- SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller
High-pressure atomising humidifier zone controller · BACnet points list
Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller BACnet points list
Updated 12 November 2026
Each EZC zone controller of an older SKH atomiser system is its own BACnet MS/TP device. It carries the zone demand and output, room and duct humidity and temperature readings, occupied, unoccupied, vacant, internal and network setpoints, network humidity and temperature inputs with a timeout, the control mode and source selectors, stage outputs, cutouts and sensor alarms, and a weekly occupancy schedule.
This page lists 121 BACnet objects for the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller — 84 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.
- Manufacturer
- Neptronic
- Model
- SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller
- Equipment
- High-pressure atomising humidifier zone controller
- Equipment type
- Humidifiers
- BACnet objects
- 121 (84 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 153000 + MAC address
- Also known as
- SKH EZC, EZC, Neptronic SKH zone controller, SKH-BACnet Guide-210104
Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.
BMS integration notes: Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller
Set MSV 2 Occupancy and BV 2 ZoneMode, choose the control mode (MSV 100) and sources (MSV 101-103). For network control write AV 1 ZoneDemand or the network setpoint and RH (AV 11, AV 13) before the network timeout (AV 102) runs out. Read MSV 1 ZoneState, AV 3 ZoneOutput, AI 4 room RH and the alarm flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | ZoneMode | Zone on/off (1 = on) | Write |
| MV 2 | Occupancy | Occupancy: 1 occ, 2 unocc, 3 vacant, 4 off | Write |
| MV 100 | Cfg_ControlMode | Control mode; 5 = network | Write |
| AV 1 | ZoneDemand | Zone demand from the BMS, % | Write |
| AV 11 | NetworkRHSetpoint | Network RH setpoint | Write |
| AV 13 | NetworkRH | Network room RH from the BMS | Write |
| MV 1 | ZoneState | Zone state | Read |
| AV 3 | ZoneOutput | Zone output, % | Read |
| AI 4 | RoomRH | Room RH | Read |
| BV 30 | AL_GlobalAlarmMask | Global alarm (zone) | Read |
Enable & remote start
BV 2 ZoneMode turns the zone on; MSV 100 Cfg_ControlMode = 5 (Network) hands the demand to the BMS.
Heartbeat & communication loss
AV 102 Cfg_NetworkTimeout (1-15 min) sets how long network values are held; AV 15 counts down and BV 36 AL_NetworkTimeout flags a lapse.
Sensors & values from the BMS
MSV 101 / 102 = Network take room RH and temperature from AV 13 NetworkRH and AV 14 NetworkTemp; MSV 103 = Network takes the setpoint from AV 11 / AV 12.
Network setup
- Baud rate and device instance can be automatic: the humidifier sets its device instance to 153000 + MAC address; the MAC (0-254) is set from the menu.
- Max_Master defaults to 127; lower it for a faster MS/TP trunk.
Watch out for
- Network values must be refreshed within Cfg_NetworkTimeout (AV 102, 1-15 min) or BV 36 AL_NetworkTimeout is raised.
- BV 102 Cfg_NetworkControlOverride is a configuration switch; check it during commissioning.
Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 3 | RoomRHSetpoint or RoomTempSetpoint | Setpoint for the room relative humidity sensor | %RH | Read | |
| AImin | 4 | RoomRH | Reading of the relative humidity in the room | %RH | Read | |
| AI | 5 | RoomTemp | Temperature reading of the room | °C | Read | |
| AI | 6 | DuctRH | Relative humidity reading of the duct | %RH | Read | |
| AI | 7 | TrlhRH | Value of the relative humidity measured on the TRL | %RH | Read | |
| AI | 8 | TrlhTemp | Value of the temperature measured on the TRL | °C | Read | |
| AI | 9 | BoardTemp | Temperature reading measured on the PC board | °C | Read | |
| AI | 200 | DI4_TpmDuty | DI4 time-proportional duty (no description printed) | ms | Read | |
| AO | 1 | FeedbackVoltage | Output feedback voltage | mV | Write | |
| AVmin | 1 | ZoneDemand | Zone demand | % | Write | |
| AV | 2 | SimulatedDemand | Simulated demand | % | Write | |
| AVmin | 3 | ZoneOutput | Value of the zone output | % | Read | |
| AV | 4 | ZoneOuputLimit | Maximum zone output limit | % | Write | |
| AV | 5 | UnoccupiedRHSetpoint | Relative humidity setpoint in the unoccupied mode | %RH | Write | |
| AV | 6 | UnoccupiedTempSetpoint | Temperature setpoint in the unoccupied mode | °C | Write | |
| AV | 7 | VacantRHSetpoint | Relative humidity setpoint in the vacancy mode | %RH | Write | |
| AV | 8 | VacantTempSetpoint | Temperature setpoint in the vacancy mode | °C | Write | |
| AV | 9 | InternalRHSetpoint | Internal relative humidity setpoint | %RH | Write | |
| AV | 10 | InternalTempSetpoint | Internal temperature setpoint | °C | Write | |
| AVmin | 11 | NetworkRHSetpoint | Network relative humidity setpoint | %RH | Write | |
| AV | 12 | NetworkTempSetpoint | Network temperature setpoint | °C | Write | |
| AVmin | 13 | NetworkRH | Network relative humidity | % | Write | |
| AV | 14 | NetworkTemp | Network temperature | °C | Write | |
| AV | 15 | NetworkDowncounter | Value of the network downcounter | s | Read | |
| AV | 100 | Cfg_InactivityDelay | System inactivity delay | h | Write | |
| AV | 101 | Cfg_InactivityDrainTime | Inactivity delay of drain | s | Write | |
| AV | 102 | Cfg_NetworkTimeout | Network timeout | min | Write | |
| AV | 103 | Cfg_FanOnDelay | Delay in seconds before the fan is turned on | s | Write | |
| AV | 104 | Cfg_FanOffDelay | Delay in seconds before the fan is turned off | s | Write | |
| AV | 200 | Stage1Runtime | Value of the stage 1 runtime | Read | ||
| AV | 201 | Stage2Runtime | Value of the stage 2 runtime | Read | ||
| AV | 202 | Stage3Runtime | Value of the stage 3 runtime | Read | ||
| AV | 203 | Stage4Runtime | Value of the stage 4 runtime | Read | ||
| AV | 300 | Cfg_DuctRHSetpoint | Duct relative humidity setpoint | %RH | Write | |
| AV | 301 | Cfg_DuctRHCutout | Duct relative humidity cutout | %RH | Write | |
| AV | 302 | Cfg_DuctRHPropBand | Duct relative humidity proportional band | %RH | Write | |
| AV | 303 | Cfg_DuctRHIntegralTime | Duct relative humidity integral time | s | Write | |
| AV | 304 | Cfg_DuctRHDerivateTime | Duct relative humidity derivate time | s | Write | |
| AV | 305 | Cfg_RHProportionalBand | Relative humidity proportional band | %RH | Write | |
