Evaporative cooler / humidifier · BACnet points list

Neptronic SKVF BACnet points list

Updated 28 October 2026

Short answer

The SKVF is an evaporative media cooler that can control on humidity or temperature. Its controller provides BACnet MS/TP and BACnet IP with selectable control profiles, network RH and temperature readings and setpoints, occupancy, operating state and alarms.

This page lists 201 BACnet objects for the Neptronic SKVF — 151 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
SKVF
Equipment
Evaporative cooler / humidifier
Equipment type
Humidifiers
BACnet objects
201 (151 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
153000 + MAC address (153001 by default)
Also known as
SKVF evaporative cooler, SKVF Series, SKVF BACnet
Source document
Evaporative Cooler SKVF Series BACnet Communication Module User Guide · SKVF-BACnet Guide (v1.08)-250212 · rev. 2025-02-12
Download CSV 201 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Neptronic SKVF

Integration in brief

Select a network control profile (MSV 28) or set MSV 43 to Network and write demand to AV 138; for internal control feed room RH (AV 106) or temperature (AV 155) with their setpoints. Switch the unit with MSV 83 and supervise BV 44.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 83System Power StateSystem on/off from the BMSWrite
MV 28Control ProfileControl profile: choose a Network profileWrite
AV 138Control Network DemandDirect demand written by the BMS, %Command
AV 156Room Temperature SetpointOccupied room temp setpoint (internal control)Write
AV 107Room RH SetpointOccupied room RH setpoint (internal control)Write
AV 155Room Temperature Network ReadingBMS room temperature for internal controlWrite
AV 106Room RH Network ReadingNetwork room RH reading for internal controlCommand
MV 58StateOperating state (Idle, Running, Alarm...)Read
MV 61System AlarmCooler alarm code (1 = Normal)Read
BV 44Network Control State1 = fault: network control lost (AV 223 timeout)Write

Enable & remote start

MSV 83 System Power State is writable (1 = Off, 2 = On); the control source follows MSV 28 Control Profile or the individual source MSVs (43, 33, 76) with the Custom profile.

Heartbeat & communication loss

AV 223 Network Timeout (1-900 s) sets how long the cooler tolerates loss of BACnet control communication before it stops; BV 44 Network Control State shows 1 = Fault.

Sensors & values from the BMS

Room RH to AV 106 (MSV 33 = Network), room temperature to AV 155 (MSV 76 = Network), setpoints AV 107-109 and AV 156-158; supply high limit RH AV 122 and temperature AV 175 with setpoints AV 123 and AV 176-178; direct demand AV 138.

