Fan coil / zone thermostat controller · BACnet points list

Neptronic TUCB / TUHB universal controller (TUxB24C6X2) BACnet points list

Updated 6 November 2026

Short answer

A wall-mount universal room controller with configurable inputs and outputs that speaks BACnet MS/TP. The BACnet guide lists 183 objects: inputs and outputs, mode, fan and occupancy commands, setpoints, demands per ramp, alarms and a large set of Cfg_ configuration objects. Which outputs and modes are used depends on how the ramps and inputs are configured.

This page lists 183 BACnet objects for the Neptronic TUCB / TUHB universal controller (TUxB24C6X2) — 153 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
TUCB / TUHB universal controller (TUxB24C6X2)
Equipment
Fan coil / zone thermostat controller
Equipment type
VAV boxes & fan coils
BACnet objects
183 (153 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
153000 + MAC address
Also known as
TUCB, TUHB, TUxB24C6X2, TUCB24C6X2, TUHB24C6X2
Source document
TUxB24C6X2 BACnet Guide · TUXB24C6X2-BACnet Guide-190904 · rev. 2019-09-04
Download CSV 183 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.

BMS integration notes: Neptronic TUCB / TUHB universal controller (TUxB24C6X2)

Integration in brief

Command occupancy with MSV.13 NsbOccCommand, the mode with MSV.1 and the fan with MSV.2, and write the setpoint to AV.9. To feed the room temperature from the BMS, set MSV.21 to Network and keep writing AV.1 ControlTemp within the AV.2 timeout. Read MSV.14, AV.1, the ramp demands and the AL_ alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 13NsbOccCommandBMS occupancy command: local, off, occupied, unoccupiedCommand
MV 1SystemModeMode: auto, heating, cooling, fan, offWrite
MV 2UserFanSpeedSelectFan speed: auto, low, medium, highWrite
AV 9TempSetPointOccupied/day temperature setpointCommand
MV 14OccupancyStatusActual occupancy incl. overrideRead
AV 1ControlTempTemperature used for controlCommand
AV 20Heating1DemandHeating ramp 1 demand, %Read
AV 35Cooling1DemandCooling ramp 1 demand, %Read
BV 37AL_FlowSwitchAirflow alarmRead
BV 36AL_ DirtyFilterFilter change requiredRead

Enable & remote start

MSV.13 NsbOccCommand: Locally lets the controller follow its occupancy input; the other states force off, occupied/day or unoccupied/night from the BMS.

Heartbeat & communication loss

With MSV.21 Cfg_TempControlSource = Network, the BMS must keep writing AV.1 ControlTemp; if nothing arrives for AV.2 Cfg_NetworkTimeOut (0-60 min) the controller goes to OFF and AV.1 shows 999 °C in fault. With AV.2 = 0, AV.1 resets to the AV.9 setpoint.

Sensors & values from the BMS

Set MSV.21 Cfg_TempControlSource to Network (1) and write the room temperature to AV.1 ControlTemp (commandable).

Network setup

Watch out for

Neptronic TUCB / TUHB universal controller (TUxB24C6X2) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

