- SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module
Electric steam humidifier · BACnet points list
Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module BACnet points list
Updated 6 November 2026
The NEPIC module gives older SK300 and SKE steam humidifiers a BACnet MS/TP interface (B-ASC). It serves 83 objects: humidity, water level and temperature readings, writable demand, setpoint, delay, PID and offset values, operating and input status, alarm flags, input type options and control, operation and source selectors.
This page lists 83 BACnet objects for the Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module — 61 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.
- Manufacturer
- Neptronic
- Model
- SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module
- Equipment
- Electric steam humidifier
- Equipment type
- Humidifiers
- BACnet objects
- 83 (61 writable)
- Transport
- BACnet MS/TP
- Firmware
- 1.00
- Default device instance
- 153000
- Also known as
- SK300, SKE, Neptronic SK300, Neptronic SKE, NEPIC, SK300-BACNET, SKE-BACNET
Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.
BMS integration notes: Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module
Set the baud with DIP switches 2-3 and give the module a unique MAC and device instance. For BMS demand control set MSV 1 Ctl_Mode to 3 (remote) and write AV 1 Humidity_Demand; for internal PID set MSV 1 to 2, choose the setpoint and humidity sources (MSV 4, MSV 5) and write AV 11 and AV 2. MSV 2 turns the unit on, off or to drain.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 2 | Operation_Mode | Unit off, on or drain | Write |
| MV 1 | Ctl_Mode | Control mode; 3 = demand from BACnet | Write |
| AV 1 | Humidity_Demand | Humidity demand from the BMS, % | Write |
| AV 11 | Ctl_SP | Humidity setpoint for internal PID, %RH | Write |
| AV 2 | Room_Humidity | Room RH from the BMS (remote source) | Write |
| BI 1 | Power_Status | Unit power on | Read |
| AI 1 | Humidity_Out | Humidifier output, % | Read |
| BI 5 | Alrm_Not_Critical | Non-critical alarm, unit still running | Read |
| BI 6 | Alarm_Critical | Critical alarm, unit stopped | Read |
Enable & remote start
MSV 2 Operation_Mode sets the unit off (1), on (2) or to drain (3). MSV 1 Ctl_Mode picks the demand source: 1 = local analog input, 2 = internal PID, 3 = remote demand over BACnet.
Sensors & values from the BMS
With MSV 5 Room_Hum_Source = 2 (remote) and MSV 6 Duct_Hum_Source = 3 (remote) the BMS writes AV 2 Room_Humidity and AV 3 Duct_Humidity; MSV 4 SP_Source = 3 takes the setpoint from BACnet.
Network setup
- DIP switch 1 selects operational (OFF) or configuration (ON) mode; switches 2 and 3 set 9600, 19200, 38400 or 76800 baud (restart after a change).
- Factory settings: MAC 0, device instance 153000, Max_Master 127; configuration mode uses MAC 254 as a non-token-passing slave.
- Device instance, object name, Max_Master and MAC (proprietary property 1000) can be written to the Device object at any time.
Watch out for
- Two modules left at the factory MAC 0 / instance 153000 will clash; configure each before connecting.
- BV 30 Reload_Factory restores factory values.
Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Humidity_Out | Humidity Output (range 0-100 %RH) | %RH | Read | |
| AI | 2 | Water_Level | Water level (range 0-120%) | % | Read | |
| AI | 3 | Delay_to_Drain | Delay until Drain (range 0-100Hrs) | hours | Read | |
| AI | 4 | Water_Temp | Water Temperature (range 0-260 °C or 32-500 °F) | °C/°F | Read | |
| AI | 5 | Chimney_Temp | Chimney Temperature (range 0-260 °C or 32-500 °F) | °C/°F | Read | |
| AI | 6 | SSR_Temp | Solid State Relay Temperature (range 0-260 °C or 32-500 °F) | °C/°F | Read | |
| AI | 7 | Op_Delay | Operation Delay (range 0-5000Hrs) | hours | Read | |
| AVmin | 1 | Humidity_Demand | Humidity Demand (range 0-100 %RH) | %RH | Write | |
| AVmin | 2 | Room_Humidity | Room Humidity (range 0-100 %RH) | %RH | Write | |
| AV | 3 | Duct_Humidity | Duct Humidity (range 0-100 %RH) | %RH | Write | |
| AV | 4 | Drain_Delay | Drain Delay (range 1-100Hrs) | hours | Write | |
| AV | 5 | Svc_Delay | Service Delay (range 1-5000Hrs) | hours | Write | |
| AV | 6 | EOS_Delay | End of season delay (range 1-250Hrs) | hours | Write | |
| AV | 7 | PID_Loop_KP | PID Loop gain KP (range 0-255) | Write | ||
| AV | 8 | PID_Loop_KI | PID Loop gain KI (range 0-255) | Write | ||
| AV | 9 | PID_Loop_KD | PID Loop gain KD (range 0-255) | Write | ||
| AV | 10 | Ctl_Band | Control band (range 0-20.0%) | % | Write | |
| AVmin | 11 | Ctl_SP | Control set point (range 0-100%RH) | %RH | Write | |
| AV | 12 | Extern_SP_Min | External set point minimum (range 0-100%RH) | %RH | Write | |
| AV | 13 | Extern_SP_Max | External set point maximum (range 0-100%RH) | %RH | Write | |
| AV | 14 | Duct_Hum_HL_SP | Duct hum. high limit set point (range 50-100%RH) | %RH | Write | |
| AV | 15 | Fan_Min_On_Time | Minimum ON time for fan (range 2-20 minutes) | min | Write | |
| AV | 16 | Min_Water_Temp | Min water temp. in On (range 10-90 °C or 50-194 °F (0 -> Mode is Off)) | °C/°F | Write | |
| AV | 17 | Antifreeze_Temp | Anti-freeze mode temp (range 4-10 °C or 39-50°F (0 -> Mode is Off)) | °C/°F | Write | |
| AV | 18 | Room_Hum_Offset | Room Humidity offset (range ±0-20 %RH) | %RH | Write | |
| AV | 19 | Duct_Hum_Offset | Duct Humidity offset (range ±0-20 %RH) | %RH | Write | |
| AV | 20 | Water_Temp_Offset | Water Temperature offset (range ±0-20 °C or ±0-40 °F) | °C/°F | Write | |
| AV | 21 | Water_Lvl_Offset | Water Level offset (range ±0-20%) | % | Write | |
| AV | 22 | SSR_Temp_Offset | SSR Temperature offset (range ±0-20 °C or ±0-40 °F) | °C/°F | Write | |
| AV | 23 | Lock_On_Cap | Lock On capacity (range 10-100%) | % | Write | |
| AV | 24 | Max_Out_Limit | Maximum output limit (range 10-100%) | % | Write | |
| AV | 25 | Outside_Temp | Outside Temperature (range -40 - 40 °C or -40 - 104 °F) | °C/°F | Write | |
| BImin | 1 | Power_Status | Power Status | Read | 0=OFF, 1=ON | |
| BI | 2 | Demand | Demand | Read | 0=NO, 1=YES | |
| BI | 3 | Auto_Drain | Auto Drain | Read | 0=NO, 1=YES | |
| BI | 4 | Manual_Drain | Manual Drain | Read | 0=NO, 1=YES | |
| BImin | 5 | Alrm_Not_Critical | Alarm not critical (unit running) | Read | 0=NO, 1=YES | |
| BImin | 6 | Alarm_Critical | Alarm critical (unit not running) | Read | 0=NO, 1=YES | |
| BI | 7 | EOS_Delay_Status | End of Season Delay | Read | 0=NO, 1=YES | |
| BI | 8 | Fan_Proof | Fan proof Status | Read | 0=OFF, 1=ON | |
| BI | 9 | Hi_Lim_Status | Hi-Limit Status | Read | 0=OFF, 1=ON | |
| BI | 10 | Interlock | Interlock | Read | 0=OFF, 1=ON | |
| BI | 11 | Power_Fuse | Power Fuse (24VAC) | Read | 0=OFF, 1=ON | |
| BI | 12 | Klixxon | Klixxon | Read | 0=OFF, 1=ON | |
