Room / indoor air quality controller (temperature, humidity, CO2, VOC) · BACnet points list

Neptronic AROB universal room / IAQ controller BACnet points list

Updated 6 November 2026

Short answer

AROB is a wall-mount room controller for temperature, humidity, CO2 and VOC with BACnet MS/TP. The BACnet guide lists 166 objects: user system modes and setpoints, sensor readings, calculated enthalpy and dew point, demands per function and output, OAT and airflow lockout and filter alarms, and configuration objects for the outputs and inputs.

This page lists 166 BACnet objects for the Neptronic AROB universal room / IAQ controller — 129 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
AROB universal room / IAQ controller
Equipment
Room / indoor air quality controller (temperature, humidity, CO2, VOC)
Equipment type
Thermostats, sensors & meters
BACnet objects
166 (129 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
153000 + MAC address
Also known as
AROB, AROB24, Neptronic AROB, IAQ controller
Source document
AROB BACnet Guide · AROB-BACnet Guide_170920 · rev. 2017-09-20
Download CSV 166 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.

BMS integration notes: Neptronic AROB universal room / IAQ controller

Integration in brief

Turn the controller on with MSV.1, pick the temperature mode with MSV.2 and write the cooling/heating setpoints AV.1/AV.2. Read AV.10 temperature, AV.11 humidity, AV.9 CO2, the demands and the filter/airflow alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1User main system modeController off or onWrite
MV 2User Temp system modeTemperature mode: off, cool, auto, heatWrite
AV 1User Cooling SetpointOccupied cooling setpointWrite
AV 2User Heating SetpointOccupied heating setpointWrite
AV 10Status Temp levelRoom temperatureRead
AV 11Status Humidity levelRoom relative humidityRead
AV 9Status CO2 levelRoom CO2, ppmRead
AV 17Status Cooling DemandCooling demand, %Read
AV 18Status Heating DemandHeating demand, %Read
BV 7Status Air Flow Switch StatusAirflow alarmRead

Enable & remote start

MSV.1 User main system mode turns the controller off or on; MSV.2-MSV.6 set the temperature, humidity, CO2, VOC and fan modes.

Network setup

Watch out for

Neptronic AROB universal room / IAQ controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

