 "manufacturer": "Neptronic",
 "manufacturer_slug": "neptronic",
 "model": "SKH4",
 "model_slug": "skh4",
 "aliases": [
  "SKH4 high-pressure atomizer",
  "SKH4 BACnet"
 ],
 "equipment_type": "High-pressure atomizing humidifier / cooler",
 "applies_to": "Neptronic SKH4 high-pressure water atomizing humidifiers and evaporative coolers with up to six zones (A-F).",
 "summary": "The SKH4 pumps treated water to high-pressure nozzles for humidification or adiabatic cooling, serving up to six zones. BACnet MS/TP and BACnet IP are built in; besides system control sources and network RH/temperature inputs the guide lists per-zone control, occupancy, demand, readings, stage and communication objects.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": "153000 + MAC address (153001 by default)",
 "access_inferred": false,
 "notes": [
  "Objects and their writable properties are taken from the guide's 'W?' column; Present_Value writable means the BMS can change it.",
  "Units follow the BACnet Server Units setting (Metric or Imperial).",
  "Zone B-F objects only apply when those zones are configured.",
  "MSV 101 is printed as MAV.101 in the guide; it is a multi-state value."
 ],
 "source": {
  "title": "SKH4 High-Pressure Atomizer BACnet Communication Module User Guide",
  "doc_number": "SKH4-BACnet Guide-240126 (V1.00)",
  "revision_date": "2024-01-26",
  "url": "https://www.neptronic.com/Humidifiers/pdf/2024/SKH4-BACnet%20Guide-240126%20(V1.00).pdf"
 },
 "integration": {
  "summary": "Choose a Network control profile (MSV 28) or demand source (MSV 43 = Network) and write demand to AV 138, or feed room RH/temperature readings (AV 106 / AV 155) for internal control. Per-zone control and occupancy are set with the Zone MSVs; watch BV 44 and the zone communication timeout BVs.",
  "minimum_points": [
   {
    "ref": "MV 95",
    "name": "Zone A Control",
    "why": "Zone A on/off: 1 = Off, 2 = Normal"
   },
   {
    "ref": "MV 96",
    "name": "Zone A Occupancy",
    "why": "1 = occupied, 2 = unoccupied, 3 = off"
   },
   {
    "ref": "MV 28",
    "name": "Control Profile",
    "why": "Control profile: choose a Network profile"
   },
   {
    "ref": "AV 138",
    "name": "Control Network Demand",
    "why": "Direct demand written by the BMS, %"
   },
   {
    "ref": "AV 107",
    "name": "Room RH Setpoint",
    "why": "Occupied room RH setpoint (internal control)"
   },
   {
    "ref": "AV 106",
    "name": "Room RH Network Reading",
    "why": "Network room RH reading for internal control"
   },
   {
    "ref": "MV 83",
    "name": "System Power State",
    "why": "System on/off status"
   },
   {
    "ref": "AV 143",
    "name": "User Demand",
    "why": "Current humidity demand %"
   },
   {
    "ref": "BV 68",
    "name": "Drive State",
    "why": "Drive status: 0 = Ok, 1 = Fault"
   },
   {
    "ref": "BV 44",
    "name": "Network Control State",
    "why": "1 = fault: network control lost (AV 223 timeout)"
   }
  ],
  "enable": "No writable system on/off object is listed (MSV 83 System Power State is read-only in this guide). Zones are switched with the Zone x Control MSVs (1 = Off, 2 = Normal...) and Zone x Occupancy; the demand source comes from MSV 28 / MSV 43.",
  "heartbeat": "AV 223 Network Timeout (1-900 s) is how long the unit tries to reach the BACnet or Modbus network before it stops operating; BV 44 Network Control State shows 1 = Fault. AV 441 sets the internal zone communication timeout, with per-zone alarms BV 86-91.",
  "remote_sensors": "Network room RH to AV 106 (MSV 33 = Network) with setpoints AV 107-109; room temperature to AV 155 for cooling profiles; supply high limit RH to AV 122 (MSV 38 = Network) and temperature to AV 175 (MSV 71 = Network). Direct demand goes to AV 138 and high limit to AV 139.",
  "setup": [
   "MS/TP MAC defaults to 1 (000-254; 128-254 are non-token-passing slaves); baud rate auto-detects (Auto, 9600, 19200, 38400, 76800); Max_Master 127.",
   "Device instance defaults to 153000 + MAC (153001 out of the box) and can be changed from the menu or by writing Device Object_Identifier.",
   "BACnet IP uses UDP 47808 (0xBAC0) by default.",
   "Network/communication settings are in the controller's Integration menu (password 5544); power-cycle after connecting to the network.",
   "Reinitialize Device (warm/cold reset) over BACnet uses the password 'nep'."