| AV | 306 | Cfg_TempProportionalBand | Temperature proportional band | °C | Write | |
| AV | 307 | Cfg_IntegralTime | Integral time | s | Write | |
| AV | 308 | Cfg_DifferentialTime | Differential time | s | Write | |
| AV | 309 | Cfg_TrlhRHSetpointMin | Minimum relative humidity setpoint measured by the TRL | %RH | Write | |
| AV | 310 | Cfg_TrlhRHSetpointMax | Maximum relative humidity setpoint measured by the TRL | %RH | Write | |
| AV | 311 | Cfg_TrlhTempSetpointMin | Minimum temperature setpoint measured by the TRL | °C | Write | |
| AV | 312 | Cfg_TrlhTempSetpointMax | Maximum temperature setpoint measured by the TRL | °C | Write | |
| AV | 313 | Cfg_RoomRHSetpointMin | Minimum relative humidity setpoint of the room | %RH | Write | |
| AV | 314 | Cfg_RoomRHSetpointMax | Maximum relative humidity setpoint of the room | %RH | Write | |
| AV | 315 | Cfg_RoomTempSetpointMin | Minimum temperature setpoint of the room | °C | Write | |
| AV | 316 | Cfg_RoomTempSetpointMax | Maximum temperature setpoint of the room | °C | Write | |
| AV | 317 | Cfg_RoomRHMin | Minimum relative humidity of the room | %RH | Write | |
| AV | 318 | Cfg_RoomRHMax | Maximum relative humidity of the room | %RH | Write | |
| AV | 319 | Cfg_RoomTempMin | Minimum temperature of the room | °C | Write | |
| AV | 320 | Cfg_RoomTempMax | Maximum temperature of the room | °C | Write | |
| AV | 321 | Cfg_StageOnDelay | Delay before each stage is on | s | Write | |
| AV | 323 | Cfg_TPMStagePeriod | TPM stage period | s | Write | |
| AV | 324 | Cfg_RoomRHSetpointOffset | Relative humidity setpoint offset value of the room | %RH | Write | |
| AV | 325 | Cfg_RoomTempSetpointOffset | Temperature setpoint offset value of the room | °C | Write | |
| AV | 326 | Cfg_RoomRHSOffset | Relative humidity offset value of the room | %RH | Write | |
| AV | 327 | Cfg_RoomTempOffset | Temperature offset value of the room | °C | Write | |
| AV | 328 | Cfg_DuctRHOffset | Relative humidity offset value of the room | %RH | Write | |
| AV | 329 | Cfg_BoardTempOffset | Temperature offset value of the board | °C | Write | |
| AV | 330 | Cfg_TrlhRoomRHOffset | Relative humidity offset value of the room measured by the TRL | %RH | Write | |
| AV | 331 | Cfg_TRLRoomTempOffset | Temperature offset value of the room measured by the TRL | °C | Write | |
| BI | 1 | DI1_AirflowCutout | Open or close the airflow cutout | Write | 0=Open, 1=Close | |
| BI | 2 | DI2_DuctRHCutout | Open or close the duct RH cutout | Write | 0=Open, 1=Close | |
| BI | 3 | DI3_InterlockCutout | Open or close the interlock cutout | Write | 0=Open, 1=Close | |
| BI | 4 | DI4_BinaryDemand | Open or close the binary demand | Write | 0=Open, 1=Close | |
| BO | 1 | FanControl | Status of Fan control | Read | 0=Off, 1=On | |
| BO | 200 | ZoneDrain | Status of zone drain | Read | 0=Off, 1=On | |
| BO | 201 | ZoneInlet | Status of zone inlet | Read | 0=Off, 1=On | |
| BV | 1 | SystemMode | Status of the system mode | Read | 0=Off, 1=On | |
| BVmin | 2 | ZoneMode | Enable or disable the zone mode | Write | 0=Off, 1=On | |
| BV | 3 | WaterPressure | Status of the water pressure | Read | 0=Not Ready, 1=Ready | |
| BV | 4 | LimitedByDuctRH | Status of the duct relative humidity | Read | 0=Off, 1=On | |
