Easy BACnet
  1. Home
  2. BACnet points lists
  3. Neptronic
  4. TUUB universal wall-mount controller

Fan coil / zone thermostat controller · BACnet points list

Neptronic TUUB universal wall-mount controller BACnet points list

Updated 6 November 2026

Short answer

A wall-mount universal room controller with configurable inputs and outputs that speaks BACnet MS/TP. The BACnet guide lists 276 objects: inputs and outputs, mode, fan and occupancy commands, setpoints, demands per ramp, alarms and a large set of Cfg_ configuration objects. Which outputs and modes are used depends on how the ramps and inputs are configured.

This page lists 276 BACnet objects for the Neptronic TUUB universal wall-mount controller — 232 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
TUUB universal wall-mount controller
Equipment
Fan coil / zone thermostat controller
Equipment type
VAV boxes & fan coils
BACnet objects
276 (232 writable)
Transport
BACnet MS/TP
Firmware
Firmware 1.13, application 1.06
Default device instance
153000 + MAC address
Also known as
TUUB, TUUB24, Neptronic TUUB
Source document
TUUB BACnet Guide · TUUB-BACnet Guide-250829 (V1.13) · rev. 2025-08-29
Download CSV 276 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.

BMS integration notes: Neptronic TUUB universal wall-mount controller

Integration in brief

Command occupancy with MSV.13 NsbOccCommand, the mode with MSV.1 and the fan with MSV.2, and write the setpoint to AV.9. To feed the room temperature from the BMS, set MSV.21 to Network and keep writing AV.1 ControlTemp within the AV.2 timeout. Read MSV.14, AV.1, the ramp demands and the AL_ alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 13NsbOccCommandBMS occupancy command: local, off, occupied, unoccupiedCommand
MV 1SystemModeMode: auto, heating, cooling, fan, offWrite
MV 2UserFanSpeedSelectFan speed: auto, low, medium, highWrite
AV 9TempSetPointOccupied/day temperature setpointCommand
MV 14OccupancyStatusActual occupancy incl. overrideRead
AV 1ControlTempTemperature used for controlCommand
AV 20Heating1DemandHeating ramp 1 demand, %Read
AV 35Cooling1DemandCooling ramp 1 demand, %Read
BV 37AL_FlowSwitchAirflow alarmRead
BV 36AL_ DirtyFilterFilter change requiredRead

Enable & remote start

MSV.13 NsbOccCommand: Locally lets the controller follow its occupancy input; the other states force off, occupied/day or unoccupied/night from the BMS.

Heartbeat & communication loss

With MSV.21 Cfg_TempControlSource = Network, the BMS must keep writing AV.1 ControlTemp; if nothing arrives for AV.2 Cfg_NetworkTimeOut (0-60 min) the controller goes to OFF and AV.1 shows 999 °C in fault. With AV.2 = 0, AV.1 resets to the AV.9 setpoint.

Sensors & values from the BMS

Set MSV.21 Cfg_TempControlSource to Network (1) and write the room temperature to AV.1 ControlTemp (commandable).

Network setup

Watch out for

Neptronic TUUB universal wall-mount controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

