VAV terminal unit controller · BACnet points list

Neptronic EVCB14N Series VAV Controller BACnet points list

Updated 28 October 2026

Short answer

The EVCB14N is an application-specific VAV box controller with built-in actuator and airflow transducer that communicates over BACnet MS/TP. It exposes a fixed table of AI/AO/AV/BI/BO/BV/MSV objects covering zone temperature, setpoints, heating/cooling ramps, airflow balancing and output configuration. Which objects apply depends on the sub-model (triac count, pressure dependent or independent, feedback).

This page lists 176 BACnet objects for the Neptronic EVCB14N Series VAV Controller — 141 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
EVCB14N Series VAV Controller
Equipment
VAV terminal unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
176 (141 writable)
Transport
BACnet MS/TP
Firmware
5.08 (as printed)
Default device instance
153000 + MAC address
Also known as
EVCB14N, EVCB14NIT0S, EVCB14NIT2S, EVCB14NIT4S, EVCB14NDT4S, EVCB14NIT0SF, EVCB14NIT4SF
Source document
EVCB14N Series BACnet Communication Module User Guide · EVCB14N-V508-BACnet Guide-EUA-210818 · rev. 2021-08-18
Download CSV 176 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Neptronic EVCB14N Series VAV Controller

Integration in brief

Read the zone temperature, setpoint, demands and airflow, and drive occupancy with MSV.11. To control from a BMS space temperature, set MSV.4 to Network Sensor and keep writing AV.1 ControlTemp faster than the NetworkTimeOut period (AV.145).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 11NsbOccCommandBMS occupancy / night setback / off commandWrite
AV 15TempSetPointOccupied/day zone setpointWrite
MV 4Cfg_TempControlSourceSelect internal, external or network temperatureWrite
AV 1ControlTempControl temp; BMS writes it when MSV.4 = Network SensorWrite
MV 12OccupancyStatusActual occupancy stateRead
AV 110ActualAirFlowMeasured airflowRead
AV 111AirFlowSetPointAirflow setpoint calculated from demandRead
AV 20HeatingDemand1Heating ramp demand, %Read
AV 40CoolingDemand1Cooling ramp demand, %Read
BV 53AL_AirFlowErrorAirflow problem alarm (0 = No, 1 = Yes)Read

Enable & remote start

Occupancy and off are commanded with MSV.11 NsbOccCommand: Locally (wired input/sensor decides), Occupancy, No Occupancy (night setback) or OFF. Changeover can also be forced by the BMS through MSV.3 Cfg_ChangeOverControlMode.

Heartbeat & communication loss

AV.145 NetworkTimeOut (0-60 min): when the temperature source is Network/Remote and the BMS has not written a temperature within this time, the EVC goes to OFF and AV.1 shows 999°C in fault. Setting it to 0 makes AV.1 fall back to the AV.15 setpoint value instead.

Sensors & values from the BMS

Set MSV.4 Cfg_TempControlSource to Network Sensor; AV.1 ControlTemp then becomes writable and must be refreshed by the BMS (see AV.145).

Network setup

Watch out for

Neptronic EVCB14N Series VAV Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

