- PowerLogic HDPM6000 high-density power meter (BACnet IP)
Multi-circuit branch power meter (high density) · BACnet points list
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP) BACnet points list
Updated 6 November 2026
The HDPM6000 head unit meters up to 192 branch channels, three-phase mains meters and circuits built from channels, and serves them on BACnet IP. Objects are grouped in numbered blocks: one object per channel, phase, circuit, TAP or harmonic. This list gives the first object of each block with its printed name pattern (e.g. 'Ch n Vrms') and the instance range. Analog Inputs hold readings; AV, PIV, BitString and CharString Values hold settings, alarm states and names.
This page lists 386 BACnet objects for the Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP) — 109 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- PowerLogic HDPM6000 high-density power meter (BACnet IP)
- Equipment
- Multi-circuit branch power meter (high density)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 386 (109 writable)
- Transport
- BACnet IP
- Firmware
- 0.60.0 (PICS 2022/02/04)
- Also known as
- HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192
- Source document
- HDPM6000 Protocol Guide · ZL0192-0G · rev. 2026-04
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Enable BACnet in the head unit's protocol settings (web interface), then read the mains meter totals and the per-channel blocks you need, computing each channel's instance from the block start. Alarm and warning states are bitstrings.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 756 | All Phase Watts total | Total power across all phases | Read |
| AI 757 | All Phase kWh total | Total energy across all phases | Read |
| AI 360 | Ch n Watts | Channel 1 power; channel n = 359 + n | Read |
| AI 480 | Ch n kWh | Channel 1 energy; channel n = 479 + n | Read |
| AI 120 | Ch n Irms | Channel 1 RMS current; channel n = 119 + n | Read |
| AI 720 | Phase n Vrms | Phase 1 RMS voltage (720-722) | Read |
| Other 1 | Alarms | Channel alarm state bits | Write |
| Other 2 | Tripped breakers | Channel tripped-breaker bits | Write |
Enable & remote start
BACnet is enabled with a protocol flag in the head unit's network settings (web interface or Modbus); there is no BMS enable point.
Network setup
- BACnet IP only, over the head unit's Ethernet port; no BACnet MS/TP.
- Network, protocol enables and device settings are set in the web interface (see the head unit installation guide Z208128) or by Modbus.
- No segmentation is claimed in the PICS.
Watch out for
- 'Ch n kWh resetting' (AI 600-719) is no longer supported and always reads 0; use 'Ch n kWh'.
- Channel numbers above 120 use separate blocks (e.g. Ch n ITHD for 121-192); check the block's n range.
- Some printed block starts are wrong in the guide (see notes); verify by reading the object names on site.
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Ch n Vrms | Instantaneous RMS voltage of the channel (1≤n≤120); instances 0-119 | Read | ||
| AImin | 120 | Ch n Irms | Instantaneous RMS current of the channel (1≤n≤120); instances 120-239 | Read | ||
| AI | 240 | Ch n PFactor | The power factor of the channel (1≤n≤120); instances 240-359 | Read | ||
| AImin | 360 | Ch n Watts | The instantaneous power of the channel (1≤n≤120); instances 360-479 | Read | ||
| AImin | 480 | Ch n kWh | Total energy measured through the channel (1≤n≤120); instances 480-599 | Read | ||
| AI | 600 | Ch n kWh resetting | No longer available, returns 0 (1≤n≤120); instances 600-719 | Read | ||
| AImin | 720 | Phase n Vrms | The RMS voltage of the phase (1≤n≤3); instances 720-722 | Read | ||
| AI | 723 | Phase n Itot | Total current of phase channels (1≤n≤3); instances 723-725 | Read | ||
| AI | 726 | Phase n PFactor avg | Average power factor of phase channels (1≤n≤3); instances 726-728 | Read | ||
| AI | 729 | Phase n Watts | Total power of phase channels (1≤n≤3); instances 729-731 | Read | ||
| AI | 732 | Phase n kWh | Total energy of phase channels (1≤n≤3); instances 732-734 | Read | ||
| AI | 735 | Dry contact n V | Instantaneous DC voltage (1≤n≤8); instances 735-742 | Read | ||
| AI | 743 | Dry contact n Irms | Instantaneous RMS current (1≤n≤8); instances 743-750 | Read | ||
| AI | 751 | Phase N Itot | Total current of all neutral channels | Read | ||
| AI | 752 | All Phase average Vrms | Average RMS voltage across all phases | Read | ||
| AI | 753 | All Phase Itot | Total RMS current across all phases | Read | ||
| AI | 754 | All Phase Iavg | Average RMS current across all phases | Read | ||
| AI | 755 | All Phase PFactor avg | Average power factor across all phases | Read | ||
| AImin | 756 | All Phase Watts total | Total power across all phases | Read | ||
| AImin | 757 | All Phase kWh total | Total energy measured across all phases | Read | ||
| AI | 758 | 3phm Phase n Vrms | Instantaneous RMS voltage of the phase (1≤n≤3); instances 758-760 | Read | ||
| AI | 761 | 3phm Phase n Irms | Instantaneous RMS current of the phase (1≤n≤3); instances 761-763 | Read | ||
| AI | 764 | 3phm Phase n PFactor avg | The power factor of the phase (1≤n≤3); instances 764-766 | Read | ||
| AI | 767 | 3phm Phase n Watts | The instantaneous power of the phase (1≤n≤3); instances 767-769 | Read | ||
| AI | 770 | 3phm Phase n kWh | Total energy measured through the phase (1≤n≤3); instances 770-772 | Read | ||
| AI | 773 | 3phm Phase N Irms | Instantaneous RMS current of the neutral phase | Read | ||
| AI | 774 | 3phm All Phase average Vrms | Average RMS voltage across all phases | Read | ||
| AI | 775 | 3phm All Phase Itot | Total RMS current across all phases | Read | ||
| AI | 776 | 3phm All Phase Iavg | Average RMS current across all phases | Read | ||
| AI | 777 | 3phm All Phase PFactor avg | Average power factor across all phases | Read | ||
| AI | 778 | 3phm All Phase Watts total | Total power across all phases | Read | ||
| AI | 779 | 3phm All Phase kWh total | Total energy measured across all phases | Read | ||
| AI | 780 | 3phm 1-2 Vrms | Instantaneous RMS voltage between phases | Read | ||
| AI | 781 | 3phm 2-3 Vrms | Instantaneous RMS voltage between phases | Read | ||
| AI | 782 | 3phm 3-1 Vrms | Instantaneous RMS voltage between phases | Read | ||
| AI | 783 | 3phm L-L avg Vrms | Average instantaneous RMS voltage between phases | Read | ||
| AI | 784 | 3phm Phase n VAR | The instantaneous reactive power of the phase (1≤n≤3); instances 784-786 | Read | ||
| AI | 787 | 3phm All Phase VAR total | Total reactive power across all phases | Read | ||
| AI | 788 | 3phm Phase n VA | The instantaneous apparent power of the phase (1≤n≤3); instances 788-790 | Read | ||
| AI | 791 | 3phm All Phase VA total | Total apparent power across all phases | Read | ||
