Power and energy meter (BACnet IP) · BACnet points list

Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The PM7000 series are panel-mount three-phase power and energy meters with Modbus Ethernet and BACnet IP. The BACnet object list is read-only: Analog Inputs for meter setup, energy (delivered, received, net and up to 16 tariffs), current, voltage, unbalance, power, power factor, frequency, demand (last, present, predicted, peak) and harmonic distortion, plus Binary and Multi-state Inputs for the digital I/O, relays and their modes. Instances follow the meter's register numbers.

This page lists 203 BACnet objects for the Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Schneider Electric’s documentation hosted by BACnet International catalog, not by Schneider Electric itself, so treat it as unofficial.

Manufacturer
Schneider Electric
Model
PowerLogic PM7000 series power and energy meter (BACnet IP)
Equipment
Power and energy meter (BACnet IP)
Equipment type
Thermostats, sensors & meters
BACnet objects
203 (0 writable)
Transport
BACnet IP
Firmware
1.0.1 (application 1.0.31)
Also known as
PM7000, PM7351DUW, PM7252DUW, PM7151DUW, PM7142DUW, PM7351, PM7252, PM7151, PM7142, PowerLogic Intuitive PM7000
Source document
PM7000 Protocol Implementation Conformance Statement · rev. 2026-07-01 (unofficial copy, hosted by BACnet International catalog)
Download CSV 203 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.

BMS integration notes: Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP)

Integration in brief

Enable BACnet IP on the meter with a unique device ID, then read total power, delivered energy, demand, power factor, voltage and current. The meter is monitoring-only over BACnet.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3060Active Power - TotalTotal active powerRead
AI 2700Active Energy DelvdActive energy deliveredRead
AI 3766Dmd - Active Power PresPresent active power demandRead
AI 3084Power Factor - TotalTotal power factorRead
AI 3026Voltage - Avg L-LAverage line-to-line voltageRead
AI 3010Current - AvgAverage phase currentRead
AI 3110FrequencySystem frequencyRead

