 "manufacturer": "Neptronic",
 "manufacturer_slug": "neptronic",
 "model": "SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module",
 "model_slug": "skg-legacy",
 "aliases": [
  "SKG",
  "SKG3",
  "Neptronic SKG",
  "NEPICSKG",
  "SKG-BACNET",
  "SKG gas fired humidifier"
 ],
 "equipment_type": "Gas-fired steam humidifier",
 "applies_to": "Older Neptronic SKG gas-fired steam humidifiers (before the SKG4) with the NEPICSKG BACnet MS/TP module, one to four tanks.",
 "summary": "The NEPICSKG module gives the older SKG gas-fired humidifier a BACnet MS/TP interface (B-ASC). A common block (instances 1-99) carries humidity output, demand, room and duct humidity, setpoints, delays, PID settings, status and alarm flags and the control, operation and source selectors; each tank adds its own block (101-199 for tank 1 up to 401-499 for tank 4) with water and chimney temperatures, water level, burner demand and fan speed, timers, status flags and alarms.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "1.00",
 "default_device_instance": 153000,
 "access_inferred": false,
 "notes": [
  "Objects for tanks 2-4 (instances 201-499) exist only on units with that many tanks; the guide gives 95 objects for one tank up to 200 for four.",
  "The tank 4 table prints OverFlow_DripPan4 as BV 414, the same instance as Tank_Temp_Low4 (it is probably BV 413); both rows are kept as printed.",
  "Typos kept as printed: H3OLvl_Prb_Bad3 / H4OLvl_Prb_Bad4 and the space in \"Modulation Stat1-4\".",
  "MSV 5 Room_Hum_Source is printed without the W flag the other selectors have.",
  "Access is from the W? column; the tank alarm BVs are printed as writable. The module does not send BACnet event notifications."
 ],
 "source": {
  "title": "Gas Fired Humidifier SKG Series - BACnet Communication Module User Guide",
  "doc_number": "SKG-BACNET",
  "revision_date": "Rev 060803",
  "url": "https://www.neptronic.com/Humidifiers/PDF/SKG3000/SKG-bacnet-user-guide.pdf"
 },
 "integration": {
  "summary": "For BMS demand control set MSV 1 Ctl_Mode to 3 and write AV 1 Humidity_Demand; for the internal PID set MSV 1 to 2, choose the setpoint and humidity sources (MSV 4-6) and write AV 16 and AV 2. MSV 2 turns the unit off, on or to drain. Read BI 1, AI 1 and the two summary alarms BI 4 and BI 5.",
  "minimum_points": [
   {
    "ref": "MV 2",
    "name": "Operation_Mode",
    "why": "Unit off, on or drain"
   },
   {
    "ref": "MV 1",
    "name": "Ctl_Mode",
    "why": "Control mode; 3 = demand from BACnet"
   },
   {
    "ref": "AV 1",
    "name": "Humidity_Demand",
    "why": "Humidity demand from the BMS, %"
   },
   {
    "ref": "AV 16",
    "name": "Ctl_SP",
    "why": "Humidity setpoint for internal PID, %RH"
   },
   {
    "ref": "AV 2",
    "name": "Room_Humidity",
    "why": "Room RH from the BMS (remote source)"
   },
   {
    "ref": "BI 1",
    "name": "Power_Status",
    "why": "Unit power on"
   },
   {
    "ref": "AI 1",
    "name": "Humidity_Out",
    "why": "Humidifier output, %"
   },
   {
    "ref": "BI 4",
    "name": "Alrm_Not_Critical",
    "why": "Non-critical alarm, unit still running"
   },
   {
    "ref": "BI 5",
    "name": "Alarm_Critical",
    "why": "Critical alarm, unit stopped"
   }
  ],
  "enable": "MSV 2 Operation_Mode sets the unit off (1), on (2) or to drain (3). MSV 1 Ctl_Mode picks the demand source: 1 = analog input 1, 2 = internal PID, 3 = remote demand over BACnet.",
  "heartbeat": null,
  "remote_sensors": "With MSV 5 Room_Hum_Source = 2 and MSV 6 Duct_Hum_Source = 3 (remote) the BMS writes AV 2 Room_Humidity and AV 4 Duct_Humidity; MSV 4 SP_Source = 3 takes the setpoint from BACnet.",
  "setup": [
   "A configuration DIP switch puts the module in configure mode (MAC 254, wildcard device instance 4194303); two more DIP switches set 9600, 19200, 38400 or 76800 baud.",
   "Defaults: MAC 0, device instance 153000, device name NEPSKGHumidifier153000, Max_Master 127; MAC and device instance can also be set from the unit keypad in configure mode."