Network setup

Watch out for

Neptronic SKVF BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

201 of 201 shown
Type
Multi-state
Access
Show
Neptronic SKVF BACnet Points List
DescriptionStates
AI5Control SignalHumidity demand control analog input signalVRead
AI6Room RH SignalRoom humidity analog input signalVRead
AI7Supply RH SignalSupply high limit humidity analog input signalVRead
AI9ECM Fan FeedbackFeedback value from the ECM fanRead
AI10Float Switch SignalFloat sensor signalVRead
AI25Main Power SupplyMeasured voltage in the power supplyVRead
AI27ECM Fan Feedback 2Feedback value from the second ECM fanRead
AI28Room Temperature SignalRoom temperature analog input signalVRead
AI29Supply Temperature SignalSupply high limit temperature analog input signalVRead
AI30Control SignalTemperature demand control analog input signalVRead
AO1Power Output Feedback SignalPower output feedback signalVRead
AO9ECM Fan SignalControl signal from the ECM fanVRead
AV10MCU LoadCurrent microcontroller load%Read
AV11Memory LoadCurrent memory load%Read
AV21DemandDemand value of the evapora+tive cooler%Read
AV41Control InputCurrent control input reading%Read
AV42Control MinMinimum value of the control demand analog input%Write
AV43Control MaxMaximum value of the control demand analog input%Write
AV44Control BiasBias value for the control demand analog input%Write
AV49Room RHRoom humidity reading%RHRead
AV50Room RH MinMinimum value of the room humidity analog input%Write
AV51Room RH MaxMaximum value of the room humidity analog input%Write
AV52Room RH BiasBias value of the room humidity analog input%RHWrite
AV57Supply High Limit RHSupply high limit humidity analog input%RHRead
AV58Supply High Limit RH MinMinimum value of the supply high limit humidity analog input%RHWrite
AV59Supply High Limit RH MaxMaximum value of the supply high limit humidity analog input%RHWrite
AV60Supply High Limit RH BiasBias value of the supply high limit humidity analog input%RHWrite
AV69Run TimeTotal runtime of the unithRead
AV70On TimeTotal operating time of the unithRead
AV71Water Treated VolumeVoulme of the water that has passed through the 5μm prefilter and...Read
AV72Service On TimeOperating time of the unit since the last servicing%Read
AV73Dead BandDeadband value for the humidity demand%Write
AV76Minimum Production OutputMinimum production output value for the fan%Write
AV77Maximum Production OutputMaximum production output value for the fan%Write
AV79RuntimeNumber of seconds that the system has been powered onsRead
AV81Idle Fan SpeedSpeed at while fan will run when the unit is in idle...%Write
AV82Service IntervalTime of operation before the evaporative cooler calls for servicinghWrite
AV85Power Output Feedback BiasBias value for the power output feedback signalVWrite
AV86Power Output Feedback MinMinimum value for the power output feedback signalVWrite
AV87Power Output Feedback MaxMaximum value for the power output feedback signalVWrite
AV88Power Output FeedbackPower output feedback signal%Write
AV92Dilution RatioDilution ratio to specify how much water will be drained during each...%Write
AV99Drain IntervalFrequency of the drain cycle when the unit is in operationhWrite
AV100Fixed Drain TimeAmount of time after which the unit will have to drain regardless...hWrite
AV101Line Rinse TimeDuration period for the pipe line rinse cycle performed upon startup of...sWrite
AV103Water Treatment Service VolumeVolume limit of water used during operation before the 5μm prefilter and...Write
AV104Water Supply Duty CyclePercentage of time that the water supply valve will stay on during...%Write
AV105Water Supply PeriodAmount of time required to complete an on and off cycle for...sWrite
AVmin106Room RH Network ReadingRoom relative humidity reading received from the network%RHCommand
AVmin107Room RH SetpointRoom relative humidity setpoint received from the network%RHWrite
AV108Room RH Unoccupied SetpointRoom relative humidity reading received from the network during no occupancy state%RHWrite
AV109Room RH Vacant SetpointRoom relative humidity reading received from the network during vacancy%RHWrite
AV110Room RH Demand Proportional GainRoom humidity demand proportional gainWrite
AV111Room RH Demand Integral TimeRoom humidity demand integral timesWrite
AV112Room RH Demand Derivative TimeRoom humidity demand derivative timesWrite
AV120Room RH DemandHumidity demand within the room%Command
AV122RH Supply High Limit Network ReadingSupply high limit humidity reading received from the network%RHCommand