| BVmin | 30 | AL_GlobalAlarmMask | Status of the global alarm mask | Read | 0=Off, 1=On | |
| BV | 31 | AL_DuctRHCutout | Status of the duct relative humidity cutout | Read | 0=Off, 1=On | |
| BV | 32 | AL_AirflowCutout | Status of the airflow cutout | Read | 0=Off, 1=On | |
| BV | 33 | AL_InterlockCutout | Status of the interlock cutout | Read | 0=Off, 1=On | |
| BV | 34 | AL_NoCoordinator | Status of the communication between the master PCB and EZC | Read | 0=Off, 1=On | |
| BV | 35 | AL_TrlhTimeout | Status of the communication timeout between the EZC and controller | Read | 0=Off, 1=On | |
| BV | 36 | AL_NetworkTimeout | Status of the communication timeout for the network | Read | 0=Off, 1=On | |
| BV | 37 | AL_InvalidConfiguration | Status of the configuration | Read | 0=Off, 1=On | |
| BV | 100 | Cfg_EnableFanControl | Enable or disable the fan control | Write | 0=Off, 1=On | |
| BV | 101 | Cfg_InhibitAirFlowCutout | Enable or disable the inhibit airflow cutout | Write | 0=Off, 1=On | |
| BV | 102 | Cfg_NetworkControlOverride | Enable or disable the network control override | Write | 0=Off, 1=On | |
| BV | 103 | Cfg_NetworkTempUnits | Temperature unit | Write | 0=Celsius, 1=Fahrenheit | |
| BV | 104 | Cfg_NetworkMassFlowUnits | Mass flow unit | Write | 0=kg/h, 1=lb/h | |
| BV | 105 | Cfg_TRLHTempUnits | Temperature unit on the TRL | Write | 0=Celsius, 1=Fahrenheit | |
| BV | 106 | Cfg_TRLHSetpointLock | Lock the setpoint on the TRL | Write | 0=Off, 1=On | |
| BV | 107 | Cfg_TRLHZoneModeLock | Lock the zone mode on the TRL | Write | 0=Off, 1=On | |
| BV | 108 | Cfg_TRLHDisplayTime | Display the time on the TRL | Write | 0=Off, 1=On | |
| BV | 109 | Cfg_TRLHTimeFormat | Time format on the TRL | Write | 0=24H, 1=12H | |
| BV | 200 | SimulationState | State of simulation mode | Read | 0=Off, 1=On | |
| BV | 201 | Stage1Output | Enable or disable the output value of stage 1 | Write | 0=Off, 1=On | |
| BV | 203 | Stage2Output | Enable or disable the output value of stage 2 | Write | 0=Off, 1=On | |
| BV | 204 | Stage3Output | Enable or disable the output value of stage 3 | Write | 0=Off, 1=On | |
| BV | 205 | Stage4Output | Enable or disable the output value of stage 4 | Write | 0=Off, 1=On | |
| BV | 230 | AL_BoardSensorFailure | Status of the alarm for the failure of the broad sensor | Read | 0=Off, 1=On | |
| BV | 231 | AL_RoomRHSensorFailure | Status of the alarm for the failure of the room relative humidity | Read | 0=Off, 1=On | |
| BV | 232 | AL_RoomTempSensorFailure | Status of the alarm for the failure of the room temperature sensor | Read | 0=Off, 1=On | |
| BV | 233 | AL_DuctRHSensorFailure | Status of the alarm for the failure of the duct relative humidity | Read | 0=Off, 1=On | |
| BV | 234 | AL_TrlhRHSensorFailure | Status of the alarm for the failure of the controller relative humidity | Read | 0=Off, 1=On | |
| BV | 235 | AL_TrlhTempSensorFailure | Status of the alarm for the failure of the controller temperature sensor | Read | 0=Off, 1=On | |
| MVmin | 1 | ZoneState | Status of zone | Read | 1=POR, 2=Alarm, 3=Stand-By, 4=Drain Stages, 5=Drain Lines, 6=Ready | |