| AI | 792 | 3phm Phase n VTHD | THD of phase voltage (1≤n≤3); instances 792-794 | Read | ||
| AI | 795 | 3phm All Phase VTHD total | Total of phase voltage THDs | Read | ||
| AI | 796 | 3phm All Phase VTHD avg | Average of phase voltage THDs | Read | ||
| AI | 797 | 3phm Phase n ITHD | THD of phase current (1≤n≤3); instances 797-799 | Read | ||
| AI | 800 | 3phm All Phase ITHD total | Total of phase current THDs | Read | ||
| AI | 801 | 3phm All Phase ITHD avg | Average of phase current THDs | Read | ||
| AI | 802 | 3phm Phase n kWh export | Total energy exported through the phase (1≤n≤3); instances 802-804 | Read | ||
| AI | 805 | 3phm All Phase kWh export | Total energy exported across all phases | Read | ||
| AI | 806 | 3phm Phase n kWh import | Total energy imported through the phase (1≤n≤3); instances 806-808 | Read | ||
| AI | 809 | 3phm All Phase kWh import | Total energy imported across all phases | Read | ||
| AI | 810 | 3phm Phase n kVARh total | Total reactive energy measured through the phase (1≤n≤3); instances 810-812 | Read | ||
| AI | 813 | 3phm All Phase kVARh total | Total reactive energy measured across all phases | Read | ||
| AI | 814 | 3phm Phase n kVARh export | Total reactive energy exported through the phase (1≤n≤3); instances 814-816 | Read | ||
| AI | 817 | 3phm All Phase kVARh export | Total reactive energy exported across all phases | Read | ||
| AI | 818 | 3phm Phase n kVARh import | Total reactive energy imported through the phase (1≤n≤3); instances 818-820 | Read | ||
| AI | 821 | 3phm All Phase kVARh import | Total reactive energy imported across all phases | Read | ||
| AI | 822 | 3phm Phase n frequency | The instantaneous frequency of the phase (1≤n≤3); instances 822-824 | Read | ||
| AI | 825 | 3phm All Phase frequency average | Average frequency across all phases | Read | ||
| AI | 826 | 3phm Phase n Watts max | Maximum phase power recorded (1≤n≤3); instances 826-828 | Read | ||
| AI | 829 | 3phm total power used | Percentage of supply power capacity in use | Read | ||
| AI | 830 | 3phm total power remaining | Power supply’s remaining capacity | Read | ||
| AI | 831 | 3phm Phase n V harmonic h | Odd harmonics 1 to 63 of phase voltage (1≤n≤3, 1≤h≤63 odd); instances 831-926 | Read | ||
| AI | 927 | 3phm Phase n I harmonic h | Odd harmonics 1 to 63 of phase current (1≤n≤3, 1≤h≤63 odd); instances 927-1022 | Read | ||
| AI | 1023 | Selected channel I harmonic h | Odd harmonics 1 to 63 of the selected channel (1≤h≤63 odd); instances 1023-1054 | Read | ||
| AI | 1055 | Ch n ITHD | THD of the channel current (1≤n≤120); instances 1055-1174 | Read | ||
| AI | 1175 | Ch n VAR | The instantaneous reactive power of the channel (1≤n≤120); instances 1175-1294 | Read | ||
| AI | 1295 | Ch n Watts max | Maximum channel power recorded (1≤n≤120); instances 1295-1414 | Read | ||
| AI | 1415 | 123N circuit c Phase n Vrms | Instantaneous RMS voltage of the circuit phase (1≤c≤48, 1≤n≤3); instances 1415-1558 | Read | ||
| AI | 1559 | 123N circuit c Phase n Irms | Instantaneous RMS current of the circuit phase (1≤c≤48, 1≤n≤3); instances 1559-1702 | Read | ||
| AI | 1703 | 123N circuit c Phase n PFactor avg | The power factor of the circuit phase (1≤c≤48, 1≤n≤3); instances 1703-1846 | Read | ||
| AI | 1847 | 123N circuit c Phase n Watts | The instantaneous power of the circuit phase (1≤c≤48, 1≤n≤3); instances 1847-1990 | Read | ||
| AI | 1991 | 123N circuit c Phase n kWh | Total energy measured through the circuit phase (1≤c≤48, 1≤n≤3); instances 1991-2134 | Read | ||
| AI | 2135 | 123N circuit c Phase N Irms | Instantaneous RMS current of the circuit neutral phase (1≤c≤48); instances 2135-2182 | Read | ||
| AI | 2183 | 123N circuit c All Phase average Vrms | Average RMS voltage across all circuit phases (1≤c≤48); instances 2183-2230 | Read | ||
| AI | 2231 | 123N circuit c All Phase Itot | Total RMS current across all circuit phases (1≤c≤48); instances 2231-2278 | Read | ||
| AI | 2279 | 123N circuit c All Phase Iavg | Average RMS current across all circuit phases (1≤c≤48); instances 2279-2326 | Read | ||
| AI | 2327 | 123N circuit c All Phase PFactor avg | Average power factor across all circuit phases (1≤c≤48); instances 2327-2374 | Read | ||
| AI | 2375 | 123N circuit c All Phase Watts total | Total power across all circuit phases (1≤c≤48); instances 2375-2422 | Read | ||
| AI | 2423 | 123N circuit c All Phase kWh total | Total energy measured across all circuit phases (1≤c≤48); instances 2423-2470 | Read | ||
| AI | 2471 | 123N circuit c 1-2 Vrms | Instantaneous RMS voltage between circuit phases (1≤c≤48); instances 2471-2518 | Read | ||
| AI | 2519 | 123N circuit c 2-3 Vrms | Instantaneous RMS voltage between circuit phases (1≤c≤48); instances 2519-2566 | Read | ||
| AI | 2567 | 123N circuit c 3-1 Vrms | Instantaneous RMS voltage between circuit phases (1≤c≤48); instances 2567-2614 | Read | ||
| AI | 2615 | 123N circuit c L-L avg Vrms | Average instantaneous RMS voltage between circuit phases (1≤c≤48); instances 2615-2662 | Read | ||
| AI | 2663 | 123N circuit c Phase n VAR | The instantaneous reactive power of the circuit phase (1≤c≤48, 1≤n≤3); instances 2663-2806 | Read | ||
| AI | 2807 | 123N circuit c All Phase VAR total | Total reactive power across all circuit phases (1≤c≤48); instances 2807-2854 | Read | ||
| AI | 2855 | 123N circuit c Phase n VA | The instantaneous apparent power of the circuit phase (1≤c≤48, 1≤n≤3); instances 2855-2998 | Read | ||
| AI | 2999 | 123N circuit c All Phase VA total | Total apparent power across all circuit phases (1≤c≤48); instances 2999-3046 | Read | ||
| AI | 3047 | 123N circuit c Phase n ITHD | THD of the circuit phase current (1≤c≤48, 1≤n≤3); instances 3047-3190 | Read | ||
| AI | 3191 | 123N circuit c Phase N ITHD | THD of the circuit neutral phase current (1≤c≤48); instances 3191-3238 | Read | ||
| AI | 3239 | 123N circuit c All Phase ITHD total | Total of the circuit phase current THDs (1≤c≤48); instances 3239-3286 | Read | ||
| AI | 3287 | 123N circuit c All Phase ITHD avg | Average of the circuit phase current THDs (1≤c≤48); instances 3287-3334 | Read | ||
| AI | 3335 | 123N circuit c Phase n Watts max | Maximum circuit phase power recorded (1≤c≤48, 1≤n≤3); instances 3335-3478 | Read | ||
| AI | 3479 | 123N circuit c total power used | Percentage of circuit’s power capacity in use (1≤c≤48); instances 3479-3526 | Read | ||
| AI | 3527 | 123N circuit c total power remaining | Circuit’s remaining power capacity (1≤c≤48); instances 3527-3574 | Read | ||
| AI | 3575 | Ch n Vrms | Instantaneous RMS voltage of the channel (121≤n≤192); instances 3575-3646 | Read | ||
| AI | 3647 | Ch n Irms | Instantaneous RMS current of the channel (121≤n≤192); instances 3647-3718 | Read | ||
| AI | 3719 | Ch n PFactor | The power factor of the channel (121≤n≤192); instances 3719-3790 | Read | ||