AV123RH Supply High Limit SetpointSupply high limit humidity setpoint received from the network%RHWrite
AV124RH Supply High Limit Unoccupied SetpointSupply high limit humidity demand setpoint value used during Unoccupied state%RHWrite
AV125RH Supply High Limit Vacant SetpointSupply high limit humidity demand setpoint value used during Vacant state%RHWrite
AV126RH Supply High Limit Proportional GainSupply high limit humidity demand proportional gainWrite
AV127RH Supply High Limit Integral TimeSupply high limit humidity demand integral timesWrite
AV128RH Supply High Limit Derivative TimeSupply high limit humidity demand derivative timesWrite
AV136RH Supply High Limit DemandSupply high limit humidity demand value%Command
AVmin138Control Network DemandHumidity control demand received from the network%Command
AV139Control Network High LimitHumidity control high limit received from the network%Command
AV143User DemandCurrent humidity demand%Read
AV150Room TemperatureActual value of the room temperature analog input°F or °CWrite
AV151Room Temperature MinMinimum value of the room temperature analog input°F or °CWrite
AV152Room Temperature MaxMaximum value of the room temperature analog input°F or °CWrite
AV153Room Temperature BiasBias value of the room temperature analog input°F or °CWrite
AVmin155Room Temperature Network ReadingRoom temperature reading received from the network°F or °CWrite
AVmin156Room Temperature SetpointRoom relative temperature setpoint received from the network°F or °CWrite
AV157Room Temperature Unoccupied SetpointRoom relative temperature reading received from the network during no occupancy state°F or °CWrite
AV158Room Temperature Vacant SetpointRoom relative temperature reading received from the network during vacancy°F or °CWrite
AV159Room Temperature Demand Proportional GainRoom temperature demand proportional gainWrite
AV160Room Temperature Demand Integral TimeRoom temperature demand integral timesWrite
AV161Room Temperature Demand Derivative TimeRoom temperature demand derivative timesWrite
AV169Room Temperature DemandTemperature demand within the room%Command
AV170HRL TemperatureRoom temperature measured by the HRL24 controller°F or °CCommand
AV171HRL HumidityRoom humidity measured by the HRL24 controller%RHCommand
AV174Room Temp Demand Proportional BandRoom temperature demand proportional band%Write
AV175Temp Supply High Limit Network ReadingSupply high limit temperature reading received from the network°F or °CWrite
AV176Temp Supply High Limit SetpointSupply high limit relative temperature setpoint received from the network°F or °CWrite
AV177Temp Supply High Limit Unoccupied SetpointSupply high limit relative temperature reading received from the network during no...°F or °CWrite
AV178Temp Supply High Limit Vacant SetpointSupply high limit relative temperature reading received from the network during vacancy°F or °CWrite
AV179Temp Supply High Limit Proportional GainSupply high limit temperature demand proportional gainWrite
AV180Temp Supply High Limit Integral TimeSupply high limit temperature demand integral timesWrite
AV181Modbus TCP IP Keep Alive Time OutAmount of time the communication to the Modbus TCP/IP server stays open...minWrite
AV182Temp Supply High Limit Derivative TimeSupply high limit temperature demand derivative timesWrite
AV190Temp Supply High Limit DemandSupply high limit temperature demand within the room%Command
AV193Temp Supply High Limit Proportional BandSupply high limit temperature demand proportional band%Write
AV196Supply High Limit TemperatureSupply high limit temperature analog input signal°F or °CWrite
AV197Supply High Limit Temperature MinMinimum value of the supply high limit temperature analog input signal°F or °CWrite
AV198Supply High Limit Temperature MaxMaximum value of the supply high limit temperature analog input signal°F or °CWrite
AV199Supply High Limit Temperature BiasBias value of the supply high limit temperature analog input signal°F or °CWrite
AV207Control InputActual value of the temperature demand control analog input°F or °CWrite
AV208Control Input MinMinimum value of the temperature demand control analog input°F or °CWrite
AV209Control Input MaxMaximum value of the temperature demand control analog input°F or °CWrite
AV210Control Input BiasBias value of the temperature demand control analog input°F or °CWrite
AV220Demand Low Dead BandLower limit deadband for the humidity demand%RHWrite
AV223Network TimeoutAmount of time the evaporative cooler may attempt to connect to the...sWrite
AV230Room RH Demand Proportional BandRoom humidity demand proportional band%Write
