Room / indoor air quality controller (temperature, humidity, CO2, VOC) · BACnet points list
Neptronic AROB universal room / IAQ controller BACnet points list
Updated 6 November 2026
AROB is a wall-mount room controller for temperature, humidity, CO2 and VOC with BACnet MS/TP. The BACnet guide lists 166 objects: user system modes and setpoints, sensor readings, calculated enthalpy and dew point, demands per function and output, OAT and airflow lockout and filter alarms, and configuration objects for the outputs and inputs.
This page lists 166 BACnet objects for the Neptronic AROB universal room / IAQ controller — 129 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.
- Manufacturer
- Neptronic
- Model
- AROB universal room / IAQ controller
- Equipment
- Room / indoor air quality controller (temperature, humidity, CO2, VOC)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 166 (129 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 153000 + MAC address
- Also known as
- AROB, AROB24, Neptronic AROB, IAQ controller
Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.
BMS integration notes: Neptronic AROB universal room / IAQ controller
Turn the controller on with MSV.1, pick the temperature mode with MSV.2 and write the cooling/heating setpoints AV.1/AV.2. Read AV.10 temperature, AV.11 humidity, AV.9 CO2, the demands and the filter/airflow alarm BVs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | User main system mode | Controller off or on | Write |
| MV 2 | User Temp system mode | Temperature mode: off, cool, auto, heat | Write |
| AV 1 | User Cooling Setpoint | Occupied cooling setpoint | Write |
| AV 2 | User Heating Setpoint | Occupied heating setpoint | Write |
| AV 10 | Status Temp level | Room temperature | Read |
| AV 11 | Status Humidity level | Room relative humidity | Read |
| AV 9 | Status CO2 level | Room CO2, ppm | Read |
| AV 17 | Status Cooling Demand | Cooling demand, % | Read |
| AV 18 | Status Heating Demand | Heating demand, % | Read |
| BV 7 | Status Air Flow Switch Status | Airflow alarm | Read |
Enable & remote start
MSV.1 User main system mode turns the controller off or on; MSV.2-MSV.6 set the temperature, humidity, CO2, VOC and fan modes.
Network setup
- MSV.22 Cfg Network unit selects metric or imperial values on BACnet.
Watch out for
- Setpoints are limited by the deadbands and min/max configuration values.
Neptronic AROB universal room / IAQ controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 3 | Status AI 1 mV | Sensor reading value on analog input 1 in millivolts | mV | Read | |
| AI | 4 | Status PCB Temp mV | Temperature of the printed circuit board in millivolts | mV | Read | |
| AI | 5 | Status Micro Temp mV | Measured temperature of the on-board microprocessor in millivolts | mV | Read | |
| AO | 1 | Status AO.1 | Status value that represents the modulation percentage of analog output 1 based | % | Command | |
| AO | 2 | Status AO.2 | Status value that represents the modulation percentage of analog output 2 based | % | Command | |
| AVmin | 1 | User Cooling Setpoint | Set the actual user cooling setpoint of the zone in the operation | °F/°C | Write | |
| AVmin | 2 | User Heating Setpoint | Set the actual user heating setpoint of the zone in the operation | °F/°C | Write | |
| AV | 3 | User Dehumidification Setpoint | Zone dehumidification setpoint | %RH | Write | |
| AV | 4 | User Humidification Setpoint | Set the actual user humidification setpoint of the zone in operation mode | %RH | Write | |
| AV | 5 | User Cooling Unocc Setpoint | Set the actual user cooling setpoint of the zone in unoccupied operation | °F/°C | Write | |
| AV | 6 | User Heating Unocc Setpoint | Set the actual user heating setpoint of the zone in unoccupied operation | °F/°C | Write | |
| AV | 7 | User CO2 Setpoint | User CO2 setpoint in parts per million (PPM) at which the outside | ppm | Write | |
| AV | 8 | User VOC Setpoint | VOC setpoint | Write | ||
| AVmin | 9 | Status CO2 level | Status of the carbon dioxide sensor (CO2) | ppm | Read | |
| AVmin | 10 | Status Temp level | Internal temperature sensor reading | °F/°C | Read | |
| AVmin | 11 | Status Humidity level | Humidity sensor reading | %RH | Read | |
| AV | 13 | Status VOC Level | VOC sensor reading | Read | ||