| AI | 3791 | Ch n Watts | The instantaneous power of the channel (121≤n≤192); instances 3791-3862 | Read | ||
| AI | 3863 | Ch n kWh | Total energy measured through the channel (121≤n≤192); instances 3863-3934 | Read | ||
| AI | 3935 | Ch n ITHD | THD of the channel current (121≤n≤192); instances 3935-4006 | Read | ||
| AI | 4007 | Ch n VAR | The instantaneous reactive power of the channel (121≤n≤192); instances 4007-4078 | Read | ||
| AI | 4079 | Ch n Watts max | Maximum channel power recorded (121≤n≤192); instances 4079-4150 | Read | ||
| AI | 4151 | Environmental sensor n, [3phm / TAP] t, port p, value v | Environmental sensor value (t 1-48, port 1-8, value 1-10); instances 4151-4406 | Read | ||
| AI | 4407 | Circuit c Phase n Vrms | Instantaneous RMS voltage of the circuit phase (1≤c≤192, 1≤n≤3); instances 4407-4982 | Read | ||
| AI | 4983 | Circuit c Phase n Irms | Instantaneous RMS current of the circuit phase (1≤c≤192, 1≤n≤3); instances 4983-5558 | Read | ||
| AI | 5559 | Circuit c Phase n PFactor avg | The power factor of the circuit phase (1≤c≤192, 1≤n≤3); instances 5559-6134 | Read | ||
| AI | 6135 | Circuit c Phase n Watts | The instantaneous power of the circuit phase (1≤c≤192, 1≤n≤3); instances 6135-6710 | Read | ||
| AI | 6711 | Circuit c Phase n kWh | Total energy measured through the circuit phase (1≤c≤192, 1≤n≤3); instances 6711-7286 | Read | ||
| AI | 7287 | Circuit c Phase N Irms | Instantaneous RMS current of the circuit neutral phase (1≤c≤192); instances 7287-7478 | Read | ||
| AI | 7479 | Circuit c All Phase average Vrms | Average RMS voltage across all circuit phases (1≤c≤192); instances 7479-7670 | Read | ||
| AI | 7671 | Circuit c All Phase Itot | Total RMS current across all circuit phases (1≤c≤192); instances 7671-7862 | Read | ||
| AI | 7863 | Circuit c All Phase Iavg | Average RMS current across all circuit phases (1≤c≤192); instances 7863-8054 | Read | ||
| AI | 8055 | Circuit c All Phase PFactor avg | Average power factor across all circuit phases (1≤c≤192); instances 8055-8246 | Read | ||
| AI | 8247 | Circuit c All Phase Watts total | Total power across all circuit phases (1≤c≤192); instances 8247-8438 | Read | ||
| AI | 8439 | Circuit c All Phase kWh total | Total energy measured across all circuit phases (1≤c≤192); instances 8439-8630 | Read | ||
| AI | 8631 | Circuit c 1-2 Vrms | Instantaneous RMS voltage between circuit phases (1≤c≤192); instances 8631-8822 | Read | ||
| AI | 8823 | Circuit c 2-3 Vrms | Instantaneous RMS voltage between circuit phases (1≤c≤192); instances 8823-9014 | Read | ||
| AI | 9015 | Circuit c 3-1 Vrms | Instantaneous RMS voltage between circuit phases (1≤c≤192); instances 9015-9206 | Read | ||
| AI | 9207 | Circuit c L-L avg Vrms | Average instantaneous RMS voltage between circuit phases (1≤c≤192); instances 9207-9398 | Read | ||
| AI | 9399 | Circuit c Phase n VAR | The instantaneous reactive power of the circuit phase (1≤c≤192, 1≤n≤3); instances 9399-9974 | Read | ||
| AI | 9975 | Circuit c All Phase VAR total | Total reactive power across all circuit phases (1≤c≤192); instances 9975-10166 | Read | ||
| AI | 10167 | Circuit c Phase n VA | The instantaneous apparent power of the circuit phase (1≤c≤192, 1≤n≤3); instances 10167-10742 | Read | ||
| AI | 10743 | Circuit c All Phase VA total | Total apparent power across all circuit phases (1≤c≤192); instances 10743-10934 | Read | ||
| AI | 10935 | Circuit c Phase n ITHD | THD of the circuit phase current (1≤c≤192, 1≤n≤3); instances 10935-11510 | Read | ||
| AI | 11511 | Circuit c Phase N ITHD | THD of the circuit neutral phase current (1≤c≤192); instances 11511-11702 | Read | ||
| AI | 11703 | Circuit c All Phase ITHD total | Total of the circuit phase current THDs (1≤c≤192); instances 11703-11894 | Read | ||
| AI | 11895 | Circuit c All Phase ITHD avg | Average of the circuit phase current THDs (1≤c≤192); instances 11895-12086 | Read | ||
| AI | 12087 | Circuit c Phase n Watts max | Maximum circuit phase power recorded (1≤c≤192, 1≤n≤3); instances 12087-12662 | Read | ||
| AI | 12663 | Circuit c total power used | Percentage of circuit’s power capacity in use (1≤c≤192); instances 12663-12854 | Read | ||
| AI | 12855 | Circuit c total power remaining | Circuit’s remaining power capacity (1≤c≤192); instances 12855-13046 | Read | ||
| AI | 13047 | 3 phase meter 2 Phase n Vrms | 3 phase meter 2 Vrms (1≤n≤3); instances 13047-13049 | Read | ||
| AI | 13050 | 3 phase meter 2 Phase n Irms | 3 phase meter 2 Irms (1≤n≤3); instances 13050-13052 | Read | ||
| AI | 13053 | 3 phase meter 2 Phase n PFactor avg | 3 phase meter 2 PFactor avg (1≤n≤3); instances 13053-13055 | Read | ||
| AI | 13056 | 3 phase meter 2 Phase n Watts | 3 phase meter 2 Watts (1≤n≤3); instances 13056-13058 | Read | ||
| AI | 13059 | 3 phase meter 2 Phase n kWh | 3 phase meter 2 kWh (1≤n≤3); instances 13059-13061 | Read | ||
| AI | 13062 | 3 phase meter 2 Phase N Irms | 3 phase meter 2 Phase N Irms | Read | ||
| AI | 13063 | 3 phase meter 2 All Phase average Vrms | 3 phase meter 2 All Phase average Vrms | Read | ||
| AI | 13064 | 3 phase meter 2 All Phase Itot | 3 phase meter 2 All Phase Itot | Read | ||
| AI | 13065 | 3 phase meter 2 All Phase Iavg | 3 phase meter 2 All Phase Iavg | Read | ||
| AI | 13066 | 3 phase meter 2 All Phase PFactor avg | 3 phase meter 2 All Phase PFactor avg | Read | ||
| AI | 13067 | 3 phase meter 2 All Phase Watts total | 3 phase meter 2 All Phase Watts total | Read | ||
| AI | 13068 | 3 phase meter 2 All Phase kWh total | 3 phase meter 2 All Phase kWh | Read | ||
| AI | 13069 | 3 phase meter 2 1-2 Vrms | 3 phase meter 2 1-2 Vrms | Read | ||
| AI | 13070 | 3 phase meter 2 2-3 Vrms | 3 phase meter 2 2-3 Vrms | Read | ||
| AI | 13071 | 3 phase meter 2 3-1 Vrms | 3 phase meter 2 3-1 Vrms | Read | ||
| AI | 13072 | 3 phase meter 2 L-L avg Vrms | 3 phase meter 2 L-L avg Vrms | Read | ||
| AI | 13073 | 3 phase meter 2 Phase n VAR | 3 phase meter 2 VAR (1≤n≤3); instances 13073-13075 | Read | ||
| AI | 13076 | 3 phase meter 2 All Phase VAR total | 3 phase meter 2 All Phase VAR total | Read | ||
| AI | 13077 | 3 phase meter 2 Phase n VA | 3 phase meter 2 VA (1≤n≤3); instances 13077-13079 | Read | ||
| AI | 13080 | 3 phase meter 2 All Phase VA total | 3 phase meter 2 All Phase VA total | Read | ||
| AI | 13081 | 3 phase meter 2 Phase n VTHD | 3 phase meter 2 VTHD (1≤n≤3); instances 13081-13083 | Read | ||
| AI | 13084 | 3 phase meter 2 All Phase VTHD total | 3 phase meter 2 All Phase VTHD total | Read | ||
| AI | 13085 | 3 phase meter 2 All Phase VTHD avg | 3 phase meter 2 All Phase VTHD avg | Read | ||
| AI | 13086 | 3 phase meter 2 Phase n ITHD | 3 phase meter 2 ITHD (1≤n≤3); instances 13086-13088 | Read | ||
| AI | 13089 | 3 phase meter 2 All Phase ITHD total | 3 phase meter 2 All Phase ITHD total | Read | ||