276 of 276 shown
Type
Multi-state
Access
Show
Neptronic TUUB universal wall-mount controller BACnet Points List
DescriptionStates
AI1AnalogInput1Sensor reading value on analog input 1VRead
AI2AnalogInput2Sensor reading value on analog input 2VRead
AI3AnalogInput3Sensor reading value on analog input 3VRead
AI4AnalogInput4Sensor reading value on analog input 4VRead
AI7InternTempInternal temp sensor value (ITS) of the integrated sensor°F/°CRead
AI8InternHumidityHumidity reading of on board humidity sensor%RHRead
AI9LightIntensityInternal light sensor reading in LuxesRead
AI10InternVOCSensorInternal VOC sensor reading in mg/m3Read
AI11InternCO2SensorInternal CO2 sensor reading in PPMppmRead
AO1AnalogOutput1Percentage value of analog output 1, based on demand%Write
AO2AnalogOutput2Percentage value of analog output 2, based on demand%Write
AO3AnalogOutput3Percentage value of analog output 3, based on demand%Write
AO4AnalogOutput4Percentage value of analog output 4, based on demand%Write
AVmin1ControlTempTemperature value that is used to calculate demand°F/°CCommand
AV2Cfg_NetworkTimeOutConfiguration time valueminWrite
AV3ExternTempExtern temperature sensor (ETS)°F/°CRead
AV4ChangeOverTempChangeover temperature sensor (SENs)°F/°CRead
AV5Cfg_InternTempOffsetCalibrate the integrated temp sensor of the TUUB (ITS)°F/°CWrite
AV6Cfg_ExternTempOffsetCalibrate the external temp sensor (ETS)°F/°CWrite
AV7Cfg_ExternTempMinMinimum temp read by the sensor (minimum range value)°F/°CWrite
AV8Cfg_ExternTempMaxMaximum temp read by the sensor (maximum range value)°F/°CWrite
AVmin9TempSetPointSet the actual user setpoint of the zone in occupied/day operation mode°F/°CCommand
AV10Cfg_MinSetPointSet the minimum temp setpoint of the zone in occupied/day operation mode°F/°CWrite
AV11Cfg_MaxSetPointSet the maximum temp setpoint of the zone in occupied/day operation mode°F/°CWrite
AV12SetPointCoolNoOccNSBConfiguration value of the cooling setpoint when in night setback or unoccupied°F/°CWrite
AV13SetPointHeatNoOccNSBConfiguration value of the heating setpoint when in night setback or unoccupied°F/°CWrite
AV14ExternTemp2Extern temperature sensor 2 (ETS2)°F/°CRead
AV15Cfg_ExternTemp2OffsetCalibrate the external temp sensor 2 (ETS2)°F/°CWrite
AV16Cfg_ExternTemp2MinMinimum temp read by the external temp sensor 2 (minimum range value)°F/°CWrite
AV17Cfg_ExternTemp2MaxMaximum temp read by the external temp sensor 2 (maximum range value)°F/°CWrite
AVmin20Heating1DemandStatus value that represents the heating demand for the Heating Ramp 1%Read
AV21Cfg_Heating1PropBandRange through which the controller will modulate the heating output from 0°F/°CWrite
AV22Cfg_Heating1DeadBandDeadband around the setpoint°F/°CWrite
AV24Heating2DemandStatus value that represents the heating demand for the Heating Ramp 2%Read
AV25Cfg_Heating2PropBandRange through which the controller will modulate the heating output from 0°F/°CWrite
AV26Cfg_Heating2DeadBandDeadband around the setpoint°F/°CWrite
AV32Cfg_IntegralTimeHeatingReciprocal of the integral time in secs (1/I or repeats per second)sWrite
AVmin35Cooling1DemandStatus value that represents the cooling demand for the Cooling Ramp 1%Read
AV36Cfg_Cooling1PropBandRange through which the controller will modulate the cooling output from 0°F/°CWrite
AV37Cfg_Cooling1DeadBandDeadband around the setpoint°F/°CWrite
AV38Cooling2DemandStatus value that represents the cooling demand for the Cooling Ramp 2%Read
AV39Cfg_Cooling2PropBandRange through which the controller will modulate the cooling output from 0°F/°CWrite
AV40Cfg_Cooling2DeadBandDeadband around the setpoint°F/°CWrite
AV45Cfg_IntegralTimeCoolingReciprocal of the integral time in secs (1/I or repeats per second)sWrite
AV46Cfg_CoolingAntiCycleDelayCooling output anti-short-cycle time, minutesminWrite
AV50ChangeOverDemandStatus value that represents the changeover demand%Read
AV51Cfg_ChangeOverPropBandProportional band for the changeover output°F/°CWrite
AV52Cfg_ChangeOverDeadBandRange at which the controller will not take action on the changeover°F/°CWrite
AV53ChangeOverSetPointEntering water temperature threshold for changeover°F/°CWrite
AV56Cfg_CL_HT_SwitchTimerDelay before changeover is allowed to switchminWrite