Network setup

Watch out for

Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

203 of 203 shown
Type
AnalogBinaryMulti-state
Show
Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP) BACnet Points List
DescriptionStates
AI2000Time since last meter power upTime since last meter power upRead
AI2004Meter Operation TimerMeter Operation TimerRead
AI2014Number of phasesNumber of phasesRead
AI2015Number of wiresNumber of wiresRead
AI2017Nominal frequencyNominal frequencyRead
AI2025Number of VTsNumber of VTsRead
AI2026VT primaryVT primaryRead
AI2028VT secondaryVT secondaryRead
AI2029Number of CTsNumber of CTsRead
AI2030CT primaryCT primaryRead
AI2031CT secondaryCT secondaryRead
AImin2700Active Energy DelvdActive Energy deliveredRead
AI2702Active Energy RcvdActive Energy receivedRead
AI2704Active Energy Delvd + RcvdActive Energy delivered plus receivedRead
AI2706Active Energy Delvd - RcvdActive Energy delivered minus receivedRead
AI2708Reactive Energy DelvdReactive Energy deliveredRead
AI2710Reactive Energy RcvdReactive Energy receivedRead
AI2712Reactive Energy Delvd + RcvdReactive Energy delivered plus receivedRead
AI2714Reactive Energy Delvd - RcvdReactive Energy delivered minus receivedRead
AI2716Apparent Energy DelvdApparent Energy deliveredRead
AI2718Apparent Energy RcvdApparent Energy receivedRead
AI2720Apparent Energy Delvd + RcvdApparent Energy delivered plus receivedRead
AI2722Apparent Energy Delvd - RcvdApparent Energy delivered minus receivedRead
AI3000Current - Ph ACurrent phase ARead
AI3002Current - Ph BCurrent phase BRead
AI3004Current - Ph CCurrent phase CRead
AI3006Current - NeutralCurrent NeutralRead
AI3008Current - GroundCurrent GroundRead
AImin3010Current - AvgCurrent averageRead
AI3012Current Unb - Ph ACurrent unbalance phase ARead
AI3014Current Unb - Ph BCurrent unbalance phase BRead
AI3016Current Unb - Ph CCurrent unbalance phase CRead
AI3018Current Unb - WorstCurrent unbalance WorstRead
AI3020Voltage - A-BVoltage A-BRead
AI3022Voltage - B-CVoltage B-CRead
AI3024Voltage - C-AVoltage C-ARead
AImin3026Voltage - Avg L-LVoltage average L-LRead
AI3028Voltage - A-NVoltage A-NRead
AI3030Voltage - B-NVoltage B-NRead
AI3032Voltage - C-NVoltage C-NRead
AI3036Voltage - Avg L-NVoltage average L-NRead
AI3038Voltage Unb - A-BVoltage unbalance A-BRead
AI3040Voltage Unb - B-CVoltage unbalance B-CRead
AI3042Voltage Unb - C-AVoltage unbalance C-ARead
AI3044Voltage Unb - Worst L-LVoltage unbalance Worst L-LRead
AI3046Voltage Unb - A-NVoltage unbalance A-NRead
AI3048Voltage Unb - B-NVoltage unbalance B-NRead
AI3050Voltage Unb - C-NVoltage unbalance C-NRead
AI3052Voltage Unb - Worst L-NVoltage unbalance Worst L-NRead
AI3054Active Power - Ph AActive Power phase ARead
AI3056Active Power - Ph BActive Power phase BRead
AI3058Active Power - Ph CActive Power phase CRead
AImin3060Active Power - TotalActive Power TotalRead
AI3062Reactive Power - Ph AReactive Power phase ARead
AI3064Reactive Power - Ph BReactive Power phase BRead
AI3066Reactive Power - Ph CReactive Power phase CRead
AI3068Reactive Power - TotalReactive Power TotalRead
AI3070Apparent Power - Ph AApparent Power phase ARead
AI3072Apparent Power - Ph BApparent Power phase BRead
AI3074Apparent Power - Ph CApparent Power phase CRead
AI3076Apparent Power - TotalApparent Power TotalRead
AI3078Power Factor - Ph APower Factor phase ARead
AI3080Power Factor - Ph BPower Factor phase BRead
AI3082Power Factor - Ph CPower Factor phase CRead
AImin3084Power Factor - TotalPower Factor TotalRead
AImin3110FrequencyFrequencyRead
AI3144Power Factor-IEC - Ph APower factor (IEC) phase ARead
AI3146Power Factor-IEC - Ph BPower factor (IEC) phase BRead
AI3148Power Factor-IEC - Ph CPower factor (IEC) phase CRead
AI3176Power Factor-IEEE - Ph APower factor (IEEE) phase ARead
