- SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station
High-pressure atomising humidifier · BACnet points list
Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station BACnet points list
Updated 12 November 2026
The older SKH high pressure atomiser shows up on BACnet MS/TP as a pump station device plus one device per EZC zone controller. The pump station device carries the system mode, pump state and demand, zone capacity, pump inlet and outlet pressure and temperature, alarm relay outputs and a long list of pump and communication alarms, plus simulation and inactivity-drain settings.
This page lists 68 BACnet objects for the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.
- Manufacturer
- Neptronic
- Model
- SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station
- Equipment
- High-pressure atomising humidifier
- Equipment type
- Humidifiers
- BACnet objects
- 68 (20 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 153000 + MAC address
- Also known as
- SKH, Neptronic SKH, SKH high pressure atomiser, SKH-BACnet Guide-210104
Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.
BMS integration notes: Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station
Turn the system on with BV 1 SystemMode and read MSV 1 PumpState, AV 1 PumpDemand and the alarm flags (BV 50/51 service, BV 52 pump global alarm). Humidity control itself is done per zone on the EZC devices.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | SystemMode | System on/off (1 = on) | Write |
| MV 1 | PumpState | Pump state (stand-by, pressurizing, ready ...) | Read |
| AV 1 | PumpDemand | Pump demand, % | Read |
| BV 7 | WaterPressureState | Water pressure ready | Read |
| AV 216 | PumpOutputPressure | Pump output pressure, kPa | Read |
| BO 1 | AlarmRelay | Alarm relay (closed on alarm) | Command |
| BV 52 | AL_PumpGlobalAlarmMask | Pump global alarm | Read |
| BV 51 | AL_ServiceAlarm | Service alarm | Read |
Enable & remote start
BV 1 SystemMode switches the system on or off.
Network setup
- Baud rate and device instance can be automatic: the humidifier sets its device instance to 153000 + MAC address; the MAC (0-254) is set from the menu.
- Max_Master defaults to 127; lower it for a faster MS/TP trunk.
Watch out for
- Simulation objects (AV 3-8, BV 2-3) are for testing; leave them alone in normal operation.
Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | SKHBoardTemp | Temperature reading measured on the SKH PC board | °C | Read | |
| AO | 1 | FeedbackVoltage | Output feedback voltage | mV | Write | |
| AVmin | 1 | PumpDemand | Pump demand of the system | % | Read | |
| AV | 2 | SystemZoneDemand | Zone demand of the system | % | Read | |
| AV | 3 | SimulationDuration | Duration of Simulation mode | min | Write | |
| AV | 4 | SimulationZoneSelection | Selection of the number of zones in simulation mode | Write | ||
| AV | 5 | SimulationZoneDemand | Number of stages for the zones in simulation mode | Write | ||
| AV | 7 | SimulationPumpDemand | Selection of pump demand for simulation mode | % | Write | |
| AV | 8 | SimulationDowncounter | Configuration vale for the simulation mode downcounter | s | Read | |
| AV | 9 | SystemPumpCapacity | Pump capacity of the system | kg/h | Read | |
| AV | 11 | SystemZoneCapacity | Zone capacity of the system | kg/h | Read | |
| AV | 12 | SystemNumOfZones | Number of zones for the system | Read | ||
| AV | 100 | Cfg_SystemInactivityDelay | System inactivity delay | h | Write | |
| AV | 101 | Cfg_SystemInactivityDrainTime | System inactivity drain time | min | Write | |
| AV | 204 | PumpFeedback | Feedback value of pump | Read | ||
| AV | 208 | PumpInletTemp | Inlet temperature of pump | °C | Read | |