  ],
  "gotchas": [
   "MSV 'BACnet Server List Mode' chooses which objects are published (Integrator, Advanced, Factory); objects marked Advanced in the guide, such as the program objects, only show in Advanced mode.",
   "Writing Out_of_Service = True disconnects an object from its physical input so the Present_Value can be overwritten; remember to set it back.",
   "The unit signals alarms through object values only; it does not send BACnet event notifications, so poll or use COV.",
   "COV subscriptions are lost on a power cycle.",
   "Many AVs in this guide are commandable (Relinquish_Default listed); write at a consistent priority."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 5,
   "name": "Control Signal",
   "description": "Control demand analog input signal",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Room RH Signal",
   "description": "Room humidity analog input signal",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Supply RH Signal",
   "description": "Duct or supply high limit humidity analog input signal",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Water Temperature Signal",
   "description": "Water temperature sensor signal",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Pressure Sensor Signal",
   "description": "Pressure sensor signal",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "Board Temperature Signal",
   "description": "Board temperature sensor signal",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Main Power Supply",
   "description": "Measured voltage in the power supply",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "Room Temperature Signal",
   "description": "Room temperature sensor signal",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "Supply Temperature Signal",
   "description": "Room temperature sensor signal",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "Control Signal",
   "description": "Control signal",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "Power Output Feedback Signal",
   "description": "Power output feedback signal",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 16,
   "name": "Drive Signal",
   "description": "Drive signal",
   "units": "V",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "MCU Load",
   "description": "Current microcontroller load",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Memory Load",
   "description": "Current memory load",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Demand",
   "description": "Demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "Control Input",
   "description": "Current control input reading",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "Control Min",
   "description": "Minimum value of the control demand analog input",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Control Max",
   "description": "Maximum value of the control demand analog input",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "Control Bias",
   "description": "Bias value for the control demand analog input",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "Room RH",
   "description": "Room humidity reading",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "Room RH Min",
   "description": "Minimum value of the room humidity analog input",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "Room RH Max",
   "description": "Maximum value of the room humidity analog input",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "Room RH Bias",
   "description": "Bias value of the room humidity analog input",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "Supply High Limit RH",
   "description": "Duct or supply high limit humidity analog input",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "Supply High Limit RH Min",
   "description": "Minimum value of the duct or supply high limit humidity analog input",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "Supply High Limit RH Max",
   "description": "Maximum value of the duct or supply high limit humidity analog input",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "Supply High Limit RH Bias",
   "description": "Bias value of the duct or supply high limit humidity analog input",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "Run Time",
   "description": "Number of seconds that the system has been powered on",
   "units": "h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "On Time",
   "description": "Total operating time of the humidifier",
   "units": "h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "Service On Time",
   "description": "Operating time of the humidifier since the last servicing",
   "units": "h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "Water Temperature",
   "description": "Temperature of water in the evaporation chamber",
   "units": "°F or °C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "Service Interval",
   "description": "System service interval",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "Power Output Feedback Bias",
   "description": "Bias value for the power output feedback signal",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "Power Output Feedback Min",
   "description": "Minimum value of the power output feedback signal",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "Power Output Feedback Max",
   "description": "Maximum value of the power output feedback signal",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "Power Output Feedback",
   "description": "Feedback value of the power output analog output",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "Motor Speed",
   "description": "Motor speed",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "Room RH Network Reading",
   "description": "Room relative humidity reading received from the network",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "Room RH Setpoint",
   "description": "Room relative humidity setpoint received from the network",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "Room RH Unoccupied Setpoint",
   "description": "Room relative humidity reading received from the network during no occupancy state",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "Room RH Vacant Setpoint",
   "description": "Room relative humidity reading received from the network during vacancy",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "Room RH Demand Proportional Gain",
   "description": "Room demand proportional gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "Room RH Demand Integral Time",
   "description": "Room demand integral time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "Room RH Demand Derivative Time",
   "description": "Room demand derivative time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "Room RH Demand",
   "description": "Humidity demand within the room",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "RH Supply High Limit Network Reading",
   "description": "Supply high limit reading received from the network",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "RH Supply High Limit Setpoint",
   "description": "Supply high limit setpoint received from the network",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "RH Supply High Limit Unoccupied Setpoint",
   "description": "Supply high limit setpoint during the unoccupied mode",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "RH Supply High Limit Vacant Setpoint",
   "description": "Supply high limit setpoint during the occupied mode",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "RH Supply High Limit Proportional Gain",