  ],
  "gotchas": [
   "Tank objects only respond for tanks that exist on the unit.",
   "Temperatures follow BV 1 Temperature_Unit (Celsius or Fahrenheit)."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Humidity_Out",
   "description": "Humidity Output (0-100 %RH)",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Humidity_Demand",
   "description": "Humidity Demand (0-100 %RH)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Room_Humidity",
   "description": "Room Humidity (0-100 %RH)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Room_Humidity_Off",
   "description": "Room Humidity offset (±0-10.0 %RH)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Duct_Humidity",
   "description": "Duct Humidity (0-100 %RH)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Duct_Humidity_Off",
   "description": "Duct Humidity offset (±0-10.0 %RH)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Outside_Temp",
   "description": "Outside Temperature (-40 - 40 °C or -40 - 104 °F)",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Lock_On_Capacity",
   "description": "Lock On capacity (10-100%)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Max_Output_Limit",
   "description": "Maximum output limit (10-100%)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Drain_Delay",
   "description": "Drain Delay (1-100Hrs)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Service_Delay",
   "description": "Service Delay (1-5000Hrs)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "End_Season_Delay",
   "description": "End of season delay (1-250Hrs)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "PID_Loop_KP",
   "description": "PID Loop gain KP (0-255)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "PID_Loop_KI",
   "description": "PID Loop gain KI (0-255)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "PID_Loop_KD",
   "description": "PID Loop gain KD (0-255)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Ctl_Band",
   "description": "Control band (0-20.0% (0..200))",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Ctl_SP",
   "description": "Control set point (0-100%RH)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Extern_SP_Min",
   "description": "External setpoint minimum (0-100%RH)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Extern_SP_Max",
   "description": "External setpoint maximum (0-100%RH)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "Duct_Hum_HiLim_SP",
   "description": "Duct hum. high limit set point (50-100%RH)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Min_ON_Time_Fan",
   "description": "Minimum ON time for fan (2-20 minutes)",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Min_H2O_Temp",
   "description": "Min. water temp. in ON mode (50-90 °C or 122-194 °F (0",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "Antifreeze_Temp",
   "description": "Anti-freeze mode temperature (7-12 °C or 44-54 °F (0 -> Mode is",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Analog_Ctl_In_Lo",
   "description": "Analog Control input Lo Limit (0-10.00VDC)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Analog_Ctl_In_Hi",
   "description": "Analog Control input Hi Limit (0-10.00VDC)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Analog_Hum_In_Lo",
   "description": "Analog Humidity input Lo Limit (0-10.00VDC)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Analog_Hum_In_Hi",
   "description": "Analog Humidity input Hi Limit (0-10.00VDC)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Analog_Duct_In_Lo",
   "description": "Analog Duct input Lo Limit (0-10.00VDC)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Analog_Duct_In_Hi",
   "description": "Analog Duct input Hi Limit (0-10.00VDC)",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Power_Status",
   "description": "Power Status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Humidity_Demand",
   "description": "Humidity Demand",
   "units": "",
   "access": "R",
   "states": "0=NO, 1=YES"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Manual_Drain",
   "description": "Manual Drain",
   "units": "",
   "access": "R",
   "states": "0=NO, 1=YES"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Alrm_Not_Critical",
   "description": "Alarm not critical (unit running)",
   "units": "",
   "access": "R",
   "states": "0=NO, 1=YES"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Alarm_Critical",
   "description": "Alarm critical (unit not running)",
   "units": "",
   "access": "R",
   "states": "0=NO, 1=YES"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "End_of_Season_Dly",
   "description": "End of Season Delay",
