High-pressure atomising humidifier zone controller · BACnet points list

Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller BACnet points list

Updated 12 November 2026

Short answer

Each EZC zone controller of an older SKH atomiser system is its own BACnet MS/TP device. It carries the zone demand and output, room and duct humidity and temperature readings, occupied, unoccupied, vacant, internal and network setpoints, network humidity and temperature inputs with a timeout, the control mode and source selectors, stage outputs, cutouts and sensor alarms, and a weekly occupancy schedule.

This page lists 121 BACnet objects for the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller — 84 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.

Manufacturer
Neptronic
Model
SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller
Equipment
High-pressure atomising humidifier zone controller
Equipment type
Humidifiers
BACnet objects
121 (84 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
153000 + MAC address
Also known as
SKH EZC, EZC, Neptronic SKH zone controller, SKH-BACnet Guide-210104
Source document
High Pressure Atomiser SKH Series BACnet User Guide · SKH-BACnet Guide-210104 · rev. 2021-01-04
Download CSV 121 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.

BMS integration notes: Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller

Integration in brief

Set MSV 2 Occupancy and BV 2 ZoneMode, choose the control mode (MSV 100) and sources (MSV 101-103). For network control write AV 1 ZoneDemand or the network setpoint and RH (AV 11, AV 13) before the network timeout (AV 102) runs out. Read MSV 1 ZoneState, AV 3 ZoneOutput, AI 4 room RH and the alarm flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2ZoneModeZone on/off (1 = on)Write
MV 2OccupancyOccupancy: 1 occ, 2 unocc, 3 vacant, 4 offWrite
MV 100Cfg_ControlModeControl mode; 5 = networkWrite
AV 1ZoneDemandZone demand from the BMS, %Write
AV 11NetworkRHSetpointNetwork RH setpointWrite
AV 13NetworkRHNetwork room RH from the BMSWrite
MV 1ZoneStateZone stateRead
AV 3ZoneOutputZone output, %Read
AI 4RoomRHRoom RHRead
BV 30AL_GlobalAlarmMaskGlobal alarm (zone)Read

Enable & remote start

BV 2 ZoneMode turns the zone on; MSV 100 Cfg_ControlMode = 5 (Network) hands the demand to the BMS.

Heartbeat & communication loss

AV 102 Cfg_NetworkTimeout (1-15 min) sets how long network values are held; AV 15 counts down and BV 36 AL_NetworkTimeout flags a lapse.

Sensors & values from the BMS

MSV 101 / 102 = Network take room RH and temperature from AV 13 NetworkRH and AV 14 NetworkTemp; MSV 103 = Network takes the setpoint from AV 11 / AV 12.