   "description": "Supply high limit demand proportional gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "RH Supply High Limit Integral Time",
   "description": "Supply high limit demand integral time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "RH Supply High Limit Derivative Time",
   "description": "Supply high limit demand derivative time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 136,
   "name": "RH Supply High Limit Demand",
   "description": "Supply high limit humidity demand value",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "Control Network Demand",
   "description": "Humidity control demand received from the network",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "Control Network High Limit",
   "description": "Humidity control high limit received from the network",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "User Demand",
   "description": "Measured humidity demand of the humidifier",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "Room Temperature Min",
   "description": "Minimum value of the room temperature signal",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 152,
   "name": "Room Temperature Max",
   "description": "Maximum value of the room temperature signal",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "Room Temperature Bias",
   "description": "Bias value of the room temperature signal",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "Room Temperature Network Reading",
   "description": "Room temperature network",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "Room Temperature Setpoint",
   "description": "Room temperature setpoint",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "Room Temperature Unoccupied Setpoint",
   "description": "Room temperature setpoint value used during unoccupied state",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "Room Temperature Vacant Setpoint",
   "description": "Room temperature setpoint value used during occupied state",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "Room Temperature Demand Proportional Gain",
   "description": "Room demand proportional gain",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 160,
   "name": "Room Temperature Demand Integral Time",
   "description": "Room demand integral time",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 161,
   "name": "Room Temperature Demand Derivative Time",
   "description": "Room demand derivative time",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 169,
   "name": "Room Temperature Demand",
   "description": "Room demand temperature",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 170,
   "name": "HRL Temperature",
   "description": "Room temperature value measured by the HRL24 controller",
   "units": "°F or °C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 171,
   "name": "HRL Humidity",
   "description": "Room humidity value measured by the HRL24 controller",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 174,
   "name": "Room Temp Demand Proportional Band",
   "description": "Room demand proportional band",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 175,
   "name": "Temp Supply High Limit Network Reading",
   "description": "Temperature supply high limit network reading",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 176,
   "name": "Temp Supply High Limit Setpoint",
   "description": "Supply high limit temperature setpoint value",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 177,
   "name": "Temp Supply High Limit Unoccupied Setpoint",
   "description": "Supply high limit temperature setpoint value used during unoccupied state",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 178,
   "name": "Temp Supply High Limit Vacant Setpoint",
   "description": "Supply high limit temperature setpoint value used during occupied state",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 179,
   "name": "Temp Supply High Limit Proportional Gain",
   "description": "Supply high limit temperature proportional gain",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 180,
   "name": "Temp Supply High Limit Integral Time",
   "description": "Supply high limit demand integral time",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 181,
   "name": "Modbus TCP IP Keep Alive Time Out",
   "description": "Amount of time the communication stays open before connection is cut out...",
   "units": "min",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 182,
   "name": "Temp Supply High Limit Derivative Time",
   "description": "Supply high limit temperature derivative time",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 190,
   "name": "Temp Supply High Limit Demand",
   "description": "The supply high limit demand temperature",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 193,
   "name": "Temp Supply High Limit Proportional Band",
   "description": "The supply high limit demand proportional band",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 196,
   "name": "Supply High Limit Temperature",
   "description": "The supply high limit temperature",
   "units": "°F or °C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 197,
   "name": "Supply High Limit Temperature Min",
   "description": "Configuration minimum value of the supply high limit temperature",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 198,
   "name": "Supply High Limit Temperature Max",
   "description": "Configuration maximum value of the supply high limit temperature",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 199,
   "name": "Supply High Limit Temperature Bias",
   "description": "Configuration bias value of the supply high limit temperature",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 220,
   "name": "Demand Low Dead Band",
   "description": "Lower limit dead band value for the humidity demand",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 223,
   "name": "Network Timeout",
   "description": "Amount of time the humidifier may attempt to connect to the BACnet...",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 230,
   "name": "Room RH Demand Proportional Band",
   "description": "Room demand humidity proportional band",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 231,
   "name": "RH Supply High Limit Proportional Band",
   "description": "The supply high limit humidity proportional band",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 234,
   "name": "Control Timer",
   "description": "Control timer",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 235,
   "name": "Zone A Demand",
   "description": "The demand for Zone A",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 236,
   "name": "Zone A Temperature",
   "description": "Temperature for Zone A",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 237,
   "name": "Zone A Humidity",
   "description": "Humidity for Zone A",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 240,
   "name": "Zone B Demand",
   "description": "The demand for Zone B",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 241,
   "name": "Zone B Temperature",
   "description": "Temperature for Zone B",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 242,
   "name": "Zone B Humidity",
   "description": "Humidity for Zone B",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 245,
   "name": "Zone C Demand",
   "description": "The demand for Zone C",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 246,