AV58CL_HT_SwitchTimerCountStatus value of the remaining time before the changeover is authorisedsRead
AV60FanDemandStatus value that represents the fan demand%Read
AV61Cfg_FanAutoTimeOutDelayPrevent the cycling of the fansWrite
AV62Cfg_FanDampingFactorConfiguration value in secs that represents the damping factor for changing fansWrite
AV70ExternHumidityExternal humidity sensor value (Erh)%RHRead
AV71Cfg_InternHumidityOffsetCalibrate the internal relative humidity sensor (irH)%RHWrite
AV72Cfg_ExternHumidityOffsetCalibrate the external relative humidity sensor (Erh)%RHWrite
AV73HumSetPointSet the actual user humidity setpoint of the zone in occupied/day operation%RHCommand
AV74Cfg_HumMinSetPointSet the minimum relative humidity setpoint of the zone in occupied/day operation%RHWrite
AV75Cfg_HumMaxSetPointSet the maximum relative humidity setpoint of the zone in occupied/day operation%RHWrite
AV76DehumdifySPNoOccNSBConfiguration value of the highest relative humidity allowed when in night setback%RHWrite
AV77HumidifySPNoOccNSBConfiguration value of the lowest relative humidity allowed when in night setback%RHWrite
AV78HumidifyDemandStatus value that represents the humidifier modulation, based on relative humidity%RHRead
AV79DehumidifyDemandStatus value that represents the dehumidification percentage, based on relative humidity%RHRead
AV80Cfg_HumPropBandProportional band for the humidity output%RHWrite
AV81Cfg_HumDeadBandDeadband around the setpoint%RHWrite
AV85Cfg_NSBOverrideDelayMaximum override time in night setback, minutesminWrite
AV86Cfg_NoOccOverrideDelayMaximum configuration time in mins when in unoccupied mode and an overrideminWrite
AV87Cfg_NoOccOvCountDownTime in mins before the state of the input changes from OccupiedminRead
AV88Cfg_OccupancyMinTimeTime in mins before the state of the input changes from OccupiedminWrite
AV90Cfg_UniversalInput1DelayConfiguration time in secssWrite
AV91Cfg_UniversalInput2DelaySee AV.90sWrite
AV92Cfg_UniversalInput3DelaySee AV.90sWrite
AV93Cfg_UniversalInput4DelaySee AV.90sWrite
AV95ExternalCO2SensorValueCarbon dioxide sensor (CO2)ppmRead
AV96CO2ControlValueStatus value that represents the current value of CO2 (PPM)ppmRead
AV97Cfg_CO2RangeStatus value that represents the maximum range of the CO2 sensor (PPM)ppmRead
AV98CO2SetpointMaximum limit of CO2 concentration before the TUUB sends an alarmppmWrite
AV100Cfg_AnalogOutput1MinThis value represents the minimum control signal of the controlled elementVWrite
AV101Cfg_AnalogOutput1MaxThis value represents the maximum control signal of the controlled elementVWrite
AV103Cfg_AnalogOutput2MinSee AV.100VWrite
AV104Cfg_AnalogOutput2MaxSee AV.101VWrite
AV105Cfg_AnalogOutput3MinSee AV.100VWrite
AV106Cfg_AnalogOutput3MaxSee AV.101VWrite
AV107Cfg_AnalogOutput4MinSee AV.100VWrite
AV108Cfg_AnalogOutput4MaxSee AV.101VWrite
AV109Cfg_MinCoolHeat1PositionConfiguration value in percentage at which the controller sets the CH1 output%Write
AV115Cfg_BinaryOutput1ClosePosConfiguration value that indicates the percentage of demand at which the contact%Write
AV116Cfg_BinaryOutput1OpenPosConfiguration value that indicates the percentage of demand at which the contact%Write
AV117Cfg_BinaryOutput1ContactDelayConfiguration value in mins to add a delay before allowing the outputminWrite
AV120Cfg_BinaryOutput2ClosePosSee AV.115%Write
AV121Cfg_BinaryOutput2OpenPosSee AV.116%Write
AV122Cfg_BinaryOutput2ContactDelaySee AV.117minWrite
AV125Cfg_BinaryOutput3ClosePosSee AV.115%Write
AV126Cfg_BinaryOutput3OpenPosSee AV.116%Write
AV127Cfg_BinaryOutput3ContactDelaySee AV.117minWrite
AV130Cfg_BinaryOutput4ClosePosSee AV.115%Write
AV131Cfg_BinaryOutput4OpenPosSee AV.116%Write
AV132Cfg_BinaryOutput4ContactDelaySee AV.117minWrite
AV133Cfg_BinaryOutput5ClosePosSee AV.115%Write
AV134Cfg_BinaryOutput5OpenPosSee AV.116%Write
AV135Cfg_BinaryOutput5ContactDelaySee AV.117minWrite
AV136Cfg_BinaryOutput6ClosePosSee AV.115%Write
AV137Cfg_BinaryOutput6OpenPosSee AV.116%Write
AV138Cfg_BinaryOutput6ContactDelaySee AV.117minWrite
AV139Cfg_BinaryOutput7ClosePosSee AV.115%Write
AV140Cfg_BinaryOutput7OpenPosSee AV.116%Write
AV141Cfg_BinaryOutput7ConatctDelaySee AV.117minWrite