| AV | 14 | Status Outdoor Temp level | Outdoor temperature | °F/°C | Read | |
| AV | 15 | Status Enthalpy | Calculated enthalpy | Read | ||
| AV | 16 | Status Dew Point | Calculated dew point | °F/°C | Read | |
| AVmin | 17 | Status Cooling Demand | Status value of the cooling demand | % | Read | |
| AVmin | 18 | Status Heating Demand | Status value that represents the heating demand | % | Read | |
| AV | 19 | Status Dehumidification Demand | Status value that represents the dehumidification percentage based on relative humidity | % | Read | |
| AV | 20 | Status Humidification Demand | Status value that represents the humidifier modulation based on relative humidity | % | Read | |
| AV | 21 | Status CO2 Demand | Status value that represents the CO2 demand based on CO2 level | % | Read | |
| AV | 22 | Status VOC Demand | Status value that represents the VOC demand based on VOC level | % | Read | |
| AV | 23 | Status AO 1 Demand | Status of the value of analog output 1 value in percentage based | % | Read | |
| AV | 24 | Status AO 2 Demand | Status of the value of analog output 2 value in percentage based | % | Read | |
| AV | 25 | Status BO 1 Demand | Status of the value of binary output 1 value in percentage based | % | Read | |
| AV | 26 | Status BO 2 Demand | Status of the value of binary output 2 value in percentage based | % | Read | |
| AV | 27 | Cfg CO2 calibration | Configuration value applied to the displayed CO2 level reading that is used | ppm | Write | |
| AV | 28 | Cfg VOC calibration | Configuration value applied to the displayed VOC level reading that is used | Write | ||
| AV | 29 | Cfg Temp calibration | Configuration value applied to the displayed temperature level reading that is used | °F/°C | Write | |
| AV | 30 | Cfg Humidity calibration | Configuration value applied to the displayed humidity level reading that is used | %RH | Write | |
| AV | 32 | Cfg Outdoor Temp calibration | Calibration offset for the outdoor air temperature reading | °F/°C | Write | |
| AV | 33 | Cfg AO 1 Min Value | Desired minimum voltage (“zero” value) for analog output 1 | V | Write | |
| AV | 34 | Cfg AO 1 Max Value | Desired maximum voltage (“span” value) for analog output 1 | V | Write | |
| AV | 35 | Cfg AO 2 Min Value | Select the desired minimum voltage (“zero” value) for analog output 2 | V | Write | |
| AV | 36 | Cfg AO 2 Max Value | Select the desired maximum voltage (“span” value) for analog output 2 | V | Write | |
| AV | 37 | Cfg AO1 Hi OAT Lockout | Select the desired high temperature limit for outside air temperature on analog | °F/°C | Write | |
| AV | 38 | Cfg AO1 Low OAT Lockout | Select the desired low teperature limit for outside air temperature on analog | °F/°C | Write | |
| AV | 39 | Cfg AO2 Hi OAT Lockout | Select the desired high temperature limit for outside air temperature on analog | °F/°C | Write | |
| AV | 40 | Cfg AO2 Low OAT Lockout | Select the desired low teperature limit for outside air temperature on analog | °F/°C | Write | |
| AV | 41 | Cfg BO1 Hi OAT Lockout | Select the desired high temperature limit for outside air temperature on binary | °F/°C | Write | |
| AV | 42 | Cfg BO1 Low OAT Lockout | Select the desired low teperature limit for outside air temperature on binary | °F/°C | Write | |
| AV | 43 | Cfg BO2 Hi OAT Lockout | Select the desired high temperature limit for outside air temperature on binary | °F/°C | Write | |
| AV | 44 | Cfg BO2 Low OAT Lockout | Select the desired low teperature limit for outside air temperature on binary | °F/°C | Write | |
| AV | 45 | Cfg BO 1 Anti Cycle Timer | Binary output 1 anti-cycle delay, seconds | s | Write | |
| AV | 46 | Cfg BO 2 Anti Cycle Timer | Binary output 2 anti-cycle delay, seconds | s | Write | |
| AV | 53 | Cfg FAN ON Speed | Minimum fan speed when the fan system mode is on | % | Write | |
| AV | 54 | Cfg BO 1 Hysteresis Low Limit | Desired binary output 1 hysteresis low percentage | % | Write | |
| AV | 55 | Cfg BO 1 Hysteresis Hi Limit | Desired binary output 1 hysteresis high percentage | % | Write | |
| AV | 56 | Cfg BO 2 Hysteresis Low Limit | Desired binary output 2 hysteresis low percentage | % | Write | |
| AV | 57 | Cfg BO 2 Hysteresis Hi Limit | Desired binary output 2 hysteresis high percentage | % | Write | |