176 of 176 shown
Type
Multi-state
Access
Show
Neptronic EVCB14N Series VAV Controller BACnet Points List
DescriptionStates
AI1AnalogInput1Status value in volts of Analog Input 1. Value is active onlyVRead
AI2AnalogInput2Status value in volts of Analog Input 2. Value is active onlyVRead
AI3InternTempIntern temperature sensor (ITS)°F/°CRead
AI5InternHumidityHumidity reading of on board humidity sensor of TRLH or TRLGH24/TDU (models%RHRead
AI6TrlgCO2CO reading of on-board sensor of TRLG24 or TRLGH24/TDU (models 2 withppmRead
AI7InternLightSensorInternal light sensor reading in LuxesluxRead
AI8InternVOCSensorInternal VOC sensor reading in ppbppbRead
AO1AnalogOutput1Modulation percentage of analog output 1 based on demand%Write
AO2AnalogOutput2Modulation percentage of analog output 2 based on demand%Write
AVmin1ControlTempControl temperature; writable when MSV.4 is Network Sensor°F/°CWrite
AV2ExternTempExtern temperature sensor (ETS)°F/°CRead
AV3ChangeOverTempChangeover temperature sensor (SENS)°F/°CRead
AV4AirSupplyTempAir supply temperature sensor (AST)°F/°CRead
AV5CO2SensorCarbon dioxide sensor (CO2)ppmRead
AV6ram_Ctl_SetPointActual temperature control setpoint value°F/°CRead
AV10Cfg_InternTempOffsetTo calibrate the integrated temperature sensor of the TRL/TDU (ITS)°F/°CWrite
AV11Cfg_ExternTempOffsetTo calibrate the external temperature sensor (ETS)°F/°CWrite
AVmin15TempSetPointActual user setpoint of the zone in occupied/day mode°F/°CWrite
AV16Cfg_MinpSetPointUser minimum permitted setpoint of the zone in occupied/day mode°F/°CWrite
AV17Cfg_MaxpSetPointUser maximum permitted setpoint of the zone in occupied/day mode°F/°CWrite
AV18SetPointCoolNoOccNSBCooling setpoint when in night setback or unoccupied°F/°CWrite
AV19SetPointHeatNoOccNSBHeating setpoint when in night setback or unoccupied°F/°CWrite
AVmin20HeatingDemand1Heating demand in percentage for the Heating Ramp 1. This value is%Read
AV21Cfg_HeatingPropBand1Range through which the controller will modulate the heating output from 0-100%°F/°CWrite
AV22Cfg_HeatingDeadBandRange where the controller will not take action when below the zone°F/°CWrite
AV23HeatingDemand2Heating demand in percentage for the Heating Ramp 2. This value is%Read
AV24Cfg_HeatingPropBand2Range through which the controller will modulate the heating output from 0-100%°F/°CWrite
AV25Cfg_HeatingDeadBand2Range where the controller will not take action when below the zone°F/°CWrite
AV30Cfg_IntegralTimeHeatingReciprocal of the integral time in seconds (1/I or repeats per second)sWrite
AVmin40CoolingDemand1Cooling demand for the Cooling Ramp 1. This value is based on%Read
AV41Cfg_CoolingPropBand1Range through which the controller will modulate the cooling output from 0-100%°F/°CWrite
AV42Cfg_CoolingDeadBand1Range at which the controller will not take action when above the°F/°CWrite
AV45CoolingDemand2Cooling demand for the Cooling Ramp 2. This value is based on%Read
AV46Cfg_CoolingPropBand2Range through which the controller will modulate the cooling output from 0-100%°F/°CWrite
AV47Cfg_CoolingDeadBand2Range at which the controller will not take action when above the°F/°CWrite
AV50Cfg_IntegralTimeCoolingReciprocal of the integral time in seconds (1/I or repeats per second)sWrite
AV51Cfg_CoolingAntiCycleDelayIn minutes to prevent the cooling outputs to cycle on and offminWrite
AV55ChangeOverDemandChangeover demand for the VAV box%Read
AV56Cfg_ChangeOverPropBandRange through which the controller will modulate the cooling and heating output°F/°CWrite
AV57Cfg_ChangeOverDeadBandRange at which the controller will not take action when above or°F/°CWrite