183 of 183 shown
Type
Multi-state
Access
Show
Neptronic TUCB / TUHB universal controller (TUxB24C6X2) BACnet Points List
DescriptionStates
AI1AnalogInput1Sensor reading value on analog input 1VRead
AI2AnalogInput2Sensor reading value on analog input 2VRead
AI7InternTempInternal temp sensor value (ITS) of the integrated sensor°F/°CRead
AI8InternHumidity*Internal humidity value measured by the internal humidity sensor%RHRead
AO1AnalogOutput1Percentage value of analog output 1, based on demand%Write
AO2AnalogOutput2Percentage value of analog output 2, based on demand%Write
AVmin1ControlTempTemperature value that is used to calculate demand°F/°CCommand
AV2Cfg_NetworkTimeOutConfiguration time valueminWrite
AV3ExternTempExtern temperature sensor (ETS)°F/°CRead
AV4ChangeOverTempChangeover temperature sensor (SENs)°F/°CRead
AV5Cfg_InternTempOffsetCalibrate the integrated temp sensor of the controller (ITS)°F/°CWrite
AV6Cfg_ExternTempOffsetCalibrate the external temp sensor (ETS)°F/°CWrite
AV7Cfg_ExternTempMinMinimum temp read by the sensor (minimum range value)°F/°CWrite
AV8Cfg_ExternTempMaxMaximum temp read by the sensor (maximum range value)°F/°CWrite
AVmin9TempSetPointSet the actual user setpoint of the zone in occupied/day operation mode°F/°CCommand
AV10Cfg_MinSetPointSet the minimum temp setpoint of the zone in occupied/day operation mode°F/°CWrite
AV11Cfg_MaxSetPointSet the maximum temp setpoint of the zone in occupied/day operation mode°F/°CWrite
AV12SetPointCoolNoOccNSBConfiguration value of the cooling setpoint when in night setback or unoccupied°F/°CWrite
AV13SetPointHeatNoOccNSBConfiguration value of the heating setpoint when in night setback or unoccupied°F/°CWrite
AVmin20Heating1DemandStatus value that represents the heating demand for the Heating Ramp 1%Read
AV21Cfg_Heating1PropBandRange through which the controller will modulate the heating output from 0°F/°CWrite
AV22Cfg_Heating1DeadBandDeadband around the setpoint°F/°CWrite
AV24Heating2DemandStatus value that represents the heating demand for the Heating Ramp 2%Read
AV25Cfg_Heating2PropBandRange through which the controller will modulate the heating output from 0°F/°CWrite
AV26Cfg_Heating2DeadBandDeadband around the setpoint°F/°CWrite
AV32Cfg_IntegralTimeHeatingReciprocal of the integral time in secs (1/I or repeats per second)sWrite
AVmin35Cooling1DemandStatus value that represents the cooling demand for the Cooling Ramp 1%Read
AV36Cfg_Cooling1PropBandRange through which the controller will modulate the cooling output from 0°F/°CWrite
AV37Cfg_Cooling1DeadBandDeadband around the setpoint°F/°CWrite
AV38Cooling2DemandStatus value that represents the cooling demand for the Cooling Ramp 2%Read
AV39Cfg_Cooling2PropBandRange through which the controller will modulate the cooling output from 0°F/°CWrite
AV40Cfg_Cooling2DeadBandDeadband around the setpoint°F/°CWrite
AV45Cfg_IntegralTimeCoolingReciprocal of the integral time in secs (1/I or repeats per second)sWrite
AV46Cfg_CoolingAntiCycleDelayCooling output anti-short-cycle time, minutesminWrite
AV50ChangeOverDemandStatus value that represents the changeover demand%Read
AV51Cfg_ChangeOverPropBandProportional band for the changeover output°F/°CWrite
AV52Cfg_ChangeOverDeadBandRange at which the controller will not take action on the changeover°F/°CWrite
AV53ChangeOverSetPointEntering water temperature threshold for changeover°F/°CWrite
AV56Cfg_CL_HT_SwitchTimerDelay before changeover is allowed to switchminWrite