| AI | 13090 | 3 phase meter 2 All Phase ITHD avg | 3 phase meter 2 All Phase ITHD avg | Read | ||
| AI | 13091 | 3 phase meter 2 Phase n kWh export | 3 phase meter 2 kWh export (1≤n≤3); instances 13091-13093 | Read | ||
| AI | 13094 | 3 phase meter 2 All Phase kWh export | 3 phase meter 2 All Phase kWh export | Read | ||
| AI | 13095 | 3 phase meter 2 Phase n kWh import | 3 phase meter 2 kWh import (1≤n≤3); instances 13095-13097 | Read | ||
| AI | 13098 | 3 phase meter 2 All Phase kWh import | 3 phase meter 2 All Phase kWh import | Read | ||
| AI | 13099 | 3 phase meter 2 Phase n kVARh total | 3 phase meter 2 kVARh total (1≤n≤3); instances 13099-13101 | Read | ||
| AI | 13102 | 3 phase meter 2 All Phase kVARh total | 3 phase meter 2 All Phase kVARh total | Read | ||
| AI | 13103 | 3 phase meter 2 Phase n kVARh export | 3 phase meter 2 kVARh export (1≤n≤3); instances 13103-13105 | Read | ||
| AI | 13106 | 3 phase meter 2 All Phase kVARh export | 3 phase meter 2 All Phase kVARh export | Read | ||
| AI | 13107 | 3 phase meter 2 Phase n kVARh import | 3 phase meter 2 kVARh import (1≤n≤3); instances 13107-13109 | Read | ||
| AI | 13110 | 3 phase meter 2 All Phase kVARh import | 3 phase meter 2 All Phase kVARh import | Read | ||
| AI | 13111 | 3 phase meter 2 Phase n frequency | 3 phase meter 2 frequency (1≤n≤3); instances 13111-13113 | Read | ||
| AI | 13114 | 3 phase meter 2 All Phase frequency average | 3 phase meter 2 All Phase frequency average | Read | ||
| AI | 13115 | 3 phase meter 2 Phase n Watts max | 3 phase meter 2 Watts max (1≤n≤3); instances 13115-13117 | Read | ||
| AI | 13118 | 3 phase meter 2 total power used | 3 phase meter 2 total power used | Read | ||
| AI | 13119 | 3 phase meter 2 total power remaining | 3 phase meter 2 total power remaining | Read | ||
| AI | 13120 | 3 phase meter 2 Phase 1 V harmonic n | Odd harmonics 1 to 63 of phase voltage (1≤n≤63 odd); instances 13120-13151 | Read | ||
| AI | 13152 | 3 phase meter 2 Phase 2 V harmonic n | Odd harmonics 1 to 63 of phase voltage (1≤n≤63 odd); instances 13152-13183 | Read | ||
| AI | 13184 | 3 phase meter 2 Phase 3 V harmonic n | Odd harmonics 1 to 63 of phase voltage (1≤n≤63 odd); instances 13184-13215 | Read | ||
| AI | 13216 | 3 phase meter 2 Phase 1 I harmonic n | Odd harmonics 1 to 63 of phase current (1≤n≤63 odd); instances 13216-13247 | Read | ||
| AI | 13248 | 3 phase meter 2 Phase 2 I harmonic n | Odd harmonics 1 to 63 of phase current (1≤n≤63 odd); instances 13248-13279 | Read | ||
| AI | 13280 | 3 phase meter 2 Phase 3 I harmonic n | Odd harmonics 1 to 63 of phase current (1≤n≤63 odd); instances 13280-13311 | Read | ||
| AI | 13312 | Load Type n Total Watts | Load Type Total Watts (1≤n≤20); instances 13312-13331 | Read | ||
| AI | 13332 | 3 phase meter Ch n Demand Avg Power | Average power for demand period for channel (1≤n≤3); instances 13332-13334 | Read | ||
| AI | 13335 | 3 phase meter Ch n Demand Min Power | Minimum power in demand period for channel (1≤n≤3); instances 13335-13337 | Read | ||
| AI | 13338 | 3 phase meter Ch n Demand Max Power | Maximum power in demand period for channel (1≤n≤3); instances 13338-13340 | Read | ||
| AI | 13341 | 3 phase meter Ch n Demand Avg Apparent Power | Average apparent power for demand period for channel (1≤n≤3); instances 13341-13343 | Read | ||
| AI | 13344 | 3 phase meter Ch n Demand Min Apparent Power | Minimum apparent power in demand period for channel (1≤n≤3); instances 13344-13346 | Read | ||
| AI | 13347 | 3 phase meter Ch n Demand Max Apparent Power | Maximum apparent power in demand period for channel (1≤n≤3); instances 13347-13349 | Read | ||
| AI | 13350 | 3 phase meter Ch n Demand Avg Reactive Power | Average reactive power for demand period for channel (1≤n≤3); instances 13350-13352 | Read | ||
| AI | 13353 | 3 phase meter Ch n Demand Min Reactive Power | Minimum reactive power in demand period for channel (1≤n≤3); instances 13353-13355 | Read | ||
| AI | 13356 | 3 phase meter Ch n Demand Max Reactive Power | Maximum reactive power in demand period for channel (1≤n≤3); instances 13356-13358 | Read | ||
| AI | 13359 | 3 phase meter Ch n Demand Avg Current | Average current for demand period for channel (1≤n≤3); instances 13359-13361 | Read | ||
| AI | 13362 | 3 phase meter Ch n Demand Min Current | Minimum current in demand period for channel (1≤n≤3); instances 13362-13364 | Read | ||
| AI | 13365 | 3 phase meter Ch n Demand Max Current | Maximum current in demand period for channel (1≤n≤3); instances 13365-13367 | Read | ||
| AI | 13368 | 3phase meter Total Demand Avg Power | Average power for demand period for circuit | Read | ||
| AI | 13369 | 3phase meter Total Demand Min Power | Minimum power in demand period for circuit | Read | ||
| AI | 13370 | 3phase meter Total Demand Max Power | Maximum power in demand period for circuit | Read | ||
| AI | 13371 | 3phase meter Total Demand Avg Apparent Power | Average apparent power for demand period for circuit | Read | ||
| AI | 13372 | 3phase meter Total Demand Min Apparent Power | Minimum apparent power in demand period for circuit | Read | ||
| AI | 13373 | 3phase meter Total Demand Max Apparent Power | Maximum apparent power in demand period for circuit | Read | ||
| AI | 13374 | 3phase meter Total Demand Avg Reactive Power | Average reactive power for demand period for circuit | Read | ||
| AI | 13375 | 3phase meter Total Demand Min Reactive Power | Minimum reactive power in demand period for circuit | Read | ||
| AI | 13376 | 3phase meter Total Demand Max Reactive Power | Maximum reactive power in demand period for circuit | Read | ||
| AI | 13377 | 3phase meter Total Demand Avg Current | Average current for demand period for circuit | Read | ||
| AI | 13378 | 3phase meter Total Demand Min Current | Minimum current in demand period for circuit | Read | ||
| AI | 13379 | 3phase meter Total Demand Max Current | Maximum current in demand period for circuit | Read | ||
| AI | 13380 | 3 phase meter Phase n Demand Daily Peak Power | Peak power of phase from previous day (1≤n≤3); instances 13380-13382 | Read | ||
| AI | 13383 | 3 phase meter Phase n Demand Peak Power | Peak power of phase since last reset (1≤n≤3); instances 13383-13385 | Read | ||
| AI | 13386 | 3 phase meter All Phase Demand Daily Peak Power | Peak total power of supply from previous day | Read | ||
| AI | 13387 | 3 phase meter All Phase Demand Peak Power | Peak total power of supply since last reset | Read | ||
| AI | 13388 | Cct n Demand Avg Power | Average power of circuit for demand period (1≤n≤192); instances 13388-13579 | Read | ||
| AI | 13580 | Cct n Demand Daily Peak Power | Peak power of circuit from previous day (1≤n≤192); instances 13580-13771 | Read | ||
| AI | 13772 | Cct n Demand Peak Power | Peak power of circuit since last reset (1≤n≤192); instances 13772-13963 | Read | ||