AV150Cfg_FloatingBO1/BO2 TimerTime required by the valve actuator to complete a strokesWrite
AV151Cfg_FloatingBO3/BO7 TimerTime required by the valve actuator to complete a strokesWrite
AV155FloatingOutputBO1/BO2Status value to show the floating signal demand%Write
AV156FloatingOutputBO3/BO7Status value to show the floating signal demand%Write
AV165CopyCfgStartAddressFirst address in the range of copied controllers while using the CopyWrite
AV166CopyCfgEndAddressLast address in the range of copied controllers while using the CopyWrite
AV167CopyCfgResultValue is used to verify whether the copy to the controller’s operationWrite
AV185PressureSensorValuePressure sensor value in PascalsWrite
AV186Cfg_PressureSensorRangeThe maximum range for pressureWrite
AV190VFDPressureLoopActual VFD Pressure loop%Write
AV191Cfg_VFDPressureSetPointSetpoint value for VFD pressureWrite
AV192Cfg_VFDPressureDeadBandDead band value for VFD pressureWrite
AV193Cfg_VFDPressurePropBandProportional band value for VFD pressureWrite
AV194Cfg_VFDPressureIntegralTimeVFD pressure integral secondssWrite
AV200VFDTempCoolLoopActual VFD temperature loop while cooling%Write
AV201VFDTempHeatLoopActual VFD temperature loop while heating%Write
AV202Cfg_VFDTempSetPointConfiguration value of VFD temperature setpoint°F/°CWrite
AV203Cfg_VFDTempDeadBandVFD temperature dead band value°F/°CWrite
AV204Cfg_VFDTempPropBandVFD temperature proportional band value°F/°CWrite
AV205Cfg_VFDTempIntegralTimeVFD temperature integral secondssWrite
AV206CloseOffVoltageConfiguration value of the voltage required in order to close the 6-wayWrite
AV207MinCoolingVoltageConfiguration value of the voltage required for the 6-way valve to startWrite
AV208MinHeatingVoltageConfiguration value of the voltage required for the 6-way valve to startWrite
AV210DeltaTemperatureStatus value of the difference between the inlet and outlet temperature°F/°CRead
AV211DeltaTempSetPointConfiguration value of the setpoint for the delta temperature control mode°F/°CWrite
AV212DeltaTempInletStatus value of the delta inlet temperature°F/°CRead
AV213DeltaTempOutletStatus value of the delta outlet temperature°F/°CRead
AV215LightIntensityRangeMaximum range of the Light Intensity sensor (Luxes)Write
AV225PulseOutput1Status value to show the pulse signal demand%Write
AV226PulseOutput2Status value to show the pulse signal demand%Write
AV227PulseOutput3Status value to show the pulse signal demand%Write
AV228PulseOutput4Status value to show the pulse signal demand%Write
AV229PulseOutput5Status value to show the pulse signal demand%Write
AV230PulseOutput6Status value to show the pulse signal demand%Write
AV231PulseOutput7Status value to show the pulse signal demand%Write
AV232AO1VoltageStatus value to show the voltage for AO1 rampRead
AV233AO2VoltageStatus value to show the voltage for AO2 rampRead
AV234AO3VoltageStatus value to show the voltage for AO3 rampRead
AV235AO4VoltageStatus value to show the voltage for AO4 rampRead
AV240UserBacklightSetPointSetpoint for backlight setting in the user mode%Write
AV241OccupancyBacklightSetPointSetpoint for the backlight setting in the occupied mode%Write
AV242UnoccupancyBacklightSetPointSetpoint for the backlight setting in the unoccupied mode%Write
BI1PIR_RelayInternal PIR sensor relay statusRead0=Relay was not activated, 1=Relay was activated
BO1BinaryOutput1Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO2BinaryOutput2Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO3BinaryOutput3Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO4BinaryOutput4Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO5BinaryOutput5Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO6BinaryOutput6Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BO7BinaryOutput7Contact status of the output: (0) Open, (1) CloseWrite0=Open, 1=Close
BV1Cfg_TempUnitBACnetTemp units used in BACnetWrite0=Celsius, 1=Fahrenheit
BV2Cfg_TempSetPointLockLocks the zone setpoint at the keypadWrite0=Disable, 1=Enable
BV3Cfg_UserSysOffModeConfiguration to allow users to turn off the controllerWrite0=Enable, 1=Disable
BV4Cfg_TempUnitTstatTemperature units on the TUUB displayWrite0=Celsius, 1=Fahrenheit
BV5Cfg _FreezeProtectionEnable or disable the automatic activation of the heating outputs when zoneWrite0=Off, 1=On