AV58CL_HT_SwitchTimerCountStatus value of the remaining time before the changeover is authorisedsRead
AV60FanDemandStatus value that represents the fan demand%Read
AV61Cfg_FanAutoTimeOutDelayPrevent the cycling of the fansWrite
AV62Cfg_FanDampingFactorConfiguration value in secs that represents the damping factor for changing fansWrite
AV70ExternHumidityExternal humidity sensor value (Erh)%RHRead
AV71Cfg_InternHumidityOffset*Calibrate the internal relative humidity sensor (irh)%RHWrite
AV72Cfg_ExternHumidityOffsetCalibrate the external relative humidity sensor (Erh)%RHWrite
AV73HumSetPointSet the actual user humidity setpoint of the zone in occupied/day operation%RHCommand
AV74Cfg_HumMinSetPointSet the minimum relative humidity setpoint of the zone in occupied/day operation%RHWrite
AV75Cfg_HumMaxSetPointSet the maximum relative humidity setpoint of the zone in occupied/day operation%RHWrite
AV76DehumdifySPNoOccNSBConfiguration value of the highest relative humidity allowed when in night setback%RHWrite
AV77HumidifySPNoOccNSBConfiguration value of the lowest relative humidity allowed when in night setback%RHWrite
AV78HumidifyDemandStatus value that represents the humidifier modulation, based on relative humidity%RHRead
AV79DehumidifyDemandStatus value that represents the dehumidification percentage, based on relative humidity%RHRead
AV80Cfg_HumPropBandProportional band for the humidity output%RHWrite
AV81Cfg_HumDeadBandDeadband around the setpoint%RHWrite
AV85Cfg_NSBOverrideDelayMaximum override time in night setback, minutesminWrite
AV86Cfg_NoOccOverrideDelayMaximum configuration time in mins when in unoccupied mode and an overrideminWrite
AV87Cfg_NoOccOvCountDownTime in mins before the state of the input changes from OccupiedminRead
AV88Cfg_OccupancyMinTimeTime in mins before the state of the input changes from OccupiedminWrite
AV90Cfg_BinaryInput1DelayConfiguration time in secssWrite
AV91Cfg_BinaryInput2DelaySee AV.90sWrite
AV92Cfg_AnalogInput1DelaySee AV.90sWrite
AV93Cfg_AnalogInput2DelaySee AV.90sWrite
AV95CO2SensorValueCarbon dioxide sensor (CO2)ppmRead
AV96Cfg_CO2RangeMaximum range of the CO2 sensor (PPM)ppmWrite
AV97CO2SetpointMaximum limit of CO2 concentration before the controller sends an alarmppmWrite
AV100Cfg_AnalogOutput1MinThis value represents the minimum control signal of the controlled elementVWrite
AV101Cfg_AnalogOutput1MaxThis value represents the maximum control signal of the controlled elementVWrite
AV103Cfg_AnalogOutput2MinSee AV.100VWrite
AV104Cfg_AnalogOutput2MaxSee AV.101VWrite
AV106Cfg_MinCoolHeat1PositionConfiguration value in percentage at which the controller sets the CH1 output%Write
AV115Cfg_BinaryOutput1ClosePosConfiguration value that indicates the percentage of demand at which the contact%Write
AV116Cfg_BinaryOutput1OpenPosConfiguration value that indicates the percentage of demand at which the contact%Write
AV117Cfg_BinaryOutput1ContactDelayConfiguration value in mins to add a delay before allowing the outputminWrite
AV120Cfg_BinaryOutput2ClosePosSee AV.115%Write
AV121Cfg_BinaryOutput2OpenPosSee AV.116%Write
AV122Cfg_BinaryOutput2ContactDelaySee AV.117minWrite
AV125Cfg_BinaryOutput3ClosePosSee AV.115%Write
AV126Cfg_BinaryOutput3OpenPosSee AV.116%Write
AV127Cfg_BinaryOutput3ContactDelaySee AV.117minWrite
AV130Cfg_BinaryOutput4ClosePosSee AV.115%Write
AV131Cfg_BinaryOutput4OpenPosSee AV.116%Write
AV132Cfg_BinaryOutput4ContactDelaySee AV.117minWrite