| AV | 58 | Status Board Temp level | Temperature of printed circuit board | °F/°C | Read | |
| AV | 59 | Status Micro Temp level | Measured temperature of the on-board microprocessor | °F/°C | Read | |
| AV | 60 | Cfg Cooling P Band | Desired proportional band value for the cooling ramp | °F/°C | Write | |
| AV | 61 | Cfg Cooling I Time | Time for cooling integral factor compensation | s | Write | |
| AV | 62 | Cfg Heating P Band | Desired proportional band value of the heating ramp | °F/°C | Write | |
| AV | 63 | Cfg Heating I Time | Desired time for heating integral factor compensation | s | Write | |
| AV | 64 | Cfg Humidity P Band | Desired proportional band value of the dehumidification and humidification ramps | %RH | Write | |
| AV | 65 | Cfg Humidity I Time | Desired value for humidification integral factor compensation of the dehumidification and humidification | s | Write | |
| AV | 66 | Cfg CO2 P Band | Desired proportional band value of the CO2 ramp | ppm | Write | |
| AV | 67 | Cfg CO2 I Time | Desired value for CO2 integral factor compensation | s | Write | |
| AV | 68 | Cfg VOC P Band | Desired proportional band value of the VOC ramp | Write | ||
| AV | 69 | Cfg VOC I Time | Desired value for VOC integral factor compensation | s | Write | |
| AV | 70 | Cfg Cooling setpoint min | Minimum cooling setpoint | °F/°C | Write | |
| AV | 71 | Cfg Cooling setpoint max | Maximum cooling setpoint | °F/°C | Write | |
| AV | 72 | Cfg Cooling Unocc setpoint min | Minimum cooling setpoint value used during no occupancy | °F/°C | Write | |
| AV | 73 | Cfg Cooling Unocc setpoint max | Maximum cooling setpoint value used during no occupancy | °F/°C | Write | |
| AV | 74 | Cfg Heating Setpoint min | Minimum heating setpoint | °F/°C | Write | |
| AV | 75 | Cfg Heating Setpoint max | Maximum heating setpoint | °F/°C | Write | |
| AV | 76 | Cfg Heating Unocc Setpoint min | Minimum heating setpoint value used during no occupancy | °F/°C | Write | |
| AV | 77 | Cfg Heating Unocc Setpoint max | Maximum heating setpoint value used during no occupancy | °F/°C | Write | |
| AV | 78 | Cfg Dehumidification Setpoint min | Value set as the minimum dehumidification setpoint | %RH | Write | |
| AV | 79 | Cfg Dehumidification Setpoint max | Value set as the maximum dehumidification setpoint | %RH | Write | |
| AV | 80 | Cfg Humidification Setpoint min | Value set as the minimum humidification setpoint | %RH | Write | |
| AV | 81 | Cfg Humidification Setpoint max | Value set as the maximum humidification setpoint | %RH | Write | |
| AV | 82 | Cfg CO2 Setpoint min | Value set as the minimum CO2 setpoint | ppm | Write | |
| AV | 83 | Cfg CO2 Setpoint max | Value set as the maximum CO2 setpoint | ppm | Write | |
| AV | 84 | Cfg VOC Setpoint min | Value set as the minimum VOC setpoint | Write | ||
| AV | 85 | Cfg VOC Setpoint max | Value set as the maximum VOC setpoint | Write | ||
| AV | 88 | Cfg CO2 Sensor Calibration Period | CO2 sensor calibration period in hours | h | Write | |
| AV | 89 | Cfg Board Temp calibration | Configuration value applied to the displayed board temperature reading that is used | °F/°C | Write | |
| AV | 90 | Cfg Micro Temp calibration | Configuration value applied to the displayed microcontroller temperature reading that is used | °F/°C | Write | |
| AV | 91 | Cfg Temp Deadband | Temperature deadband | °F/°C | Write | |
| AV | 92 | Cfg Humidity Deadband | Humidity deadband | %RH | Write | |
| AV | 93 | Status AO 1 mV | Status value that represents the analog output 1 in millivolts | mV | Read | |
| AV | 94 | Status AO 2 mV | Status value that represents the analog output 2 in millivolts | mV | Read | |
| BI | 1 | Status BI 1 | Status of the binary input 1 reading | Read | 0=Open, 1=Close | |
| BI | 2 | Status Programing Mode | Status of the programming mode, jumper JP3 (B and C) | Read | 0=Open, 1=Close | |
| BI | 3 | Status Production Mode | Status of the production mode jumper J4 (3 and 4) | Read | 0=Open, 1=Close | |
| BO | 1 | Status BO 1 | Contact status of the binary output 1 | Command | 0=Open, 1=Close | |
| BO | 2 | Status BO 2 | Contact status of the binary output 2 | Command | 0=Open, 1=Close | |