| AI | 13964 | 3 phase meter Phase n kVAh total | Total apparent energy measured through the phase (1≤n≤3); instances 13964-13966 | Read | ||
| AI | 13967 | 3 phase meter All Phase kVAh total | Total apparent energy measured across all phases | Read | ||
| AI | 13968 | 3 phase meter Phase n kVAh export | Total apparent energy exported through the phase (1≤n≤3); instances 13968-13970 | Read | ||
| AI | 13971 | 3 phase meter All Phase kVAh export | Total apparent energy exported across all phases | Read | ||
| AI | 13972 | 3 phase meter Phase n kVAh import | Total apparent energy imported through the phase (1≤n≤3); instances 13972-13974 | Read | ||
| AI | 13975 | 3 phase meter All Phase kVAh import | Total apparent energy imported across all phases | Read | ||
| AI | 13976 | 3 phase meter I imbalance | I imbalance for 3 phase meter | Read | ||
| AI | 13977 | 3 phase meter V imbalance | V imbalance for 3 phase meter | Read | ||
| AI | 13978 | 3 phase meter I total demand distortion | I total demand distortion for 3 phase meter | Read | ||
| AI | 13979 | 3 phase meter 2 I imbalance | I imbalance for second 3 phase meter | Read | ||
| AI | 13980 | 3 phase meter 2 V imbalance | V imbalance for second 3 phase meter | Read | ||
| AI | 13981 | 3 phase meter 2 I total demand distortion | I total demand distortion for second 3 phase meter | Read | ||
| AI | 13982 | Phase n DPF | Displacement Power Factor for phase (1≤n≤3); instances 13982-13984 | Read | ||
| AI | 13985 | 3 phase meter Ch n Demand Min VLN | Minimum Line to Neutral Voltage in demand period for channel (1≤n≤3); instances 13985-13987 | Read | ||
| AI | 13988 | 3 phase meter Ch n Demand Max VLN | Maximum Line to Neutral Voltage in demand period for channel (1≤n≤3); instances 13988-13990 | Read | ||
| AI | 13991 | 3 phase meter Ch n Demand Avg VLN | Average Line to Neutral Voltage in demand period for channel (1≤n≤3); instances 13991-13993 | Read | ||
| AI | 13994 | 3 phase meter Ch n Demand Min VLL | Minimum Line to Line Voltage in demand period for channel (1≤n≤3); instances 13994-13996 | Read | ||
| AI | 13997 | 3 phase meter Ch n Demand Max VLL | Maximum Line to Line Voltage in demand period for channel (1≤n≤3); instances 13997-13999 | Read | ||
| AI | 14000 | 3 phase meter Ch n Demand Avg VLL | Average Line to Line Voltage in demand period for channel (1≤n≤3); instances 14000-14002 | Read | ||
| AI | 14003 | 3 phase meter 2 Ch n Demand Avg Power | Average power for demand period for channel (1≤n≤3); instances 14003-14005 | Read | ||
| AI | 14006 | 3 phase meter 2 Ch n Demand Min Power | Minimum power in demand period for channel (1≤n≤3); instances 14006-14008 | Read | ||
| AI | 14009 | 3 phase meter 2 Ch n Demand Max Power | Maximum power in demand period for channel (1≤n≤3); instances 14009-14011 | Read | ||
| AI | 14012 | 3 phase meter 2 Ch n Demand Avg Apparent Power | Average apparent power for demand period for channel (1≤n≤3); instances 14012-14014 | Read | ||
| AI | 14015 | 3 phase meter 2 Ch n Demand Min Apparent Power | Minimum apparent power in demand period for channel (1≤n≤3); instances 14015-14017 | Read | ||
| AI | 14018 | 3 phase meter 2 Ch n Demand Max Apparent Power | Maximum apparent power in demand period for channel (1≤n≤3); instances 14018-14020 | Read | ||
| AI | 14021 | 3 phase meter 2 Ch n Demand Avg Reactive Power | Average reactive power for demand period for channel (1≤n≤3); instances 14021-14023 | Read | ||
| AI | 14024 | 3 phase meter 2 Ch n Demand Min Reactive Power | Minimum reactive power in demand period for channel (1≤n≤3); instances 14024-14026 | Read | ||
| AI | 14027 | 3 phase meter 2 Ch n Demand Max Reactive Power | Maximum reactive power in demand period for channel (1≤n≤3); instances 14027-14029 | Read | ||
| AI | 14030 | 3 phase meter 2 Ch n Demand Avg Current | Average current for demand period for channel (1≤n≤3); instances 14030-14032 | Read | ||
| AI | 14033 | 3 phase meter 2 Ch n Demand Min Current | Minimum current in demand period for channel (1≤n≤3); instances 14033-14035 | Read | ||
| AI | 14036 | 3 phase meter 2 Ch n Demand Max Current | Maximum current in demand period for channel (1≤n≤3); instances 14036-14038 | Read | ||
| AI | 14039 | 3phase meter 2 Total Demand Avg Power | Average power for demand period for circuit | Read | ||
| AI | 14040 | 3phase meter 2 Total Demand Min Power | Minimum power in demand period for circuit | Read | ||
| AI | 14041 | 3phase meter 2 Total Demand Max Power | Maximum power in demand period for circuit | Read | ||
| AI | 14042 | 3phase meter 2 Total Demand Avg Apparent Power | Average apparent power for demand period for circuit | Read | ||
| AI | 14043 | 3phase meter 2 Total Demand Min Apparent Power | Minimum apparent power in demand period for circuit | Read | ||
| AI | 14044 | 3phase meter 2 Total Demand Max Apparent Power | Maximum apparent power in demand period for circuit | Read | ||
| AI | 14045 | 3phase meter 2 Total Demand Avg Reactive Power | Average reactive power for demand period for circuit | Read | ||
| AI | 14046 | 3phase meter 2 Total Demand Min Reactive Power | Minimum reactive power in demand period for circuit | Read | ||
| AI | 14047 | 3phase meter 2 Total Demand Max Reactive Power | Maximum reactive power in demand period for circuit | Read | ||
| AI | 14048 | 3phase meter 2 Total Demand Avg Current | Average current for demand period for circuit | Read | ||
| AI | 14049 | 3phase meter 2 Total Demand Min Current | Minimum current in demand period for circuit | Read | ||
| AI | 14050 | 3phase meter 2 Total Demand Max Current | Maximum current in demand period for circuit | Read | ||
| AI | 14051 | 3 phase meter 3 Ch n Demand Avg Power | Average power for demand period for channel (1≤n≤3); instances 14051-14053 | Read | ||
| AI | 14054 | 3 phase meter 3 Ch n Demand Min Power | Minimum power in demand period for channel (1≤n≤3); instances 14054-14056 | Read | ||
| AI | 14057 | 3 phase meter 3 Ch n Demand Max Power | Maximum power in demand period for channel (1≤n≤3); instances 14057-14059 | Read | ||
| AI | 14060 | 3 phase meter 3 Ch n Demand Avg Apparent Power | Average apparent power for demand period for channel (1≤n≤3); instances 14060-14062 | Read | ||
| AI | 14063 | 3 phase meter 3 Ch n Demand Min Apparent Power | Minimum apparent power in demand period for channel (1≤n≤3); instances 14063-14065 | Read | ||
| AI | 14066 | 3 phase meter 3 Ch n Demand Max Apparent Power | Maximum apparent power in demand period for channel (1≤n≤3); instances 14066-14068 | Read | ||
| AI | 14069 | 3 phase meter 3 Ch n Demand Avg Reactive Power | Average reactive power for demand period for channel (1≤n≤3); instances 14069-14071 | Read | ||