166 of 166 shown
Type
Multi-state
Access
Show
Neptronic AROB universal room / IAQ controller BACnet Points List
DescriptionStates
AI3Status AI 1 mVSensor reading value on analog input 1 in millivoltsmVRead
AI4Status PCB Temp mVTemperature of the printed circuit board in millivoltsmVRead
AI5Status Micro Temp mVMeasured temperature of the on-board microprocessor in millivoltsmVRead
AO1Status AO.1Status value that represents the modulation percentage of analog output 1 based%Command
AO2Status AO.2Status value that represents the modulation percentage of analog output 2 based%Command
AVmin1User Cooling SetpointSet the actual user cooling setpoint of the zone in the operation°F/°CWrite
AVmin2User Heating SetpointSet the actual user heating setpoint of the zone in the operation°F/°CWrite
AV3User Dehumidification SetpointZone dehumidification setpoint%RHWrite
AV4User Humidification SetpointSet the actual user humidification setpoint of the zone in operation mode%RHWrite
AV5User Cooling Unocc SetpointSet the actual user cooling setpoint of the zone in unoccupied operation°F/°CWrite
AV6User Heating Unocc SetpointSet the actual user heating setpoint of the zone in unoccupied operation°F/°CWrite
AV7User CO2 SetpointUser CO2 setpoint in parts per million (PPM) at which the outsideppmWrite
AV8User VOC SetpointVOC setpointWrite
AVmin9Status CO2 levelStatus of the carbon dioxide sensor (CO2)ppmRead
AVmin10Status Temp levelInternal temperature sensor reading°F/°CRead
AVmin11Status Humidity levelHumidity sensor reading%RHRead
AV13Status VOC LevelVOC sensor readingRead
AV14Status Outdoor Temp levelOutdoor temperature°F/°CRead
AV15Status EnthalpyCalculated enthalpyRead
AV16Status Dew PointCalculated dew point°F/°CRead
AVmin17Status Cooling DemandStatus value of the cooling demand%Read
AVmin18Status Heating DemandStatus value that represents the heating demand%Read
AV19Status Dehumidification DemandStatus value that represents the dehumidification percentage based on relative humidity%Read
AV20Status Humidification DemandStatus value that represents the humidifier modulation based on relative humidity%Read
AV21Status CO2 DemandStatus value that represents the CO2 demand based on CO2 level%Read
AV22Status VOC DemandStatus value that represents the VOC demand based on VOC level%Read
AV23Status AO 1 DemandStatus of the value of analog output 1 value in percentage based%Read
AV24Status AO 2 DemandStatus of the value of analog output 2 value in percentage based%Read
AV25Status BO 1 DemandStatus of the value of binary output 1 value in percentage based%Read
AV26Status BO 2 DemandStatus of the value of binary output 2 value in percentage based%Read
AV27Cfg CO2 calibrationConfiguration value applied to the displayed CO2 level reading that is usedppmWrite
AV28Cfg VOC calibrationConfiguration value applied to the displayed VOC level reading that is usedWrite
AV29Cfg Temp calibrationConfiguration value applied to the displayed temperature level reading that is used°F/°CWrite
AV30Cfg Humidity calibrationConfiguration value applied to the displayed humidity level reading that is used%RHWrite
AV32Cfg Outdoor Temp calibrationCalibration offset for the outdoor air temperature reading°F/°CWrite
AV33Cfg AO 1 Min ValueDesired minimum voltage (“zero” value) for analog output 1VWrite
AV34Cfg AO 1 Max ValueDesired maximum voltage (“span” value) for analog output 1VWrite
AV35Cfg AO 2 Min ValueSelect the desired minimum voltage (“zero” value) for analog output 2VWrite
AV36Cfg AO 2 Max ValueSelect the desired maximum voltage (“span” value) for analog output 2VWrite
AV37Cfg AO1 Hi OAT LockoutSelect the desired high temperature limit for outside air temperature on analog°F/°CWrite
AV38Cfg AO1 Low OAT LockoutSelect the desired low teperature limit for outside air temperature on analog°F/°CWrite
AV39Cfg AO2 Hi OAT LockoutSelect the desired high temperature limit for outside air temperature on analog°F/°CWrite
AV40Cfg AO2 Low OAT LockoutSelect the desired low teperature limit for outside air temperature on analog°F/°CWrite
AV41Cfg BO1 Hi OAT LockoutSelect the desired high temperature limit for outside air temperature on binary°F/°CWrite
AV42Cfg BO1 Low OAT LockoutSelect the desired low teperature limit for outside air temperature on binary°F/°CWrite
AV43Cfg BO2 Hi OAT LockoutSelect the desired high temperature limit for outside air temperature on binary°F/°CWrite
AV44Cfg BO2 Low OAT LockoutSelect the desired low teperature limit for outside air temperature on binary°F/°CWrite
AV45Cfg BO 1 Anti Cycle TimerBinary output 1 anti-cycle delay, secondssWrite
AV46Cfg BO 2 Anti Cycle TimerBinary output 2 anti-cycle delay, secondssWrite
AV53Cfg FAN ON SpeedMinimum fan speed when the fan system mode is on%Write
AV54Cfg BO 1 Hysteresis Low LimitDesired binary output 1 hysteresis low percentage%Write
AV55Cfg BO 1 Hysteresis Hi LimitDesired binary output 1 hysteresis high percentage%Write
AV56Cfg BO 2 Hysteresis Low LimitDesired binary output 2 hysteresis low percentage%Write
AV57Cfg BO 2 Hysteresis Hi LimitDesired binary output 2 hysteresis high percentage%Write
AV58Status Board Temp levelTemperature of printed circuit board°F/°CRead
AV59Status Micro Temp levelMeasured temperature of the on-board microprocessor°F/°CRead