Network setup

Watch out for

Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

121 of 121 shown
Type
Multi-state
Access
Show
Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller BACnet Points List
DescriptionStates
AI3RoomRHSetpoint or RoomTempSetpointSetpoint for the room relative humidity sensor%RHRead
AImin4RoomRHReading of the relative humidity in the room%RHRead
AI5RoomTempTemperature reading of the room°CRead
AI6DuctRHRelative humidity reading of the duct%RHRead
AI7TrlhRHValue of the relative humidity measured on the TRL%RHRead
AI8TrlhTempValue of the temperature measured on the TRL°CRead
AI9BoardTempTemperature reading measured on the PC board°CRead
AI200DI4_TpmDutyDI4 time-proportional duty (no description printed)msRead
AO1FeedbackVoltageOutput feedback voltagemVWrite
AVmin1ZoneDemandZone demand%Write
AV2SimulatedDemandSimulated demand%Write
AVmin3ZoneOutputValue of the zone output%Read
AV4ZoneOuputLimitMaximum zone output limit%Write
AV5UnoccupiedRHSetpointRelative humidity setpoint in the unoccupied mode%RHWrite
AV6UnoccupiedTempSetpointTemperature setpoint in the unoccupied mode°CWrite
AV7VacantRHSetpointRelative humidity setpoint in the vacancy mode%RHWrite
AV8VacantTempSetpointTemperature setpoint in the vacancy mode°CWrite
AV9InternalRHSetpointInternal relative humidity setpoint%RHWrite
AV10InternalTempSetpointInternal temperature setpoint°CWrite
AVmin11NetworkRHSetpointNetwork relative humidity setpoint%RHWrite
AV12NetworkTempSetpointNetwork temperature setpoint°CWrite
AVmin13NetworkRHNetwork relative humidity%Write
AV14NetworkTempNetwork temperature°CWrite
AV15NetworkDowncounterValue of the network downcountersRead
AV100Cfg_InactivityDelaySystem inactivity delayhWrite
AV101Cfg_InactivityDrainTimeInactivity delay of drainsWrite
AV102Cfg_NetworkTimeoutNetwork timeoutminWrite
AV103Cfg_FanOnDelayDelay in seconds before the fan is turned onsWrite
AV104Cfg_FanOffDelayDelay in seconds before the fan is turned offsWrite
AV200Stage1RuntimeValue of the stage 1 runtimeRead
AV201Stage2RuntimeValue of the stage 2 runtimeRead
AV202Stage3RuntimeValue of the stage 3 runtimeRead
AV203Stage4RuntimeValue of the stage 4 runtimeRead
AV300Cfg_DuctRHSetpointDuct relative humidity setpoint%RHWrite
AV301Cfg_DuctRHCutoutDuct relative humidity cutout%RHWrite
AV302Cfg_DuctRHPropBandDuct relative humidity proportional band%RHWrite
AV303Cfg_DuctRHIntegralTimeDuct relative humidity integral timesWrite
AV304Cfg_DuctRHDerivateTimeDuct relative humidity derivate timesWrite
AV305Cfg_RHProportionalBandRelative humidity proportional band%RHWrite
AV306Cfg_TempProportionalBandTemperature proportional band°CWrite
AV307Cfg_IntegralTimeIntegral timesWrite
AV308Cfg_DifferentialTimeDifferential timesWrite
AV309Cfg_TrlhRHSetpointMinMinimum relative humidity setpoint measured by the TRL%RHWrite
AV310Cfg_TrlhRHSetpointMaxMaximum relative humidity setpoint measured by the TRL%RHWrite
AV311Cfg_TrlhTempSetpointMinMinimum temperature setpoint measured by the TRL°CWrite
AV312Cfg_TrlhTempSetpointMaxMaximum temperature setpoint measured by the TRL°CWrite
AV313Cfg_RoomRHSetpointMinMinimum relative humidity setpoint of the room%RHWrite
AV314Cfg_RoomRHSetpointMaxMaximum relative humidity setpoint of the room%RHWrite
AV315Cfg_RoomTempSetpointMinMinimum temperature setpoint of the room°CWrite
AV316Cfg_RoomTempSetpointMaxMaximum temperature setpoint of the room°CWrite
AV317Cfg_RoomRHMinMinimum relative humidity of the room%RHWrite
AV318Cfg_RoomRHMaxMaximum relative humidity of the room%RHWrite
AV319Cfg_RoomTempMinMinimum temperature of the room°CWrite
AV320Cfg_RoomTempMaxMaximum temperature of the room°CWrite
AV321Cfg_StageOnDelayDelay before each stage is onsWrite
AV323Cfg_TPMStagePeriodTPM stage periodsWrite
AV324Cfg_RoomRHSetpointOffsetRelative humidity setpoint offset value of the room%RHWrite
AV325Cfg_RoomTempSetpointOffsetTemperature setpoint offset value of the room°CWrite
AV326Cfg_RoomRHSOffsetRelative humidity offset value of the room%RHWrite
AV327Cfg_RoomTempOffsetTemperature offset value of the room°CWrite
AV328Cfg_DuctRHOffsetRelative humidity offset value of the room%RHWrite
AV329Cfg_BoardTempOffsetTemperature offset value of the board°CWrite
AV330Cfg_TrlhRoomRHOffsetRelative humidity offset value of the room measured by the TRL%RHWrite
AV331Cfg_TRLRoomTempOffsetTemperature offset value of the room measured by the TRL°CWrite
BI1DI1_AirflowCutoutOpen or close the airflow cutoutWrite0=Open, 1=Close
BI2DI2_DuctRHCutoutOpen or close the duct RH cutoutWrite0=Open, 1=Close