BV10Cfg_Heating1RampLockLock the heating ramp 1 even when a heating demand is activeWrite0=Off, 1=On
BV11Cfg_Heating2RampLockLock the heating ramp 2 even when a heating demand is activeWrite0=Off, 1=On
BV13Cfg_CoolingRampLockLock the cooling ramp even when a cooling demand is activeWrite0=Off, 1=On
BV17Cfg_ChangeOverRampLockLocks the changeover rampWrite0=Off, 1=On
BV20Cfg_UserFanAutoModeEnable or disable the automatic fan optionWrite0=Enable, 1=Disable
BV21Cfg_FanSpeedOptionSelect between the Standard (Neptronic) and Advanced (OE1) fan speed specificationsWrite0=Standard, 1=Advanced
BV22Cfg_UserSysFanModeEnable or disable the fan option in MSV.1Write0=Disable, 1=Enable
BV23Cfg_HideFanDisplayHide or show the fan symbol displayed on the controllerWrite0=Yes, 1=No
BV25Cfg_HumControlSourceConfiguration value that controls the humidity source, either internal or externalWrite0=Intern Sensor, 1=Extern Sensor
BV26Cfg_HumSetPointLockPrevent the user from changing the relative humidity setpointWrite0=Disable, 1=Enable
BV27Cfg_HumidifyRampLockLock the humidification ramp even when a humidification demand is activeWrite0=Off, 1=On
BV28Cfg_DehumidifyRampLockLock the dehumidification ramp even when a dehumidification demand is activeWrite0=Off, 1=On
BV30ChangeOverModeStatus value of the actual changeover mode (0) Cooling, (1) HeatingWrite0=Cooling, 1=Heating
BV31Cfg_CO2ControlSourceSelect the source for CO controlWrite0=Internal Sensor, 1=External Sensor
BV35Cfg_NightorNoOccModeConfiguration to determine the action of the TUUB when in night setbackWrite0=Setpoint, 1=OFF
BVmin36AL_ DirtyFilterStatus value to inform if a filter change is requiredRead0=No, 1=Yes
BVmin37AL_FlowSwitchStatus value to inform if an airflow alarm is activeRead0=No, 1=Yes
BV38AL_OverrideStatus value to inform if an override is activeRead0=No, 1=Yes
BV39AL_WindowOpenedStatus value to inform that a window has been openedRead0=No, 1=Yes
BV40AL_DoorOpenedStatus value to inform that a door has been openedRead0=No, 1=Yes
BV41AL_OverHeatStatus value to inform if a heat/reheat with fan override is activeRead0=No, 1=Yes
BV42AL_SelectorSwitchStatusStatus value to inform if the selector switch is in (0) RemoteRead0=Remote mode, 1=Local mode
BV45Cfg_AnalogInput1ContactConfiguration to change the contact's normal positionWrite0=Norm Open, 1=Norm Close
BV46Cfg_AnalogInput2ContactSee BV.45Write0=Norm Open, 1=Norm Close
BV47Cfg_AnalogInput3ContactSee BV.45Write0=Norm Open, 1=Norm Close
BV48Cfg_AnalogInput4ContactSee BV.45Write0=Norm Open, 1=Norm Close
BV49Cfg_WindowOpenedModeConfiguration to determine the action of the TUUB when window is openWrite0=Setpoint, 1=OFF
BV50Cfg_DoorOpenedModeConfiguration to determine the action of the TUUB when door is openWrite0=Setpoint, 1=OFF
BV55Cfg_AnalogOutput1DirectionAnalog output directionWrite0=Direct, 1=Reverse
BV56Cfg_AnalogOutput2DirectionSee BV.55Write0=Direct, 1=Reverse
BV57Cfg_AnalogOutput3DirectionSee BV.55Write0=Direct, 1=Reverse
BV58Cfg_AnalogOutput4DirectionSee BV.55Write0=Direct, 1=Reverse
BV59Cfg_AnalogOutputRatioDetermine analog output AO1 to AO4 percentage ratio representationWrite0=Control Range, 1=Electrical Range
BV60Cfg_BinaryOutput1DirectionBinary output directionWrite0=Direct, 1=Reverse
BV61Cfg_BinaryOutput2DirectionSee BV.60Write0=Direct, 1=Reverse
BV62Cfg_BinaryOutput3DirectionSee BV.60Write0=Direct, 1=Reverse
BV63Cfg_BinaryOutput4DirectionSee BV.60Write0=Direct, 1=Reverse
BV64Cfg_BinaryOutput5DirectionSee BV.60Write0=Direct, 1=Reverse
BV65Cfg_BinaryOutput6DirectionSee BV.60Write0=Direct, 1=Reverse
BV66Cfg_BinaryOutput7DirectionSee BV.60Write0=Direct, 1=Reverse
BV74Cfg_FloatingBO1/BO2DirectionBinary contact normal state (Normally Open, Normally Close) when MSV.77 BO1 SignalWrite0=Direct, 1=Reverse
BV75Cfg_FloatingBO3/BO4DirectionBinary contact normally state (Normally Open, Normally Close) when MSV.79 VO3 SignalWrite0=Direct, 1=Reverse
BV76Cfg_FloatingBO5/BO6DirectionBinary contact normal state (Normally open, Normally close) when MSV. 81 BO3Write0=Direct, 1=Reverse
BV85Cfg_ServiceDisplayAddressWhen activated, the TUUB lights up and displays the MSTP addressWrite0=Off, 1=On