AV60Cfg Cooling P BandDesired proportional band value for the cooling ramp°F/°CWrite
AV61Cfg Cooling I TimeTime for cooling integral factor compensationsWrite
AV62Cfg Heating P BandDesired proportional band value of the heating ramp°F/°CWrite
AV63Cfg Heating I TimeDesired time for heating integral factor compensationsWrite
AV64Cfg Humidity P BandDesired proportional band value of the dehumidification and humidification ramps%RHWrite
AV65Cfg Humidity I TimeDesired value for humidification integral factor compensation of the dehumidification and humidificationsWrite
AV66Cfg CO2 P BandDesired proportional band value of the CO2 rampppmWrite
AV67Cfg CO2 I TimeDesired value for CO2 integral factor compensationsWrite
AV68Cfg VOC P BandDesired proportional band value of the VOC rampWrite
AV69Cfg VOC I TimeDesired value for VOC integral factor compensationsWrite
AV70Cfg Cooling setpoint minMinimum cooling setpoint°F/°CWrite
AV71Cfg Cooling setpoint maxMaximum cooling setpoint°F/°CWrite
AV72Cfg Cooling Unocc setpoint minMinimum cooling setpoint value used during no occupancy°F/°CWrite
AV73Cfg Cooling Unocc setpoint maxMaximum cooling setpoint value used during no occupancy°F/°CWrite
AV74Cfg Heating Setpoint minMinimum heating setpoint°F/°CWrite
AV75Cfg Heating Setpoint maxMaximum heating setpoint°F/°CWrite
AV76Cfg Heating Unocc Setpoint minMinimum heating setpoint value used during no occupancy°F/°CWrite
AV77Cfg Heating Unocc Setpoint maxMaximum heating setpoint value used during no occupancy°F/°CWrite
AV78Cfg Dehumidification Setpoint minValue set as the minimum dehumidification setpoint%RHWrite
AV79Cfg Dehumidification Setpoint maxValue set as the maximum dehumidification setpoint%RHWrite
AV80Cfg Humidification Setpoint minValue set as the minimum humidification setpoint%RHWrite
AV81Cfg Humidification Setpoint maxValue set as the maximum humidification setpoint%RHWrite
AV82Cfg CO2 Setpoint minValue set as the minimum CO2 setpointppmWrite
AV83Cfg CO2 Setpoint maxValue set as the maximum CO2 setpointppmWrite
AV84Cfg VOC Setpoint minValue set as the minimum VOC setpointWrite
AV85Cfg VOC Setpoint maxValue set as the maximum VOC setpointWrite
AV88Cfg CO2 Sensor Calibration PeriodCO2 sensor calibration period in hourshWrite
AV89Cfg Board Temp calibrationConfiguration value applied to the displayed board temperature reading that is used°F/°CWrite
AV90Cfg Micro Temp calibrationConfiguration value applied to the displayed microcontroller temperature reading that is used°F/°CWrite
AV91Cfg Temp DeadbandTemperature deadband°F/°CWrite
AV92Cfg Humidity DeadbandHumidity deadband%RHWrite
AV93Status AO 1 mVStatus value that represents the analog output 1 in millivoltsmVRead
AV94Status AO 2 mVStatus value that represents the analog output 2 in millivoltsmVRead
BI1Status BI 1Status of the binary input 1 readingRead0=Open, 1=Close
BI2Status Programing ModeStatus of the programming mode, jumper JP3 (B and C)Read0=Open, 1=Close
BI3Status Production ModeStatus of the production mode jumper J4 (3 and 4)Read0=Open, 1=Close
BO1Status BO 1Contact status of the binary output 1Command0=Open, 1=Close
BO2Status BO 2Contact status of the binary output 2Command0=Open, 1=Close
BV1Status Occupancy StatusOccupancy status based on AI1 or BI1 set to Occupancy or NightRead0=No, 1=Yes
BV2Status AO 1 OAT LockoutOAT lockout active for analog output 1Read0=No, 1=Yes
BV3Status AO 2 OAT LockoutOAT lockout active for analog output 1Read0=No, 1=Yes
BV4Status BO 1 OAT LockoutOAT lockout active for analog output 1Read0=No, 1=Yes
BV5Status BO 2 OAT LockoutOAT lockout active for analog output 1Read0=No, 1=Yes
BV6Status Dirty filter StatusStatus value to inform if a filter change is requiredRead0=No, 1=Yes
BVmin7Status Air Flow Switch StatusStatus value to inform if an airflow alarm is activeRead0=No, 1=Yes
BV8Status Air Flow Lockout StatusStatus value to inform if an airflow lockout alarm is activeRead0=No, 1=Yes
BV9CfgDisplayCO2LevelDisplay CO2 in RUN modeWrite0=No, 1=Yes
BV10CfgDisplay VOCLevelDisplay VOC in RUN modeWrite0=No, 1=Yes
BV11CfgDisplayTempLevelDisplay Temp in RUN modeWrite0=No, 1=Yes
BV12CfgDisplayHumidityLevelDisplay %RH in RUN modeWrite0=No, 1=Yes
BV16Cfg Enable BacklightDesired status of LCD backlightWrite0=Off, 1=On
BV17Cfg Enable Auto- ScrollDesired status of the auto-scroll of sensor readings in the RUN modeWrite0=Off, 1=On
BV18Cfg Key Pad Upper Left LockLock the star (*) buttonWrite0 = Off, 1 = On If set to On, the functionality of these buttons will not be available.
BV19Cfg Key Pad Bottom Left LockLock the enter/return buttonWrite0 = Off, 1 = On If set to On, functionality of these buttons will not be available.
BV20Cfg Key Pad Arrows LockLock the arrow buttonsWrite0 = Off, 1 = On If set to On, functionality of these buttons will not be available.
BV21Cfg Program Mode LockLocks the Program Mode when the jumper JP3 is set to PGM.Write0 = Off, 1 = On If set to On, Program Mode will not be available.
BV22Cfg Cooling Command AO 1Status of the cooling command for Analog Output 1Write0=No, 1=Yes
BV23Cfg Heating Command AO 1Status of the heating command for Analog Output 1Write0=No, 1=Yes
BV24Cfg Dehumidification Command AO 1Status of the dehumidification command for Analog Output 1Write0=No, 1=Yes