| AV | 212 | PumpInletPressure | Inlet pressure of pump | kPa | Read | |
| AVmin | 216 | PumpOutputPressure | Output pressure of pump | kPa | Read | |
| AV | 220 | PumpDutyTime | Duty time of pump | Read | ||
| AV | 224 | PumpWeightedDutyTime | Weighted duty time of pump | Read | ||
| AV | 300 | Cfg_PumpInactivityDelay | Pump inactivity delay | h | Write | |
| AV | 304 | Cfg_PumpInactivityDrainTime | Pump inactivity drain time | s | Write | |
| BOmin | 1 | AlarmRelay | Open or close the alarm relay | Command | 0=Open, 1=Close | |
| BO | 2 | MaintenanceRelay | Open or close the maintenance relay | Command | 0=Open, 1=Close | |
| BO | 3 | Buzzer | Activate or not the buzzer | Write | 0=Inactive, 1=Active | |
| BVmin | 1 | SystemMode | Enable or disable the system mode | Write | 0=Off, 1=On | |
| BV | 2 | SimulationState | Status of the simulation state | Read | 0=Off, 1=On | |
| BV | 3 | SimulationPumpOverride | Status of the simulation pump override | Read | 0=Off, 1=On | |
| BV | 4 | SystemDrainPending | Status of the system drain pending | Read | 0=Off, 1=On | |
| BV | 5 | SystemDrain | Status of the system drain | Read | 0=Off, 1=On | |
| BV | 6 | SystemZoneDemand | Status of system zone demand | Read | 0=Off, 1=On | |
| BVmin | 7 | WaterPressureState | Status of the water pressure state | Read | 0=Not Ready, 1=Ready | |
| BV | 8 | UVLampChangeDue | Status of the UV lamp change due | Read | 0=Off, 1=On | |
| BV | 50 | AL_ServiceWarning | Status of the service warning | Read | 0=Off, 1=On | |
| BVmin | 51 | AL_ServiceAlarm | Status of the service alarm | Read | 0=Off, 1=On | |
| BVmin | 52 | AL_PumpGlobalAlarmMask | Status of the pump global alarm mask | Read | 0=Off, 1=On | |
| BV | 56 | AL_GlobalPumpComTimeout | Status of the global pump communication timeout | Read | 0=Off, 1=On | |
| BV | 57 | AL_GlobalZoneComTimeout | Status of the global zone communication timeout | Read | 0=Off, 1=On | |
| BV | 200 | PumpDrainValve | Status of pump drain valve | Read | 0=Off, 1=On | |
| BV | 204 | PumpEnableVFD | Status of the pump enable VFD | Read | 0=Off, 1=On | |
| BV | 210 | AL_PumpInletTempSensorFailure | Status of the pump inlet temperature sensor failure | Read | 0=Off, 1=On | |
| BV | 214 | AL_PumpInletPressureSensorFailure | Status of the pump inlet pressure sensor failure | Read | 0=Off, 1=On | |
| BV | 218 | AL_PumpOutputPressureSensorFailure | Status of the pump output pressure sensor failure | Read | 0=Off, 1=On | |
| BV | 222 | AL_PumpVFDFailure | Status of the pump VFD failure | Read | 0=Off, 1=On | |
| BV | 226 | AL_PumpInletTempTooHigh | Status of the pump if the inlet water temperature of pump is | Read | 0=Off, 1=On | |
| BV | 230 | AL_PumpInletTempTooLow | Status of the pump if the inlet water temperature of pump is | Read | 0=Off, 1=On | |
| BV | 234 | AL_PumpInletPressureToLow | Status of the pump if the inlet pressure of pump is below | Read | 0=Off, 1=On | |
| BV | 238 | AL_PumpInletPressureToHigh | Status of the pump if the inlet pressure of pump is above | Read | 0=Off, 1=On | |
| BV | 242 | AL_PumpOutputPressureTooLow | Status of the pump if the output pressure of pump is below | Read | 0=Off, 1=On | |
| BV | 246 | AL_PumpOutputPressureTooHigh | Status of the pump if the output pressure of pump is above | Read | 0=Off, 1=On | |
| BV | 250 | AL_PumpTemperatureTooHigh | Status of the pump if the temperature of pump is above the | Read | 0=Off, 1=On | |
| BV | 254 | AL_PumpServiceAlarm | Whether the service alarm for the pump if currently enabled signifying the | Read | 0=Off, 1=On | |
| BV | 258 | AL_PumpPressurizingTimeout | Status of the communication timeout for pressurizing of pump | Read | 0=Off, 1=On | |