AV231RH Supply High Limit Proportional BandSupply high limit humidity demand proportional band%Write
AV233Complete Dry DelayConfiguration value for the duration of time of the drying cycle for...hWrite
AV234Hours of Day Drying CycleConfiguration value for the hour of day during which the drying state...hWrite
AV235Drying Fan SpeedSpeed of the fan when the unit is in the drying state%Write
AV236HRL Temperature BiasBias value of the HRL temperature analog input signal°F or °CWrite
AV237HRL Humidity BiasBias value of the HRL humidity analog input signal%RHWrite
BI1Air FlowStatus of the airflow switchRead0=Closed, 1=Open
BI2Supply High LimitStatus of the high limit contactRead0=Closed, 1=Open
BI3InterlockStatus of the interlockRead0=Closed, 1=Open
BI4Binary External DemandDemand value when in On/Off control modeRead0=0%, 1=100%
BI8Water Leak DetectionWhether a water leak has been detectedRead0=OK, 1=Leak
BI20RS485 InterfaceWhether the RS485 interface is available or notRead0=No, 1=Yes
BI21Ethernet InterfaceWhether the Ethernet interface is available or notRead0=No, 1=Yes
BI22Relay FuseStatus of the contactors PCB fuseRead0=Normal, 1=Blown Fuse
BI23Control PCB FuseStatus of the control PCB fuseRead0=Normal, 1=Open Fuse
BO2Alarm Warning RelayAlarm warning relayRead0=Off, 1=On
BO3Service Warning RelayService warning relayRead0=Off, 1=On
BO4Water Supply ValveWater supply valveRead0=Off, 1=On
BO5Drain ValveNormally open drain valveRead0=Off, 1=On
BO7Circulation PumpCirculation pumpRead0=Off, 1=On
BO18Alarm LEDAlarm LEDRead0=Off, 1=On
BO19Power LEDPower LEDRead0=Off, 1=On
BO20BuzzerBuzzerRead0=Off, 1=On
BV3Alarm BuzzerConfiguration value that enables or disables the alarm buzzer sound when there...Write0=Normal, 1=Disabled
BV14Float SwitchFloat switchRead0=Inactive, 1=Active
BV16Water Treatment Service DueWhether the 5μm pre-filter and silver ion cartridges are due for servicingRead0=No, 1=Yes
BV17Service DueWhether the evaporative cooler is due for servicingRead0=No, 1=Yes
BV18Run While Water Service AlarmEnable the unit to continue operating, even when the 5μm prefilter and...Write0=Not Allowed, 1=Allowed
BV30Startup Line RinsePerform an automatic tank rinse cycle upon each start-up of the evaporative...Write0=Off, 1=On
BV32Run While Service AlarmEnable the unit to continue operating, even when it is due for...Write0=Not Allowed, 1=Allowed
BV38HRL Lock SetpointWhether the setpoint obtained from the HRL24 controller can be modifiedCommand0=Unlock, 1=Lock
BVmin44Network Control StateState of the control communication between the device and the BACnet networkWrite0=Normal, 1=Fault
BV52SMTP SSLUse a secure socket layer encrypt the communication between the device and...Write0=Off, 1=On
BV53SMTP PortPort number to be used for email transferWrite0=25, 1=587
BV54Notify AlarmGet notified of all evaporative cooler alarm messages by emailWrite0=Off, 1=On
BV55Notify WarningGet notified of all evaporative cooler warning messages by emailWrite0=Off, 1=On
BV56Notify App MsgGet notified of all evaporative cooler event messages by emailWrite0=Off, 1=On
BV157Memory StatusStatus of the NVMRead0=Ok, 1=Fail
BV159Float Switch TypeType of float switch usedWrite0=Legacy, 1=Digital
CSV22SMTP Server IP AddressServer IP address for the email accountWrite
CSV24SMTP Mail FromEmail address that will be sending the evaporative cooler notification messagesWrite
CSV25SMTP Mail ToEmail address that will be receiving the evaporative cooler notification messagesWrite
CSV26SMTP UsernameLogin username for the email accountWrite
CSV37EthernetMacAddMAC address of the Ethernet interfaceWrite
CSV62SMTP PasswordLogin password for the email accountWrite
CSV65Database VersionDatabase versionWrite
MV9BACnet Server LanguageBACnet server languageWrite1=English
MV10BACnet Server List ModeCategory of BACnet objects to displayWrite1=Integrator, 2=Advanced, 3=Factory
MV11BACnet Server UnitsDisplay units for the BACnet serverWrite1=Metric, 2=Imperial
MV24Control Signal TypeSignal type for the control demand analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV25Room RH Signal TypeSignal type for the room humidity analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV26Supply RH Signal TypeSignal type for the supply high limit humidity analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MVmin28Control ProfileA preconfigured control mode profile for the modulating humidity demandWrite1=ExternAnalog, 2=ExternNetwork, 3=InternHumAnalog, 4=InternHumNetwork, 5=InternCoolNetwork, 6=HRL Hum, 7=HRL Cool, 8=Custom
