High-pressure atomising humidifier · BACnet points list

Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station BACnet points list

Updated 12 November 2026

Short answer

The older SKH high pressure atomiser shows up on BACnet MS/TP as a pump station device plus one device per EZC zone controller. The pump station device carries the system mode, pump state and demand, zone capacity, pump inlet and outlet pressure and temperature, alarm relay outputs and a long list of pump and communication alarms, plus simulation and inactivity-drain settings.

This page lists 68 BACnet objects for the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station
Equipment
High-pressure atomising humidifier
Equipment type
Humidifiers
BACnet objects
68 (20 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
153000 + MAC address
Also known as
SKH, Neptronic SKH, SKH high pressure atomiser, SKH-BACnet Guide-210104
Source document
High Pressure Atomiser SKH Series BACnet User Guide · SKH-BACnet Guide-210104 · rev. 2021-01-04
Download CSV 68 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.

BMS integration notes: Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station

Integration in brief

Turn the system on with BV 1 SystemMode and read MSV 1 PumpState, AV 1 PumpDemand and the alarm flags (BV 50/51 service, BV 52 pump global alarm). Humidity control itself is done per zone on the EZC devices.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1SystemModeSystem on/off (1 = on)Write
MV 1PumpStatePump state (stand-by, pressurizing, ready ...)Read
AV 1PumpDemandPump demand, %Read
BV 7WaterPressureStateWater pressure readyRead
AV 216PumpOutputPressurePump output pressure, kPaRead
BO 1AlarmRelayAlarm relay (closed on alarm)Command
BV 52AL_PumpGlobalAlarmMaskPump global alarmRead
BV 51AL_ServiceAlarmService alarmRead

Enable & remote start

BV 1 SystemMode switches the system on or off.