BV86Cfg_KeyPadUpperLeftLockWhen on, the button is locked in run modeWrite0 = Off 1 = On If set to "On", functionality of these buttons will not be available.
BV87Cfg_KeyPadBottomLeftLockWhen on, the button is locked in run modeWrite0 = Off 1 = On If set to "On", functionality of these buttons will not be available.
BV88Cfg_KeyPadArrowsLockWhen on, the button is locked in run modeWrite0 = Off 1 = On If set to "On", functionality of these buttons will not be available.
BV89Cfg_ProgramModeLockWhen on, all buttons are lockedWrite0=Off, 1=On
BV90CopyCfgExecuteWhen using Copy Config, this value is used to start the copyWrite0=No, 1=Yes
BV91Cfg_ActivateScheduleConfiguration to activate the scheduleWrite0=No, 1=Yes
BV95Cfg_HeatPumpOptionConfiguration to enable or disable the heat pump optionWrite0=Off, 1=On
BV96Cfg_ReversingValveConfiguration to set the mode in which the reversing valve is energizedWrite0=O, 1=B
BV97Cfg_EMHAutoModeEnable or disable the EMH Auto modeWrite0=No, 1=Yes
BV98Cfg_EMHOutputEnable or disable emergency heat (EMH)Write0=Disable, 1=Enable
BV99Cfg_Y2OutputEnable or disable compressor Y2 outputWrite0=Disable, 1=Enable
BV105Cfg_AnalogInput1MinVoltMinimum voltage for Analog Input 1Write0=0 Volt, 1=2 Volt
BV106Cfg_AnalogInput2MinVoltMinimum voltage for Analog Input 2Write0=0 Volt, 1=2 Volt
BV107Cfg_AnalogInput3MinVoltMinimum voltage for Analog Input 3Write0=0 Volt, 1=2 Volt
BV108Cfg_AnalogInput4MinVoltMinimum voltage for Analog Input 4Write0=0 Volt, 1=2 Volt
BV111Cfg_DeltaTempLogicEnable or disable the delta temperature control modeWrite0=Off, 1=On
BV112Cfg_DisplayHumidityDisplay or hide the humidity valueWrite0=No, 1=Yes
BV113Cfg_DisplayCO2Display or hide the CO valueWrite0=No, 1=Yes
BV114Cfg_VFDTempSetpointSourceConfiguration value for the source for the VFD temperature setpointWrite0=VFDTempSetPoint, 1=TempSetPoint
BV115Cfg_AnalogOutput1OffVoltageSet the analog output 1 voltage to either 0V or the minimumWrite0=Min, 1=Off
BV116Cfg_AnalogOutput2OffVoltageSet the analog output 2 voltage to either 0V or the minimumWrite0=Min, 1=Off
BV117Cfg_AnalogOutput3OffVoltageSet the analog output 3 voltage to either 0V or the minimumWrite0=Min, 1=Off
BV118Cfg_AnalogOutput4OffVoltageSet the analog output 4 voltage to either 0V or the minimumWrite0=Min, 1=Off
BV119Cfg_CO2AutoSelfCalibEnable or disable the automatic self-calibration of the CO sensorWrite0=Off, 1=On
MVmin1SystemModeActual mode selectedWriteAuto, Heating, EMH, Cooling, Fan, Off (options depend on configuration)
MVmin2UserFanSpeedSelectActual fan speedWrite1=Auto, 2=Low, 3=Medium, 4=High
MV5HumControlModeAuthorize humidification and/or dehumidification in order to maintain relative humidity setpointsWrite1=Auto, 2=Dehumidification, 3=Humidification, 4=OFF
MV10Cfg_ChangeOverControlModeConfiguration that indicates the source of the changeover valueWrite1=Locally, 2=Cooling, 3=Heating
MVmin13NsbOccCommandConfiguration to set the occupancy or night setback modeCommandIf BI = Occupancy or Night Setback at MSV.35, MSV.36, MSV.37 and/or MSV.38 1 = Locally 2 = Off 3 = Occupancy/Day 4 = No Occupancy/Night If BI = any option except Occupancy or Night Setback at MSV.35, MSV.36, MSV.37...
MVmin14OccupancyStatusStatus that indicates the actual occupancyRead1=NoOccupancy, 2=Occupancy, 3=Override
MV15NightSetBackStatusStatus that indicates the actual mode of the zoneRead1=Day, 2=Night, 3=Override
MV20Cfg_Sequence SelectLimit available options at MSV.1Write1=Auto, 2=Heating, 3=Cooling, 4=HeatingOrCooling, 5=Auto Lock
MV21Cfg_ TempControlSourceSet the control temp to be used by the TUUB. (1) NetworkWrite1=Network (Net), 2=Internal (ItS), 3=External (EtS)
MV22Cfd_VFDTempInputSelect the source for VFD temperature controlWrite1=InternSensor(ItS), 2=ExternSensor(EtS), 3=ExternSensor2(EtS2)
MV25Cfg_FanOperationTypeSet the number of fan speed available on the fan coilWrite1=1Speed, 2=2Speeds, 3=3Speeds
MV26Cfg_FanModeNoOccNightSet the fan speed for no occupancy or night setback modeWrite1=Low, 2=Medium, 3=High, 4=Auto
MV27Cfg_FanModeWindowOpenedSet the fan speed mode when the window is openWrite1=Low, 2=Medium, 3=High, 4=Auto
MV28Cfg_FanModeDoorOpenedSet the fan speed mode when the door is openWrite1=Low, 2=Medium, 3=High, 4=Auto