MV29Modulating High Limit ProfileA preconfigured control mode profile for the modulating high limit demandWrite1=Disabled, 2=ExternAnalog, 3=ExternNetwork, 4=InternHumAnalog, 5=InternHumNetwork, 6=InternCoolAnalog, 7=InternCoolNetwork, 8=Custom
MV32Occupancy StateOccupancy stateRead1=Occupied, 2=Unoccupied, 3=Vacant, 4=Off
MV33Room RH SourceReading source for the room demandWrite1=None, 2=RoomRH, 3=Network, 4=HRL
MV34Room RH Setpoint SourceRoom demand setpoint sourceWrite1=None, 2=Internal, 3=ControlInput
MV38RH Supply High Limit Reading SourceReading source for the supply high limit demandWrite1=None, 2=SupplyHLRH, 3=Network
MV39RH Supply High Limit Setpoint SourceSupply high limit demand setpoint sourceWrite1=None, 2=Internal, 3=ControlInput
MV43Control Demand SourceHumidity control demand sourceWrite1=None, 2=ControlInput, 3=HumRoomDemand, 4=Network, 5=TempRoomDemand
MV44Control High Limit SourceHumidity control high limit sourceWrite1=None, 2=ControlInput, 3=RHSupplyHLDemand, 4=Network, 5=TempSupplyHLDemand
MV46Control Binary Demand Sourcefiguration value to select the binary demand sourceWrite1=None, 2=BinaryExtDemand
MV51Control Cutout StateState of the safety control circuit and whether the circuit has been...Read1=Off, 2=Normal, 3=LowLimit, 4=HighLimit, 5=NoAirFlow, 6=Interlock
MVmin58StateState of operation of the evaporative coolerRead1=Off, 2=Idle, 3=LineRinse, 4=Filling, 5=Draining, 6=Running, 7=Alarm, 8=Drying
MVmin61System AlarmStatus of the evaporative cooler alarmRead1=Normal, 2=DrainTimeout, 3=FillTimeout, 4=WaterLeak, 5=FanDefect
MV63Fan RequestPerform one of the following actions for the fan: turn off the...Write1=Off, 2=Default, 3=On
MV64Pump RequestPerform one of the following actions for the circulation pump: turn off...Write1=Off, 2=Default, 3=On
MV66Water Supply RequestPerform one of the following actions for the water supply valve: turn...Write1=Off, 2=Default, 3=On
MV67Room Temperature Setpoint SourceRoom temperature demand setpoint sourceWrite1=None, 2=Internal, 3=ControlInput
MV71Temp Supply High Limit Reading SourceSupply high limit temperature demand reading sourceWrite1=None, 2=SupplyHLTemp, 3=Network
MV72Temp Supply High Limit Setpoint SourceSupply high limit temperature demand setpoint sourceWrite1=None, 2=Internal, 3=ControlInput
MV76Room Temperature SourceReading source for the room temperature demandWrite1=None, 2=RoomTemp, 3=Network, 4=HRL
MV77Room Temperature Signal TypeSignal type for the room temperature analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV78Supply Temperature Signal TypeSignal type for the room humidity analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MV79Control Signal TypeSignal type for the room humidity analog inputWrite1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA
MVmin83System Power StateWhether the system is powered on or offWrite1=Off, 2=On
MV95Recirculation RequestPerform one of the following actions for the evaporative cooler: reset warning...Write1=None, 2=ResetAlarms, 3=Drain, 4=ResetServCnt, 5=ResetWtrServCnt, 6=Filling
MV96DirectFeed RequestPerform one of the following actions for the evaporative cooler: reset warning...Write1=None, 2=ResetAlarms, 3=ResetServCnt, 4=ResetWtrServCnt
MV137DirectFeed Water Supply AdaptWhether the direct feed water supply is enabled or notWrite1=Disable, 2=Enable
MV176Update Process StatusStatus of the Firmware update processRead1=Ok, 2=CRC, 3=Device, 4=Failed
Other1NSDF Core ProgramNSDF Core ProgramWrite
Other2BACnet Server ProgramBACnet Server ProgramWrite
Other3LCD_Display ProgramLCD Display ProgramWrite
Other4Modbus Server ProgramModbus Server ProgramWrite
Other5RMHI ProgramRHMI ProgramWrite
Other6SKVF ProgramSKVF ProgramWrite
Other7Universal Humidifier Manager ProgramUniversal Humidifier Manager ProgramWrite
Other8Universal User Control ProgramUniversal User Control ProgramWrite
Other9Web Server ProgramWeb Server ProgramWrite
Other10Water Level Probe ProgramWater Level Probe ProgramWrite
Other15Database ProgramDatabase ProgramWrite
FILE2SysLogAlarmSystem Log AlarmWrite
FILE7USB System Log FileUSB System Log fileWrite
FILE8USB System Alarm Log FileUSB System Alarm Log fileWrite
FILE16System Log FileSystem Log fileWrite
FILE19UpdatePackageFileUpdate Package fileWrite
SCH1Occupancy ScheduleWeekly occupancy schedule to specify which occupancy state is active during specific...Write
SCH2Drain ScheduleCustomized draining schedule with up to six events per dayWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKVF and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic SKVF