| BI | 13 | Ext_Therm_Fuse | Thermal fuse (external 24VAC) | Read | 0=OFF, 1=ON | |
| BI | 14 | Int_Therm_Fuse | Thermal fuse (internal 24VDC) | Read | 0=OFF, 1=ON | |
| BI | 15 | Foam_Probe | Foam Probe | Read | 0=OFF, 1=ON | |
| BV | 1 | Over_Temp_ON | Over temperature contact ON | Write | 0=Normal, 1=Alarm | |
| BV | 2 | Pwr_Fuse_Open | Power fuse (24VAC) open | Write | 0=Normal, 1=Alarm | |
| BV | 3 | Ext_Th_Fuse_Open | Thermal Fuse open (24VAC) | Write | 0=Normal, 1=Alarm | |
| BV | 4 | Int_Th_Fuse_Open | Thermal Fuse open (24VDC) | Write | 0=Normal, 1=Alarm | |
| BV | 5 | Hi_Duct_Hum | High humidity level in the duct | Write | 0=Normal, 1=Alarm | |
| BV | 6 | Low_Input_Volt | Input voltage too low | Write | 0=Normal, 1=Alarm | |
| BV | 7 | Bad_Tank_Sensor | Tank sensor defective | Write | 0=Normal, 1=Alarm | |
| BV | 8 | Bad_SSR_Sensor | SSR sensor defective | Write | 0=Normal, 1=Alarm | |
| BV | 9 | Bad_Water_Sensor | Water level probe defect | Write | 0=Normal, 1=Alarm | |
| BV | 10 | Foam_Sensor_ON | Foam Sensor ON | Write | 0=Normal, 1=Alarm | |
| BV | 11 | Low_Tank_Temp | Tank temperature too low (freeze) | Write | 0=Normal, 1=Alarm | |
| BV | 12 | Hi_Tank_Temp | Tank temperature too high | Write | 0=Normal, 1=Alarm | |
| BV | 13 | Hi_SSR_Temp | SSR temperature too high | Write | 0=Normal, 1=Alarm | |
| BV | 14 | Bad_Fill_Tank | Defective filling tank | Write | 0=Normal, 1=Alarm | |
| BV | 15 | Bad_Refill_Tank | Defective refill tank (too long) | Write | 0=Normal, 1=Alarm | |
| BV | 16 | Bad_Drain_Tank | Defective draining tank | Write | 0=Normal, 1=Alarm | |
| BV | 17 | Duct_Hi_Lim_CO | Duct Hi limit cut-out | Write | 0=Normal, 1=Alarm | |
| BV | 18 | Interlock_In_Open | Interlock Input Open | Write | 0=Normal, 1=Alarm | |
| BV | 19 | Hum_Clean_Time | Humidifier started cleaning period | Write | 0=Normal, 1=Alarm | |
| BV | 20 | Hum_Svc_Time | Humidifier exceeded service time | Write | 0=Normal, 1=Alarm | |
| BV | 21 | Demand_SP_Type | Demand-Set point type | Write | 0=Voltage, 1=Current | |
| BV | 22 | Demand_SP_Span | Demand-Set point span | Write | 0=2-10VDC, 1=0-10VDC | |
| BV | 23 | Humidity_In_Type | Humidity input type | Write | 0=Voltage, 1=Current | |
| BV | 24 | Humidity_In_Span | Humidity input span | Write | 0=2-10VDC, 1=0-10VDC | |
| BV | 25 | Hi_Lim_In_Type | Hi-limit humidity input type | Write | 0=Voltage, 1=Current | |
| BV | 26 | Hi_Lim_In_Span | Hi-limit humidity input span | Write | 0=2-10VDC, 1=0-10VDC | |
| BV | 27 | Temp_Units | Temperature Units | Write | 0=Celsius, 1=Fahrenheit | |
| BV | 28 | Outside_Temp_Comp | Outside Temperature Compensation | Write | 0=OFF, 1=ON | |
| BV | 29 | Alarm_Beep | Alarm Beep | Write | 0=OFF, 1=ON | |
| BV | 30 | Reload_Factory | Reload Factory default value | Write | 0=NO, 1=YES | |
| MVmin | 1 | Ctl_Mode | Control Mode | Write | 1=Local Demand from Analog Input 1, 2=Internal PID calculation, 3=Demand from remote communication port (e.g. BACnet®) | |
| MVmin | 2 | Operation_Mode | Operation Mode | Write | 1=Set unit Off, 2=Set unit On, 3=Set unit in drain mode | |
| MV | 3 | Unit_Display_Lang | Unit Display Language | Write | 1=English (Default), 2=French, 3=Spanish | |
| MV | 4 | SP_Source | Set point Source | Write | 1=Local analog input 1, 2=Local Internal digital value, 3=Remote from communication port (e.g. BACnet®) | |
| MV | 5 | Room_Hum_Source | Room Humidity source | Write | 1=Local analog input 2, 2=Remote from communication port (e.g. BACnet®) | |
| MV | 6 | Duct_Hum_Source | Duct Humidity source | Write | 1=Not used, 2=Local analog input 3, 3=Remote from communication port (e.g. BACnet®) |
No points match these filters.