AV58ChangeOverSetPointTemperature at which the primary air from the central system is considered°F/°CWrite
AV60Cfg_NSBSetBackOverrideDelayTime in minutes when in night setback and an override has beenminWrite
AV61Cfg_NoOccOverrideDelayTime in minutes when unoccupied and an override has been activated onminWrite
AV62Cfg_OccupancyMinTimeTime in minutes for minimum time to maintain occupancy mode after aminWrite
AV64Cfg_DigitalInput2DelayTime in secondssWrite
AV70Cfg_AnalogOutput1MinMinimum control signal of the controlled elementVWrite
AV71Cfg_AnalogOutput1MaxMaximum control signal of the controlled elementVWrite
AV72Cfg_AnalogOutput2MinMinimum control signal of the controlled elementVWrite
AV73Cfg_AnalogOutput2MaxMaximum control signal of the controlled elementVWrite
AV75FloatingTO1/TO2TimerTime required by the valve actuator to complete a 90° runsWrite
AV76FloatingTO3/TO4TimerTime required by the valve actuator to complete a 90° runsWrite
AV77Cfg_TO1ClosePosThat indicates at what percentage of the demand the contact closes to%Write
AV78Cfg_TO1OpenPosThat indicates at what percentage of the demand the contact opens to%Write
AV79Cfg_TO2ClosePos%Write
AV80Cfg_TO2OpenPos%Write
AV81Cfg_TO3ClosePos%Write
AV82Cfg_TO3OpenPos%Write
AV83Cfg_TO4ClosePos%Write
AV84Cfg_TO4OpenPos%Write
AV89Cfg_MotorMinPositionCoolHeatMinimum position in cooling/heating mode the VAV box is allowed%Write
AV90Cfg_MotorMinPositionCoolMinimum position in cooling mode the VAV box is allowed%Write
AV91Cfg_MotorMinPositionHeatMinimum position in heating mode the VAV box is allowed%Write
AV93MotorPositionDamper actuator position%Read
AV100Cfg_PressureNumFilterTo stabilize the reading of the differential pressure transducer when balancingsWrite
AV101Cfg_AirFlowVnomOrKFactorMaximum airflow of the VAV box at 1" w.cWrite
AV102Cfg_AirFlowCoolMinMinimum cooling airflow when system is in cooling modeWrite
AV103Cfg_AirFlowCoolMaxMaximum cooling airflow when system is in cooling mode%Write
AV104Cfg_AirFlowHeatMinMinimum heating airflow when system is in heating modeWrite
AV105Cfg_AirFlowHeatMaxMaximum cooling airflow when system is in heating mode%Write
AV106Cfg_AirFlowIntegralTimeReciprocal of the integral time in seconds (1/I or repeats per second)minWrite
AVmin110ActualAirFlowActual converted airflow measured by the differential pressure transducerRead
AVmin111AirFlowSetPointAirflow calculated by demandRead
AV112Cfg_AdjustAirFlowMaxDuring airflow balancing sequenceWrite
AV113Cfg_AdjustAirFlowMinDuring airflow balancing sequenceWrite
AV114Cfg_AirFlowOffsetTo adjust the calibration of the differential pressure transducerWrite
AV116Cfg_AirFlowHysteresisStopAirflow setpoint percentage used to prevent damper actuator oscillations%Write
AV117Cfg_AirFlowHysteresisStartAirflow setpoint percentage used to prevent actuator from oscillations%Write
AV133Cfg_Input3 ReadingPressure sensorPaRead
AV135AirFlowFaultDeadBandAirflow dead band used when BV.52 is activated%Write
AV136AirFlowFaultErrorAirflow fault error used when BV.52 is activated%Write
AV137AirFlowFaultHysterisisAirflow fault hysterisis used when BV.52 is activated%Write
AV138AirFlowFaultTimeAirflow fault time used when BV.52 is activatedminWrite
AV140CO2RangeMaximum range of the CO2 sensor (PPM) or the external sensor ifppmWrite
AV141CO2SetpointMaximum limit of CO2 concentration before the EVC sends an alarmppmWrite
AV145NetworkTimeOutBMS temperature timeout when control source is networkminWrite
AV165CopyCfgStartAddressWhen using copy config, this value represents the first address in theWrite
AV166CopyCfgEndAddressWhen using copy config, this value represents the last address in theWrite