Network setup

Watch out for

Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

68 of 68 shown
Type
Multi-state
Access
Show
Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station BACnet Points List
DescriptionStates
AI1SKHBoardTempTemperature reading measured on the SKH PC board°CRead
AO1FeedbackVoltageOutput feedback voltagemVWrite
AVmin1PumpDemandPump demand of the system%Read
AV2SystemZoneDemandZone demand of the system%Read
AV3SimulationDurationDuration of Simulation modeminWrite
AV4SimulationZoneSelectionSelection of the number of zones in simulation modeWrite
AV5SimulationZoneDemandNumber of stages for the zones in simulation modeWrite
AV7SimulationPumpDemandSelection of pump demand for simulation mode%Write
AV8SimulationDowncounterConfiguration vale for the simulation mode downcountersRead
AV9SystemPumpCapacityPump capacity of the systemkg/hRead
AV11SystemZoneCapacityZone capacity of the systemkg/hRead
AV12SystemNumOfZonesNumber of zones for the systemRead
AV100Cfg_SystemInactivityDelaySystem inactivity delayhWrite
AV101Cfg_SystemInactivityDrainTimeSystem inactivity drain timeminWrite
AV204PumpFeedbackFeedback value of pumpRead
AV208PumpInletTempInlet temperature of pump°CRead
AV212PumpInletPressureInlet pressure of pumpkPaRead
AVmin216PumpOutputPressureOutput pressure of pumpkPaRead
AV220PumpDutyTimeDuty time of pumpRead
AV224PumpWeightedDutyTimeWeighted duty time of pumpRead
AV300Cfg_PumpInactivityDelayPump inactivity delayhWrite
AV304Cfg_PumpInactivityDrainTimePump inactivity drain timesWrite
BOmin1AlarmRelayOpen or close the alarm relayCommand0=Open, 1=Close
BO2MaintenanceRelayOpen or close the maintenance relayCommand0=Open, 1=Close
BO3BuzzerActivate or not the buzzerWrite0=Inactive, 1=Active
BVmin1SystemModeEnable or disable the system modeWrite0=Off, 1=On
BV2SimulationStateStatus of the simulation stateRead0=Off, 1=On
BV3SimulationPumpOverrideStatus of the simulation pump overrideRead0=Off, 1=On
BV4SystemDrainPendingStatus of the system drain pendingRead0=Off, 1=On
BV5SystemDrainStatus of the system drainRead0=Off, 1=On
BV6SystemZoneDemandStatus of system zone demandRead0=Off, 1=On
BVmin7WaterPressureStateStatus of the water pressure stateRead0=Not Ready, 1=Ready
BV8UVLampChangeDueStatus of the UV lamp change dueRead0=Off, 1=On
BV50AL_ServiceWarningStatus of the service warningRead0=Off, 1=On
BVmin51AL_ServiceAlarmStatus of the service alarmRead0=Off, 1=On
BVmin52AL_PumpGlobalAlarmMaskStatus of the pump global alarm maskRead0=Off, 1=On
BV56AL_GlobalPumpComTimeoutStatus of the global pump communication timeoutRead0=Off, 1=On
BV57AL_GlobalZoneComTimeoutStatus of the global zone communication timeoutRead0=Off, 1=On
BV200PumpDrainValveStatus of pump drain valveRead0=Off, 1=On
BV204PumpEnableVFDStatus of the pump enable VFDRead0=Off, 1=On
BV210AL_PumpInletTempSensorFailureStatus of the pump inlet temperature sensor failureRead0=Off, 1=On
BV214AL_PumpInletPressureSensorFailureStatus of the pump inlet pressure sensor failureRead0=Off, 1=On
BV218AL_PumpOutputPressureSensorFailureStatus of the pump output pressure sensor failureRead0=Off, 1=On
BV222AL_PumpVFDFailureStatus of the pump VFD failureRead0=Off, 1=On
BV226AL_PumpInletTempTooHighStatus of the pump if the inlet water temperature of pump isRead0=Off, 1=On
BV230AL_PumpInletTempTooLowStatus of the pump if the inlet water temperature of pump isRead0=Off, 1=On
BV234AL_PumpInletPressureToLowStatus of the pump if the inlet pressure of pump is belowRead0=Off, 1=On
BV238AL_PumpInletPressureToHighStatus of the pump if the inlet pressure of pump is aboveRead0=Off, 1=On
BV242AL_PumpOutputPressureTooLowStatus of the pump if the output pressure of pump is belowRead0=Off, 1=On
BV246AL_PumpOutputPressureTooHighStatus of the pump if the output pressure of pump is aboveRead0=Off, 1=On
BV250AL_PumpTemperatureTooHighStatus of the pump if the temperature of pump is above theRead0=Off, 1=On
BV254AL_PumpServiceAlarmWhether the service alarm for the pump if currently enabled signifying theRead0=Off, 1=On
BV258AL_PumpPressurizingTimeoutStatus of the communication timeout for pressurizing of pumpRead0=Off, 1=On
BV262AL_PumpCoolingTimeoutStatus of the communication timeout for the cooling of pumpRead0=Off, 1=On
BV266AL_PumpInvalidConfigStatus of configuration of the pumpRead0=Off, 1=On
BV270AL_PumpComTimeoutStatus of the communication timeout of pumpRead0=Off, 1=On
BV274AL_Zone1ComTimeoutStatus of communication timeout for the zone 1Read0=Off, 1=On
BV275AL_Zone2ComTimeoutStatus of communication timeout for the zone 2Read0=Off, 1=On
BV276AL_Zone3ComTimeoutStatus of communication timeout for the zone 3Read0=Off, 1=On
MVmin1PumpStateStatus of pumpRead1=Stand-by, 2=Start Pump, 3=Pressurizing, 4=Ready, 5=Cooling, 6=Manual Prime, 7=System Drain, 8=Inactivity Drain, 9=Alarm, 10=Closing
MV100Cfg_PressureUnitsSelect the pressure unitsWrite1=kPa, 2=PSI, 3=Bar
MV101Cfg_LanguageLanguage of the BACnet serverWrite1=English
MV102Cfg_ObjectListModeSelect the category of BACnet objects to displayWrite1=Integrator, 2=Advanced, 3=Factory
FILE1FirmwareUpdateFileFile object of the firmware upgradeWrite
FILE2BootloaderUpdateFileFile object of the bootloader firmware upgradeWrite
FILE3PumpFirmwareUpdateFileFile object for pump firmware upgradeWrite
FILE4PumpBootloaderUpdateFileFile object for pump bootloader upgradeWrite
Other1FirmwareUpdateTaskFirmware upgrade taskRead
Object ID lookup: Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station

How many BACnet points does the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station have?

This list has 68 BACnet objects: 1 analog input, 1 analog output, 20 analog values, 3 binary outputs, 34 binary values, 4 files, 4 multi-state values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station BACnet points are writable?

20 of the 68 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station BACnet documentation?

The source is High Pressure Atomiser SKH Series BACnet User Guide (SKH-BACnet Guide-210104), revision 2021-01-04, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/SKH/20210107/SKH-BACnet%20Guide-210104.pdf.

What are the minimum BACnet points to integrate the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station?

Start with BV 1 SystemMode (System on/off (1 = on)); MV 1 PumpState (Pump state (stand-by, pressurizing, ready ...)); AV 1 PumpDemand (Pump demand, %); BV 7 WaterPressureState (Water pressure ready); AV 216 PumpOutputPressure (Pump output pressure, kPa); BO 1 AlarmRelay (Alarm relay (closed on alarm)); BV 52 AL_PumpGlobalAlarmMask (Pump global alarm); BV 51 AL_ServiceAlarm (Service alarm).

How do I enable BMS control of the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station?

BV 1 SystemMode switches the system on or off.

How do I check these points on the real SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: High Pressure Atomiser SKH Series BACnet User Guide · SKH-BACnet Guide-210104 · rev. 2021-01-04. Object names, instances and units are reproduced as published; descriptions are our own.