| BV | 262 | AL_PumpCoolingTimeout | Status of the communication timeout for the cooling of pump | Read | 0=Off, 1=On | |
| BV | 266 | AL_PumpInvalidConfig | Status of configuration of the pump | Read | 0=Off, 1=On | |
| BV | 270 | AL_PumpComTimeout | Status of the communication timeout of pump | Read | 0=Off, 1=On | |
| BV | 274 | AL_Zone1ComTimeout | Status of communication timeout for the zone 1 | Read | 0=Off, 1=On | |
| BV | 275 | AL_Zone2ComTimeout | Status of communication timeout for the zone 2 | Read | 0=Off, 1=On | |
| BV | 276 | AL_Zone3ComTimeout | Status of communication timeout for the zone 3 | Read | 0=Off, 1=On | |
| MVmin | 1 | PumpState | Status of pump | Read | 1=Stand-by, 2=Start Pump, 3=Pressurizing, 4=Ready, 5=Cooling, 6=Manual Prime, 7=System Drain, 8=Inactivity Drain, 9=Alarm, 10=Closing | |
| MV | 100 | Cfg_PressureUnits | Select the pressure units | Write | 1=kPa, 2=PSI, 3=Bar | |
| MV | 101 | Cfg_Language | Language of the BACnet server | Write | 1=English | |
| MV | 102 | Cfg_ObjectListMode | Select the category of BACnet objects to display | Write | 1=Integrator, 2=Advanced, 3=Factory | |
| FILE | 1 | FirmwareUpdateFile | File object of the firmware upgrade | Write | ||
| FILE | 2 | BootloaderUpdateFile | File object of the bootloader firmware upgrade | Write | ||
| FILE | 3 | PumpFirmwareUpdateFile | File object for pump firmware upgrade | Write | ||
| FILE | 4 | PumpBootloaderUpdateFile | File object for pump bootloader upgrade | Write | ||
| Other | 1 | FirmwareUpdateTask | Firmware upgrade task | Read |
No points match these filters.
Object ID lookup: Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station point IDs by name
AI1SKHBoardTempAO1FeedbackVoltageAV1PumpDemandAV2SystemZoneDemandAV3SimulationDurationAV4SimulationZoneSelectionAV5SimulationZoneDemandAV7SimulationPumpDemandAV8SimulationDowncounterAV9SystemPumpCapacityAV11SystemZoneCapacityAV12SystemNumOfZonesAV100Cfg_SystemInactivityDelayAV101Cfg_SystemInactivityDrainTimeAV204PumpFeedbackAV208PumpInletTempAV212PumpInletPressureAV216PumpOutputPressureAV220PumpDutyTimeAV224PumpWeightedDutyTimeAV300Cfg_PumpInactivityDelayAV304Cfg_PumpInactivityDrainTimeBO1AlarmRelayBO2MaintenanceRelayBO3BuzzerBV1SystemModeBV2SimulationStateBV3SimulationPumpOverrideBV4SystemDrainPendingBV5SystemDrainBV6SystemZoneDemandBV7WaterPressureStateBV8UVLampChangeDueBV50AL_ServiceWarningBV51AL_ServiceAlarmBV52AL_PumpGlobalAlarmMaskBV56AL_GlobalPumpComTimeoutBV57AL_GlobalZoneComTimeoutBV200PumpDrainValveBV204PumpEnableVFDBV210AL_PumpInletTempSensorFailureBV214AL_PumpInletPressureSensorFailureBV218AL_PumpOutputPressureSensorFailureBV222AL_PumpVFDFailureBV226AL_PumpInletTempTooHighBV230AL_PumpInletTempTooLowBV234AL_PumpInletPressureToLowBV238AL_PumpInletPressureToHighBV242AL_PumpOutputPressureTooLowBV246AL_PumpOutputPressureTooHighBV250AL_PumpTemperatureTooHighBV254AL_PumpServiceAlarmBV258AL_PumpPressurizingTimeoutBV262AL_PumpCoolingTimeoutBV266AL_PumpInvalidConfigBV270AL_PumpComTimeoutBV274AL_Zone1ComTimeoutBV275AL_Zone2ComTimeoutBV276AL_Zone3ComTimeoutMV1PumpStateMV100Cfg_PressureUnitsMV101Cfg_LanguageMV102Cfg_ObjectListModeFILE1FirmwareUpdateFileFILE2BootloaderUpdateFileFILE3PumpFirmwareUpdateFileFILE4PumpBootloaderUpdateFile
Integration notes
- Objects are grouped as Integrator, Integrator configuration and Advanced; MSV Cfg_ObjectListMode chooses which groups the device shows (Integrator, Advanced or Factory).
- Access: "Present Value" in the W? column is listed as writable, "Out of Service" (only the out-of-service property is writable) as read-only; commandable BOs are marked C.
- Out-of-service is cleared automatically after 15 minutes by default (Device proprietary property #1002).