   "name": "Zone C Temperature",
   "description": "Temperature for Zone C",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 247,
   "name": "Zone C Humidity",
   "description": "Humidity for Zone C",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 250,
   "name": "Zone D Demand",
   "description": "The demand for Zone D",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 251,
   "name": "Zone D Temperature",
   "description": "Temperature for Zone D",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 252,
   "name": "Zone D Humidity",
   "description": "Humidity for Zone D",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 255,
   "name": "Zone E Demand",
   "description": "The demand for Zone E",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 256,
   "name": "Zone E Temperature",
   "description": "Temperature for Zone E",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 257,
   "name": "Zone E Humidity",
   "description": "Humidity for Zone E",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 260,
   "name": "Zone F Demand",
   "description": "The demand for Zone F",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 261,
   "name": "Zone F Temperature",
   "description": "Temperature for Zone F",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 262,
   "name": "Zone F Humidity",
   "description": "Humidity for Zone F",
   "units": "%RH",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 263,
   "name": "Stage 1 Capacity",
   "description": "Capacity for stage 1",
   "units": "L/h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 264,
   "name": "Stage 1 Drain Volume",
   "description": "Drain volume for stage 1",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 265,
   "name": "Stage 2 Capacity",
   "description": "Capacity for stage 2",
   "units": "L/h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 266,
   "name": "Stage 2 Drain Volume",
   "description": "Drain volume for stage 2",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 267,
   "name": "Stage 3 Capacity",
   "description": "Capacity for stage 3",
   "units": "L/h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 268,
   "name": "Stage 3 Drain Volume",
   "description": "Drain volume for stage 3",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 269,
   "name": "Stage 4 Capacity",
   "description": "Capacity for stage 4",
   "units": "L/h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 270,
   "name": "Stage 4 Drain Volume",
   "description": "Drain volume for stage 4",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 271,
   "name": "Stage 5 Capacity",
   "description": "Capacity for stage 5",
   "units": "L/h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 272,
   "name": "Stage 5 Drain Volume",
   "description": "Drain volume for stage 5",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 273,
   "name": "Stage 6 Capacity",
   "description": "Capacity for stage 6",
   "units": "L/h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 278,
   "name": "Stage 6 Drain Volume",
   "description": "Drain volume for stage 6",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 279,
   "name": "Stage 1 Drain Time",
   "description": "The drain time for stage 1",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 280,
   "name": "Stage 2 Drain Time",
   "description": "Drain time for stage 2",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 281,
   "name": "Stage 3 Drain Time",
   "description": "Drain time for stage 3",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 282,
   "name": "Stage 4 Drain Time",
   "description": "Drain time for stage 4",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 283,
   "name": "Stage 5 Drain Time",
   "description": "Drain time for stage 5",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 284,
   "name": "Stage 6 Drain Time",
   "description": "Drain time for stage 6",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 307,
   "name": "Stage 1 Idle Time",
   "description": "The idle time for stage 1",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 308,
   "name": "Stage 2 Idle Time",
   "description": "The idle time for stage 2",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 309,
   "name": "Stage 3 Idle Time",
   "description": "The idle time for stage 3",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 310,
   "name": "Stage 4 Idle Time",
   "description": "The idle time for stage 4",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 311,
   "name": "Stage 5 Idle Time",
   "description": "The idle time for stage 5",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 312,
   "name": "Stage 6 Idle Time",
   "description": "The idle time for stage 6",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 313,
   "name": "Stage 1 Run Time",
   "description": "The run time for stage 1",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 314,
   "name": "Stage 2 Run Time",
   "description": "The run time for stage 2",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 315,
   "name": "Stage 3 Run Time",
   "description": "The run time for stage 3",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 316,
   "name": "Stage 4 Run Time",
   "description": "The run time for stage 4",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 317,
   "name": "Stage 5 Run Time",
   "description": "The run time for stage 5",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 318,
   "name": "Stage 6 Run Time",
   "description": "The run time for stage 6",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 319,
   "name": "Stage 1 Cycle Count",
   "description": "The cycle count for stage 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 320,
   "name": "Stage 2 Cycle Count",
   "description": "The cycle count for stage 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 321,
   "name": "Stage 3 Cycle Count",
   "description": "The cycle count for stage 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 322,
   "name": "Stage 4 Cycle Count",
   "description": "The cycle count for stage 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 323,
   "name": "Stage 5 Cycle Count",
   "description": "The cycle count for stage 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 324,
   "name": "Stage 6 Cycle Count",
   "description": "The cycle count for stage 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 325,
   "name": "Cool Drain Timer",
   "description": "Cool drain timer",
   "units": "min",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 382,
   "name": "Stage 1 Max On Time",
   "description": "Maximum on time for stage 1",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 383,
   "name": "Stage 2 Max On Time",
   "description": "Maximum on time for stage 2",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 384,
   "name": "Stage 3 Max On Time",
   "description": "Maximum on time for stage 3",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 385,
   "name": "Stage 4 Max On Time",
   "description": "Maximum on time for stage 4",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 386,
   "name": "Stage 5 MaxOn Time",
   "description": "Maximum on time for stage 5",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 387,
   "name": "Stage 6 Max On Time",
   "description": "Maximum on time for stage 6",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 388,
   "name": "Stage 1 Pause Time",