   "units": "",
   "access": "R",
   "states": "0=NO, 1=YES"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Fan_Proof_Status",
   "description": "Fan proof Status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "HiLimit_Status",
   "description": "Hi-Limit Status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Interlock",
   "description": "Interlock",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "Thermal_Fuse_Ext",
   "description": "Thermal fuse (external 24VAC)",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Thermal_Fuse_Int",
   "description": "Thermal fuse (internal 24VDC)",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "Interlock_In_Open",
   "description": "Interlock input open",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "High_Hum_In_Duct",
   "description": "High humidity level in the duct",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Input_Voltage_Low",
   "description": "Input voltage too low",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "Thermal_Fuse_Open",
   "description": "Thermal Fuse open (24VAC)",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "Slave_Comm_Lost",
   "description": "Comm lost with slave board",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "Hum_Clean_Start",
   "description": "Humidifier started cleaning period",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "Hum_Ex_Svc_Time",
   "description": "Humidifier exceeded service time",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Temperature_Unit",
   "description": "Temperature Unit",
   "units": "",
   "access": "W",
   "states": "0=Celcius, 1=Fahrenheit"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "Outside_Temp_Comp",
   "description": "Outside Temp. Compensation",
   "units": "",
   "access": "W",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Alarm_Beep",
   "description": "Alarm Beep",
   "units": "",
   "access": "W",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "Demand_SP_Type",
   "description": "Demand/Set point type",
   "units": "",
   "access": "W",
   "states": "0=Voltage, 1=Current"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Humidity_In_Type",
   "description": "Humidity input type",
   "units": "",
   "access": "W",
   "states": "0=Voltage, 1=Current"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "HiLim_Hum_In_Type",
   "description": "Hi-limit humidity input type",
   "units": "",
   "access": "W",
   "states": "0=Voltage, 1=Current"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Ctl_Mode",
   "description": "Control Mode",
   "units": "",
   "access": "W",
   "states": "1=Demand from analog input 1 (default), 2=Internal PID loop calculation, 3=Demand from remote communication port (e.g. BACnet)"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Operation_Mode",
   "description": "Operation Mode",
   "units": "",
   "access": "W",
   "states": "1=Set unit Off, 2=Set unit On, 3=Set unit in drain mode"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "Unit_Display_Lang",
   "description": "Unit Display Language",
   "units": "",
   "access": "W",
   "states": "1=English (Default), 2=French, 3=Spanish"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "SP_Source",
   "description": "Setpoint Source",
   "units": "",
   "access": "W",
   "states": "1=Local analog input 1, 2=Local Internal digital value, 3=Remote from communication port (e.g. BACnet)"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "Room_Hum_Source",
   "description": "Room Humidity Source",
   "units": "",
   "access": "R",
   "states": "1=Local analog input 2 (default), 2=Remote from communication port (e.g. BACnet)"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "Duct_Hum_Source",
   "description": "Duct Humidity Source",
   "units": "",
   "access": "W",
   "states": "1=Not used, 2=Local analog input 3, 3=Remote from communication port (e.g. BACnet)"
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "Water_Temp1",
   "description": "Water Temperature 1 (0-260 °C or 32-500 °F)",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "Chimney_Temp1",
   "description": "Chimney Temperature 1 (0-260 °C or 32-500 °F)",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "Water_Level1",
   "description": "Water level 1 (0-120%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "Burner_Demand1",
   "description": "Burner Demand 1 (0.0 - 100.0%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "Op_Timer_Total1",
   "description": "Operation Timer 1 (Total time) (1-1677215Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 106,
   "name": "Op_Timer1",