BV25Cfg Humidification Command AO 1Status of the humidification command for Analog Output 1Write0=No, 1=Yes
BV26Cfg CO 2 Command AO 1Status of the CO2 command for Analog Output 1Write0=No, 1=Yes
BV27Cfg VOC Command AO 1Status of the VOC command for Analog Output 1Write0=No, 1=Yes
BV28Cfg FAN Command AO 1Status of the fan command for Analog Output 1Write0=No, 1=Yes
BV29Cfg Cooling Command AO 2Status of the cooling command for Analog Output 2Write0=No, 1=Yes
BV30Cfg Heating Command AO 2Status of the heating command for Analog Output 2Write0=No, 1=Yes
BV31Cfg Dehumidification Command AO 2Status of the dehumidification command for Analog Output 2Write0=No, 1=Yes
BV32Cfg Humidification Command AO 2Status of the humidification command for Analog Output 2Write0=No, 1=Yes
BV33Cfg CO 2 Command AO 2Status of the CO2 command for Analog Output 2Write0=No, 1=Yes
BV34Cfg VOC Command AO 2Status of the VOC command for Analog Output 2Write0=No, 1=Yes
BV35Cfg FAN Command AO 2Status of the fan command for Analog Output 2Write0=No, 1=Yes
BV36Cfg Cooling Command BO 1Status of the cooling command for Binary Output 1Write0=No, 1=Yes
BV37Cfg Heating Command BO 1Status of the heating command for Binary Output 1Write0=No, 1=Yes
BV38Cfg Dehumidification Command BO 1Status of the dehumidification command for Binary Output 1Write0=No, 1=Yes
BV39Cfg Humidification Command BO 1Status of the humidification command for Binary Output 1Write0=No, 1=Yes
BV40Cfg CO 2 Command BO 1Status of the CO2 command for Binary Output 1Write0=No, 1=Yes
BV41Cfg VOC Command BO 1Status of the VOC command for Binary Output 1Write0=No, 1=Yes
BV42Cfg FAN Command BO 1Status of the fan command for Binary Output 1Write0=No, 1=Yes
BV43Cfg Cooling Command BO 2Status of the cooling command for Binary Output 2Write0=No, 1=Yes
BV44Cfg Heating Command BO 2Status of the heating command for Binary Output 2Write0=No, 1=Yes
BV45Cfg Dehumidification Command BO 2Status of the dehumidification command for Binary Output 2Write0=No, 1=Yes
BV46Cfg Humidification Command BO 2Status of the humidification command for Binary Output 2Write0=No, 1=Yes
BV47Cfg CO 2 Command BO 2Status of the CO2 command for Binary Output 2Write0=No, 1=Yes
BV48Cfg VOC Command BO 2Status of the VOC command for Binary Output 2Write0=No, 1=Yes
BV49Cfg FAN Command BO 2Status of the fan command for Binary Output 2Write0=No, 1=Yes
MVmin1User main system modeActual mode selectedWriteOff On
MVmin2User Temp system modeStatus of the actual temperature system modeWriteOff Cool Auto Heat
MV3User Humidity system modeStatus of the actual humidity system modeWriteOff Dehumidification Auto Humidification
MV4User CO 2 system modeStatus of the actual CO2 system modeWriteOff On
MV5User VOC system modeStatus of the actual VOC system modeWriteOff On
MV6User FAN system modeStatus of the actual FAN system modeWriteOff Auto On
MV7Cfg Object list modeSet the Object list modeWriteIntegrator Advanced Factory
MV8Cfg AO 1 Control ModeSet the Analog Output 1 control modeWriteHighest Average
MV9Cfg AO 2 Control ModeSet the Analog Output 2 control modeWriteHighest Average
MV12Cfg BO 1 Control ModeSet the Binary Output 1 control modeWriteHighest Average
MV13Cfg BO 2 Control ModeSet the Binary Output 2 control modeWriteHighest Average
MV14Cfg AO 1 DA/RA ModeSet the directions from 'Direct Mode' and 'Reverse Mode' for Analog OutputWriteDirect mode Reverse Mode
MV15Cfg AO 2 DA/RA ModeSet the directions from 'Direct Mode' and 'Reverse Mode' for Analog OutputWriteDirect mode Reverse Mode
MV16Cfg BO 1 NO/NC ModeSet the direction 'Normally Close (NC)' and 'Normally Open (NO)' for BinaryWriteNC mode NO Mode
MV17Cfg BO 2 NO/NC ModeSet the direction 'Normally Close (NC)' and 'Normally Open (NO)' for BinaryWriteNC mode NO Mode
MV18Cfg AI 1 configSelect the input signal type for Analog Input 1 (AI1)WriteOff OAT Sensor Occupancy Night Setback Dirty Filter Air Flow Switch Air Flow Lockout
MV19Cfg BI 1 configSelect the input signal type for Binary Input 1 (BI1)WriteOff Occupancy Night Setback Dirty Filter Air Flow Switch Air Flow Lockout
MV21Cfg Local unitSet the desired unit of the displayed value on the deviceWriteMetric Imperial
MV22Cfg Network unitSet the displayed value on BACnetWriteMetric Imperial
MV23Cfg Application ProfileSet the desired application profileWriteNo Profile Temp Only Temp, RH, and CO2
MV24Cfg BO 1 TPM/Hysteresis ModeSet the binary output 1 type from the options: Hysteresis and TPMWriteTPM Mode Hysteresis Mode
MV25Cfg BO 2 TPM/Hysteresis ModeBinary output 2 type: hysteresis or TPMWriteTPM Mode Hysteresis Mode
MV26Cfg BO 1 TPM CPHBinary output 1 TPM cycles per hourWriteTPM CPH 8 TPM CPH 4 TPM CPH 3
MV27Cfg BO 2 TPM CPHBinary output 2 TPM cycles per hourWriteTPM CPH 8 TPM CPH 4 TPM CPH 3
MV28Status Relay 1Status value that represents the actual relay state of Binary Output 1ReadOff Set Reset
MV29Status Relay 2Status value that represents the actual relay state of Binary Output 2ReadOff Set Reset
Object ID lookup: Neptronic AROB universal room / IAQ controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AROB universal room / IAQ controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic AROB universal room / IAQ controller