| AI | 14072 | 3 phase meter 3 Ch n Demand Min Reactive Power | Minimum reactive power in demand period for channel (1≤n≤3); instances 14072-14074 | Read | ||
| AI | 14075 | 3 phase meter 3 Ch n Demand Max Reactive Power | Maximum reactive power in demand period for channel (1≤n≤3); instances 14075-14077 | Read | ||
| AI | 14078 | 3 phase meter 3 Ch n Demand Avg Current | Average current for demand period for channel (1≤n≤3); instances 14078-14080 | Read | ||
| AI | 14081 | 3 phase meter 3 Ch n Demand Min Current | Minimum current in demand period for channel (1≤n≤3); instances 14081-14083 | Read | ||
| AI | 14084 | 3 phase meter 3 Ch n Demand Max Current | Maximum current in demand period for channel (1≤n≤3); instances 14084-14086 | Read | ||
| AI | 14087 | 3phase meter 3 Total Demand Avg Power | Average power for demand period for circuit | Read | ||
| AI | 14088 | 3phase meter 3 Total Demand Min Power | Minimum power in demand period for circuit | Read | ||
| AI | 14089 | 3phase meter 3 Total Demand Max Power | Maximum power in demand period for circuit | Read | ||
| AI | 14090 | 3phase meter 3 Total Demand Avg Apparent Power | Average apparent power for demand period for circuit | Read | ||
| AI | 14091 | 3phase meter 3 Total Demand Min Apparent Power | Minimum apparent power in demand period for circuit | Read | ||
| AI | 14092 | 3phase meter 3 Total Demand Max Apparent Power | Maximum apparent power in demand period for circuit | Read | ||
| AI | 14093 | 3phase meter 3 Total Demand Avg Reactive Power | Average reactive power for demand period for circuit | Read | ||
| AI | 14094 | 3phase meter 3 Total Demand Min Reactive Power | Minimum reactive power in demand period for circuit | Read | ||
| AI | 14095 | 3phase meter 3 Total Demand Max Reactive Power | Maximum reactive power in demand period for circuit | Read | ||
| AI | 14096 | 3phase meter 3 Total Demand Avg Current | Average current for demand period for circuit | Read | ||
| AI | 14097 | 3phase meter 3 Total Demand Min Current | Minimum current in demand period for circuit | Read | ||
| AI | 14098 | 3phase meter 3 Total Demand Max Current | Maximum current in demand period for circuit | Read | ||
| AI | 14099 | Circuit c Current Imbalance | Imbalance between phase current magnitudes in a three phase circuit (1≤c≤192); instances 14099-14290 | Read | ||
| AV | 0 | Ch n CT factor | CT factor for each channel (1≤n≤120); instances 0-119 | Write | ||
| AV | 120 | Ch n alarm breaker size | Current scale against which warning and alarm thresholds are measured. (1≤n≤120); instances 120-239 | Write | ||
| AV | 240 | Phase n Vlo threshold | Threshold for triggering the Vlo alarm (1≤n≤3); instances 240-242 | Write | ||
| AV | 243 | Phase n Vhi threshold | Threshold for triggering the Vhi alarm (1≤n≤3); instances 243-245 | Write | ||
| AV | 246 | Tripped breaker current | Current at which the tripped breaker alarm becomes active | Write | ||
| AV | 247 | 3phm SAGV | 3 phase meter wave capture sag voltage threshold | Write | ||
| AV | 248 | 3phm OV | 3 phase meter wave capture over voltage threshold | Write | ||
| AV | 249 | 3phm OI | 3 phase meter current wave capture threshold | Write | ||
| AV | 250 | 3phm OI hold-off | 3 phase meter current wave capture hold-off | Write | ||
| AV | 251 | TAPs TB hold-off | TAPs current wave capture hold-off | Write | ||
| AV | 252 | TAPs TB trigger level | TAPs current wave capture threshold | Write | ||
| AV | 253 | 123N circuit n total power limit | 123N circuit total power limit (1≤n≤48); instances 253-300 | Write | ||
| AV | 301 | 3phm total power limit | 3 phase meter total power limit | Write | ||
| AV | 302 | Ch n CT factor | CT factor for each channel (121≤n≤192); instances 302-373 | Write | ||
| AV | 374 | Ch n alarm breaker size | Current scale against which warning and alarm thresholds are measured. (121≤n≤192); instances 374-445 | Write | ||
| AV | 446 | Circuit c total power limit | Circuit total power limit (1≤c≤192); instances 446-637 | Write | ||
| AV | 638 | 3 phase meter 2 total power limit | 3 phase meter 2 total power limit | Write | ||
| AV | 639 | CT Type n Hardware Version 1 Factor | CT Type’s factor for Hardware Version 1 (1≤n≤120); instances 639-758 | Write | ||
| AV | 759 | CT Type n Hardware Version 2 Factor | CT Type’s factor for Hardware Version 2 (1≤n≤120); instances 759-878 | Write | ||
| AV | 879 | Harmonic calculations nominal voltage | Harmonic calculations nominal voltage | Write | ||
| AV | 880 | CT Type n Hardware Version 1 Factor | CT Type’s factor for Hardware Version 1 (121≤n≤500); instances 880-1259 | Write | ||
| AV | 1260 | CT Type n Hardware Version 2 Factor | CT Type’s factor for Hardware Version 2 (121≤n≤500); instances 1260-1639 | Write | ||
| AV | 1640 | PT Ratio | PT Ratio | Write | ||
| AV | 1641 | Zero Threshold | Zero Threshold | Write | ||
| AV | 1642 | Imbalance phases | Expected Voltage Lines for HU Imbalance | Write | ||
| PIV | 0 | Ch n circuit | Circuit grouping number: single, two or three phase (1≤n≤120); instances 0-119 | Write | ||
| PIV | 120 | Ch n CT | CT identifier and max current (1≤n≤120); instances 120-239 | Write | ||
| PIV | 240 | Ch n phase | The phase connection is derived from the board by the jumper setting. (1≤n≤120); instances 240-359 | Write | ||
| PIV | 360 | Ch n Exp phase | This is the phase that the board expects to be connected. (1≤n≤120); instances 360-479 | Write | ||
| PIV | 480 | Ch n warning threshold | Channel’s warning level. (1≤n≤120); instances 480-599 | Write | ||
| PIV | 600 | Ch n alarm threshold | Channel’s alarm level. (1≤n≤120); instances 600-719 | Write | ||
| PIV | 720 | Ch n warning delay | Time over warning level before warning is triggered. (1≤n≤120); instances 720-839 | Write | ||
| PIV | 840 | Ch n alarm delay | Time over alarm level before alarm is triggered. (1≤n≤120); instances 840-959 | Write | ||
| PIV | 960 | Log n configuration count | Version of the log configuration. (0≤n≤9); instances 960-969 | Write | ||
| PIV | 970 | Log n mode | Rollover or stop logging when full. (0≤n≤9); instances 970-979 | Write | ||
| PIV | 980 | Log n max entries | Maximum number of entries in log (≤ 65535). (0≤n≤9); instances 980-989 | Write | ||
| PIV | 990 | Log n interval | How often log entry is made. (0≤n≤9); instances 990-999 | Write | ||
| PIV | 1000 | Log n offset | Offset from day/hour/minute to make log entry. (0≤n≤9); instances 1000-1009 | Write | ||
| PIV | 1010 | Log n register list length | Number of registers in log entry. (0≤n≤9); instances 1010-1019 | Write | ||
| PIV | 1020 | Voltage alarm delay | Time under or over threshold before alarm is triggered | Write | ||
| PIV | 1021 | Tripped breaker timeframe | Time over tripped breaker current before tripped breaker alarm becomes active | Write | ||
| PIV | 1022 | Nr channels | Number of physical channels | Write | ||