How many BACnet points does the Neptronic SKVF have?

This list has 201 BACnet objects: 10 analog inputs, 2 analog outputs, 97 analog values, 9 binary inputs, 8 binary outputs, 16 binary values, 5 files, 2 schedules, 34 multi-state values, 7 characterstring values, 11 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic SKVF BACnet points are writable?

151 of the 201 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic SKVF BACnet documentation?

The source is Evaporative Cooler SKVF Series BACnet Communication Module User Guide (SKVF-BACnet Guide (v1.08)-250212), revision 2025-02-12, published free by Neptronic at https://www.neptronic.com/Humidifiers/pdf/2025/SKVF-BACnet%20Guide%20(v1.08)-250212.pdf.

What are the minimum BACnet points to integrate the Neptronic SKVF?

Start with MV 83 System Power State (System on/off from the BMS); MV 28 Control Profile (Control profile: choose a Network profile); AV 138 Control Network Demand (Direct demand written by the BMS, %); AV 156 Room Temperature Setpoint (Occupied room temp setpoint (internal control)); AV 107 Room RH Setpoint (Occupied room RH setpoint (internal control)); AV 155 Room Temperature Network Reading (BMS room temperature for internal control); AV 106 Room RH Network Reading (Network room RH reading for internal control); MV 58 State (Operating state (Idle, Running, Alarm...)); MV 61 System Alarm (Cooler alarm code (1 = Normal)); BV 44 Network Control State (1 = fault: network control lost (AV 223 timeout)).

How do I enable BMS control of the Neptronic SKVF?

MSV 83 System Power State is writable (1 = Off, 2 = On); the control source follows MSV 28 Control Profile or the individual source MSVs (43, 33, 76) with the Custom profile.

Does the Neptronic SKVF need a BACnet heartbeat or have a communication timeout?

AV 223 Network Timeout (1-900 s) sets how long the cooler tolerates loss of BACnet control communication before it stops; BV 44 Network Control State shows 1 = Fault.

Can the BMS supply sensor values to the Neptronic SKVF?

Room RH to AV 106 (MSV 33 = Network), room temperature to AV 155 (MSV 76 = Network), setpoints AV 107-109 and AV 156-158; supply high limit RH AV 122 and temperature AV 175 with setpoints AV 123 and AV 176-178; direct demand AV 138.

How do I check these points on the real SKVF?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: Evaporative Cooler SKVF Series BACnet Communication Module User Guide · SKVF-BACnet Guide (v1.08)-250212 · rev. 2025-02-12. Object names, instances and units are reproduced as published; descriptions are our own.