Object ID lookup: Neptronic SK300 / SKE (legacy) point IDs by name
AI1Humidity_OutAI2Water_LevelAI3Delay_to_DrainAI4Water_TempAI5Chimney_TempAI6SSR_TempAI7Op_DelayAV1Humidity_DemandAV2Room_HumidityAV3Duct_HumidityAV4Drain_DelayAV5Svc_DelayAV6EOS_DelayAV7PID_Loop_KPAV8PID_Loop_KIAV9PID_Loop_KDAV10Ctl_BandAV11Ctl_SPAV12Extern_SP_MinAV13Extern_SP_MaxAV14Duct_Hum_HL_SPAV15Fan_Min_On_TimeAV16Min_Water_TempAV17Antifreeze_TempAV18Room_Hum_OffsetAV19Duct_Hum_OffsetAV20Water_Temp_OffsetAV21Water_Lvl_OffsetAV22SSR_Temp_OffsetAV23Lock_On_CapAV24Max_Out_LimitAV25Outside_TempBI1Power_StatusBI2DemandBI3Auto_DrainBI4Manual_DrainBI5Alrm_Not_CriticalBI6Alarm_CriticalBI7EOS_Delay_StatusBI8Fan_ProofBI9Hi_Lim_StatusBI10InterlockBI11Power_FuseBI12KlixxonBI13Ext_Therm_FuseBI14Int_Therm_FuseBI15Foam_ProbeBV1Over_Temp_ONBV2Pwr_Fuse_OpenBV3Ext_Th_Fuse_OpenBV4Int_Th_Fuse_OpenBV5Hi_Duct_HumBV6Low_Input_VoltBV7Bad_Tank_SensorBV8Bad_SSR_SensorBV9Bad_Water_SensorBV10Foam_Sensor_ONBV11Low_Tank_TempBV12Hi_Tank_TempBV13Hi_SSR_TempBV14Bad_Fill_TankBV15Bad_Refill_TankBV16Bad_Drain_TankBV17Duct_Hi_Lim_COBV18Interlock_In_OpenBV19Hum_Clean_TimeBV20Hum_Svc_TimeBV21Demand_SP_TypeBV22Demand_SP_SpanBV23Humidity_In_TypeBV24Humidity_In_SpanBV25Hi_Lim_In_TypeBV26Hi_Lim_In_SpanBV27Temp_UnitsBV28Outside_Temp_CompBV29Alarm_BeepBV30Reload_FactoryMV1Ctl_ModeMV2Operation_ModeMV3Unit_Display_LangMV4SP_SourceMV5Room_Hum_SourceMV6Duct_Hum_Source
Integration notes
- The SK300 and SKE guides (SK300-BACNET Rev 060606 and SKE-BACNET Rev 081104) print identical object tables; one list covers both. These are the older models, separate from the SKE4/SKG4 lists.
- Access is from the W? column. The alarm BVs are printed as writable.
- Temperature values follow BV 27 Temp_Units (Celsius or Fahrenheit).
- The module does not send BACnet event notifications; alarms are read from the BI/BV objects.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module
How many BACnet points does the Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module have?