   "description": "Pause time for stage 1",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 389,
   "name": "Stage 2 Pause Time",
   "description": "Pause time for stage 2",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 390,
   "name": "Stage 3 Pause Time",
   "description": "Pause time for stage 3",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 391,
   "name": "Stage 4 Pause Time",
   "description": "Pause time for stage 4",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 392,
   "name": "Stage 5 Pause Time",
   "description": "Pause time for stage 5",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 393,
   "name": "Stage 6 Pause Time",
   "description": "Pause time for stage 6",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 394,
   "name": "Zone A Stage Opening Delay",
   "description": "Stage opening delay for zone A",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 395,
   "name": "Zone B Stage Opening Delay",
   "description": "Stage opening delay for zone B",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 396,
   "name": "Zone C Stage Opening Delay",
   "description": "Stage opening delay for zone C",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 397,
   "name": "Zone D Stage Opening Delay",
   "description": "Stage opening delay for zone D",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 398,
   "name": "Zone E Stage Opening Delay",
   "description": "Stage opening delay for zone E",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 399,
   "name": "Zone F Stage Opening Delay",
   "description": "Stage opening delay for zone F",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 400,
   "name": "Drain 1 Cycle Count",
   "description": "The drain cycle count for stage 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 401,
   "name": "Drain 2 Cycle Count",
   "description": "The drain cycle count for stage 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 402,
   "name": "Drain 3 Cycle Count",
   "description": "The drain cycle count for stage 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 403,
   "name": "Drain 4 Cycle Count",
   "description": "The drain cycle count for stage 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 404,
   "name": "Drain 5 Cycle Count",
   "description": "The drain cycle count for stage 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 405,
   "name": "Drain 6 Cycle Count",
   "description": "The drain cycle count for stage 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 406,
   "name": "Stage 1 On Time",
   "description": "The operating time of the humidifier since the last servicing for stage...",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 407,
   "name": "Stage 2 On Time",
   "description": "The operating time of the humidifier since the last servicing for stage...",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 408,
   "name": "Stage 3 On Time",
   "description": "The operating time of the humidifier since the last servicing for stage...",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 409,
   "name": "Stage 4 On Time",
   "description": "The operating time of the humidifier since the last servicing for stage...",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 410,
   "name": "Stage 5 On Time",
   "description": "The operating time of the humidifier since the last servicing for stage...",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 411,
   "name": "Stage 6 On Time",
   "description": "The operating time of the humidifier since the last servicing for stage...",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 412,
   "name": "Diagnostic Period",
   "description": "Value of the diagnostic period",
   "units": "min",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 414,
   "name": "Zone A MAC",
   "description": "Value of the MAC address for Zone A",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 415,
   "name": "Zone B MAC",
   "description": "Value of the MAC address for Zone B",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 416,
   "name": "Zone C MAC",
   "description": "Value of the MAC address for Zone C",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 417,
   "name": "Zone D MAC",
   "description": "Value of the MAC address for Zone D",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 418,
   "name": "Zone E MAC",
   "description": "Value of the MAC address for Zone E",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 419,
   "name": "Zone F MAC",
   "description": "Value of the MAC address for Zone F",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 420,
   "name": "Control Input",
   "description": "Value of the control input",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 423,
   "name": "Control Min",
   "description": "Minimum value of the control input",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 424,
   "name": "Control Max",
   "description": "Maximum value of the control input",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 425,
   "name": "Control Bias",
   "description": "Bias value of the control input",
   "units": "°F or °C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 441,
   "name": "Zone Communication Timeout Delay",
   "description": "Zone communication timeout delay",
   "units": "s",
   "access": "C",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Air Flow",
   "description": "Status of the airflow switch",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Supply High Limit",
   "description": "Status of the high limit contact",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Interlock",
   "description": "Status of the interlock",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Binary External Demand",
   "description": "Status of the binary external demand",
   "units": "",
   "access": "R",
   "states": "0=0%, 1=100%"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Water Leak Detection",
   "description": "Whether a water leak has been detected",
   "units": "",
   "access": "R",
   "states": "0=OK, 1=Leak"
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Drive Status",
   "description": "Status of the drive",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Fault"
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "Inlet Pressure Switch",
   "description": "Whether the inlet pressure switch is available or not",
   "units": "",
   "access": "R",
   "states": "0=Low, 1=Ok"
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "RS485 Interface",
   "description": "Whether the RS485 interface is available or not",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "Ethernet Interface",
   "description": "Whether the Ethernet interface is available or not",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "Relay Fuse",
   "description": "Status of the relay fuse",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Open Fuse"
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "Control PCB Fuse",
   "description": "Status of the control PCB fuse",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Open Fuse"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "Alarm Warning Relay",
   "description": "Alarm warning relay",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "Service Warning Relay",
   "description": "Service warning relay",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "Valve 1",
   "description": "Valve 1",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "Valve 2",