| BV | 1 | Status Occupancy Status | Occupancy status based on AI1 or BI1 set to Occupancy or Night | Read | 0=No, 1=Yes | |
| BV | 2 | Status AO 1 OAT Lockout | OAT lockout active for analog output 1 | Read | 0=No, 1=Yes | |
| BV | 3 | Status AO 2 OAT Lockout | OAT lockout active for analog output 1 | Read | 0=No, 1=Yes | |
| BV | 4 | Status BO 1 OAT Lockout | OAT lockout active for analog output 1 | Read | 0=No, 1=Yes | |
| BV | 5 | Status BO 2 OAT Lockout | OAT lockout active for analog output 1 | Read | 0=No, 1=Yes | |
| BV | 6 | Status Dirty filter Status | Status value to inform if a filter change is required | Read | 0=No, 1=Yes | |
| BVmin | 7 | Status Air Flow Switch Status | Status value to inform if an airflow alarm is active | Read | 0=No, 1=Yes | |
| BV | 8 | Status Air Flow Lockout Status | Status value to inform if an airflow lockout alarm is active | Read | 0=No, 1=Yes | |
| BV | 9 | CfgDisplayCO2Level | Display CO2 in RUN mode | Write | 0=No, 1=Yes | |
| BV | 10 | CfgDisplay VOCLevel | Display VOC in RUN mode | Write | 0=No, 1=Yes | |
| BV | 11 | CfgDisplayTempLevel | Display Temp in RUN mode | Write | 0=No, 1=Yes | |
| BV | 12 | CfgDisplayHumidityLevel | Display %RH in RUN mode | Write | 0=No, 1=Yes | |
| BV | 16 | Cfg Enable Backlight | Desired status of LCD backlight | Write | 0=Off, 1=On | |
| BV | 17 | Cfg Enable Auto- Scroll | Desired status of the auto-scroll of sensor readings in the RUN mode | Write | 0=Off, 1=On | |
| BV | 18 | Cfg Key Pad Upper Left Lock | Lock the star (*) button | Write | 0 = Off, 1 = On If set to On, the functionality of these buttons will not be available. | |
| BV | 19 | Cfg Key Pad Bottom Left Lock | Lock the enter/return button | Write | 0 = Off, 1 = On If set to On, functionality of these buttons will not be available. | |
| BV | 20 | Cfg Key Pad Arrows Lock | Lock the arrow buttons | Write | 0 = Off, 1 = On If set to On, functionality of these buttons will not be available. | |
| BV | 21 | Cfg Program Mode Lock | Locks the Program Mode when the jumper JP3 is set to PGM. | Write | 0 = Off, 1 = On If set to On, Program Mode will not be available. | |
| BV | 22 | Cfg Cooling Command AO 1 | Status of the cooling command for Analog Output 1 | Write | 0=No, 1=Yes | |
| BV | 23 | Cfg Heating Command AO 1 | Status of the heating command for Analog Output 1 | Write | 0=No, 1=Yes | |
| BV | 24 | Cfg Dehumidification Command AO 1 | Status of the dehumidification command for Analog Output 1 | Write | 0=No, 1=Yes | |
| BV | 25 | Cfg Humidification Command AO 1 | Status of the humidification command for Analog Output 1 | Write | 0=No, 1=Yes | |
| BV | 26 | Cfg CO 2 Command AO 1 | Status of the CO2 command for Analog Output 1 | Write | 0=No, 1=Yes | |
| BV | 27 | Cfg VOC Command AO 1 | Status of the VOC command for Analog Output 1 | Write | 0=No, 1=Yes | |
| BV | 28 | Cfg FAN Command AO 1 | Status of the fan command for Analog Output 1 | Write | 0=No, 1=Yes | |
| BV | 29 | Cfg Cooling Command AO 2 | Status of the cooling command for Analog Output 2 | Write | 0=No, 1=Yes | |
| BV | 30 | Cfg Heating Command AO 2 | Status of the heating command for Analog Output 2 | Write | 0=No, 1=Yes | |
| BV | 31 | Cfg Dehumidification Command AO 2 | Status of the dehumidification command for Analog Output 2 | Write | 0=No, 1=Yes | |
| BV | 32 | Cfg Humidification Command AO 2 | Status of the humidification command for Analog Output 2 | Write | 0=No, 1=Yes | |
| BV | 33 | Cfg CO 2 Command AO 2 | Status of the CO2 command for Analog Output 2 | Write | 0=No, 1=Yes | |
| BV | 34 | Cfg VOC Command AO 2 | Status of the VOC command for Analog Output 2 | Write | 0=No, 1=Yes | |
| BV | 35 | Cfg FAN Command AO 2 | Status of the fan command for Analog Output 2 | Write | 0=No, 1=Yes | |
| BV | 36 | Cfg Cooling Command BO 1 | Status of the cooling command for Binary Output 1 | Write | 0=No, 1=Yes | |
| BV | 37 | Cfg Heating Command BO 1 | Status of the heating command for Binary Output 1 | Write | 0=No, 1=Yes | |
| BV | 38 | Cfg Dehumidification Command BO 1 | Status of the dehumidification command for Binary Output 1 | Write | 0=No, 1=Yes | |
| BV | 39 | Cfg Humidification Command BO 1 | Status of the humidification command for Binary Output 1 | Write | 0=No, 1=Yes | |