This list has 83 BACnet objects: 7 analog inputs, 25 analog values, 15 binary inputs, 30 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module BACnet points are writable?
61 of the 83 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module BACnet documentation?
The source is SK300 Steam Humidifier BACnet Communication Module User Guide (SK300 Humidifier Object Table) (SK300-BACNET), revision Rev 060606, published free by Neptronic at https://www.neptronic.com/humidifiers/PDF/SK300/SK300-bacnet-user-guide.pdf.
What are the minimum BACnet points to integrate the Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module?
Start with MV 2 Operation_Mode (Unit off, on or drain); MV 1 Ctl_Mode (Control mode; 3 = demand from BACnet); AV 1 Humidity_Demand (Humidity demand from the BMS, %); AV 11 Ctl_SP (Humidity setpoint for internal PID, %RH); AV 2 Room_Humidity (Room RH from the BMS (remote source)); BI 1 Power_Status (Unit power on); AI 1 Humidity_Out (Humidifier output, %); BI 5 Alrm_Not_Critical (Non-critical alarm, unit still running); BI 6 Alarm_Critical (Critical alarm, unit stopped).
How do I enable BMS control of the Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module?
MSV 2 Operation_Mode sets the unit off (1), on (2) or to drain (3). MSV 1 Ctl_Mode picks the demand source: 1 = local analog input, 2 = internal PID, 3 = remote demand over BACnet.
Can the BMS supply sensor values to the Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module?
With MSV 5 Room_Hum_Source = 2 (remote) and MSV 6 Duct_Hum_Source = 3 (remote) the BMS writes AV 2 Room_Humidity and AV 3 Duct_Humidity; MSV 4 SP_Source = 3 takes the setpoint from BACnet.
How do I check these points on the real SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Neptronic BACnet points lists
- Room / indoor air quality controller (temperature, humidity, CO2, VOC)
Neptronic AROB universal room / IAQ controller
Neptronic AROB room controllers measuring temperature, humidity, CO2 and VOC, with 2 analog and 2 binary outputs.
Also known as: AROB, AROB24, Neptronic AROB, IAQ controller - Make-up air unit (electric heat)
Neptronic CMU Compact Make-up Air Unit
Neptronic CMU compact make-up air units with electric heating, EC fan, damper and optional exhaust fan outputs.
Also known as: CMU, Neptronic CMU - Fan coil unit controller
Neptronic EFCB Series Fan Coil Controller
Neptronic EFCB fan coil controllers (24, 120 or 240 Vac, 2 or 4 relays) for 2-pipe and 4-pipe fan coils with TFL/TDF room sensors.
Also known as: EFCB, EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4 - Fan coil unit controller
Neptronic EFCB-OE1 Series Fan Coil Controller
Neptronic EFCB-OE1 fan coil controllers (24 or 240 Vac, 0, 2 or 4 relays), an OEM variant of the EFCB series.
Also known as: EFCB-OE1, EFCB10T-OE1, EFCB12T-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1 - VAV terminal unit controller
Neptronic EVCB14N Series VAV Controller
Neptronic EVCB14N networkable VAV controllers with integrated damper actuator, pressure-independent or pressure-dependent, with 0-4 triac outputs.
Also known as: EVCB14N, EVCB14NIT0S, EVCB14NIT2S, EVCB14NIT4S, EVCB14NDT4S, EVCB14NIT0SF, EVCB14NIT4SF - VAV terminal unit controller
Neptronic EVCB14NxT4X VAV Controller (external motor)
Neptronic EVCB14N VAV controllers with four triac outputs that drive an external damper motor, pressure independent (IT4X) or dependent (DT4X).
Also known as: EVCB14NxT4X, EVCB14NIT4X, EVCB14NDT4X - VAV terminal unit controller
Neptronic EVCB44N Series VAV Controller
Neptronic EVCB44N VAV controllers without triac outputs, pressure independent (IT0S) or pressure dependent (DT0S).
Also known as: EVCB44N, EVCB44NIT0S, EVCB44NDT0S - Dual duct VAV terminal controller
Neptronic EVCBM Dual Duct VAV Controller
Neptronic EVCBM master controller used on dual duct terminals, with a second (slave) airflow channel for the other duct.