- The zone controllers are separate BACnet devices with their own object list (see the SKH EZC list).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station
How many BACnet points does the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station have?
This list has 68 BACnet objects: 1 analog input, 1 analog output, 20 analog values, 3 binary outputs, 34 binary values, 4 files, 4 multi-state values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station BACnet points are writable?
20 of the 68 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station BACnet documentation?
The source is High Pressure Atomiser SKH Series BACnet User Guide (SKH-BACnet Guide-210104), revision 2021-01-04, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/SKH/20210107/SKH-BACnet%20Guide-210104.pdf.
What are the minimum BACnet points to integrate the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station?
Start with BV 1 SystemMode (System on/off (1 = on)); MV 1 PumpState (Pump state (stand-by, pressurizing, ready ...)); AV 1 PumpDemand (Pump demand, %); BV 7 WaterPressureState (Water pressure ready); AV 216 PumpOutputPressure (Pump output pressure, kPa); BO 1 AlarmRelay (Alarm relay (closed on alarm)); BV 52 AL_PumpGlobalAlarmMask (Pump global alarm); BV 51 AL_ServiceAlarm (Service alarm).
How do I enable BMS control of the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station?
BV 1 SystemMode switches the system on or off.
How do I check these points on the real SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Neptronic BACnet points lists
- Room / indoor air quality controller (temperature, humidity, CO2, VOC)
Neptronic AROB universal room / IAQ controller
Neptronic AROB room controllers measuring temperature, humidity, CO2 and VOC, with 2 analog and 2 binary outputs.
Also known as: AROB, AROB24, Neptronic AROB, IAQ controller - Make-up air unit (electric heat)
Neptronic CMU Compact Make-up Air Unit
Neptronic CMU compact make-up air units with electric heating, EC fan, damper and optional exhaust fan outputs.
Also known as: CMU, Neptronic CMU - Fan coil unit controller
Neptronic EFCB Series Fan Coil Controller
Neptronic EFCB fan coil controllers (24, 120 or 240 Vac, 2 or 4 relays) for 2-pipe and 4-pipe fan coils with TFL/TDF room sensors.
Also known as: EFCB, EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4 - Fan coil unit controller
Neptronic EFCB-OE1 Series Fan Coil Controller
Neptronic EFCB-OE1 fan coil controllers (24 or 240 Vac, 0, 2 or 4 relays), an OEM variant of the EFCB series.
Also known as: EFCB-OE1, EFCB10T-OE1, EFCB12T-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1 - VAV terminal unit controller
Neptronic EVCB14N Series VAV Controller
Neptronic EVCB14N networkable VAV controllers with integrated damper actuator, pressure-independent or pressure-dependent, with 0-4 triac outputs.
Also known as: EVCB14N, EVCB14NIT0S, EVCB14NIT2S, EVCB14NIT4S, EVCB14NDT4S, EVCB14NIT0SF, EVCB14NIT4SF - VAV terminal unit controller
Neptronic EVCB14NxT4X VAV Controller (external motor)
Neptronic EVCB14N VAV controllers with four triac outputs that drive an external damper motor, pressure independent (IT4X) or dependent (DT4X).
Also known as: EVCB14NxT4X, EVCB14NIT4X, EVCB14NDT4X - VAV terminal unit controller
Neptronic EVCB44N Series VAV Controller
Neptronic EVCB44N VAV controllers without triac outputs, pressure independent (IT0S) or pressure dependent (DT0S).
Also known as: EVCB44N, EVCB44NIT0S, EVCB44NDT0S - Dual duct VAV terminal controller
Neptronic EVCBM Dual Duct VAV Controller
Neptronic EVCBM master controller used on dual duct terminals, with a second (slave) airflow channel for the other duct.
Also known as: EVCBM, EVCBM Dual Duct, EVCB dual duct - Electric duct heater / terminal reheat controller
Neptronic HECB electric duct heater controller
Neptronic electric duct heaters fitted with the HECB intelligent controller (staged and SSR, with optional EAS airflow sensing).
Also known as: HECB, HEC, Neptronic HECB, electric duct heater controller - Electric steam humidifier
Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module
Legacy Neptronic SK300 and SKE electric steam humidifiers fitted with the NEPIC BACnet MS/TP communication module.