How many BACnet points does the Neptronic AROB universal room / IAQ controller have?

This list has 166 BACnet objects: 3 analog inputs, 2 analog outputs, 84 analog values, 3 binary inputs, 2 binary outputs, 46 binary values, 26 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic AROB universal room / IAQ controller BACnet points are writable?

129 of the 166 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic AROB universal room / IAQ controller BACnet documentation?

The source is AROB BACnet Guide (AROB-BACnet Guide_170920), revision 2017-09-20, published free by Neptronic at https://www.neptronic.com/Controls/IAQController/PDF/AROB-BACnet%20Guide_170920.pdf.

What are the minimum BACnet points to integrate the Neptronic AROB universal room / IAQ controller?

Start with MV 1 User main system mode (Controller off or on); MV 2 User Temp system mode (Temperature mode: off, cool, auto, heat); AV 1 User Cooling Setpoint (Occupied cooling setpoint); AV 2 User Heating Setpoint (Occupied heating setpoint); AV 10 Status Temp level (Room temperature); AV 11 Status Humidity level (Room relative humidity); AV 9 Status CO2 level (Room CO2, ppm); AV 17 Status Cooling Demand (Cooling demand, %); AV 18 Status Heating Demand (Heating demand, %); BV 7 Status Air Flow Switch Status (Airflow alarm).

How do I enable BMS control of the Neptronic AROB universal room / IAQ controller?

MSV.1 User main system mode turns the controller off or on; MSV.2-MSV.6 set the temperature, humidity, CO2, VOC and fan modes.

How do I check these points on the real AROB universal room / IAQ controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.