BI3DI3_InterlockCutoutOpen or close the interlock cutoutWrite0=Open, 1=Close
BI4DI4_BinaryDemandOpen or close the binary demandWrite0=Open, 1=Close
BO1FanControlStatus of Fan controlRead0=Off, 1=On
BO200ZoneDrainStatus of zone drainRead0=Off, 1=On
BO201ZoneInletStatus of zone inletRead0=Off, 1=On
BV1SystemModeStatus of the system modeRead0=Off, 1=On
BVmin2ZoneModeEnable or disable the zone modeWrite0=Off, 1=On
BV3WaterPressureStatus of the water pressureRead0=Not Ready, 1=Ready
BV4LimitedByDuctRHStatus of the duct relative humidityRead0=Off, 1=On
BVmin30AL_GlobalAlarmMaskStatus of the global alarm maskRead0=Off, 1=On
BV31AL_DuctRHCutoutStatus of the duct relative humidity cutoutRead0=Off, 1=On
BV32AL_AirflowCutoutStatus of the airflow cutoutRead0=Off, 1=On
BV33AL_InterlockCutoutStatus of the interlock cutoutRead0=Off, 1=On
BV34AL_NoCoordinatorStatus of the communication between the master PCB and EZCRead0=Off, 1=On
BV35AL_TrlhTimeoutStatus of the communication timeout between the EZC and controllerRead0=Off, 1=On
BV36AL_NetworkTimeoutStatus of the communication timeout for the networkRead0=Off, 1=On
BV37AL_InvalidConfigurationStatus of the configurationRead0=Off, 1=On
BV100Cfg_EnableFanControlEnable or disable the fan controlWrite0=Off, 1=On
BV101Cfg_InhibitAirFlowCutoutEnable or disable the inhibit airflow cutoutWrite0=Off, 1=On
BV102Cfg_NetworkControlOverrideEnable or disable the network control overrideWrite0=Off, 1=On
BV103Cfg_NetworkTempUnitsTemperature unitWrite0=Celsius, 1=Fahrenheit
BV104Cfg_NetworkMassFlowUnitsMass flow unitWrite0=kg/h, 1=lb/h
BV105Cfg_TRLHTempUnitsTemperature unit on the TRLWrite0=Celsius, 1=Fahrenheit
BV106Cfg_TRLHSetpointLockLock the setpoint on the TRLWrite0=Off, 1=On
BV107Cfg_TRLHZoneModeLockLock the zone mode on the TRLWrite0=Off, 1=On
BV108Cfg_TRLHDisplayTimeDisplay the time on the TRLWrite0=Off, 1=On
BV109Cfg_TRLHTimeFormatTime format on the TRLWrite0=24H, 1=12H
BV200SimulationStateState of simulation modeRead0=Off, 1=On
BV201Stage1OutputEnable or disable the output value of stage 1Write0=Off, 1=On
BV203Stage2OutputEnable or disable the output value of stage 2Write0=Off, 1=On
BV204Stage3OutputEnable or disable the output value of stage 3Write0=Off, 1=On
BV205Stage4OutputEnable or disable the output value of stage 4Write0=Off, 1=On
BV230AL_BoardSensorFailureStatus of the alarm for the failure of the broad sensorRead0=Off, 1=On
BV231AL_RoomRHSensorFailureStatus of the alarm for the failure of the room relative humidityRead0=Off, 1=On
BV232AL_RoomTempSensorFailureStatus of the alarm for the failure of the room temperature sensorRead0=Off, 1=On
BV233AL_DuctRHSensorFailureStatus of the alarm for the failure of the duct relative humidityRead0=Off, 1=On
BV234AL_TrlhRHSensorFailureStatus of the alarm for the failure of the controller relative humidityRead0=Off, 1=On
BV235AL_TrlhTempSensorFailureStatus of the alarm for the failure of the controller temperature sensorRead0=Off, 1=On
MVmin1ZoneStateStatus of zoneRead1=POR, 2=Alarm, 3=Stand-By, 4=Drain Stages, 5=Drain Lines, 6=Ready
MVmin2OccupancyCurrent occupancy stateWrite1=Occupied, 2=Unoccupied, 3=Vacant, 4=Off
MVmin100Cfg_ControlModeSelect the control modeWrite1=External AI3, 2=Internal RH, 3=Internal Temp, 4=Internal Alternating, 5=Network
MV101Cfg_ControlRHSourceSelect the control humidity sourceWrite1=None, 2=AI4, 3=TRLH, 4=Network
MV102Cfg_ControlTempSourceSelect the control temperature sourceWrite1=None, 2=AI5, 3=TRLH, 4=Network
MV103Cfg_ControlSetpointSourceSelect the control setpoint sourceWrite1=AI3, 2=Internal, 3=Network
MV104Cfg_HighLimitSourceSelect high limit source for analog input 1Write1=None, 2=AI6, 3=Network
MV105Cfg_ObjectListModeSelect the category of BACnet objects to displayWrite1=Integrator, 2=Advanced, 3=Factory
MV300Cfg_AI3SignalSignal type for the analog input 3Write1=0-10Vdc, 2=2-10Vdc
MV301Cfg_AI4SignalSignal type for the analog input 4Write1=0-10Vdc, 2=2-10Vdc
MV302Cfg_AI5SignalSignal type for the analog input 5Write1=0-10Vdc, 2=2-10Vdc
MV303Cfg_AI6SignalSignal type for the analog input 6Write1=0-10Vdc, 2=2-10Vdc
MV304Cfg_FeedbackSignalSignal type for the feedback signalWrite1=0-20mA, 2=4-20mA
FILE1FirmwareUpdateFileFile object of the firmware upgradeWrite
FILE2BootloaderUpdateFileFile object of the bootloader firmware upgradeWrite
Other1FirmwareUpdateTaskFirmware upgrade taskRead
SCH1OccupancyScheduleWeekly occupancy schedule to specify which occupancy state is active during specificWrite
Object ID lookup: Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller

How many BACnet points does the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller have?

This list has 121 BACnet objects: 8 analog inputs, 1 analog output, 55 analog values, 4 binary inputs, 3 binary outputs, 33 binary values, 2 files, 1 schedule, 13 multi-state values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller BACnet points are writable?

84 of the 121 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller BACnet documentation?

The source is High Pressure Atomiser SKH Series BACnet User Guide (SKH-BACnet Guide-210104), revision 2021-01-04, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/SKH/20210107/SKH-BACnet%20Guide-210104.pdf.

What are the minimum BACnet points to integrate the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller?

Start with BV 2 ZoneMode (Zone on/off (1 = on)); MV 2 Occupancy (Occupancy: 1 occ, 2 unocc, 3 vacant, 4 off); MV 100 Cfg_ControlMode (Control mode; 5 = network); AV 1 ZoneDemand (Zone demand from the BMS, %); AV 11 NetworkRHSetpoint (Network RH setpoint); AV 13 NetworkRH (Network room RH from the BMS); MV 1 ZoneState (Zone state); AV 3 ZoneOutput (Zone output, %); AI 4 RoomRH (Room RH); BV 30 AL_GlobalAlarmMask (Global alarm (zone)).

How do I enable BMS control of the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller?

BV 2 ZoneMode turns the zone on; MSV 100 Cfg_ControlMode = 5 (Network) hands the demand to the BMS.

Does the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller need a BACnet heartbeat or have a communication timeout?

AV 102 Cfg_NetworkTimeout (1-15 min) sets how long network values are held; AV 15 counts down and BV 36 AL_NetworkTimeout flags a lapse.

Can the BMS supply sensor values to the Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller?

MSV 101 / 102 = Network take room RH and temperature from AV 13 NetworkRH and AV 14 NetworkTemp; MSV 103 = Network takes the setpoint from AV 11 / AV 12.

How do I check these points on the real SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Neptronic BACnet points lists

Source: High Pressure Atomiser SKH Series BACnet User Guide · SKH-BACnet Guide-210104 · rev. 2021-01-04. Object names, instances and units are reproduced as published; descriptions are our own.