AV167CopyCfgResultWhen using copy config, this value is used to verify that theWrite
AV170CL_HT_SwitchTimerTime required before the changeover is permitted to take place (time inminWrite
AV171CL_HT_SwitchTimerCountRemaining time before the changeover is authorisedsRead
AV180FloatingTO1/TO2Status value to show the floating signal demand%Write
AV181FloatingTO3/TO4Status value to show the floating signal demand%Write
AV182TO1PulsingTR Status value to show the pulse signal demand%Write
AV183TO2PulsingStatus value to show the pulse signal demand%Write
AV184TO3PulsingStatus value to show the pulse signal demand%Write
AV185TO4PulsingStatus value to show the pulse signal demand%Write
AV190Cfg_CO2PropBandRange through which the controller modulates the CO control output from 0ppmWrite
AV191Cfg_CO2DeadBandRange at which the controller will not take action when below orppmWrite
AV192AverageTempAverage temperature of the combination of sensors selected using MSV.45 Cfg_TempSensorCombo°F/°CRead
AV193MaximumTempMaximum temperature of the combination of sensors selected using MSV.45 Cfg_TempSensorCombo°F/°CRead
AV194ExternalSensorValue_AI2Temperature reading of AI2 configured as an external temperature sensor°F/°CRead
BI1DigitalInput1Contact status of the inputRead0 = Open 1 = Close
BI2DigitalInput2Contact status of the inputRead0 = Open 1 = Close
BI3InternPIRInternal PIR sensor value: (0) NoOccupancy, (1) OccupancyRead0 = NoOccupancy 1 = Occupancy
BO1TO1OnOffStatus value to show if TO1 is active or notWrite0 = Off 1 = On
BO2TO2OnOffStatus value to show if TO2 is active or notWrite0 = Off 1 = On
BO3TO3OnOffStatus value to show if TO3 is active or notWrite0 = Off 1 = On
BO4TO4OnOffStatus value to show if TO4 is active or notWrite0 = Off 1 = On
BV1Cfg_TempUnitBACnetTemperature units used in BACnetWrite0 = Celsius, 1 = Fahrenheit
BV2Cfg_TempSetPointLockLock the zone setpoint and prevent users to change the valueWrite0 = Disable, 1 = Enable
BV3UserSysOffModeAllow users to turn off the EVC. (0) Enable user to turnWrite0 = Enable, 1 = Disable
BV4Cfg_TempUnitTstatUser temperature units used on TRL/TDU. If set to (0), the temperatureWrite0 = Celsius, 1 = Fahrenheit
BV5ChangeOverModeActual mode (0) Cooling, (1) HeatingWrite0 = Cooling, 1 = Heating
BV6Cfg_FreezeProtectionPrevent a zone from falling below 4°C (39.2°F)Write0 = Off, 1 = On
BV7Cfg_KeyPadUpperLeftLockLock the Cool/Heat buttonWrite0 = Off, 1 = On (If set to “On”, functionality of these buttons will not be available.)
BV8Cfg_KeyPadBottomLeftLockLock the °C/°F buttonWrite0 = Off, 1 = On If set to “On”, functionality of these buttons will not be available.
BV9Cfg_KeyPadArrowsLockLock the arrow buttonsWrite0 = Off, 1 = On If set to “On”, functionality of these buttons will not be available.
BV10Cfg_ProgramLockLock the all TRL/TDU buttonsWrite0 = Off, 1 = On If set to “On”, functionality of these buttons will not be available.
BV20Cfg_NightSetBackModeDetermine the action of the EVC when in night setbackWrite0 = Setpoint, 1 = OFF
BV23Cfg_OccControlSourceDetermines the source of occupancy control to be used by the EVCWrite0 = BI1, 1 = Intern Sensor
BV25Cfg_AnalogOutput1DirectionAnalog output directionWrite0 = Direct, 1 = Reverse
BV26Cfg_AnalogOutput2DirectionAnalog output directionWrite0 = Direct, 1 = Reverse
BV30Cfg_FloatingTO1/TO2DirectionTRIAC contact normal state (Normally Open, Normally Close) when MSV.26 TO1 SignalWrite0 = Direct, 1 = Reverse
BV31Cfg_FloatingTO3/TO4DirectionTRIAC contact normal state (Normally Open, Normally Close) when MSV.30 TO3 SignalWrite0 = Direct, 1 = Reverse
BV32Cfg_TO1 DirectionTRIAC contact normal state value of the rotation when MSV.26 TO1 SignalWrite0 = Direct, 1 = Reverse