| PIV | 1023 | kWh scale | Multiplier for kWh readings | Write | ||
| PIV | 1024 | High power mode | Readings over high or low power range | Write | ||
| PIV | 1025 | CPU serial nr | CPU’s serial number | Write | ||
| PIV | 1026 | ANSI/IEC channel numbering | ANSI/IEC channel numbering | Write | ||
| PIV | 1027 | Nr channels on TAP n | Number of channels on TAP (1≤n≤30); instances 1027-1056 | Write | ||
| PIV | 1057 | Supply type | Supply type | Write | ||
| PIV | 1058 | 3 phase meter current wave capture mode | 3 phase meter current wave capture mode | Write | ||
| PIV | 1059 | TAPs current wave capture mode | TAPs current wave capture mode | Write | ||
| PIV | 1060 | Channel selected for I harmonics | Channel selected for I harmonics | Write | ||
| PIV | 1061 | 123N circuit n warning threshold | 123N circuit warning threshold (1≤n≤48); instances 1061-1108 | Write | ||
| PIV | 1109 | 123N circuit n alarm threshold | 123N circuit alarm threshold (1≤n≤48); instances 1109-1156 | Write | ||
| PIV | 1157 | 123N circuit n warning delay | 123N circuit warning delay (1≤n≤48); instances 1157-1204 | Write | ||
| PIV | 1205 | 123N circuit n alarm delay | 123N circuit alarm delay (1≤n≤48); instances 1205-1252 | Write | ||
| PIV | 1253 | 3 phase meter warning threshold | 3 phase meter warning threshold | Write | ||
| PIV | 1254 | 3 phase meter alarm threshold | 3 phase meter alarm threshold | Write | ||
| PIV | 1255 | 3 phase meter warning delay | 3 phase meter warning delay | Write | ||
| PIV | 1256 | 3 phase meter alarm delay | 3 phase meter alarm delay | Write | ||
| PIV | 1257 | Ch n circuit | Circuit grouping number: single, two or three phase (121≤n≤192); instances 1257-1328 | Write | ||
| PIV | 1329 | Ch n CT | CT identifier and max current (121≤n≤192); instances 1329-1400 | Write | ||
| PIV | 1401 | Ch n phase | The phase connection is derived from the board by the jumper setting. (121≤n≤192); instances 1401-1472 | Write | ||
| PIV | 1473 | Ch n Exp phase | This is the phase that the board expects to be connected. (121≤n≤192); instances 1473-1544 | Write | ||
| PIV | 1545 | Ch n warning threshold | Channel’s warning level. (121≤n≤192); instances 1545-1616 | Write | ||
| PIV | 1617 | Ch n alarm threshold | Channel’s alarm level. (121≤n≤192); instances 1617-1689 | Write | ||
| PIV | 1689 | Ch n warning delay | Time over warning level before warning is triggered. (121≤n≤192); instances 1689-1760 | Write | ||
| PIV | 1761 | Ch n alarm delay | Time over alarm level before alarm is triggered. (121≤n≤192); instances 1761-1832 | Write | ||
| PIV | 1833 | Log n configuration count | Version of the log configuration. (10≤n≤20); instances 1833-1843 | Write | ||
| PIV | 1844 | Log n mode | Rollover or stop logging when full. (10≤n≤20); instances 1844-1854 | Write | ||
| PIV | 1855 | Log n max entries | Maximum number of entries in log (≤ 65535). (10≤n≤20); instances 1855-1865 | Write | ||
| PIV | 1866 | Log n interval | How often log entry is made. (10≤n≤20); instances 1866-1876 | Write | ||
| PIV | 1877 | Log n offset | Offset from day/hour/minute to make log entry. (10≤n≤20); instances 1877-1887 | Write | ||
| PIV | 1888 | Log n register list length | Number of registers in log entry. (10≤n≤20); instances 1888-1898 | Write | ||
| PIV | 1899 | Circuit c warning threshold | Circuit warning threshold (1≤c≤192); instances 1899-2090 | Write | ||
| PIV | 2091 | Circuit c alarm threshold | Circuit alarm threshold (1≤c≤192); instances 2091-2282 | Write | ||
| PIV | 2283 | Circuit c warning delay | Circuit warning delay (1≤c≤192); instances 2283-2474 | Write | ||
| PIV | 2475 | Circuit c alarm delay | Circuit alarm delay (1≤c≤192); instances 2475-2666 | Write | ||
| PIV | 2667 | 3 phase meter 2 warning threshold | 3 phase meter 2 warning threshold | Write | ||
| PIV | 2668 | 3 phase meter 2 alarm threshold | 3 phase meter 2 alarm threshold | Write | ||
| PIV | 2669 | 3 phase meter 2 warning delay | 3 phase meter 2 warning delay | Write | ||
| PIV | 2670 | 3 phase meter 2 alarm delay | 3 phase meter 2 alarm delay | Write | ||
| PIV | 2671 | Ch n Load Type | Channel’s load type (1≤n≤192); instances 2671-2862 | Write | ||
| PIV | 2863 | CT Type n Hardware Version 1 PHCAL | CT Type’s PHCAL for Hardware Version 1 (1≤n≤120); instances 2863-2982 | Write | ||
| PIV | 2983 | CT Type n Hardware Version 2 PHCAL | CT Type’s PHCAL for Hardware Version 2 (1≤n≤120); instances 2983-3102 | Write | ||
| PIV | 3103 | Demand Interval | Demand Interval | Write | ||
| PIV | 3104 | Demand Subinterval | Demand Subinterval | Write | ||
| PIV | 3105 | Last Demand Interval | Interval of last demand period | Write | ||
| PIV | 3106 | Last Demand Subinterval | Subinterval of last demand period | Write | ||
| PIV | 3107 | Last Demand Timestamp | Time the last demand period was ended | Write | ||
| Other | 0 | Warnings | BitString Value. Channel warning states | Write | ||
| Othermin | 1 | Alarms | BitString Value. Channel alarm states | Write | ||
| Othermin | 2 | Tripped breakers | BitString Value. Channel tripped breaker states | Write | ||
| Other | 3 | Warnings latched | BitString Value. Channel latched warning states | Write | ||
| Other | 4 | Alarms latched | BitString Value. Channel latched alarm states | Write | ||
| Other | 5 | Tripped breakers latched | BitString Value. Channel latched tripped breaker states | Write | ||
| Other | 6 | Voltage low alarms | BitString Value. Voltage low alarm states | Write | ||
| Other | 7 | Voltage high alarms | BitString Value. Voltage high alarm states | Write | ||
| Other | 8 | Voltage low alarms latched | BitString Value. Voltage low latched alarm states | Write | ||
| Other | 9 | Voltage high alarms latched | BitString Value. Voltage high latched alarm states | Write | ||
| Other | 10 | Dry contact inputs | BitString Value. Dry contact inputs | Write | ||
| Other | 11 | 123N circuit n power alarms | BitString Value. 123N circuit power alarms (1≤n≤48); instances 11-58 | Write | ||
| Other | 59 | 3 phase meter power alarms | BitString Value. 3 phase meter power alarms | Write | ||
| Other | 60 | Circuit c power alarms | BitString Value. Circuit power alarms (1≤c≤192); instances 60-251 | Write | ||
| Other | 252 | 3 phase meter 2 power alarms | BitString Value. 3 phase meter 2 power alarms | Write | ||
| Other | 253 | Card c dry inputs | BitString Value. Dry input states (1≤c≤10); instances 253-262 | Write | ||
| CSV | 0 | CT Type n Name | CT type names (1≤n≤120); instances 0-119 | Write | ||
| CSV | 120 | Load Type n Name | Load type names (1≤n≤20); instances 120-139 | Write | ||
| CSV | 140 | Circuit n Name | Circuit names (1≤n≤192); instances 140-331 | Write | ||
| CSV | 332 | Circuit n Identifier | Circuit rack identifier (1≤n≤192); instances 332-523 | Write |
No points match these filters.