   "description": "Valve 2",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "Valve 3",
   "description": "Valve 3",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 7,
   "name": "Valve 4",
   "description": "Valve 4",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 8,
   "name": "Valve 5",
   "description": "Valve 5",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 10,
   "name": "Valve 6",
   "description": "Valve 6",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 11,
   "name": "Valve 7",
   "description": "Valve 7",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 12,
   "name": "Valve 8",
   "description": "Valve 8",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 13,
   "name": "Valve 9",
   "description": "Valve 9",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 14,
   "name": "Valve 10",
   "description": "Valve 10",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 15,
   "name": "Valve 11",
   "description": "Valve 11",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 16,
   "name": "Valve 12",
   "description": "Valve 12",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 18,
   "name": "Alarm LED",
   "description": "Alarm LED",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 19,
   "name": "Power LED",
   "description": "Power LED",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 20,
   "name": "Buzzer",
   "description": "Buzzer",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 21,
   "name": "Contactor Pump",
   "description": "Contactor pump",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 22,
   "name": "Drive Enable",
   "description": "Drive enable",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Alarm Buzzer",
   "description": "Configuration value that enables or disables the alarm buzzer sound when there...",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Disabled"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "Service Due",
   "description": "Whether the humidifier is due for servicing",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "Startup Line Rinse",
   "description": "Perform an automatic tank rinse cycle upon each start-up of the humidifier",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "Run While Service Alarm",
   "description": "Status of the run while service alarm",
   "units": "",
   "access": "W",
   "states": "0=Not Allowed, 1=Allowed"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "HRL Lock Setpoint",
   "description": "Whether the setpoint obtained from the HRL24 controller can be modified",
   "units": "",
   "access": "C",
   "states": "0=Unlock, 1=Lock"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "Network Control State",
   "description": "State of the control communication between the device and the BACnet network",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Fault"
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "SMTP SSL",
   "description": "Use a secure socket layer encrypt the communication between the device and...",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "SMTP Port",
   "description": "Port number to be used for email transfer",
   "units": "",
   "access": "W",
   "states": "0=25, 1=587"
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "Notify Alarm",
   "description": "Get notified of all humidifier alarm messages by email",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "Notify Warning",
   "description": "Get notified of all humidifier warning messages by email",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "Notify App Msg",
   "description": "Get notified of all humidifier event messages by email",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 68,
   "name": "Drive State",
   "description": "Status of the drive",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Fault"
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "Stage 1 Diagnostic Enable",
   "description": "Status of the diagnostic enable for stage 1",
   "units": "",
   "access": "W",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "Stage 2 Diagnostic Enable",
   "description": "Status of the diagnostic enable for stage 2",
   "units": "",
   "access": "W",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BV",
   "instance": 72,
   "name": "Stage 3 Diagnostic Enable",
   "description": "Status of the diagnostic enable for stage 3",
   "units": "",
   "access": "W",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BV",
   "instance": 73,
   "name": "Stage 4 Diagnostic Enable",
   "description": "Status of the diagnostic enable for stage 4",
   "units": "",
   "access": "W",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BV",
   "instance": 74,
   "name": "Stage 5 Diagnostic Enable",
   "description": "Status of the diagnostic enable for stage 5",
   "units": "",
   "access": "W",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "Stage 6 Diagnostic Enable",
   "description": "Status of the diagnostic enable for stage 6",
   "units": "",
   "access": "W",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BV",
   "instance": 86,
   "name": "Zone A Communication Timeout",
   "description": "Status of the communication timeout for zone A",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Timeout"
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "Zone B Communication Timeout",
   "description": "Status of the communication timeout for zone B",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Timeout"
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "Zone C Communication Timeout",
   "description": "Status of the communication timeout for zone C",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Timeout"
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "Zone D Communication Timeout",
   "description": "Status of the communication timeout for zone D",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Timeout"
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "Zone E Communication Timeout",
   "description": "Status of the communication timeout for zone E",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Timeout"
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "Zone F Communication Timeout",
   "description": "Status of the communication timeout for zone F",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Timeout"
  },
  {
   "type": "BV",
   "instance": 98,
   "name": "Low Water Temperature Warning",
   "description": "Status of the low water temperature warning",
   "units": "",
   "access": "R",
   "states": "0=Ok, 1=Timeout"
  },
  {
   "type": "CSV",
   "instance": 10,
   "name": "HMI Overwrite",
   "description": "Overwrite the value displayed on the local display menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 22,
   "name": "SMTP Server IP Address",
   "description": "Server IP address for the email account",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 24,
   "name": "SMTP Mail From",
   "description": "Email address that will be sending the humidifier notification messages",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 25,
   "name": "SMTP Mail To",
   "description": "Email address that will be receiving the humidifier notification messages",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 26,
   "name": "SMTP Username",
   "description": "Login username for the email account",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 37,
   "name": "SMTP Password",
   "description": "Login password for the email account",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 62,