AV133Cfg_BinaryOutput5ClosePosSee AV.115%Write
AV134Cfg_BinaryOutput5OpenPosSee AV.116%Write
AV135Cfg_BinaryOutput5ContactDelaySee AV.117minWrite
AV136Cfg_BinaryOutput6ClosePosSee AV.115%Write
AV137Cfg_BinaryOutput6OpenPosSee AV.116%Write
AV138Cfg_BinaryOutput6ContactDelaySee AV.117minWrite
AV165CopyCfgStartAddressFirst address in the range of copied controllers while using the CopyWrite
AV166CopyCfgEndAddressLast address in the range of copied controllers while using the CopyWrite
AV167CopyCfgResultValue is used to verify whether the copy to the controllers operationWrite
AV206CloseOffVoltageConfiguration value of the voltage required in order to close the 6-wayWrite
AV207MinCoolingVoltageConfiguration value of the voltage required for the 6-way valve to startWrite
AV208MinHeatingVoltageConfiguration value of the voltage required for the 6-way valve to startWrite
BI1BinaryInput1Contact status of the input: (0) Open, (1) CloseRead0=Open, 1=Close
BI2BinaryInput2Contact status of the input: (0) Open, (1) CloseRead0=Open, 1=Close
BO1BinaryOutput1Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO2BinaryOutput2Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO3BinaryOutput3Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO4BinaryOutput4Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO5BinaryOutput5Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO6BinaryOutput6Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BV1Cfg_TempUnitBACnetTemp units used in BACnetWrite0=Celsius, 1=Fahrenheit
BV2Cfg_TempSetPointLockLocks the zone setpoint at the keypadWrite0=Disable, 1=Enable
BV3Cfg_UserSysOffModeConfiguration to allow users to turn off the controllerWrite0=Enable, 1=Disable
BV4Cfg_TempUnitTstatTemp units used on the controllerWrite0=Celsius, 1=Fahrenheit
BV5Cfg _FreezeProtectionEnable or disable the automatic activation of the heating outputs when zoneWrite0=Off, 1=On
BV10Cfg_Heating1RampLockLock the heating ramp 1 even when a heating demand is activeWrite0=Off, 1=On
BV11Cfg_Heating2RampLockLock the heating ramp 2 even when a heating demand is activeWrite0=Off, 1=On
BV13Cfg_ CoolingRampLockLock the cooling ramp even when a cooling demand is activeWrite0=Off, 1=On
BV17Cfg_ChangeOverRampLockLocks the changeover rampWrite0=Off, 1=On
BV20Cfg_UserFanAutoModeEnable or disable the automatic fan optionWrite0=Enable, 1=Disable
BV21Cfg_FanSpeedOptionSelect between the Standard (Neptronic) and Advanced (OE1) fan speed specificationsWrite0=Standard, 1=Advanced
BV25Cfg_HumControlSourceConfiguration value that controls the humidity source, either internal or externalWrite0=Intern Sensor, 1=Extern Sensor
BV26Cfg_HumSetPointLockPrevent the user from changing the relative humidity setpointWrite0=Disable, 1=Enable
BV27Cfg_HumidifyRampLockLock the humidification ramp even when a humidification demand is activeWrite0=Off, 1=On
BV28Cfg_DehumidifyRampLockLock the dehumidification ramp even when a dehumidification demand is activeWrite0=Off, 1=On
BV30ChangeOverModeStatus value of the actual changeover mode (0) Cooling, (1) HeatingWrite0=Cooling, 1=Heating
BV35Cfg_NightorNoOccModeConfiguration to determine the action of the controller when in night setbackWrite0=Setpoint, 1=OFF
BVmin36AL_ DirtyFilterStatus value to inform if a filter change is requiredRead0=No, 1=Yes
BVmin37AL_FlowSwitchStatus value to inform if an airflow alarm is activeRead0=No, 1=Yes
BV38AL_OverrideStatus value to inform if an override is activeRead0=No, 1=Yes