MV35Cfg_AnalogInput1TypeSelect the input signal type for Analog Input 1 (AI1)Write1 = OFF 2 = Extern Sensor 10k 3 = Change Over Sensor 4 = Ch Ov Contact Norm Cool 5 = Ch Ov Contact Norm Heat 6 = Outside Air Sensor 7 = Extern Sensor 0-10V 8 = CO2 0-10V 9 = Occupancy 10 = Night Set Back 11 =...
MV36Cfg_AnalogInput2TypeSee MSV.35Write
MV37Cfg_AnalogInput3TypeSee MSV.35Write
MV38Cfg_AnalogInput4TypeSee MSV.35Write
MV55Cfg_AnalogOutput1RampRamp used to modulate AO1 based on demandWrite1=Off, 2=Change Over With Fan, 3=Cooling1 With Fan, 4=Cooling2 With Fan, 5=Heating1 With Fan, 6=Heating2 With Fan, 7=Heating2, 8=Cooling1 Heating1 With Fan, 9=HumidifyWithFan, 10=CO2 Alarm, 11=6 Way valve, 12=Delta Temperature, 13=VFD/ECMTempLoopEnable, 14=VFD Pressure Loop
MV56Cfg_AnalogOutput1SignalTypeAnalog output signal typeWrite1=Analog, 2=On-Off, 3=Pulsing
MV57Cfg_AnalogOutput2RampRamp assigned to AO2 (see MSV.55 and BV.95)Write1=Off, 2=Change Over With Fan, 3=Cooling1 With Fan, 4=Cooling2 With Fan, 5=Heating1 With Fan, 6=Heating2 With Fan, 7=Heating2, 8=Cooling1 Heating1 With Fan, 9=HumidifyWithFan, 10=CO2 Alarm, 11=6 Way valve, 12=Delta Temperature, 13=VFD/ECMTempLoopEnable, 14=VFD Pressure Loop, 15=FAN
MV58Cfg_AnalogOutput2SignalTypeSee MSV.56Write1=Analog, 2=On-Off, 3=Pulsing
MV59Cfg_AnalogOutput3RampSee MSV.55Write1=Off, 2=Change Over With Fan, 3=Cooling1 With Fan, 4=Cooling2 With Fan, 5=Heating1 With Fan, 6=Heating2 With Fan, 7=Heating2, 8=Cooling1 Heating1 With Fan, 9=HumidifyWithFan, 10=CO2 Alarm, 11=6 Way valve, 12=Delta Temperature
MV60Cfg_AnalogOutput3SignalTypeSee MSV.56Write1=Analog, 2=On-Off, 3=Pulsing
MV61Cfg_AnalogOutput4RampSee MSV.55Write1=Off, 2=Change Over With Fan, 3=Cooling1 With Fan, 4=Cooling2 With Fan, 5=Heating1 With Fan, 6=Heating2 With Fan, 7=Heating, 8=Cooling 1 Heating 1 With Fan, 9=HumidifyWithFan, 10=CO2 Alarm, 11=6 Way valve, 12=Delta Temperature
MV62Cfg_AnalogOutput4SignalTypeSee MSV.56Write1=Analog, 2=On-Off, 3=Pulsing
MV70Cfg_BinaryOutput1RampRamp used to modulate BO1 based on demandWrite1=Off, 2=Change Over With Fan, 3=Cooling1 With Fan, 4=Cooling2 With Fan, 5=Heating1 With Fan, 6=Heating2 With Fan, 7=Heating2, 8=Cooling1Heating1 With Fan, 9=HumidifyWithFan, 10=CO2 Alarm
MV71Cfg_BinaryOutput2RampSee MSV.70Write
MV72Cfg_BinaryOutput3RampSee MSV.70Write
MV73Cfg_BinaryOutput4RampIf MSV.25 Cfg_FanOperationType is set to 3 speeds, (1) Fan: High speedWrite
MV74Cfg_BinaryOutput5RampIf MSV.25 Cfg_FanOperationType is set to 3 speeds, (1) Fan: Medium speedWrite
MV75Cfg_BinaryOutput6RampIf MSV.25 Cfg_FanOperationType is set to 3 speeds, (1) Fan: Low speedWrite1=Off, 2=Change Over With Fan, 3=Cooling1 With Fan, 4=Cooling2 With Fan, 5=Heating1 With Fan, 6=Heating2 With Fan, 7=Heating2, 8=Cooling1Heating1 With Fan, 9=HumidityWithFan, 10=CO2 Alarm, 11=6 Way valve, 12=Delta Temperature, 13=VFD/ECMTempLoopEnable, 14=VFD Pressure Loop
MV76Cfg_BinaryOutput7RampSee MSV.70Write
MV77Cfg_BinaryOutput1SignalTypeOutput signal typeWrite1=Pulsing, 2=On-Off, 3=Floating
MV78Cfg_BinaryOutput2SignalTypeSee MSV.77Write1=Pulsing, 2=On-Off
MV79Cfg_BinaryOutput3SignalTypeSee MSV.77Write1=Pulsing, 2=On-Off, 3=Floating
MV80Cfg_BinaryOutput4SignalTypeSee MSV.77Write1=Pulsing, 2=On-Off
MV81Cfg_BinaryOutput5SignalTypeSee MSV.77Write1=Pulsing, 2=On-Off
MV82Cfg_BinaryOutput6SignalTypeSee MSV.77Write1=Pulsing, 2=On-Off
MV83Cfg_BinaryOutput7SignalTypeSee MSV.77Write1=Pulsing, 2=On-Off
MV95Cfg_DisplayInfoConfiguration value of the information displayed on the TUUB. (1) Display TempWrite1=Temp and demand, 2=Setpoint and demand, 3=Temp only, 4=Setpoint only, 5=Off
MV96Cfg_ValveSizeConfiguration value of the valve size in inches for the 6-way valveWrite1=1/2, 2=3/4, 3=1
SCH1OccupancyScheduleWeekly occupancy schedule to specify which occupancy state is active during specificRead
Other1ProgramFirmwareProgram object for firmware update (LOAD or RESTART)Write
FILE1FirmwareBinaryFileFirmware binary file written for an updateWrite
Object ID lookup: Neptronic TUUB universal wall-mount controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TUUB universal wall-mount controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic TUUB universal wall-mount controller