| BV | 40 | Cfg CO 2 Command BO 1 | Status of the CO2 command for Binary Output 1 | Write | 0=No, 1=Yes | |
| BV | 41 | Cfg VOC Command BO 1 | Status of the VOC command for Binary Output 1 | Write | 0=No, 1=Yes | |
| BV | 42 | Cfg FAN Command BO 1 | Status of the fan command for Binary Output 1 | Write | 0=No, 1=Yes | |
| BV | 43 | Cfg Cooling Command BO 2 | Status of the cooling command for Binary Output 2 | Write | 0=No, 1=Yes | |
| BV | 44 | Cfg Heating Command BO 2 | Status of the heating command for Binary Output 2 | Write | 0=No, 1=Yes | |
| BV | 45 | Cfg Dehumidification Command BO 2 | Status of the dehumidification command for Binary Output 2 | Write | 0=No, 1=Yes | |
| BV | 46 | Cfg Humidification Command BO 2 | Status of the humidification command for Binary Output 2 | Write | 0=No, 1=Yes | |
| BV | 47 | Cfg CO 2 Command BO 2 | Status of the CO2 command for Binary Output 2 | Write | 0=No, 1=Yes | |
| BV | 48 | Cfg VOC Command BO 2 | Status of the VOC command for Binary Output 2 | Write | 0=No, 1=Yes | |
| BV | 49 | Cfg FAN Command BO 2 | Status of the fan command for Binary Output 2 | Write | 0=No, 1=Yes | |
| MVmin | 1 | User main system mode | Actual mode selected | Write | Off On | |
| MVmin | 2 | User Temp system mode | Status of the actual temperature system mode | Write | Off Cool Auto Heat | |
| MV | 3 | User Humidity system mode | Status of the actual humidity system mode | Write | Off Dehumidification Auto Humidification | |
| MV | 4 | User CO 2 system mode | Status of the actual CO2 system mode | Write | Off On | |
| MV | 5 | User VOC system mode | Status of the actual VOC system mode | Write | Off On | |
| MV | 6 | User FAN system mode | Status of the actual FAN system mode | Write | Off Auto On | |
| MV | 7 | Cfg Object list mode | Set the Object list mode | Write | Integrator Advanced Factory | |
| MV | 8 | Cfg AO 1 Control Mode | Set the Analog Output 1 control mode | Write | Highest Average | |
| MV | 9 | Cfg AO 2 Control Mode | Set the Analog Output 2 control mode | Write | Highest Average | |
| MV | 12 | Cfg BO 1 Control Mode | Set the Binary Output 1 control mode | Write | Highest Average | |
| MV | 13 | Cfg BO 2 Control Mode | Set the Binary Output 2 control mode | Write | Highest Average | |
| MV | 14 | Cfg AO 1 DA/RA Mode | Set the directions from 'Direct Mode' and 'Reverse Mode' for Analog Output | Write | Direct mode Reverse Mode | |
| MV | 15 | Cfg AO 2 DA/RA Mode | Set the directions from 'Direct Mode' and 'Reverse Mode' for Analog Output | Write | Direct mode Reverse Mode | |
| MV | 16 | Cfg BO 1 NO/NC Mode | Set the direction 'Normally Close (NC)' and 'Normally Open (NO)' for Binary | Write | NC mode NO Mode | |
| MV | 17 | Cfg BO 2 NO/NC Mode | Set the direction 'Normally Close (NC)' and 'Normally Open (NO)' for Binary | Write | NC mode NO Mode | |
| MV | 18 | Cfg AI 1 config | Select the input signal type for Analog Input 1 (AI1) | Write | Off OAT Sensor Occupancy Night Setback Dirty Filter Air Flow Switch Air Flow Lockout | |
| MV | 19 | Cfg BI 1 config | Select the input signal type for Binary Input 1 (BI1) | Write | Off Occupancy Night Setback Dirty Filter Air Flow Switch Air Flow Lockout | |
| MV | 21 | Cfg Local unit | Set the desired unit of the displayed value on the device | Write | Metric Imperial | |
| MV | 22 | Cfg Network unit | Set the displayed value on BACnet | Write | Metric Imperial | |
| MV | 23 | Cfg Application Profile | Set the desired application profile | Write | No Profile Temp Only Temp, RH, and CO2 | |
| MV | 24 | Cfg BO 1 TPM/Hysteresis Mode | Set the binary output 1 type from the options: Hysteresis and TPM | Write | TPM Mode Hysteresis Mode | |
| MV | 25 | Cfg BO 2 TPM/Hysteresis Mode | Binary output 2 type: hysteresis or TPM | Write | TPM Mode Hysteresis Mode | |
| MV | 26 | Cfg BO 1 TPM CPH | Binary output 1 TPM cycles per hour | Write | TPM CPH 8 TPM CPH 4 TPM CPH 3 | |
| MV | 27 | Cfg BO 2 TPM CPH | Binary output 2 TPM cycles per hour | Write | TPM CPH 8 TPM CPH 4 TPM CPH 3 | |
| MV | 28 | Status Relay 1 | Status value that represents the actual relay state of Binary Output 1 | Read | Off Set Reset | |
| MV | 29 | Status Relay 2 | Status value that represents the actual relay state of Binary Output 2 | Read | Off Set Reset |
No points match these filters.