BV33Cfg_TO2 DirectionTRIAC contact normal state value of the rotation when MSV.28 TO2 SignalWrite0 = Direct, 1 = Reverse
BV34Cfg_TO3 DirectionTRIAC contact normal state value of the rotation when MSV.30 TO3 SignalWrite0 = Direct, 1 = Reverse
BV35Cfg_TO4 DirectionTRIAC contact normal state value of the rotation when MSV.32 TO4 SignalWrite0 = Direct, 1 = Reverse
BV36Cfg_Digital Input 2 ContactChange the contact's normal positionWrite0 = Norm Open, 1 = Norm Close
BV40Cfg_MotorDirectionChange the rotation direction of the damper actuatorWrite0 = Direct, 1 = Reverse
BV41Cfg_MotorPosControlTempFaultTo select the control mode for the motor position when there isWrite0 = Close, 1 = Open
BV45AirFlowBalancingTo enable and disable the airflow balancingWrite0= Disable, 1= Enable
BV50Cfg_PressureModeSelectTo configure the VAV box as (0) pressure independent or (1) pressureWrite0= Independent, 1= Dependent
BV51PressureModeStatusActual pressure modeRead0= Independent, 1= Dependent
BV52PressureModeAutoChangeTo enable the VAV box to pass from pressure independent to pressureWrite0 = Off, 1 = On
BVmin53AL_AirFlowErrorStatus value to show if an airflow problem is occurringRead0= No, 1= Yes
BV55AL_HighCO2LevelStatus which indicates that the CO2 concentration is above setpointRead0= No, 1= Yes
BV56AL_OverrideStatus to inform if an override is activeRead0= No, 1= Yes
BV60Cfg_DisplayRHDetermines if the digital room sensor displays the %RH valueWrite0= Off, 1= On
BV65Cfg_DisplayCO2Determines if the digital room sensor displays the CO2 valueWrite0= Off, 1= On
BV66Cfg_CO2ControlSourceDetermines the source of the CO2 readingWrite0= Analog Input, 1= TRLG
BV70Cfg_ActiveScheduleActivate the scheduleWrite0= No, 1= Yes
BV90CopyCfgExecuteWhen using copy config, this value is used to start the copyWrite0= No, 1= Yes
BV91Cfg_Pressure CalibrationTo recalibrate the differential pressure transducerWrite0= No, 1= Yes
BV92Cfg_Pressure Calibration LockTo unlock the calibration process of BV.91Write0 = Lock, 1 = Unlock
BV100Cfg_Fan Always On ModeFan operation when an output is configured with the option "Fan On".Write0 = On, 1 = Off
BV101Cfg_CO2ControlModeTo select the control mode for the CO control 2 outputWrite0 = Open, 1 = Control ramp loop
MV1Cfg_UniversalInputAI1TypeInputWriteOff Extern Sensor Changeover Sensor ChOvContactNormCool ChOvContactNormHeat Airflow Setpoint* CO2 Sensor Air Supply Temp Motor Position SensorExtern50K** TSTAT temp sensor** TSTAT Setpoint** TSTAT Setpoint 2-10V** * not available with EVCB14NDT4S ** only available with EVCB14NIT0S
MV2Cfg_UniversalInputAI2TypeWriteOff Extern Sensor Changeover Sensor ChOv Contact Norm Cool ChOv Contact Norm Heat Airflow Setpoint CO2 Sensor Air Supply Temp Motor Position SensorExtern50K* TSTAT temp sensor* TSTAT Setpoint* TSTAT Setpoint 2-10V* * only available with EVCB14NIT0S
MV3Cfg_ChangeOverControlModeIndicates where the changeover value is coming fromWriteLocally Cooling Heating
MVmin4Cfg_TempControlSourceControl temperature to be used by the EVC. Intern Temp, the controlWriteIntern Sensor Extern Sensor Network Sensor Average Temp Maximum Temp
MV10Cfg_NsbOccContactDI1 modeWriteOff Occ Norm Open Occ Norm Close NSB Norm Open NSB Norm Close Unoccupied Damper* * only available with EVCB14NIT0S
MVmin11NsbOccCommandSet the occupancy or night setback modeWriteOFF/Locally/Locally Occupancy/OFF/OFF No Occupancy/Occupancy/Day -- /No Occupancy/Night
MVmin12OccupancyStatusStatus that indicates the actual occupancy when occupancy is usedReadNoOccupancy Occupancy Override
MV13NightSetBackStatusStatus that indicates the actual mode of the zone when night setbackReadDay Night Override