   "description": "Operation Timer 1 (1-5000Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 107,
   "name": "Delay_Autodrain1",
   "description": "Delay until Auto-drain 1 (1-100Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 108,
   "name": "Foam_Probe_Sensr1",
   "description": "Foam Probe Sensor 1 (0-255)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 109,
   "name": "Burner_Fan_Speed1",
   "description": "Burner Fan Speed 1 (0-1000Hz)",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "Water_Temp_Off1",
   "description": "Water Temperature offset 1 (±0-20 °C or ±0-40 °F)",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "Chimney_Temp_Off1",
   "description": "Chimney Temperature offset 1 (±0-20 °C or ±0-40 °F)",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "Water_Level_Off1",
   "description": "Water Level offset 1 (±0-20%)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 101,
   "name": "OverTemp_Cont_ON1",
   "description": "Over temperature contact ON 1",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 102,
   "name": "Bad_Fill_Tank1",
   "description": "Defective filling tank 1",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 103,
   "name": "Bad_Refill_Tank1",
   "description": "Defective refill tank 1(too long)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 104,
   "name": "Bad_Drain_Tank1",
   "description": "Defective draining tank 1",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 105,
   "name": "Bad_Burner_Fan1",
   "description": "Defective Burner Fan 1",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 106,
   "name": "Bad_Burner_Gas1",
   "description": "Defective Burner Gas 1(Locked)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 107,
   "name": "Input_Volt_Low1",
   "description": "Input voltage 1 too low",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 108,
   "name": "Power_Fuse_Open1",
   "description": "Power Fuse 1 open (24VAC)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 109,
   "name": "Tank_Sens_Bad1",
   "description": "Tank sensor 1 defective",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 110,
   "name": "Chim_Sens_Bad1",
   "description": "Chimney sensor 1 defective",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 111,
   "name": "H2OLvl_Prb_Bad1",
   "description": "Water level probe 1 defect",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 112,
   "name": "Foam_Sens_ON1",
   "description": "Foam Sensor 1 ON",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 113,
   "name": "OverFlow_DripPan1",
   "description": "Over Flow, Drip Pan 1",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 114,
   "name": "Tank_Temp_Low1",
   "description": "Tank temper. 1 Too low (freeze)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 115,
   "name": "Tank_Temp_Hi1",
   "description": "Tank temperature 1 too high",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 116,
   "name": "Chimney_Temp_Hi1",
   "description": "Chimney temperature 1 too high",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 101,
   "name": "Burner_Valve1",
   "description": "Burner Valve 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 102,
   "name": "Burner_Fan1",
   "description": "Burner Fan 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 103,
   "name": "Fill_Tank1",
   "description": "Fill Tank 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 104,
   "name": "Drain_Tank1",
   "description": "Drain Tank 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 105,
   "name": "Water_Level_OK1",
   "description": "Water Level 1 Okay",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 106,
   "name": "Modulation Stat1",
   "description": "Modulation Status 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "MI",
   "instance": 101,
   "name": "Unit_Size1",
   "description": "Unit Size 1",
   "units": "",
   "access": "R",
   "states": "1=100Lbs/Hr, 2=150Lbs/Hr, 3=175Lbs/Hr, 4=200Lbs/Hr"
  },
  {
   "type": "AI",
   "instance": 201,
   "name": "Water_Temp2",
   "description": "Water Temperature 2 (0-260 °C or 32-500 °F)",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 202,
   "name": "Chimney_Temp2",
   "description": "Chimney Temperature 2 (0-260 °C or 32-500 °F)",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 203,
   "name": "Water_Level2",
   "description": "Water level 2 (0-120%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 204,
   "name": "Burner_Demand2",
   "description": "Burner Demand 2 (0.0 - 100.0%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 205,
   "name": "Op_Timer_Total2",