AI3178Power Factor-IEEE - Ph BPower factor (IEEE) phase BRead
AI3180Power Factor-IEEE - Ph CPower factor (IEEE) phase CRead
AI3192Power Factor IEC - TotalPower factor (IEC) TotalRead
AI3194Power Factor-IEEE - TotalPower factor (IEEE) TotalRead
AI3764Dmd - Active Power LastDemand Active Power last intervalRead
AImin3766Dmd - Active Power PresDemand Active Power presentRead
AI3768Dmd - Active Power PredDemand Active Power predictedRead
AI3770Dmd - Active Power PeakDemand Active Power peakRead
AI3780Dmd - Reactive Power LastDemand Reactive Power last intervalRead
AI3782Dmd - Reactive Power PresDemand Reactive Power presentRead
AI3784Dmd - Reactive Power PredDemand Reactive Power predictedRead
AI3786Dmd - Reactive Power PeakDemand Reactive Power peakRead
AI3796Dmd - Apparent Power LastDemand Apparent Power last intervalRead
AI3798Dmd - Apparent Power PresDemand Apparent Power presentRead
AI3800Dmd - Apparent Power PredDemand Apparent Power predictedRead
AI3802Dmd - Apparent Power PeakDemand Apparent Power peakRead
AI3812Dmd - Active Current Ph A LastDemand Active Current phase A last intervalRead
AI3814Dmd - Active Current Ph A PresDemand Active Current phase A presentRead
AI3816Dmd - Active Current Ph A PredDemand Active Current phase A predictedRead
AI3818Dmd - Active Current Ph A PeakDemand Active Current phase A peakRead
AI3828Dmd - Active Current Ph B LastDemand Active Current phase B last intervalRead
AI3830Dmd - Active Current Ph B PresDemand Active Current phase B presentRead
AI3832Dmd - Active Current Ph B PredDemand Active Current phase B predictedRead
AI3834Dmd - Active Current Ph B PeakDemand Active Current phase B peakRead
AI3844Dmd - Active Current Ph C LastDemand Active Current phase C last intervalRead
AI3846Dmd - Active Current Ph C PresDemand Active Current phase C presentRead
AI3848Dmd - Active Current Ph C PredDemand Active Current phase C predictedRead
AI3850Dmd - Active Current Ph C PeakDemand Active Current phase C peakRead
AI3860Dmd - Current Neutral LastDemand Current Neutral last intervalRead
AI3862Dmd - Current Neutral PresDemand Current Neutral presentRead
AI3864Dmd - Current Neutral PredDemand Current Neutral predictedRead
AI3866Dmd - Current Neutral PeakDemand Current Neutral peakRead
AI3876Dmd - Current Average LastDemand Current Average last intervalRead
AI3878Dmd - Current Average PresDemand Current Average presentRead
AI3880Dmd - Current Average PredDemand Current Average predictedRead
AI3882Dmd - Current Average PeakDemand Current Average peakRead
AI3972Dmd - Active Power Ph A LastDemand Active Power phase A last intervalRead
AI3974Dmd - Active Power Ph A PresDemand Active Power phase A presentRead
AI3976Dmd - Active Power Ph A PredDemand Active Power phase A predictedRead
AI3978Dmd - Active Power Ph A PeakDemand Active Power phase A peakRead
AI3988Dmd - Reactive Power Ph A LastDemand Reactive Power phase A last intervalRead
AI3990Dmd - Reactive Power Ph A PresDemand Reactive Power phase A presentRead
AI3992Dmd - Reactive Power Ph A PredDemand Reactive Power phase A predictedRead
AI3994Dmd - Reactive Power Ph A PeakDemand Reactive Power phase A peakRead
AI4004Dmd - Apparent Power Ph A LastDemand Apparent Power phase A last intervalRead
AI4006Dmd - Apparent Power Ph A PresDemand Apparent Power phase A presentRead
AI4008Dmd - Apparent Power Ph A PredDemand Apparent Power phase A predictedRead
AI4010Dmd - Apparent Power Ph A PeakDemand Apparent Power phase A peakRead
AI4020Dmd - Active Power Ph B LastDemand Active Power phase B last intervalRead
AI4022Dmd - Active Power Ph B PresDemand Active Power phase B presentRead
AI4024Dmd - Active Power Ph B PredDemand Active Power phase B predictedRead
AI4026Dmd - Active Power Ph B PeakDemand Active Power phase B peakRead
AI4036Dmd - Reactive Power Ph B LastDemand Reactive Power phase B last intervalRead