Object ID lookup: Neptronic AROB universal room / IAQ controller point IDs by name
AI3Status AI 1 mVAI4Status PCB Temp mVAI5Status Micro Temp mVAO1Status AO.1AO2Status AO.2AV1User Cooling SetpointAV2User Heating SetpointAV3User Dehumidification SetpointAV4User Humidification SetpointAV5User Cooling Unocc SetpointAV6User Heating Unocc SetpointAV7User CO2 SetpointAV8User VOC SetpointAV9Status CO2 levelAV10Status Temp levelAV11Status Humidity levelAV13Status VOC LevelAV14Status Outdoor Temp levelAV15Status EnthalpyAV16Status Dew PointAV17Status Cooling DemandAV18Status Heating DemandAV19Status Dehumidification DemandAV20Status Humidification DemandAV21Status CO2 DemandAV22Status VOC DemandAV23Status AO 1 DemandAV24Status AO 2 DemandAV25Status BO 1 DemandAV26Status BO 2 DemandAV27Cfg CO2 calibrationAV28Cfg VOC calibrationAV29Cfg Temp calibrationAV30Cfg Humidity calibrationAV32Cfg Outdoor Temp calibrationAV33Cfg AO 1 Min ValueAV34Cfg AO 1 Max ValueAV35Cfg AO 2 Min ValueAV36Cfg AO 2 Max ValueAV37Cfg AO1 Hi OAT LockoutAV38Cfg AO1 Low OAT LockoutAV39Cfg AO2 Hi OAT LockoutAV40Cfg AO2 Low OAT LockoutAV41Cfg BO1 Hi OAT LockoutAV42Cfg BO1 Low OAT LockoutAV43Cfg BO2 Hi OAT LockoutAV44Cfg BO2 Low OAT LockoutAV45Cfg BO 1 Anti Cycle TimerAV46Cfg BO 2 Anti Cycle TimerAV53Cfg FAN ON SpeedAV54Cfg BO 1 Hysteresis Low LimitAV55Cfg BO 1 Hysteresis Hi LimitAV56Cfg BO 2 Hysteresis Low LimitAV57Cfg BO 2 Hysteresis Hi LimitAV58Status Board Temp levelAV59Status Micro Temp levelAV60Cfg Cooling P BandAV61Cfg Cooling I TimeAV62Cfg Heating P BandAV63Cfg Heating I TimeAV64Cfg Humidity P BandAV65Cfg Humidity I TimeAV66Cfg CO2 P BandAV67Cfg CO2 I TimeAV68Cfg VOC P BandAV69Cfg VOC I TimeAV70Cfg Cooling setpoint minAV71Cfg Cooling setpoint maxAV72Cfg Cooling Unocc setpoint minAV73Cfg Cooling Unocc setpoint maxAV74Cfg Heating Setpoint minAV75Cfg Heating Setpoint maxAV76Cfg Heating Unocc Setpoint minAV77Cfg Heating Unocc Setpoint maxAV78Cfg Dehumidification Setpoint minAV79Cfg Dehumidification Setpoint maxAV80Cfg Humidification Setpoint minAV81Cfg Humidification Setpoint maxAV82Cfg CO2 Setpoint minAV83Cfg CO2 Setpoint maxAV84Cfg VOC Setpoint minAV85Cfg VOC Setpoint maxAV88Cfg CO2 Sensor Calibration PeriodAV89Cfg Board Temp calibrationAV90Cfg Micro Temp calibrationAV91Cfg Temp DeadbandAV92Cfg Humidity DeadbandAV93Status AO 1 mVAV94Status AO 2 mVBI1Status BI 1BI2Status Programing ModeBI3Status Production ModeBO1Status BO 1BO2Status BO 2BV1Status Occupancy StatusBV2Status AO 1 OAT LockoutBV3Status AO 2 OAT LockoutBV4Status BO 1 OAT LockoutBV5Status BO 2 OAT LockoutBV6Status Dirty filter StatusBV7Status Air Flow Switch StatusBV8Status Air Flow Lockout StatusBV9CfgDisplayCO2LevelBV10CfgDisplay VOCLevelBV11CfgDisplayTempLevelBV12CfgDisplayHumidityLevelBV16Cfg Enable BacklightBV17Cfg Enable Auto- ScrollBV18Cfg Key Pad Upper Left LockBV19Cfg Key Pad Bottom Left LockBV20Cfg Key Pad Arrows LockBV21Cfg Program Mode LockBV22Cfg Cooling Command AO 1BV23Cfg Heating Command AO 1BV24Cfg Dehumidification Command AO 1BV25Cfg Humidification Command AO 1BV26Cfg CO 2 Command AO 1BV27Cfg VOC Command AO 1BV28Cfg FAN Command AO 1BV29Cfg Cooling Command AO 2BV30Cfg Heating Command AO 2BV31Cfg Dehumidification Command AO 2BV32Cfg Humidification Command AO 2BV33Cfg CO 2 Command AO 2BV34Cfg VOC Command AO 2BV35Cfg FAN Command AO 2BV36Cfg Cooling Command BO 1BV37Cfg Heating Command BO 1BV38Cfg Dehumidification Command BO 1BV39Cfg Humidification Command BO 1BV40Cfg CO 2 Command BO 1BV41Cfg VOC Command BO 1BV42Cfg FAN Command BO 1BV43Cfg Cooling Command BO 2BV44Cfg Heating Command BO 2BV45Cfg Dehumidification Command BO 2BV46Cfg Humidification Command BO 2BV47Cfg CO 2 Command BO 2BV48Cfg VOC Command BO 2BV49Cfg FAN Command BO 2MV1User main system modeMV2User Temp system modeMV3User Humidity system modeMV4User CO 2 system modeMV5User VOC system modeMV6User FAN system modeMV7Cfg Object list modeMV8Cfg AO 1 Control ModeMV9Cfg AO 2 Control ModeMV12Cfg BO 1 Control ModeMV13Cfg BO 2 Control ModeMV14Cfg AO 1 DA/RA ModeMV15Cfg AO 2 DA/RA ModeMV16Cfg BO 1 NO/NC ModeMV17Cfg BO 2 NO/NC ModeMV18Cfg AI 1 configMV19Cfg BI 1 configMV21Cfg Local unitMV22Cfg Network unitMV23Cfg Application ProfileMV24Cfg BO 1 TPM/Hysteresis ModeMV25Cfg BO 2 TPM/Hysteresis ModeMV26Cfg BO 1 TPM CPHMV27Cfg BO 2 TPM CPHMV28Status Relay 1MV29Status Relay 2