   "name": "EthernetMacAdd",
   "description": "MAC address of the Ethernet interface",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "System Log Verbose Level",
   "description": "Type of information to be stored on the log file",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Emergency, 3=Alert, 4=Critical, 5=Error, 6=Warning, 7=Notice, 8=Info, 9=Debug"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "BACnet Server Language",
   "description": "BACnet server language",
   "units": "",
   "access": "W",
   "states": "1=English"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "BACnet Server List Mode",
   "description": "Category of BACnet objects to display",
   "units": "",
   "access": "W",
   "states": "1=Integrator, 2=Advanced, 3=Factory"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "BACnet Server Units",
   "description": "Display units for the BACnet server",
   "units": "",
   "access": "W",
   "states": "1=Metric, 2=Imperial"
  },
  {
   "type": "MV",
   "instance": 24,
   "name": "Control Signal Type",
   "description": "Signal type for the control demand analog input",
   "units": "",
   "access": "W",
   "states": "1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA"
  },
  {
   "type": "MV",
   "instance": 25,
   "name": "Room RH Signal Type",
   "description": "Signal type for the room humidity analog input",
   "units": "",
   "access": "W",
   "states": "1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA"
  },
  {
   "type": "MV",
   "instance": 26,
   "name": "Supply RH Signal Type",
   "description": "Signal type for the duct or supply high limit humidity analog input",
   "units": "",
   "access": "W",
   "states": "1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA"
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "Request",
   "description": "Request for the humidifier",
   "units": "",
   "access": "W",
   "states": "1=None, 2=ResetAlarms, 3=Drain, 4=ResetServCnt"
  },
  {
   "type": "MV",
   "instance": 28,
   "name": "Control Profile",
   "description": "Control profile",
   "units": "",
   "access": "W",
   "states": "1=ExternAnalog, 2=ExternNetwork, 3=InternHumAnalog, 4=InternHumNetwork, 5=InternCoolAnalog, 6=InternCoolNetwork, 7=HRL Hum, 8=HRL Cool"
  },
  {
   "type": "MV",
   "instance": 29,
   "name": "Modulating High Limit Profile",
   "description": "A preconfigured control mode profile for the modulating high limit demand",
   "units": "",
   "access": "R",
   "states": "1=Disabled, 2=ExternAnalog, 3=ExternNetwork, 4=InternHumAnalog, 5=InternHumNetwork, 6=InternCoolAnalog, 7=InternCoolNetwork, 8=Custom"
  },
  {
   "type": "MV",
   "instance": 32,
   "name": "Occupancy State",
   "description": "Occupancy state",
   "units": "",
   "access": "R",
   "states": "1=Occupied, 2=Unoccupied, 3=Vacant, 4=Off"
  },
  {
   "type": "MV",
   "instance": 33,
   "name": "Room RH Source",
   "description": "Reading source for the room demand",
   "units": "",
   "access": "W",
   "states": "1=None, 2=RoomRH, 3=Network, 4=HRL"
  },
  {
   "type": "MV",
   "instance": 34,
   "name": "Room RH Setpoint Source",
   "description": "Room demand setpoint source",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Internal, 3=ControlInput"
  },
  {
   "type": "MV",
   "instance": 38,
   "name": "RH Supply High Limit Reading Source",
   "description": "Reading source for the supply high limit demand",
   "units": "",
   "access": "W",
   "states": "1=None, 2=SupplyHLRH, 3=Network"
  },
  {
   "type": "MV",
   "instance": 39,
   "name": "RH Supply High Limit Setpoint Source",
   "description": "Supply high limit demand setpoint source",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Internal, 3=ControlInput"
  },
  {
   "type": "MV",
   "instance": 43,
   "name": "Control Demand Source",
   "description": "Humidity control demand source",
   "units": "",
   "access": "W",
   "states": "1=None, 2=ControlInput, 3=HumRoomDemand, 4=Network, 5=TempRoomDemand"
  },
  {
   "type": "MV",
   "instance": 44,
   "name": "Control High Limit Source",
   "description": "Current state of the safety control circuit and whether the circuit has...",
   "units": "",
   "access": "W",
   "states": "1=None, 2=ControlInput, 3=RHSupplyHLDemand, 4=Network, 5=TempSupplyHLDemand"
  },
  {
   "type": "MV",
   "instance": 46,
   "name": "Control Binary Demand Source",
   "description": "Binary demand source",
   "units": "",
   "access": "W",
   "states": "1=None, 2=BinaryExtDemand"
  },
  {
   "type": "MV",
   "instance": 67,
   "name": "Room Temperature Setpoint Source",
   "description": "Room temperature setpoint source",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Internal, 3=ControlInput"
  },
  {
   "type": "MV",
   "instance": 71,
   "name": "Temp Supply High Limit Reading Source",
   "description": "Temperature supply high limit reading source",
   "units": "",
   "access": "W",
   "states": "1=None, 2=SupplyHLTemp, 3=Network"
  },
  {
   "type": "MV",
   "instance": 72,
   "name": "Temp Supply High Limit Setpoint Source",
   "description": "Temperature supply high limit setpoint source",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Internal, 3=ControlInput"
  },
  {
   "type": "MV",
   "instance": 76,
   "name": "Room Temperature Source",
   "description": "Room temperature source",
   "units": "",
   "access": "W",
   "states": "1=None, 2=RoomTemp, 3=Network, 4=HRL"
  },
  {
   "type": "MV",
   "instance": 77,
   "name": "Room Temperature Signal Type",
   "description": "Room temperature signal type",
   "units": "",
   "access": "W",
   "states": "1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA"
  },
  {
   "type": "MV",
   "instance": 78,
   "name": "Supply Temperature Signal Type",
   "description": "Supply temperature signal type",
   "units": "",
   "access": "W",
   "states": "1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA"
  },
  {
   "type": "MV",
   "instance": 83,
   "name": "System Power State",
   "description": "Whether the system is powered on or off",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 95,
   "name": "Zone A Control",
   "description": "Control mode for zone A",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock"
  },
  {
   "type": "MV",
   "instance": 96,
   "name": "Zone A Occupancy",
   "description": "Occupied status for zone A",
   "units": "",
   "access": "W",
   "states": "1=Occupied, 2=Unoccupied, 3=Off"
  },
  {
   "type": "MV",
   "instance": 97,
   "name": "Zone B Control",
   "description": "Control mode for zone B",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock"
  },
  {
   "type": "MV",
   "instance": 98,
   "name": "Zone B Occupancy",
   "description": "Occupied status for zone B",
   "units": "",
   "access": "W",
   "states": "1=Occupied, 2=Unoccupied, 3=Off"
  },
  {
   "type": "MV",
   "instance": 99,
   "name": "Zone C Control",
   "description": "Control mode for zone C",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock"
  },
  {
   "type": "MV",
   "instance": 100,
   "name": "Zone C Occupancy",
   "description": "Occupied status for zone C",
   "units": "",
   "access": "W",
   "states": "1=Occupied, 2=Unoccupied, 3=Off"
  },
  {
   "type": "MV",
   "instance": 101,
   "name": "Zone D Control",
   "description": "Control mode for zone D (printed as MAV.101)",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock"
  },
  {
   "type": "MV",
   "instance": 102,
   "name": "Zone D Occupancy",