MV14Cfg_DigitalInput2TypeDI2 modeWriteOff Override Over Heat1 Over Heat2 Over Heat All ChOv Contact Norm Cool ChOv Contact Norm Heat Unoccupied Damper* * only available with EVCB14NIT0S
MV15OverHeatStatusStatus to inform if a heat override is activeReadOverHeatNormal Over Heat1 Over Heat2 Over Heat All
MV16UserSystemModeZone mode the user has set on the TRL/TDU. Not to beWriteAuto Heating Cooling Off
MV17UserSysModeSelectSet the permissions or restrictions to change the zone mode by theWriteAuto Heating Cooling Heating or Cooling Auto Lock
MV20Cfg_AnalogOutput1RampRamp used to modulate AO1 based on demandWriteOff Cooling Ramp1 Cooling Ramp2 Heating Ramp1 Heating Ramp2 AirFlow Read CO2 Alarm Airflow Setpoint *Fan Auto (follows any demand) *Fan On (always on) * for fan powered box applications and applies only to EVCB14NIT4S, EVCB14NDT4S, and EVCB14NIT4SF
MV22Cfg_AnalogOutput2RampWriteOff Cooling Ramp1 Cooling Ramp2 Heating Ramp1 Heating Ramp2 AirFlow Read CO2 Alarm Airflow Setpoint *Fan Auto (follows any demand) *Fan On (always on) * for fan powered box applications and applies only to EVCB14NIT4S, EVCB14NDT4S, and EVCB14NIT4SF
MV25Cfg_TO1RampRamp used to modulate (pulse or floating) or activate/deactivate (On/Off) TO1 basedWriteOff Cooling Ramp1 Cooling Ramp2 Heating Ramp1 Heating Ramp2 CO2 Alarm *Fan Auto (follows any demand) *Fan On (always on) * for fan powered box applications and applies only to EVCB14NIT4S, EVCB14NDT4S, and EVCB14NIT4SF
MV26Cfg_TO1SignalTypeOutput signal typeWritePulsing (If Hr1 or Hr2 is selected)  On_Off  Floating
MV27Cfg_TO2RampWriteOff Cooling Ramp1 Cooling Ramp2 Heating Ramp1 Heating Ramp2 CO2 Alarm *Fan Auto (follows any demand) *Fan On (always on) * for fan powered box applications and applies only to EVCB14NIT4S, EVCB14NDT4S, and EVCB14NIT4SF
MV28Cfg_TO2SignalTypeOutput signal typeWritePulsing (If Hr1 or Hr2 is selected) 2On_Off 3Floating
MV29Cfg_TO3RampWriteOff Cooling Ramp1 Cooling Ramp2 Heating Ramp1 Heating Ramp2 CO2 Alarm *Fan Auto (follows any demand) *Fan On (always on) * for fan powered box applications and applies only to EVCB14NIT4S, EVCB14NDT4S, and EVCB14NIT4SF
MV30Cfg_TO3SignalTypeOutput signal typeWritePulsing (If Hr1 or Hr2 is selected) On_Off Floating
MV31Cfg_TO4RampWriteOff Cooling Ramp1 Cooling Ramp2 Heating Ramp1 Heating Ramp2 CO2 Alarm *Fan Auto (follows any demand) *Fan On (always on) * for fan powered box applications and applies only to EVCB14NIT4S, EVCB14NDT4S, and EVCB14NIT4SF
MV32Cfg_TO4SignalTypeOutput signal typeWritePulsing (If Hr1 or Hr2 is selected) On_Off Floating
MV35Cfg_MotorRampRamp used to modulate the damper actuator based on demandWriteCooling Ramp1 Cooling Ramp2 Heating Ramp1 Heating Ramp2 AirflowSetPoint* Changeover Ramp Cooling Heating Ramp 1 Analog * Airflow setpoint not available with EVCB14NDT4S
MV36Cfg_NSBMotorModeSet the motor position while in night setbackWriteAuto Open
MV37MotorPositionOverrideTo override the motor positionWriteAuto Open Close Air Flow Min (heat/cool as per current mode) Air Flow Max (heat/cool as per current mode)
MV41Cfg_AirFlowScaleAirflow scale used to get a better resolution when small airflows areWriteScale1 | Scale10 | Scale100
MV42AirFlowBal_ModePosition the damper actuator to preset positionsWriteClosed | Min Flow | Max Flow | Full Open
MV45Cfg_TempSensorComboSelect the combination of sensors that will be used in the calculationWriteTSTAT+AI1 | TSTAT +AI2 | TSTAT+AI1+AI2 | AI1+AI2
MV95Cfg_DisplayInfoInformation displayed on the TRL/TDU. Display Temp Demand: the TRL/TDU will displayWriteTemp and Demand | Setpoint and Demand Temp only | Setpoint only | Off