BV39AL_WindowOpenedStatus value to inform that a window has been openedRead0=No, 1=Yes
BV40AL_DoorOpenedStatus value to inform that a door has been openedRead0=No, 1=Yes
BV41AL_OverHeatStatus value to inform if a heat/reheat with fan override is activeRead0=No, 1=Yes
BV42AL_SelectorSwitchStatusStatus value to inform if the selector switch is in (0) RemoteRead0=Remote mode, 1=Local mode
BV45Cfg_BinaryInput1ContactConfiguration to change the contact's normal positionWrite0=Norm Open, 1=Norm Close
BV46Cfg_BinaryInput2ContactSee BV.45Write0=Norm Open, 1=Norm Close
BV47Cfg_AnalogInput1ContactSee BV.45Write0=Norm Open, 1=Norm Close
BV48Cfg_AnalogInput2ContactSee BV.45Write0=Norm Open, 1=Norm Close
BV49Cfg_WindowOpenedModeController action when the window contact opensWrite0=Setpoint, 1=OFF
BV50Cfg_DoorOpenedModeController action when the door contact opensWrite0=Setpoint, 1=OFF
BV55Cfg_AnalogOutput1DirectionAnalog output directionWrite0=Direct, 1=Reverse
BV56Cfg_AnalogOutput2DirectionSee BV.55Write0=Direct, 1=Reverse
BV60Cfg_BinaryOutput1DirectionBinary output directionWrite0=Direct, 1=Reverse
BV61Cfg_BinaryOutput2DirectionSee BV.60Write0=Direct, 1=Reverse
BV62Cfg_BinaryOutput3DirectionSee BV.60Write0=Direct, 1=Reverse
BV63Cfg_BinaryOutput4DirectionSee BV.60Write0=Direct, 1=Reverse
BV64Cfg_BinaryOutput5DirectionSee BV.60Write0=Direct, 1=Reverse
BV65Cfg_BinaryOutput6DirectionSee BV.60Write0=Direct, 1=Reverse
BV85Cfg_ServiceDisplayAddressWhen activated, the controller lights up and displays the MSTP addressWrite0=Off, 1=On
BV86Cfg_KeyPadUpperLeftLockWhen on, the button is locked in run modeWrite0 = Off, 1 = On If set to "On", functionality of these buttons will not be available.
BV87Cfg_KeyPadBottomLeftLockWhen on, the button is locked in run modeWrite0 = Off, 1 = On If set to "On", functionality of these buttons will not be available.
BV88Cfg_KeyPadArrowsLockWhen on, the button is locked in run modeWrite0 = Off, 1 = On If set to "On", functionality of these buttons will not be available.
BV89Cfg_ProgramModeLockWhen on, all buttons are lockedWrite0=Off, 1=On
BV90CopyCfgExecuteWhen using Copy Config, this value is used to start the copyWrite0=No, 1=Yes
BV91Cfg_ActivateScheduleConfiguration to activate the scheduleWrite0=No, 1=Yes
BV95Cfg_HeatPumpOptionConfiguration to enable or disable the heat pump optionWrite0=Off, 1=On
BV96Cfg_ReversingValveConfiguration to set the mode in which the reversing valve is energizedWrite0=O, 1=B
BV97Cfg_EMHAutoModeEnable or disable the EMH Auto modeWrite0=No, 1=Yes
BV98Cfg_EMHOutputEnable or disable emergency heat (EMH)Write0=Disable, 1=Enable
BV99Cfg_Y2OutputEnable or disable compressor Y2 outputWrite0=Disable, 1=Enable
MVmin1SystemModeActual mode selectedWriteAuto, Heating, EMH, Cooling, Fan, Off (options depend on configuration)
MVmin2UserFanSpeedSelectActual fan speedWrite1=Auto, 2=Low, 3=Medium, 4=High
MV5HumControlModeAuthorize humidification and/or dehumidification in order to maintain relative humidity setpointsWrite1=Auto, 2=Dehumidification, 3=Humidification, 4=Off
MV10Cfg_ChangeOverControlModeConfiguration that indicates the source of the changeover valueWrite1=Locally, 2=Cooling, 3=Heating
MVmin13NsbOccCommandConfiguration to set the occupancy or night setback modeCommandIf BI = Occupancy or Night Setback at MSV.46 and/or MSV.47 1 = Locally 2 = Off 3 = Occupancy/Day 4 = No Occupancy/Night If BI = any option except Occupancy or Night Setback at MSV.46 and/or MSV.47 1 = Off 2 =...