   "description": "Operation Timer 2 (Total time) (1-1677215Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 206,
   "name": "Op_Timer2",
   "description": "Operation Timer 2 (1-5000Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 207,
   "name": "Delay_Autodrain2",
   "description": "Delay until Auto-drain 2 (1-100Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 208,
   "name": "Foam_Probe_Sensr2",
   "description": "Foam Probe Sensor 2 (0-255)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 209,
   "name": "Burner_Fan_Speed2",
   "description": "Burner Fan Speed 2 (0-1000Hz)",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 201,
   "name": "Water_Temp_Off2",
   "description": "Water Temperature offset 2 (±0-20 °C or ±0-40 °F)",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 202,
   "name": "Chimney_Temp_Off2",
   "description": "Chimney Temperature offset 2 (±0-20 °C or ±0-40 °F)",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 203,
   "name": "Water_Level_Off2",
   "description": "Water Level offset 2 (±0-20%)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 201,
   "name": "OverTemp_Cont_ON2",
   "description": "Over temperature contact ON 2",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 202,
   "name": "Bad_Fill_Tank2",
   "description": "Defective filling tank 2",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 203,
   "name": "Bad_Refill_Tank2",
   "description": "Defective refill tank 2(too long)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 204,
   "name": "Bad_Drain_Tank2",
   "description": "Defective draining tank 2",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 205,
   "name": "Bad_Burner_Fan2",
   "description": "Defective Burner Fan 2",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 206,
   "name": "Bad_Burner_Gas2",
   "description": "Defective Burner Gas 2(Locked)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 207,
   "name": "Input_Volt_Low2",
   "description": "Input voltage 2 too low",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 208,
   "name": "Power_Fuse_Open2",
   "description": "Power Fuse 2 open (24VAC)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 209,
   "name": "Tank_Sens_Bad2",
   "description": "Tank sensor 2 defective",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 210,
   "name": "Chim_Sens_Bad2",
   "description": "Chimney sensor 2 defective",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 211,
   "name": "H2OLvl_Prb_Bad2",
   "description": "Water level probe 2 defect",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 212,
   "name": "Foam_Sens_ON2",
   "description": "Foam Sensor 2 ON",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 213,
   "name": "OverFlow_DripPan2",
   "description": "Over Flow, Drip Pan 2",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 214,
   "name": "Tank_Temp_Low2",
   "description": "Tank temper. 2 Too low (freeze)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 215,
   "name": "Tank_Temp_Hi2",
   "description": "Tank temperature 2 too high",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 216,
   "name": "Chimney_Temp_Hi2",
   "description": "Chimney temperature 2 too high",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 201,
   "name": "Burner_Valve2",
   "description": "Burner Valve 2",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 202,
   "name": "Burner_Fan2",
   "description": "Burner Fan 2",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 203,
   "name": "Fill_Tank2",
   "description": "Fill Tank 2",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 204,
   "name": "Drain_Tank2",
   "description": "Drain Tank 2",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 205,
   "name": "Water_Level_OK2",
   "description": "Water Level 2 Okay",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 206,
   "name": "Modulation Stat2",
   "description": "Modulation Status 2",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "MI",
   "instance": 201,
   "name": "Unit_Size2",
   "description": "Unit Size 2",
   "units": "",
   "access": "R",
   "states": "1=100Lbs/Hr, 2=150Lbs/Hr, 3=175Lbs/Hr, 4=200Lbs/Hr"
  },
  {
   "type": "AI",
   "instance": 301,
   "name": "Water_Temp3",
   "description": "Water Temperature 3 (0-260 °C or 32-500 °F)",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 302,
   "name": "Chimney_Temp3",
   "description": "Chimney Temperature 3 (0-260 °C or 32-500 °F)",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 303,
   "name": "Water_Level3",
   "description": "Water level 3 (0-120%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 304,
   "name": "Burner_Demand3",