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EVCB14N Series VAV Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic EVCB14N Series VAV Controller

How many BACnet points does the Neptronic EVCB14N Series VAV Controller have?

This list has 176 BACnet objects: 7 analog inputs, 2 analog outputs, 92 analog values, 3 binary inputs, 4 binary outputs, 39 binary values, 29 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic EVCB14N Series VAV Controller BACnet points are writable?

141 of the 176 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic EVCB14N Series VAV Controller BACnet documentation?

The source is EVCB14N Series BACnet Communication Module User Guide (EVCB14N-V508-BACnet Guide-EUA-210818), revision 2021-08-18, published free by Neptronic at http://www.neptronic.com/controls/pdf/20210908/EVCB14N-V508-BACnet%20Guide-EUA-210818.pdf.

What are the minimum BACnet points to integrate the Neptronic EVCB14N Series VAV Controller?

Start with MV 11 NsbOccCommand (BMS occupancy / night setback / off command); AV 15 TempSetPoint (Occupied/day zone setpoint); MV 4 Cfg_TempControlSource (Select internal, external or network temperature); AV 1 ControlTemp (Control temp; BMS writes it when MSV.4 = Network Sensor); MV 12 OccupancyStatus (Actual occupancy state); AV 110 ActualAirFlow (Measured airflow); AV 111 AirFlowSetPoint (Airflow setpoint calculated from demand); AV 20 HeatingDemand1 (Heating ramp demand, %); AV 40 CoolingDemand1 (Cooling ramp demand, %); BV 53 AL_AirFlowError (Airflow problem alarm (0 = No, 1 = Yes)).

How do I enable BMS control of the Neptronic EVCB14N Series VAV Controller?

Occupancy and off are commanded with MSV.11 NsbOccCommand: Locally (wired input/sensor decides), Occupancy, No Occupancy (night setback) or OFF. Changeover can also be forced by the BMS through MSV.3 Cfg_ChangeOverControlMode.

Does the Neptronic EVCB14N Series VAV Controller need a BACnet heartbeat or have a communication timeout?

AV.145 NetworkTimeOut (0-60 min): when the temperature source is Network/Remote and the BMS has not written a temperature within this time, the EVC goes to OFF and AV.1 shows 999°C in fault. Setting it to 0 makes AV.1 fall back to the AV.15 setpoint value instead.

Can the BMS supply sensor values to the Neptronic EVCB14N Series VAV Controller?

Set MSV.4 Cfg_TempControlSource to Network Sensor; AV.1 ControlTemp then becomes writable and must be refreshed by the BMS (see AV.145).

How do I check these points on the real EVCB14N Series VAV Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: EVCB14N Series BACnet Communication Module User Guide · EVCB14N-V508-BACnet Guide-EUA-210818 · rev. 2021-08-18. Object names, instances and units are reproduced as published; descriptions are our own.