MVmin14OccupancyStatusStatus that indicates the actual occupancyRead1=NoOccupancy, 2=Occupancy, 3=Override
MV15NightSetBackStatusStatus that indicates the actual mode of the zoneRead1=Day, 2=Night, 3=Override
MV20Cfg_Sequence SelectLimit available options at MSV.1Write1=Auto, 2=Heating, 3=Cooling, 4=HeatingOrCooling, 5=Auto Lock
MV21Cfg_ TempControlSourceSet the control temp to be used by the controllerWrite1=Network (Net), 2=Internal (ItS), 3=External (EtS)
MV25Cfg_FanOperationTypeSet the number of fan speed available on the fan coilWrite1=1Speed, 2=2Speeds, 3=3Speeds
MV26Cfg_FanModeNoOccNightSet the fan speed for no occupancy or night setback modeWrite1=Low, 2=Medium, 3=High, 4=Auto
MV27Cfg_FanModeWindowOpenedSet the fan speed mode when the window is openWrite1=Low, 2=Medium, 3=High, 4=Auto
MV28Cfg_FanModeDoorOpenedSet the fan speed mode when the door is openWrite1=Low, 2=Medium, 3=High, 4=Auto
MV35Cfg_AnalogInput1TypeSelect the input signal type for Analog Input 1 (AI1)Write1=OFF, 2=Extern Sensor 10k, 3=Change Over Sensor, 4=Ch Ov Contact Norm Cool, 5=Ch Ov Contact Norm Heat, 6=Outside Air Sensor, 7=Extern Sensor0_10V, 8=CO2_0_10V, 9=Occupancy, 10=Night Set Back, 11=Override, 12=Window, 13=Door, 14=Dirty Filter, 15=Flow Switch, 16=Overheat, 17=Selector Switch, 18=Humidity Sensor0_10V
MV36Cfg_AnalogInput2TypeSee MSV.35Write
MV46Cfg_BinaryInput1TypeSelect the input signal type for Binary Input 1 (BI1)Write1=OFF, 2=Override, 3=Window, 4=Door, 5=Dirty Filter, 6=Flow Switch, 7=Overheat, 8=Selector Switch, 9=Ch Ov Contact Norm Cool, 10=Ch Ov Contact Norm Heat, 11=Occupancy, 12=Night Set Back
MV47Cfg_BinaryInput2TypeSee MSV.46Write
MV55Cfg_AnalogOutput1RampRamp used to modulate AO1 based on demandWrite1=OFF, 2=Change Over With Fan, 3=Cooling1 With Fan, 4=Cooling2 With Fan, 5=Heating1 With Fan, 6=Heating2 With Fan, 7=Heating2, 8=Cooling1 Heating1 With Fan, 9=HumidifyWithFan, 10=CO2 Alarm, 11=6 way valve
MV57Cfg_AnalogOutput2RampRamp assigned to AO2 (see MSV.55 and BV.95)Write
MV70Cfg_BinaryOutput1RampRamp used to modulate BO1 based on demandWrite1=OFF, 2=Change Over With Fan, 3=Cooling1 With Fan, 4=Cooling2 With Fan, 5=Heating1 With Fan, 6=Heating2 With Fan, 7=Heating2, 8=Cooling1 Heating1 With Fan, 9=HumidifyWithFan, 10=CO2 Alarm
MV71Cfg_BinaryOutput2RampSee MSV.70Write
MV72Cfg_BinaryOutput3RampSee MSV.70Write
MV73Cfg_BinaryOutput4RampIf MSV.25 Cfg_FanOperationType is set to 3 speeds, (1) Fan: High speedWrite
MV74Cfg_BinaryOutput5RampIf MSV.25 Cfg_FanOperationType is set to 3 speeds, (1) Fan: Medium speedWrite
MV75Cfg_BinaryOutput6RampIf MSV.25 Cfg_FanOperationType is set to 3 speeds, (1) Fan: Low speedWrite
MV95Cfg_DisplayInfoConfiguration value of the information displayed on the controllerWrite1=Temp and demand, 2=Setpoint and demand, 3=Temp only, 4=Setpoint only, 5=Off
MV96Cfg_ValveSizeConfiguration value of the valve size in inches for the 6-way valveWrite1=1/2, 2=3/4, 3=1
SCH1OccupancyScheduleWeekly occupancy schedule to specify which occupancy state is active during specificRead
Other1ProgramFirmwareProgram object for firmware update (LOAD or RESTART)Write
FILE1FirmwareBinaryFileFirmware binary file written for an updateWrite
Object ID lookup: Neptronic TUCB / TUHB universal controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TUCB / TUHB universal controller (TUxB24C6X2) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic TUCB / TUHB universal controller (TUxB24C6X2)