AI4038Dmd - Reactive Power Ph B PresDemand Reactive Power phase B presentRead
AI4040Dmd - Reactive Power Ph B PredDemand Reactive Power phase B predictedRead
AI4042Dmd - Reactive Power Ph B PeakDemand Reactive Power phase B peakRead
AI4052Dmd - Apparent Power Ph B LastDemand Apparent Power phase B last intervalRead
AI4054Dmd - Apparent Power Ph B PresDemand Apparent Power phase B presentRead
AI4056Dmd - Apparent Power Ph B PredDemand Apparent Power phase B predictedRead
AI4058Dmd - Apparent Power Ph B PeakDemand Apparent Power phase B peakRead
AI4068Dmd - Active Power Ph C LastDemand Active Power phase C last intervalRead
AI4070Dmd - Active Power Ph C PresDemand Active Power phase C presentRead
AI4072Dmd - Active Power Ph C PredDemand Active Power phase C predictedRead
AI4074Dmd - Active Power Ph C PeakDemand Active Power phase C peakRead
AI4084Dmd - Reactive Power Ph C LastDemand Reactive Power phase C last intervalRead
AI4086Dmd - Reactive Power Ph C PresDemand Reactive Power phase C presentRead
AI4088Dmd - Reactive Power Ph C PredDemand Reactive Power phase C predictedRead
AI4090Dmd - Reactive Power Ph C PeakDemand Reactive Power phase C peakRead
AI4100Dmd - Apparent Power Ph C LastDemand Apparent Power phase C last intervalRead
AI4102Dmd - Apparent Power Ph C PresDemand Apparent Power phase C presentRead
AI4104Dmd - Apparent Power Ph C PredDemand Apparent Power phase C predictedRead
AI4106Dmd - Apparent Power Ph C PeakDemand Apparent Power phase C peakRead
AI21300THD Current - Ph AHarmonic distortion (THD), current phase ARead
AI21302THD Current - Ph BHarmonic distortion (THD), current phase BRead
AI21304THD Current - Ph CHarmonic distortion (THD), current phase CRead
AI21306THD Current - Ph NHarmonic distortion (THD), current neutralRead
AI21308THD Current - Ph GHarmonic distortion (THD), current groundRead
AI21310thd Current - Ph AHarmonic distortion (thd), current phase ARead
AI21312thd Current - Ph BHarmonic distortion (thd), current phase BRead
AI21314thd Current - Ph CHarmonic distortion (thd), current phase CRead
AI21316thd Current - Ph NHarmonic distortion (thd), current neutralRead
AI21318thd Current - Ph GHarmonic distortion (thd), current groundRead
AI21320Total Dmd DistortionTotal Dmd DistortionRead
AI21322THD Voltage - A-BHarmonic distortion (THD), voltage A-BRead
AI21324THD Voltage - B-CHarmonic distortion (THD), voltage B-CRead
AI21326THD Voltage - C-AHarmonic distortion (THD), voltage C-ARead
AI21328THD Voltage - Avg L-LHarmonic distortion (THD), voltage average L-LRead
AI21330THD Voltage - A-NHarmonic distortion (THD), voltage A-NRead
AI21332THD Voltage - B-NHarmonic distortion (THD), voltage B-NRead
AI21334THD Voltage - C-NHarmonic distortion (THD), voltage C-NRead
AI21338THD Voltage - Avg L-NHarmonic distortion (THD), voltage average L-NRead
AI21340thd Voltage - A-BHarmonic distortion (thd), voltage A-BRead
AI21342thd Voltage - B-CHarmonic distortion (thd), voltage B-CRead
AI21344thd Voltage - C-AHarmonic distortion (thd), voltage C-ARead
AI21346thd Voltage - Avg L-LHarmonic distortion (thd), voltage average L-LRead
AI21348thd Voltage - A-NHarmonic distortion (thd), voltage A-NRead
AI21350thd Voltage - B-NHarmonic distortion (thd), voltage B-NRead
AI21352thd Voltage - C-NHarmonic distortion (thd), voltage C-NRead
AI21356thd Voltage - Avg L-NHarmonic distortion (thd), voltage average L-NRead
AI65000Active Energy Delvd (Tariff 1)Active Energy delivered (Tariff 1)Read
AI65002Active Energy Delvd (Tariff 2)Active Energy delivered (Tariff 2)Read
AI65004Active Energy Delvd (Tariff 3)Active Energy delivered (Tariff 3) (not PM7142)Read
AI65006Active Energy Delvd (Tariff 4)Active Energy delivered (Tariff 4) (not PM7142)Read
AI65008Active Energy Delvd (Tariff 5)Active Energy delivered (Tariff 5) (PM7351 only)Read