| MVmin | 2 | Occupancy | Current occupancy state | Write | 1=Occupied, 2=Unoccupied, 3=Vacant, 4=Off | |
| MVmin | 100 | Cfg_ControlMode | Select the control mode | Write | 1=External AI3, 2=Internal RH, 3=Internal Temp, 4=Internal Alternating, 5=Network | |
| MV | 101 | Cfg_ControlRHSource | Select the control humidity source | Write | 1=None, 2=AI4, 3=TRLH, 4=Network | |
| MV | 102 | Cfg_ControlTempSource | Select the control temperature source | Write | 1=None, 2=AI5, 3=TRLH, 4=Network | |
| MV | 103 | Cfg_ControlSetpointSource | Select the control setpoint source | Write | 1=AI3, 2=Internal, 3=Network | |
| MV | 104 | Cfg_HighLimitSource | Select high limit source for analog input 1 | Write | 1=None, 2=AI6, 3=Network | |
| MV | 105 | Cfg_ObjectListMode | Select the category of BACnet objects to display | Write | 1=Integrator, 2=Advanced, 3=Factory | |
| MV | 300 | Cfg_AI3Signal | Signal type for the analog input 3 | Write | 1=0-10Vdc, 2=2-10Vdc | |
| MV | 301 | Cfg_AI4Signal | Signal type for the analog input 4 | Write | 1=0-10Vdc, 2=2-10Vdc | |
| MV | 302 | Cfg_AI5Signal | Signal type for the analog input 5 | Write | 1=0-10Vdc, 2=2-10Vdc | |
| MV | 303 | Cfg_AI6Signal | Signal type for the analog input 6 | Write | 1=0-10Vdc, 2=2-10Vdc | |
| MV | 304 | Cfg_FeedbackSignal | Signal type for the feedback signal | Write | 1=0-20mA, 2=4-20mA | |
| FILE | 1 | FirmwareUpdateFile | File object of the firmware upgrade | Write | ||
| FILE | 2 | BootloaderUpdateFile | File object of the bootloader firmware upgrade | Write | ||
| Other | 1 | FirmwareUpdateTask | Firmware upgrade task | Read | ||
| SCH | 1 | OccupancySchedule | Weekly occupancy schedule to specify which occupancy state is active during specific | Write |
No points match these filters.
Object ID lookup: Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller point IDs by name
AI3RoomRHSetpoint or RoomTempSetpointAI4RoomRHAI5RoomTempAI6DuctRHAI7TrlhRHAI8TrlhTempAI9BoardTempAI200DI4_TpmDutyAO1FeedbackVoltageAV1ZoneDemandAV2SimulatedDemandAV3ZoneOutputAV4ZoneOuputLimitAV5UnoccupiedRHSetpointAV6UnoccupiedTempSetpointAV7VacantRHSetpointAV8VacantTempSetpointAV9InternalRHSetpointAV10InternalTempSetpointAV11NetworkRHSetpointAV12NetworkTempSetpointAV13NetworkRHAV14NetworkTempAV15NetworkDowncounterAV100Cfg_InactivityDelayAV101Cfg_InactivityDrainTimeAV102Cfg_NetworkTimeoutAV103Cfg_FanOnDelayAV104Cfg_FanOffDelayAV200Stage1RuntimeAV201Stage2RuntimeAV202Stage3RuntimeAV203Stage4RuntimeAV300Cfg_DuctRHSetpointAV301Cfg_DuctRHCutoutAV302Cfg_DuctRHPropBandAV303Cfg_DuctRHIntegralTimeAV304Cfg_DuctRHDerivateTimeAV305Cfg_RHProportionalBandAV306Cfg_TempProportionalBandAV307Cfg_IntegralTimeAV308Cfg_DifferentialTimeAV309Cfg_TrlhRHSetpointMinAV310Cfg_TrlhRHSetpointMaxAV311Cfg_TrlhTempSetpointMinAV312Cfg_TrlhTempSetpointMaxAV313Cfg_RoomRHSetpointMinAV314Cfg_RoomRHSetpointMaxAV315Cfg_RoomTempSetpointMinAV316Cfg_RoomTempSetpointMaxAV317Cfg_RoomRHMinAV318Cfg_RoomRHMaxAV319Cfg_RoomTempMinAV320Cfg_RoomTempMaxAV321Cfg_StageOnDelayAV323Cfg_TPMStagePeriodAV324Cfg_RoomRHSetpointOffsetAV325Cfg_RoomTempSetpointOffsetAV326Cfg_RoomRHSOffsetAV327Cfg_RoomTempOffsetAV328Cfg_DuctRHOffsetAV329Cfg_BoardTempOffsetAV330Cfg_TrlhRoomRHOffsetAV331Cfg_TRLRoomTempOffsetBI1DI1_AirflowCutoutBI2DI2_DuctRHCutoutBI3DI3_InterlockCutoutBI4DI4_BinaryDemandBO1FanControlBO200ZoneDrainBO201ZoneInletBV1SystemModeBV2ZoneModeBV3WaterPressureBV4LimitedByDuctRHBV30AL_GlobalAlarmMaskBV31AL_DuctRHCutoutBV32AL_AirflowCutoutBV33AL_InterlockCutoutBV34AL_NoCoordinatorBV35AL_TrlhTimeoutBV36AL_NetworkTimeoutBV37AL_InvalidConfigurationBV100Cfg_EnableFanControlBV101Cfg_InhibitAirFlowCutoutBV102Cfg_NetworkControlOverrideBV103Cfg_NetworkTempUnitsBV104Cfg_NetworkMassFlowUnitsBV105Cfg_TRLHTempUnitsBV106Cfg_TRLHSetpointLockBV107Cfg_TRLHZoneModeLockBV108Cfg_TRLHDisplayTimeBV109Cfg_TRLHTimeFormatBV200SimulationStateBV201Stage1OutputBV203Stage2OutputBV204Stage3OutputBV205Stage4OutputBV230AL_BoardSensorFailureBV231AL_RoomRHSensorFailureBV232AL_RoomTempSensorFailureBV233AL_DuctRHSensorFailureBV234AL_TrlhRHSensorFailureBV235AL_TrlhTempSensorFailureMV1ZoneStateMV2OccupancyMV100Cfg_ControlModeMV101Cfg_ControlRHSourceMV102Cfg_ControlTempSourceMV103Cfg_ControlSetpointSourceMV104Cfg_HighLimitSourceMV105Cfg_ObjectListModeMV300Cfg_AI3SignalMV301Cfg_AI4SignalMV302Cfg_AI5SignalMV303Cfg_AI6SignalMV304Cfg_FeedbackSignalFILE1FirmwareUpdateFileFILE2BootloaderUpdateFileSCH1OccupancySchedule
Integration notes
- Objects are grouped as Integrator, Integrator configuration and Advanced; MSV Cfg_ObjectListMode chooses which groups the device shows (Integrator, Advanced or Factory).
- Access: "Present Value" in the W? column is listed as writable, "Out of Service" (only the out-of-service property is writable) as read-only; commandable BOs are marked C.
- Out-of-service is cleared automatically after 15 minutes by default (Device proprietary property #1002).
- The pump station is a separate BACnet device with its own object list (see the SKH pump station list).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller
How many BACnet points does the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller have?
This list has 121 BACnet objects: 8 analog inputs, 1 analog output, 55 analog values, 4 binary inputs, 3 binary outputs, 33 binary values, 2 files, 1 schedule, 13 multi-state values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller BACnet points are writable?
84 of the 121 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller BACnet documentation?
The source is High Pressure Atomiser SKH Series BACnet User Guide (SKH-BACnet Guide-210104), revision 2021-01-04, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/SKH/20210107/SKH-BACnet%20Guide-210104.pdf.
What are the minimum BACnet points to integrate the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller?
Start with BV 2 ZoneMode (Zone on/off (1 = on)); MV 2 Occupancy (Occupancy: 1 occ, 2 unocc, 3 vacant, 4 off); MV 100 Cfg_ControlMode (Control mode; 5 = network); AV 1 ZoneDemand (Zone demand from the BMS, %); AV 11 NetworkRHSetpoint (Network RH setpoint); AV 13 NetworkRH (Network room RH from the BMS); MV 1 ZoneState (Zone state); AV 3 ZoneOutput (Zone output, %); AI 4 RoomRH (Room RH); BV 30 AL_GlobalAlarmMask (Global alarm (zone)).
How do I enable BMS control of the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller?
BV 2 ZoneMode turns the zone on; MSV 100 Cfg_ControlMode = 5 (Network) hands the demand to the BMS.