Also known as: EVCBM, EVCBM Dual Duct, EVCB dual duct - Electric duct heater / terminal reheat controller
Neptronic HECB electric duct heater controller
Neptronic electric duct heaters fitted with the HECB intelligent controller (staged and SSR, with optional EAS airflow sensing).
Also known as: HECB, HEC, Neptronic HECB, electric duct heater controller - Steam humidifier valve controller
Neptronic SKDESC-xB
Neptronic SKDESC-xB electronic controllers for steam-to-steam / direct steam injection humidifier valves (ESCJx jacketed, ESCMx models).
Also known as: SKDESC, SKDESCxB, ESCJx, ESCMx, Electronic Steam Controller - Electric steam humidifier
Neptronic SKE4
Neptronic SKE4 electric (heating element) steam humidifiers, indoor and outdoor versions.
Also known as: SKE4 electric steam humidifier, SKE4-N, SKE4-E, SKE4 BACnet - Gas-fired steam humidifier
Neptronic SKG4
Neptronic SKG4 gas-fired steam humidifiers with up to four humidifier modules.
Also known as: SKG4 gas fired humidifier, SKG4-N, SKG4-E, SKG4 BACnet - High-pressure atomizing humidifier / cooler
Neptronic SKH4
Neptronic SKH4 high-pressure water atomizing humidifiers and evaporative coolers with up to six zones (A-F).
Also known as: SKH4 high-pressure atomizer, SKH4 BACnet - Reverse osmosis water treatment unit
Neptronic SKRO
Neptronic SKRO reverse osmosis water treatment units feeding humidifiers.
Also known as: SKRO reverse osmosis, SKRO BACnet - Steam-to-steam humidifier
Neptronic SKS4
Neptronic SKS4 steam-to-steam (boiler steam heated) humidifiers.
Also known as: SKS4 steam to steam humidifier, SKS4 BACnet - Evaporative humidifier
Neptronic SKV
Neptronic SKV evaporative (media) humidifiers with up to four modules.
Also known as: SKV evaporative humidifier, SKV BACnet - Evaporative cooler / humidifier
Neptronic SKVF
Neptronic SKVF series evaporative coolers (also used for humidification).
Also known as: SKVF evaporative cooler, SKVF Series, SKVF BACnet - Fan coil / zone thermostat controller
Neptronic TFxB Series Thermostat Controller
Neptronic TFxB24 communicating thermostats for 2-pipe and 4-pipe fan coils and zone heating/cooling, including the humidity (TFHB) and OE variants.
Also known as: TFCB24F3XYZ1, TFCB24F3XY2, TFHB24F3XYZ1, TFHB24F3XYZ2, TFCB24P3-OE1, TFHB24P3-OE1, TFHB24P3-OE2, TFxB24 - Zone thermostat controller (VAV / fan coil)
Neptronic TROB24 thermostat controller
Neptronic TROB24 communicating thermostats with universal inputs, analog outputs and triac (on/off, pulsing or floating) outputs.
Also known as: TROB24, TROB, TROB24T4, Neptronic TROB - Fan coil / zone thermostat controller
Neptronic TSUB universal wall-mount controller
Neptronic TSUB universal wall-mount controllers for fan coils, heat pumps and zone heating/cooling.
Also known as: TSUB, TSUB24, Neptronic TSUB - Fan coil / zone thermostat controller
Neptronic TUCB / TUHB universal controller (TUxB24C6X2)
Neptronic TUCB (cooling/heating) and TUHB (with humidity) universal room controllers, model TUxB24C6X2.
Also known as: TUCB, TUHB, TUxB24C6X2, TUCB24C6X2, TUHB24C6X2 - Fan coil / zone thermostat controller
Neptronic TUUB universal wall-mount controller
Neptronic TUUB universal wall-mount controllers for fan coils, heat pumps, VFDs and zone heating/cooling.
Also known as: TUUB, TUUB24, Neptronic TUUB
Source: SK300 Steam Humidifier BACnet Communication Module User Guide (SK300 Humidifier Object Table) · SK300-BACNET · rev. Rev 060606. Object names, instances and units are reproduced as published; descriptions are our own.