How many BACnet points does the Neptronic TUUB universal wall-mount controller have?

This list has 276 BACnet objects: 9 analog inputs, 4 analog outputs, 137 analog values, 1 binary input, 7 binary outputs, 73 binary values, 1 file, 1 schedule, 42 multi-state values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic TUUB universal wall-mount controller BACnet points are writable?

232 of the 276 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic TUUB universal wall-mount controller BACnet documentation?

The source is TUUB BACnet Guide (TUUB-BACnet Guide-250829 (V1.13)), revision 2025-08-29, published free by Neptronic at https://www.neptronic.com/Controls/PDF/2025/TUUB-BACnet%20Guide-250829%20(V1.13).pdf.

What are the minimum BACnet points to integrate the Neptronic TUUB universal wall-mount controller?

Start with MV 13 NsbOccCommand (BMS occupancy command: local, off, occupied, unoccupied); MV 1 SystemMode (Mode: auto, heating, cooling, fan, off); MV 2 UserFanSpeedSelect (Fan speed: auto, low, medium, high); AV 9 TempSetPoint (Occupied/day temperature setpoint); MV 14 OccupancyStatus (Actual occupancy incl. override); AV 1 ControlTemp (Temperature used for control); AV 20 Heating1Demand (Heating ramp 1 demand, %); AV 35 Cooling1Demand (Cooling ramp 1 demand, %); BV 37 AL_FlowSwitch (Airflow alarm); BV 36 AL_ DirtyFilter (Filter change required).

How do I enable BMS control of the Neptronic TUUB universal wall-mount controller?

MSV.13 NsbOccCommand: Locally lets the controller follow its occupancy input; the other states force off, occupied/day or unoccupied/night from the BMS.

Does the Neptronic TUUB universal wall-mount controller need a BACnet heartbeat or have a communication timeout?

With MSV.21 Cfg_TempControlSource = Network, the BMS must keep writing AV.1 ControlTemp; if nothing arrives for AV.2 Cfg_NetworkTimeOut (0-60 min) the controller goes to OFF and AV.1 shows 999 °C in fault. With AV.2 = 0, AV.1 resets to the AV.9 setpoint.

Can the BMS supply sensor values to the Neptronic TUUB universal wall-mount controller?

Set MSV.21 Cfg_TempControlSource to Network (1) and write the room temperature to AV.1 ControlTemp (commandable).

How do I check these points on the real TUUB universal wall-mount controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: TUUB BACnet Guide · TUUB-BACnet Guide-250829 (V1.13) · rev. 2025-08-29. Object names, instances and units are reproduced as published; descriptions are our own.