Does the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller need a BACnet heartbeat or have a communication timeout?
AV 102 Cfg_NetworkTimeout (1-15 min) sets how long network values are held; AV 15 counts down and BV 36 AL_NetworkTimeout flags a lapse.
Can the BMS supply sensor values to the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller?
MSV 101 / 102 = Network take room RH and temperature from AV 13 NetworkRH and AV 14 NetworkTemp; MSV 103 = Network takes the setpoint from AV 11 / AV 12.
How do I check these points on the real SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Neptronic BACnet points lists
- Room / indoor air quality controller (temperature, humidity, CO2, VOC)
Neptronic AROB universal room / IAQ controller
Neptronic AROB room controllers measuring temperature, humidity, CO2 and VOC, with 2 analog and 2 binary outputs.
Also known as: AROB, AROB24, Neptronic AROB, IAQ controller - Make-up air unit (electric heat)
Neptronic CMU Compact Make-up Air Unit
Neptronic CMU compact make-up air units with electric heating, EC fan, damper and optional exhaust fan outputs.
Also known as: CMU, Neptronic CMU - Fan coil unit controller
Neptronic EFCB Series Fan Coil Controller
Neptronic EFCB fan coil controllers (24, 120 or 240 Vac, 2 or 4 relays) for 2-pipe and 4-pipe fan coils with TFL/TDF room sensors.
Also known as: EFCB, EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4 - Fan coil unit controller
Neptronic EFCB-OE1 Series Fan Coil Controller
Neptronic EFCB-OE1 fan coil controllers (24 or 240 Vac, 0, 2 or 4 relays), an OEM variant of the EFCB series.
Also known as: EFCB-OE1, EFCB10T-OE1, EFCB12T-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1 - VAV terminal unit controller
Neptronic EVCB14N Series VAV Controller
Neptronic EVCB14N networkable VAV controllers with integrated damper actuator, pressure-independent or pressure-dependent, with 0-4 triac outputs.
Also known as: EVCB14N, EVCB14NIT0S, EVCB14NIT2S, EVCB14NIT4S, EVCB14NDT4S, EVCB14NIT0SF, EVCB14NIT4SF - VAV terminal unit controller
Neptronic EVCB14NxT4X VAV Controller (external motor)
Neptronic EVCB14N VAV controllers with four triac outputs that drive an external damper motor, pressure independent (IT4X) or dependent (DT4X).
Also known as: EVCB14NxT4X, EVCB14NIT4X, EVCB14NDT4X - VAV terminal unit controller
Neptronic EVCB44N Series VAV Controller
Neptronic EVCB44N VAV controllers without triac outputs, pressure independent (IT0S) or pressure dependent (DT0S).
Also known as: EVCB44N, EVCB44NIT0S, EVCB44NDT0S - Dual duct VAV terminal controller
Neptronic EVCBM Dual Duct VAV Controller
Neptronic EVCBM master controller used on dual duct terminals, with a second (slave) airflow channel for the other duct.
Also known as: EVCBM, EVCBM Dual Duct, EVCB dual duct - Electric duct heater / terminal reheat controller
Neptronic HECB electric duct heater controller
Neptronic electric duct heaters fitted with the HECB intelligent controller (staged and SSR, with optional EAS airflow sensing).
Also known as: HECB, HEC, Neptronic HECB, electric duct heater controller - Electric steam humidifier
Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module
Legacy Neptronic SK300 and SKE electric steam humidifiers fitted with the NEPIC BACnet MS/TP communication module.
Also known as: SK300, SKE, Neptronic SK300, Neptronic SKE, NEPIC, SK300-BACNET, SKE-BACNET - Steam humidifier valve controller
Neptronic SKDESC-xB
Neptronic SKDESC-xB electronic controllers for steam-to-steam / direct steam injection humidifier valves (ESCJx jacketed, ESCMx models).
Also known as: SKDESC, SKDESCxB, ESCJx, ESCMx, Electronic Steam Controller - Electric steam humidifier
Neptronic SKE4
Neptronic SKE4 electric (heating element) steam humidifiers, indoor and outdoor versions.