AI65010Active Energy Delvd (Tariff 6)Active Energy delivered (Tariff 6) (PM7351 only)Read
AI65012Active Energy Delvd (Tariff 7)Active Energy delivered (Tariff 7) (PM7351 only)Read
AI65014Active Energy Delvd (Tariff 8)Active Energy delivered (Tariff 8) (PM7351 only)Read
AI65016Active Energy Delvd (Tariff 9)Active Energy delivered (Tariff 9) (PM7351 only)Read
AI65018Active Energy Delvd (Tariff 10)Active Energy delivered (Tariff 10) (PM7351 only)Read
AI65020Active Energy Delvd (Tariff 11)Active Energy delivered (Tariff 11) (PM7351 only)Read
AI65022Active Energy Delvd (Tariff 12)Active Energy delivered (Tariff 12) (PM7351 only)Read
AI65024Active Energy Delvd (Tariff 13)Active Energy delivered (Tariff 13) (PM7351 only)Read
AI65026Active Energy Delvd (Tariff 14)Active Energy delivered (Tariff 14) (PM7351 only)Read
AI65028Active Energy Delvd (Tariff 15)Active Energy delivered (Tariff 15) (PM7351 only)Read
AI65030Active Energy Delvd (Tariff 16)Active Energy delivered (Tariff 16) (PM7351 only)Read
BI100000Digital Input 1Digital Input 1Read
BI100001Digital Input 2Digital Input 2 (not PM7142)Read
BI100009Digital Output 1Digital Output 1Read
BI100010Digital Output 2Digital Output 2 (not PM7142)Read
BI100017Relay Output 1Relay Output 1 (not PM7142)Read
BI100018Relay Output 2Relay Output 2 (not PM7142)Read
MI2016Power System ConfigurationPower System ConfigurationRead
MI2036VT Connection TypeVT Connection TypeRead
MI3701Power Demand MethodPower Demand MethodRead
MI3711Current Demand MethodCurrent Demand MethodRead
MI3721Input Metering Demand MethodInput Metering Demand MethodRead
MI4191Applicable Tariff Energy RateApplicable Tariff Energy RateRead
MI7274Digital Input 1 Control ModeDigital Input 1 Control ModeRead
MI7298Digital Input 2 Control ModeDigital Input 2 Control Mode (not PM7142)Read
MI9673Digital Output 1 Control ModeDigital Output 1 Control ModeRead
MI9681Digital Output 2 Control ModeDigital Output 2 Control Mode (not PM7142)Read
MI9689Relay Output 1 Control ModeRelay Output 1 Control Mode (not PM7142)Read
MI9697Relay Output 2 Control ModeRelay Output 2 Control Mode (not PM7142)Read
Object ID lookup: Schneider Electric PowerLogic PM7000 series power and energy meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PowerLogic PM7000 series power and energy meter (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP)

How many BACnet points does the Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP) have?

This list has 203 BACnet objects: 185 analog inputs, 6 binary inputs, 12 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP) BACnet documentation?

Schneider Electric does not publish it on its own website. This list comes from PM7000 Protocol Implementation Conformance Statement, revision 2026-07-01, a copy hosted by BACnet International catalog at https://www.bacnetinternational.net/catalog/manu/schneider%20electric/PICS__pm7000_pics.pdf. Ask Schneider Electric or its representative for the current revision.

What are the minimum BACnet points to integrate the Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP)?

Start with AI 3060 Active Power - Total (Total active power); AI 2700 Active Energy Delvd (Active energy delivered); AI 3766 Dmd - Active Power Pres (Present active power demand); AI 3084 Power Factor - Total (Total power factor); AI 3026 Voltage - Avg L-L (Average line-to-line voltage); AI 3010 Current - Avg (Average phase current); AI 3110 Frequency (System frequency).

How do I check these points on the real PowerLogic PM7000 series power and energy meter (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Schneider Electric BACnet points lists

Source: PM7000 Protocol Implementation Conformance Statement · rev. 2026-07-01. Object names, instances and units are reproduced as published; descriptions are our own.