   "description": "Occupied status for zone D",
   "units": "",
   "access": "W",
   "states": "1=Occupied, 2=Unoccupied, 3=Off"
  },
  {
   "type": "MV",
   "instance": 103,
   "name": "Zone E Control",
   "description": "Control mode for zone E",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock"
  },
  {
   "type": "MV",
   "instance": 104,
   "name": "Zone E Occupancy",
   "description": "Occupied status for zone E",
   "units": "",
   "access": "W",
   "states": "1=Occupied, 2=Unoccupied, 3=Off"
  },
  {
   "type": "MV",
   "instance": 105,
   "name": "Zone F Control",
   "description": "Control mode for zone F",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Airflow, 4=SupplyHighLimit, 5=Interlock"
  },
  {
   "type": "MV",
   "instance": 106,
   "name": "Zone F Occupancy",
   "description": "Occupied status for zone F",
   "units": "",
   "access": "W",
   "states": "1=Occupied, 2=Unoccupied, 3=Off"
  },
  {
   "type": "MV",
   "instance": 107,
   "name": "Stage 1 Zone",
   "description": "Stage 1 zone",
   "units": "",
   "access": "W",
   "states": "1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF"
  },
  {
   "type": "MV",
   "instance": 108,
   "name": "Stage1 Drain",
   "description": "Stage 1 drain",
   "units": "",
   "access": "W",
   "states": "1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12"
  },
  {
   "type": "MV",
   "instance": 109,
   "name": "Stage 2 Zone",
   "description": "Stage 2 zone",
   "units": "",
   "access": "W",
   "states": "1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF"
  },
  {
   "type": "MV",
   "instance": 110,
   "name": "Stage 2 Drain",
   "description": "Stage 2 drain",
   "units": "",
   "access": "W",
   "states": "1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12"
  },
  {
   "type": "MV",
   "instance": 111,
   "name": "Stage 3 Zone",
   "description": "Stage 3 zone",
   "units": "",
   "access": "W",
   "states": "1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF"
  },
  {
   "type": "MV",
   "instance": 112,
   "name": "Stage 3 Drain",
   "description": "Stage 3 drain",
   "units": "",
   "access": "W",
   "states": "1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12"
  },
  {
   "type": "MV",
   "instance": 113,
   "name": "Stage 4 Zone",
   "description": "Stage 4 zone",
   "units": "",
   "access": "W",
   "states": "1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF"
  },
  {
   "type": "MV",
   "instance": 114,
   "name": "Stage 4 Drain",
   "description": "Stage 4 drain",
   "units": "",
   "access": "W",
   "states": "1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12"
  },
  {
   "type": "MV",
   "instance": 115,
   "name": "Stage 5 Zone",
   "description": "Stage 5 zone",
   "units": "",
   "access": "W",
   "states": "1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF"
  },
  {
   "type": "MV",
   "instance": 116,
   "name": "Stage 5 Drain",
   "description": "Stage 5 drain",
   "units": "",
   "access": "W",
   "states": "1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12"
  },
  {
   "type": "MV",
   "instance": 117,
   "name": "Stage 6 Zone",
   "description": "Stage 6 zone",
   "units": "",
   "access": "W",
   "states": "1=ZoneA, 2=ZoneB, 3=ZoneC, 4=ZoneD, 5=ZoneE, 6=ZoneF"
  },
  {
   "type": "MV",
   "instance": 118,
   "name": "Stage 6 Drain",
   "description": "Stage 6 drain",
   "units": "",
   "access": "W",
   "states": "1=Drain7, 2=Drain8, 3=Drain9, 4=Drain10, 5=Drain11, 6=Drain12"
  },
  {
   "type": "MV",
   "instance": 120,
   "name": "Cooling Drain Control Mode",
   "description": "Cooling drain control mode",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=TimeLatch"
  },
  {
   "type": "MV",
   "instance": 135,
   "name": "Low Water Temperature Alarm",
   "description": "Status of the low water temperature alarm",
   "units": "",
   "access": "W",
   "states": "1=Alarm, 2=Warning"
  },
  {
   "type": "MV",
   "instance": 160,
   "name": "Diagnostic State",
   "description": "Status of the diagnostic state",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 161,
   "name": "Diagnostic Command",
   "description": "Status of the diagnostic command",
   "units": "",
   "access": "W",
   "states": "1=Spray, 2=Drain"
  },
  {
   "type": "MV",
   "instance": 162,
   "name": "Control Signal Type",
   "description": "Control signal type",
   "units": "",
   "access": "W",
   "states": "1=0-10Vdc, 2=2-10Vdc, 3=4-20mA, 4=0-20mA"
  },
  {
   "type": "Other",
   "instance": 1,
   "name": "NSDF Core Program",
   "description": "NSDF Core Program",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 2,
   "name": "Module 1",
   "description": "Module 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 3,
   "name": "Module 2",
   "description": "Module 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 4,
   "name": "Module 3",
   "description": "Module 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 5,
   "name": "Module 4",
   "description": "Module 4",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 6,
   "name": "Module 5",
   "description": "Module 5",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 7,
   "name": "Module 6",
   "description": "Module 6",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 8,
   "name": "Module 7",
   "description": "Module 7",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 9,
   "name": "Module 8",
   "description": "Module 8",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 10,
   "name": "Module 9",
   "description": "Module 9",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 11,
   "name": "Module 10",
   "description": "Module 10",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 12,
   "name": "Module 11",
   "description": "Module 11",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 13,
   "name": "Module 12",
   "description": "Module 12",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 14,
   "name": "Module 13",
   "description": "Module 13",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 15,
   "name": "NSDF Database",
   "description": "NSDF Database",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "FILE",
   "instance": 1,
   "name": "Core File.",
   "description": "Core File",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "FILE",
   "instance": 2,
   "name": "SysLogAlarm",
   "description": "System Log Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "FILE",
   "instance": 7,
   "name": "USB System Log File",
   "description": "USB System Log file",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "FILE",
   "instance": 8,
   "name": "USB System Alarm Log File",
   "description": "USB System Alarm Log file",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "FILE",
   "instance": 16,
   "name": "System Log File",
   "description": "System Log file",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "FILE",
   "instance": 19,
   "name": "UpdatePackageFile",
   "description": "Update Package file",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "SCH",
   "instance": 1,
   "name": "Occupancy Schedule",
   "description": "Weekly occupancy schedule to specify which occupancy state is active during specific...",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "SCH",
   "instance": 2,
   "name": "Drain Schedule",
   "description": "Customized draining schedule with up to six events per day",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/neptronic/skh4",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}