Also known as: SK300, SKE, Neptronic SK300, Neptronic SKE, NEPIC, SK300-BACNET, SKE-BACNET - Steam humidifier valve controller
Neptronic SKDESC-xB
Neptronic SKDESC-xB electronic controllers for steam-to-steam / direct steam injection humidifier valves (ESCJx jacketed, ESCMx models).
Also known as: SKDESC, SKDESCxB, ESCJx, ESCMx, Electronic Steam Controller - Electric steam humidifier
Neptronic SKE4
Neptronic SKE4 electric (heating element) steam humidifiers, indoor and outdoor versions.
Also known as: SKE4 electric steam humidifier, SKE4-N, SKE4-E, SKE4 BACnet - Gas-fired steam humidifier
Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module
Older Neptronic SKG gas-fired steam humidifiers (before the SKG4) with the NEPICSKG BACnet MS/TP module, one to four tanks.
Also known as: SKG, SKG3, Neptronic SKG, NEPICSKG, SKG-BACNET, SKG gas fired humidifier - Gas-fired steam humidifier
Neptronic SKG4
Neptronic SKG4 gas-fired steam humidifiers with up to four humidifier modules.
Also known as: SKG4 gas fired humidifier, SKG4-N, SKG4-E, SKG4 BACnet - High-pressure atomising humidifier zone controller
Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller
EZC zone controllers of older Neptronic SKH high pressure atomising humidifiers, before the SKH4; each zone is its own BACnet device.
Also known as: SKH EZC, EZC, Neptronic SKH zone controller, SKH-BACnet Guide-210104 - High-pressure atomizing humidifier / cooler
Neptronic SKH4
Neptronic SKH4 high-pressure water atomizing humidifiers and evaporative coolers with up to six zones (A-F).
Also known as: SKH4 high-pressure atomizer, SKH4 BACnet - Reverse osmosis water treatment unit
Neptronic SKRO
Neptronic SKRO reverse osmosis water treatment units feeding humidifiers.
Also known as: SKRO reverse osmosis, SKRO BACnet - Steam-to-steam humidifier
Neptronic SKS4
Neptronic SKS4 steam-to-steam (boiler steam heated) humidifiers.
Also known as: SKS4 steam to steam humidifier, SKS4 BACnet - Evaporative humidifier
Neptronic SKV
Neptronic SKV evaporative (media) humidifiers with up to four modules.
Also known as: SKV evaporative humidifier, SKV BACnet - Evaporative cooler / humidifier
Neptronic SKVF
Neptronic SKVF series evaporative coolers (also used for humidification).
Also known as: SKVF evaporative cooler, SKVF Series, SKVF BACnet - Fan coil / zone thermostat controller
Neptronic TFxB Series Thermostat Controller
Neptronic TFxB24 communicating thermostats for 2-pipe and 4-pipe fan coils and zone heating/cooling, including the humidity (TFHB) and OE variants.
Also known as: TFCB24F3XYZ1, TFCB24F3XY2, TFHB24F3XYZ1, TFHB24F3XYZ2, TFCB24P3-OE1, TFHB24P3-OE1, TFHB24P3-OE2, TFxB24 - Zone thermostat controller (VAV / fan coil)
Neptronic TROB24 thermostat controller
Neptronic TROB24 communicating thermostats with universal inputs, analog outputs and triac (on/off, pulsing or floating) outputs.
Also known as: TROB24, TROB, TROB24T4, Neptronic TROB - Fan coil / zone thermostat controller
Neptronic TSUB universal wall-mount controller
Neptronic TSUB universal wall-mount controllers for fan coils, heat pumps and zone heating/cooling.
Also known as: TSUB, TSUB24, Neptronic TSUB - Fan coil / zone thermostat controller
Neptronic TUCB / TUHB universal controller (TUxB24C6X2)
Neptronic TUCB (cooling/heating) and TUHB (with humidity) universal room controllers, model TUxB24C6X2.
Also known as: TUCB, TUHB, TUxB24C6X2, TUCB24C6X2, TUHB24C6X2 - Fan coil / zone thermostat controller
Neptronic TUUB universal wall-mount controller
Neptronic TUUB universal wall-mount controllers for fan coils, heat pumps, VFDs and zone heating/cooling.
Also known as: TUUB, TUUB24, Neptronic TUUB
Source: High Pressure Atomiser SKH Series BACnet User Guide · SKH-BACnet Guide-210104 · rev. 2021-01-04. Object names, instances and units are reproduced as published; descriptions are our own.