Integration notes
- Multistate state texts are listed as printed in the guide (option names in order, without numbers).
- MSV.7 Cfg Object list mode (Integrator, Advanced, Factory) changes which objects are visible.
- Sensor values can be overridden with Out_of_Service where the W? column says so.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AROB universal room / IAQ controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Neptronic AROB universal room / IAQ controller
How many BACnet points does the Neptronic AROB universal room / IAQ controller have?
This list has 166 BACnet objects: 3 analog inputs, 2 analog outputs, 84 analog values, 3 binary inputs, 2 binary outputs, 46 binary values, 26 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Neptronic AROB universal room / IAQ controller BACnet points are writable?
129 of the 166 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Neptronic AROB universal room / IAQ controller BACnet documentation?
The source is AROB BACnet Guide (AROB-BACnet Guide_170920), revision 2017-09-20, published free by Neptronic at https://www.neptronic.com/Controls/IAQController/PDF/AROB-BACnet%20Guide_170920.pdf.
What are the minimum BACnet points to integrate the Neptronic AROB universal room / IAQ controller?
Start with MV 1 User main system mode (Controller off or on); MV 2 User Temp system mode (Temperature mode: off, cool, auto, heat); AV 1 User Cooling Setpoint (Occupied cooling setpoint); AV 2 User Heating Setpoint (Occupied heating setpoint); AV 10 Status Temp level (Room temperature); AV 11 Status Humidity level (Room relative humidity); AV 9 Status CO2 level (Room CO2, ppm); AV 17 Status Cooling Demand (Cooling demand, %); AV 18 Status Heating Demand (Heating demand, %); BV 7 Status Air Flow Switch Status (Airflow alarm).
How do I enable BMS control of the Neptronic AROB universal room / IAQ controller?
MSV.1 User main system mode turns the controller off or on; MSV.2-MSV.6 set the temperature, humidity, CO2, VOC and fan modes.
How do I check these points on the real AROB universal room / IAQ controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Neptronic BACnet points lists
- Make-up air unit (electric heat)
Neptronic CMU Compact Make-up Air Unit
Neptronic CMU compact make-up air units with electric heating, EC fan, damper and optional exhaust fan outputs.
Also known as: CMU, Neptronic CMU - Fan coil unit controller
Neptronic EFCB Series Fan Coil Controller
Neptronic EFCB fan coil controllers (24, 120 or 240 Vac, 2 or 4 relays) for 2-pipe and 4-pipe fan coils with TFL/TDF room sensors.
Also known as: EFCB, EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4 - Fan coil unit controller
Neptronic EFCB-OE1 Series Fan Coil Controller
Neptronic EFCB-OE1 fan coil controllers (24 or 240 Vac, 0, 2 or 4 relays), an OEM variant of the EFCB series.
Also known as: EFCB-OE1, EFCB10T-OE1, EFCB12T-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1 - VAV terminal unit controller
Neptronic EVCB14N Series VAV Controller
Neptronic EVCB14N networkable VAV controllers with integrated damper actuator, pressure-independent or pressure-dependent, with 0-4 triac outputs.
Also known as: EVCB14N, EVCB14NIT0S, EVCB14NIT2S, EVCB14NIT4S, EVCB14NDT4S, EVCB14NIT0SF, EVCB14NIT4SF - VAV terminal unit controller
Neptronic EVCB14NxT4X VAV Controller (external motor)
Neptronic EVCB14N VAV controllers with four triac outputs that drive an external damper motor, pressure independent (IT4X) or dependent (DT4X).