How many BACnet points does the Neptronic TUCB / TUHB universal controller (TUxB24C6X2) have?

This list has 183 BACnet objects: 4 analog inputs, 2 analog outputs, 89 analog values, 2 binary inputs, 6 binary outputs, 50 binary values, 1 file, 1 schedule, 27 multi-state values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic TUCB / TUHB universal controller (TUxB24C6X2) BACnet points are writable?

153 of the 183 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic TUCB / TUHB universal controller (TUxB24C6X2) BACnet documentation?

The source is TUxB24C6X2 BACnet Guide (TUXB24C6X2-BACnet Guide-190904), revision 2019-09-04, published free by Neptronic at https://www.neptronic.com/Controls/PDF/2025/TUXB24C6X2-BACnet%20Guide-190904.pdf.

What are the minimum BACnet points to integrate the Neptronic TUCB / TUHB universal controller (TUxB24C6X2)?

Start with MV 13 NsbOccCommand (BMS occupancy command: local, off, occupied, unoccupied); MV 1 SystemMode (Mode: auto, heating, cooling, fan, off); MV 2 UserFanSpeedSelect (Fan speed: auto, low, medium, high); AV 9 TempSetPoint (Occupied/day temperature setpoint); MV 14 OccupancyStatus (Actual occupancy incl. override); AV 1 ControlTemp (Temperature used for control); AV 20 Heating1Demand (Heating ramp 1 demand, %); AV 35 Cooling1Demand (Cooling ramp 1 demand, %); BV 37 AL_FlowSwitch (Airflow alarm); BV 36 AL_ DirtyFilter (Filter change required).

How do I enable BMS control of the Neptronic TUCB / TUHB universal controller (TUxB24C6X2)?

MSV.13 NsbOccCommand: Locally lets the controller follow its occupancy input; the other states force off, occupied/day or unoccupied/night from the BMS.

Does the Neptronic TUCB / TUHB universal controller (TUxB24C6X2) need a BACnet heartbeat or have a communication timeout?

With MSV.21 Cfg_TempControlSource = Network, the BMS must keep writing AV.1 ControlTemp; if nothing arrives for AV.2 Cfg_NetworkTimeOut (0-60 min) the controller goes to OFF and AV.1 shows 999 °C in fault. With AV.2 = 0, AV.1 resets to the AV.9 setpoint.

Can the BMS supply sensor values to the Neptronic TUCB / TUHB universal controller (TUxB24C6X2)?

Set MSV.21 Cfg_TempControlSource to Network (1) and write the room temperature to AV.1 ControlTemp (commandable).

How do I check these points on the real TUCB / TUHB universal controller (TUxB24C6X2)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: TUxB24C6X2 BACnet Guide · TUXB24C6X2-BACnet Guide-190904 · rev. 2019-09-04. Object names, instances and units are reproduced as published; descriptions are our own.