   "description": "Burner Demand 3 (0.0 - 100.0%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 305,
   "name": "Op_Timer_Total3",
   "description": "Operation Timer 3 (Total time) (1-1677215Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 306,
   "name": "Op_Timer3",
   "description": "Operation Timer 3 (1-5000Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 307,
   "name": "Delay_Autodrain3",
   "description": "Delay until Auto-drain 3 (1-100Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 308,
   "name": "Foam_Probe_Sensr3",
   "description": "Foam Probe Sensor 3 (0-255)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 309,
   "name": "Burner_Fan_Speed3",
   "description": "Burner Fan Speed 3 (0-1000Hz)",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 301,
   "name": "Water_Temp_Off3",
   "description": "Water Temperature offset 3 (±0-20 °C or ±0-40 °F)",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 302,
   "name": "Chimney_Temp_Off3",
   "description": "Chimney Temperature offset 3 (±0-20 °C or ±0-40 °F)",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 303,
   "name": "Water_Level_Off3",
   "description": "Water Level offset 3 (±0-20%)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 301,
   "name": "OverTemp_Cont_ON3",
   "description": "Over temperature contact ON 3",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 302,
   "name": "Bad_Fill_Tank3",
   "description": "Defective filling tank 3",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 303,
   "name": "Bad_Refill_Tank3",
   "description": "Defective refill tank 3(too long)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 304,
   "name": "Bad_Drain_Tank3",
   "description": "Defective draining tank 3",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 305,
   "name": "Bad_Burner_Fan3",
   "description": "Defective Burner Fan 3",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 306,
   "name": "Bad_Burner_Gas3",
   "description": "Defective Burner Gas 3(Locked)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 307,
   "name": "Input_Volt_Low3",
   "description": "Input voltage 3 too low",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 308,
   "name": "Power_Fuse_Open3",
   "description": "Power Fuse 3 open (34VAC)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 309,
   "name": "Tank_Sens_Bad3",
   "description": "Tank sensor 3 defective",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 310,
   "name": "Chim_Sens_Bad3",
   "description": "Chimney sensor 3 defective",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 311,
   "name": "H3OLvl_Prb_Bad3",
   "description": "Water level probe 3 defect",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 312,
   "name": "Foam_Sens_ON3",
   "description": "Foam Sensor 3 ON",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 313,
   "name": "OverFlow_DripPan3",
   "description": "Over Flow, Drip Pan 3",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 314,
   "name": "Tank_Temp_Low3",
   "description": "Tank temper. 3 Too low (freeze)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 315,
   "name": "Tank_Temp_Hi3",
   "description": "Tank temperature 3 too high",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 316,
   "name": "Chimney_Temp_Hi3",
   "description": "Chimney temperature 3 too high",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 301,
   "name": "Burner_Valve3",
   "description": "Burner Valve 3",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 302,
   "name": "Burner_Fan3",
   "description": "Burner Fan 3",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 303,
   "name": "Fill_Tank3",
   "description": "Fill Tank 3",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 304,
   "name": "Drain_Tank3",
   "description": "Drain Tank 3",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 305,
   "name": "Water_Level_OK3",
   "description": "Water Level 3 Okay",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 306,
   "name": "Modulation Stat3",
   "description": "Modulation Status 3",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "MI",
   "instance": 301,
   "name": "Unit_Size3",
   "description": "Unit Size 3",
   "units": "",
   "access": "R",
   "states": "1=100Lbs/Hr, 2=150Lbs/Hr, 3=175Lbs/Hr, 4=200Lbs/Hr"
  },
  {
   "type": "AI",
   "instance": 401,
   "name": "Water_Temp4",
   "description": "Water Temperature 4 (0-260 °C or 32-500 °F)",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 402,
   "name": "Chimney_Temp4",
   "description": "Chimney Temperature 4 (0-260 °C or 32-500 °F)",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 403,