Also known as: SKE4 electric steam humidifier, SKE4-N, SKE4-E, SKE4 BACnet - Gas-fired steam humidifier
Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module
Older Neptronic SKG gas-fired steam humidifiers (before the SKG4) with the NEPICSKG BACnet MS/TP module, one to four tanks.
Also known as: SKG, SKG3, Neptronic SKG, NEPICSKG, SKG-BACNET, SKG gas fired humidifier - Gas-fired steam humidifier
Neptronic SKG4
Neptronic SKG4 gas-fired steam humidifiers with up to four humidifier modules.
Also known as: SKG4 gas fired humidifier, SKG4-N, SKG4-E, SKG4 BACnet - High-pressure atomising humidifier
Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station
The SKH pump station (master board) of older Neptronic SKH high pressure atomising humidifiers, before the SKH4.
Also known as: SKH, Neptronic SKH, SKH high pressure atomiser, SKH-BACnet Guide-210104 - High-pressure atomizing humidifier / cooler
Neptronic SKH4
Neptronic SKH4 high-pressure water atomizing humidifiers and evaporative coolers with up to six zones (A-F).
Also known as: SKH4 high-pressure atomizer, SKH4 BACnet - Reverse osmosis water treatment unit
Neptronic SKRO
Neptronic SKRO reverse osmosis water treatment units feeding humidifiers.
Also known as: SKRO reverse osmosis, SKRO BACnet - Steam-to-steam humidifier
Neptronic SKS4
Neptronic SKS4 steam-to-steam (boiler steam heated) humidifiers.
Also known as: SKS4 steam to steam humidifier, SKS4 BACnet - Evaporative humidifier
Neptronic SKV
Neptronic SKV evaporative (media) humidifiers with up to four modules.
Also known as: SKV evaporative humidifier, SKV BACnet - Evaporative cooler / humidifier
Neptronic SKVF
Neptronic SKVF series evaporative coolers (also used for humidification).
Also known as: SKVF evaporative cooler, SKVF Series, SKVF BACnet - Fan coil / zone thermostat controller
Neptronic TFxB Series Thermostat Controller
Neptronic TFxB24 communicating thermostats for 2-pipe and 4-pipe fan coils and zone heating/cooling, including the humidity (TFHB) and OE variants.
Also known as: TFCB24F3XYZ1, TFCB24F3XY2, TFHB24F3XYZ1, TFHB24F3XYZ2, TFCB24P3-OE1, TFHB24P3-OE1, TFHB24P3-OE2, TFxB24 - Zone thermostat controller (VAV / fan coil)
Neptronic TROB24 thermostat controller
Neptronic TROB24 communicating thermostats with universal inputs, analog outputs and triac (on/off, pulsing or floating) outputs.
Also known as: TROB24, TROB, TROB24T4, Neptronic TROB - Fan coil / zone thermostat controller
Neptronic TSUB universal wall-mount controller
Neptronic TSUB universal wall-mount controllers for fan coils, heat pumps and zone heating/cooling.
Also known as: TSUB, TSUB24, Neptronic TSUB - Fan coil / zone thermostat controller
Neptronic TUCB / TUHB universal controller (TUxB24C6X2)
Neptronic TUCB (cooling/heating) and TUHB (with humidity) universal room controllers, model TUxB24C6X2.
Also known as: TUCB, TUHB, TUxB24C6X2, TUCB24C6X2, TUHB24C6X2 - Fan coil / zone thermostat controller
Neptronic TUUB universal wall-mount controller
Neptronic TUUB universal wall-mount controllers for fan coils, heat pumps, VFDs and zone heating/cooling.
Also known as: TUUB, TUUB24, Neptronic TUUB
Source: High Pressure Atomiser SKH Series BACnet User Guide · SKH-BACnet Guide-210104 · rev. 2021-01-04. Object names, instances and units are reproduced as published; descriptions are our own.