Also known as: EVCB14NxT4X, EVCB14NIT4X, EVCB14NDT4X - VAV terminal unit controller
Neptronic EVCB44N Series VAV Controller
Neptronic EVCB44N VAV controllers without triac outputs, pressure independent (IT0S) or pressure dependent (DT0S).
Also known as: EVCB44N, EVCB44NIT0S, EVCB44NDT0S - Dual duct VAV terminal controller
Neptronic EVCBM Dual Duct VAV Controller
Neptronic EVCBM master controller used on dual duct terminals, with a second (slave) airflow channel for the other duct.
Also known as: EVCBM, EVCBM Dual Duct, EVCB dual duct - Electric duct heater / terminal reheat controller
Neptronic HECB electric duct heater controller
Neptronic electric duct heaters fitted with the HECB intelligent controller (staged and SSR, with optional EAS airflow sensing).
Also known as: HECB, HEC, Neptronic HECB, electric duct heater controller - Electric steam humidifier
Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module
Legacy Neptronic SK300 and SKE electric steam humidifiers fitted with the NEPIC BACnet MS/TP communication module.
Also known as: SK300, SKE, Neptronic SK300, Neptronic SKE, NEPIC, SK300-BACNET, SKE-BACNET - Steam humidifier valve controller
Neptronic SKDESC-xB
Neptronic SKDESC-xB electronic controllers for steam-to-steam / direct steam injection humidifier valves (ESCJx jacketed, ESCMx models).
Also known as: SKDESC, SKDESCxB, ESCJx, ESCMx, Electronic Steam Controller - Electric steam humidifier
Neptronic SKE4
Neptronic SKE4 electric (heating element) steam humidifiers, indoor and outdoor versions.
Also known as: SKE4 electric steam humidifier, SKE4-N, SKE4-E, SKE4 BACnet - Gas-fired steam humidifier
Neptronic SKG4
Neptronic SKG4 gas-fired steam humidifiers with up to four humidifier modules.
Also known as: SKG4 gas fired humidifier, SKG4-N, SKG4-E, SKG4 BACnet - High-pressure atomizing humidifier / cooler
Neptronic SKH4
Neptronic SKH4 high-pressure water atomizing humidifiers and evaporative coolers with up to six zones (A-F).
Also known as: SKH4 high-pressure atomizer, SKH4 BACnet - Reverse osmosis water treatment unit
Neptronic SKRO
Neptronic SKRO reverse osmosis water treatment units feeding humidifiers.
Also known as: SKRO reverse osmosis, SKRO BACnet - Steam-to-steam humidifier
Neptronic SKS4
Neptronic SKS4 steam-to-steam (boiler steam heated) humidifiers.
Also known as: SKS4 steam to steam humidifier, SKS4 BACnet - Evaporative humidifier
Neptronic SKV
Neptronic SKV evaporative (media) humidifiers with up to four modules.
Also known as: SKV evaporative humidifier, SKV BACnet - Evaporative cooler / humidifier
Neptronic SKVF
Neptronic SKVF series evaporative coolers (also used for humidification).
Also known as: SKVF evaporative cooler, SKVF Series, SKVF BACnet - Fan coil / zone thermostat controller
Neptronic TFxB Series Thermostat Controller
Neptronic TFxB24 communicating thermostats for 2-pipe and 4-pipe fan coils and zone heating/cooling, including the humidity (TFHB) and OE variants.
Also known as: TFCB24F3XYZ1, TFCB24F3XY2, TFHB24F3XYZ1, TFHB24F3XYZ2, TFCB24P3-OE1, TFHB24P3-OE1, TFHB24P3-OE2, TFxB24 - Zone thermostat controller (VAV / fan coil)
Neptronic TROB24 thermostat controller
Neptronic TROB24 communicating thermostats with universal inputs, analog outputs and triac (on/off, pulsing or floating) outputs.
Also known as: TROB24, TROB, TROB24T4, Neptronic TROB - Fan coil / zone thermostat controller
Neptronic TSUB universal wall-mount controller
Neptronic TSUB universal wall-mount controllers for fan coils, heat pumps and zone heating/cooling.
Also known as: TSUB, TSUB24, Neptronic TSUB - Fan coil / zone thermostat controller
Neptronic TUCB / TUHB universal controller (TUxB24C6X2)
Neptronic TUCB (cooling/heating) and TUHB (with humidity) universal room controllers, model TUxB24C6X2.
Also known as: TUCB, TUHB, TUxB24C6X2, TUCB24C6X2, TUHB24C6X2 - Fan coil / zone thermostat controller
Neptronic TUUB universal wall-mount controller
Neptronic TUUB universal wall-mount controllers for fan coils, heat pumps, VFDs and zone heating/cooling.
Also known as: TUUB, TUUB24, Neptronic TUUB
Source: AROB BACnet Guide · AROB-BACnet Guide_170920 · rev. 2017-09-20. Object names, instances and units are reproduced as published; descriptions are our own.