = Off, 1 = On
BV38NoHeatDetectionAlarmStatus value to indicate whether the No Heat Detection alarm has beenRead0 = Off, 1 = On
BV39ECMFanFeedbackHostAlarmStatus value to indicate whether the ECM Fan Feedback alarm has beenRead0 = Off, 1 = On
BV40Cfg_AutoPIDTo enable or disable Auto PID (Factory list)Write0 = No, 1 = Yes
MVmin1OccupancyStateStatus that indicates the state of actual occupancyReadOccupied Unoccupied Off
MV2Cfg_ObjectListModeTo select the category of BACnet objects to displayWriteIntegrator Advanced Factory
MV3Cfg_AI1_ModeFor the mode of Analog Input 1. This input accepts a 0-10Vdc (Advanced list)WriteOff SAT SARH OAT OARH StaticPressure FanSetpoint DamperFeedback
MV4Cfg_AI2_ModeSame description as MSV.3 (Advanced list)WriteOff SAT SARH OAT OARH StaticPressure FanSetpoint DamperFeedback
MV5Cfg_AI3_BI3_ModeFor the mode of Analog input 3/Binary input 3. This input accepts (Advanced list)WriteOff SAT OAT DamperFeedback Occupancy FanSpeedStage
MV6Cfg_AI4_BI4_ModeSame description as MSV.5 (Advanced list)WriteOff SAT OAT DamperFeedback Occupancy FanSpeedStage
MV7Cfg_AO1_ModeFor the mode of Analog output 1. Provides a 0-10Vdc signal (Advanced list)WriteOff ExhaustFan Damper
MV8Cfg_AO2_ModeSame description as MSV.7 (Advanced list)WriteOff ExhaustFan Damper
MV9Cfg_BO1_ModeFor the mode of Binary output 1. Provides a dry contact signal (Advanced list)WriteOff ExhaustFan Damper
MV10Cfg_BO2_ModeSame description as MSV.9 (Advanced list)WriteOff ExhaustFan Damper
MV11Cfg_StaticPressureSensorRangeSelect the range of the static pressure sensor in Pascal (Advanced list)Write250 500 1250
MV12Cfg_AI1_SignalRangeTo select the signal type range for analog input 1 (Advanced list)Write2-10Vdc 0-10Vdc
MV13Cfg_AI2_SignalRangeTo select the signal type range for analog input 2 (Advanced list)Write2-10Vdc 0-10Vdc
MV14Cfg_AO1_SignalRangeTo select the signal type range for analog output 1 (Advanced list)Write2-10Vdc 0-10Vdc
MV15Cfg_AO2_SignalRangeTo select the signal type range for analog output 2 (Advanced list)Write2-10Vdc 0-10Vdc
MV16Cfg_TempControlSourceTemperature control source (Advanced list)WriteSAT RAT
MVmin17Cfg_TempSetpointSourceTemperature setpoint sourceWriteOnBoard Tstat Network
MV18Cfg_AdditionalDisplaySecond line of display on the TDF. None: No value is displayed (Advanced list)WriteNone Time CO2 SARH RAT
MV19Cfg_TemperatureDisplayedTemperature value to displayWriteDefault Alternate SAT Tstat
MV20Reset_reasonReason for the previous system reset (Advanced list)ReadnoReason ndependentWatchdog windowWatchdog softwareReset powerDown

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CMU Compact Make-up Air Unit and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic CMU Compact Make-up Air Unit

How many BACnet points does the Neptronic CMU Compact Make-up Air Unit have?

This list has 130 BACnet objects: 14 analog inputs, 2 analog outputs, 48 analog values, 4 binary inputs, 2 binary outputs, 40 binary values, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic CMU Compact Make-up Air Unit BACnet points are writable?

76 of the 130 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic CMU Compact Make-up Air Unit BACnet documentation?

The source is Compact Make-up Air Unit BACnet Communication Module User Guide (CMU-BACnet Guide-211201), revision 2021-12-01, published free by Neptronic at https://www.neptronic.com/heaters/pdf/20211206/CMU-BACnet%20Guide-211201.pdf.

What are the minimum BACnet points to integrate the Neptronic CMU Compact Make-up Air Unit?

Start with BV 18 SystemOnOff (Turns the unit on or off); MV 17 Cfg_TempSetpointSource (Select OnBoard, Tstat or Network setpoint source); AV 10 NetworkTempSetpoint (Temperature setpoint written by the BMS); AV 7 CurrentAirflowSetpoint (Fan speed / airflow setpoint % (commandable)); MV 1 OccupancyState (Occupied, unoccupied or off); BV 4 CMUFanEnable (Shows whether the supply fan is enabled); AV 1 SAT (Supply air temperature); BV 19 HostThermalCutoutAlarm (Heater thermal cutout alarm); BV 28 HostAirFlowDetectAlarm (Airflow sensor alarm).

How do I enable BMS control of the Neptronic CMU Compact Make-up Air Unit?

BV.18 SystemOnOff turns the system on or off from the network. Occupancy can come from inputs (BV.13 enables them, BV.17 picks Unoccupied or Off when inactive) or from the internal schedule enabled by BV.11; without a schedule the unit stays occupied.

Can the BMS supply sensor values to the Neptronic CMU Compact Make-up Air Unit?

Set MSV.17 Cfg_TempSetpointSource to Network and write AV.10 NetworkTempSetpoint. MSV.16 selects whether control is on supply (SAT) or room (RAT) temperature; the doc lists no BMS-written temperature input.

How do I check these points on the real CMU Compact Make-up Air Unit?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: Compact Make-up Air Unit BACnet Communication Module User Guide · CMU-BACnet Guide-211201 · rev. 2021-12-01. Object names, instances and units are reproduced as published; descriptions are our own.