   "name": "Water_Level4",
   "description": "Water level 4 (0-120%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 404,
   "name": "Burner_Demand4",
   "description": "Burner Demand 4 (0.0 - 100.0%)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 405,
   "name": "Op_Timer_Total4",
   "description": "Operation Timer 4 (Total time) (1-1677215Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 406,
   "name": "Op_Timer4",
   "description": "Operation Timer 4 (1-5000Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 407,
   "name": "Delay_Autodrain4",
   "description": "Delay until Auto-drain 4 (1-100Hrs)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 408,
   "name": "Foam_Probe_Sensr4",
   "description": "Foam Probe Sensor 4 (0-255)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 409,
   "name": "Burner_Fan_Speed4",
   "description": "Burner Fan Speed 4 (0-1000Hz)",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 401,
   "name": "Water_Temp_Off4",
   "description": "Water Temperature offset 4 (±0-20 °C or ±0-40 °F)",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 402,
   "name": "Chimney_Temp_Off4",
   "description": "Chimney Temperature offset 4 (±0-20 °C or ±0-40 °F)",
   "units": "°C/°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 403,
   "name": "Water_Level_Off4",
   "description": "Water Level offset 4 (±0-20%)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 401,
   "name": "OverTemp_Cont_ON4",
   "description": "Over temperature contact ON 4",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 402,
   "name": "Bad_Fill_Tank4",
   "description": "Defective filling tank 4",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 403,
   "name": "Bad_Refill_Tank4",
   "description": "Defective refill tank 4(too long)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 404,
   "name": "Bad_Drain_Tank4",
   "description": "Defective draining tank 4",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 405,
   "name": "Bad_Burner_Fan4",
   "description": "Defective Burner Fan 4",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 406,
   "name": "Bad_Burner_Gas4",
   "description": "Defective Burner Gas 4(Locked)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 407,
   "name": "Input_Volt_Low4",
   "description": "Input voltage 4 too low",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 408,
   "name": "Power_Fuse_Open4",
   "description": "Power Fuse 4 open (44VAC)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 409,
   "name": "Tank_Sens_Bad4",
   "description": "Tank sensor 4 defective",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 410,
   "name": "Chim_Sens_Bad4",
   "description": "Chimney sensor 4 defective",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 411,
   "name": "H4OLvl_Prb_Bad4",
   "description": "Water level probe 4 defect",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 412,
   "name": "Foam_Sens_ON4",
   "description": "Foam Sensor 4 ON",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 414,
   "name": "OverFlow_DripPan4",
   "description": "Over Flow, Drip Pan 4",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 414,
   "name": "Tank_Temp_Low4",
   "description": "Tank temper. 4 Too low (freeze)",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 415,
   "name": "Tank_Temp_Hi4",
   "description": "Tank temperature 4 too high",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 416,
   "name": "Chimney_Temp_Hi4",
   "description": "Chimney temperature 4 too high",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 401,
   "name": "Burner_Valve4",
   "description": "Burner Valve 4",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 402,
   "name": "Burner_Fan4",
   "description": "Burner Fan 4",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 403,
   "name": "Fill_Tank4",
   "description": "Fill Tank 4",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 404,
   "name": "Drain_Tank4",
   "description": "Drain Tank 4",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 405,
   "name": "Water_Level_OK4",
   "description": "Water Level 4 Okay",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 406,
   "name": "Modulation Stat4",
   "description": "Modulation Status 4",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "MI",
   "instance": 401,
   "name": "Unit_Size4",
   "description": "Unit Size 4",
   "units": "",
   "access": "R",
   "states": "1=100Lbs/Hr, 2=150Lbs/Hr, 3=175Lbs/Hr, 4=200Lbs/Hr"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/neptronic/skg-legacy",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}