Object ID lookup: Schneider Electric PowerLogic HDPM6000 high-density power meter point IDs by name
AI0Ch n VrmsAI120Ch n IrmsAI240Ch n PFactorAI360Ch n WattsAI480Ch n kWhAI600Ch n kWh resettingAI720Phase n VrmsAI723Phase n ItotAI726Phase n PFactor avgAI729Phase n WattsAI732Phase n kWhAI735Dry contact n VAI743Dry contact n IrmsAI751Phase N ItotAI752All Phase average VrmsAI753All Phase ItotAI754All Phase IavgAI755All Phase PFactor avgAI756All Phase Watts totalAI757All Phase kWh totalAI7583phm Phase n VrmsAI7613phm Phase n IrmsAI7643phm Phase n PFactor avgAI7673phm Phase n WattsAI7703phm Phase n kWhAI7733phm Phase N IrmsAI7743phm All Phase average VrmsAI7753phm All Phase ItotAI7763phm All Phase IavgAI7773phm All Phase PFactor avgAI7783phm All Phase Watts totalAI7793phm All Phase kWh totalAI7803phm 1-2 VrmsAI7813phm 2-3 VrmsAI7823phm 3-1 VrmsAI7833phm L-L avg VrmsAI7843phm Phase n VARAI7873phm All Phase VAR totalAI7883phm Phase n VAAI7913phm All Phase VA totalAI7923phm Phase n VTHDAI7953phm All Phase VTHD totalAI7963phm All Phase VTHD avgAI7973phm Phase n ITHDAI8003phm All Phase ITHD totalAI8013phm All Phase ITHD avgAI8023phm Phase n kWh exportAI8053phm All Phase kWh exportAI8063phm Phase n kWh importAI8093phm All Phase kWh importAI8103phm Phase n kVARh totalAI8133phm All Phase kVARh totalAI8143phm Phase n kVARh exportAI8173phm All Phase kVARh exportAI8183phm Phase n kVARh importAI8213phm All Phase kVARh importAI8223phm Phase n frequencyAI8253phm All Phase frequency averageAI8263phm Phase n Watts maxAI8293phm total power usedAI8303phm total power remainingAI8313phm Phase n V harmonic hAI9273phm Phase n I harmonic hAI1023Selected channel I harmonic hAI1055Ch n ITHDAI1175Ch n VARAI1295Ch n Watts maxAI1415123N circuit c Phase n VrmsAI1559123N circuit c Phase n IrmsAI1703123N circuit c Phase n PFactor avgAI1847123N circuit c Phase n WattsAI1991123N circuit c Phase n kWhAI2135123N circuit c Phase N IrmsAI2183123N circuit c All Phase average VrmsAI2231123N circuit c All Phase ItotAI2279123N circuit c All Phase IavgAI2327123N circuit c All Phase PFactor avgAI2375123N circuit c All Phase Watts totalAI2423123N circuit c All Phase kWh totalAI2471123N circuit c 1-2 VrmsAI2519123N circuit c 2-3 VrmsAI2567123N circuit c 3-1 VrmsAI2615123N circuit c L-L avg VrmsAI2663123N circuit c Phase n VARAI2807123N circuit c All Phase VAR totalAI2855123N circuit c Phase n VAAI2999123N circuit c All Phase VA totalAI3047123N circuit c Phase n ITHDAI3191123N circuit c Phase N ITHDAI3239123N circuit c All Phase ITHD totalAI3287123N circuit c All Phase ITHD avgAI3335123N circuit c Phase n Watts maxAI3479123N circuit c total power usedAI3527123N circuit c total power remainingAI3575Ch n VrmsAI3647Ch n IrmsAI3719Ch n PFactorAI3791Ch n WattsAI3863Ch n kWhAI3935Ch n ITHDAI4007Ch n VARAI4079Ch n Watts maxAI4151Environmental sensor n, [3phm / TAP] t, port p, value vAI4407Circuit c Phase n VrmsAI4983Circuit c Phase n IrmsAI5559Circuit c Phase n PFactor avgAI6135Circuit c Phase n WattsAI6711Circuit c Phase n kWhAI7287Circuit c Phase N IrmsAI7479Circuit c All Phase average VrmsAI7671Circuit c All Phase ItotAI7863Circuit c All Phase IavgAI8055Circuit c All Phase PFactor avgAI8247Circuit c All Phase Watts totalAI8439Circuit c All Phase kWh totalAI8631Circuit c 1-2 VrmsAI8823Circuit c 2-3 VrmsAI9015Circuit c 3-1 VrmsAI9207Circuit c L-L avg VrmsAI9399Circuit c Phase n VARAI9975Circuit c All Phase VAR totalAI10167Circuit c Phase n VAAI10743Circuit c All Phase VA totalAI10935Circuit c Phase n ITHDAI11511Circuit c Phase N ITHDAI11703Circuit c All Phase ITHD totalAI11895Circuit c All Phase ITHD avgAI12087Circuit c Phase n Watts maxAI12663Circuit c total power usedAI12855Circuit c total power remainingAI130473 phase meter 2 Phase n VrmsAI130503 phase meter 2 Phase n IrmsAI130533 phase meter 2 Phase n PFactor avgAI130563 phase meter 2 Phase n WattsAI130593 phase meter 2 Phase n kWhAI130623 phase meter 2 Phase N IrmsAI130633 phase meter 2 All Phase average VrmsAI130643 phase meter 2 All Phase ItotAI130653 phase meter 2 All Phase IavgAI130663 phase meter 2 All Phase PFactor avgAI130673 phase meter 2 All Phase Watts totalAI130683 phase meter 2 All Phase kWh totalAI130693 phase meter 2 1-2 VrmsAI130703 phase meter 2 2-3 VrmsAI130713 phase meter 2 3-1 VrmsAI130723 phase meter 2 L-L avg VrmsAI130733 phase meter 2 Phase n VARAI130763 phase meter 2 All Phase VAR totalAI130773 phase meter 2 Phase n VAAI130803 phase meter 2 All Phase VA totalAI130813 phase meter 2 Phase n VTHDAI130843 phase meter 2 All Phase VTHD totalAI130853 phase meter 2 All Phase VTHD avgAI130863 phase meter 2 Phase n ITHDAI130893 phase meter 2 All Phase ITHD totalAI130903 phase meter 2 All Phase ITHD avgAI130913 phase meter 2 Phase n kWh exportAI130943 phase meter 2 All Phase kWh exportAI130953 phase meter 2 Phase n kWh importAI130983 phase meter 2 All Phase kWh importAI130993 phase meter 2 Phase n kVARh totalAI131023 phase meter 2 All Phase kVARh totalAI131033 phase meter 2 Phase n kVARh exportAI131063 phase meter 2 All Phase kVARh exportAI131073 phase meter 2 Phase n kVARh importAI131103 phase meter 2 All Phase kVARh importAI131113 phase meter 2 Phase n frequencyAI131143 phase meter 2 All Phase frequency averageAI131153 phase meter 2 Phase n Watts maxAI131183 phase meter 2 total power usedAI131193 phase meter 2 total power remainingAI131203 phase meter 2 Phase 1 V harmonic nAI131523 phase meter 2 Phase 2 V harmonic nAI131843 phase meter 2 Phase 3 V harmonic nAI132163 phase meter 2 Phase 1 I harmonic nAI132483 phase meter 2 Phase 2 I harmonic nAI132803 phase meter 2 Phase 3 I harmonic nAI13312Load Type n Total WattsAI133323 phase meter Ch n Demand Avg PowerAI133353 phase meter Ch n Demand Min PowerAI133383 phase meter Ch n Demand Max PowerAI133413 phase meter Ch n Demand Avg Apparent PowerAI133443 phase meter Ch n Demand Min Apparent PowerAI133473 phase meter Ch n Demand Max Apparent PowerAI133503 phase meter Ch n Demand Avg Reactive PowerAI133533 phase meter Ch n Demand Min Reactive PowerAI133563 phase meter Ch n Demand Max Reactive PowerAI133593 phase meter Ch n Demand Avg CurrentAI133623 phase meter Ch n Demand Min CurrentAI133653 phase meter Ch n Demand Max CurrentAI133683phase meter Total Demand Avg PowerAI133693phase meter Total Demand Min PowerAI133703phase meter Total Demand Max PowerAI133713phase meter Total Demand Avg Apparent PowerAI133723phase meter Total Demand Min Apparent PowerAI133733phase meter Total Demand Max Apparent PowerAI133743phase meter Total Demand Avg Reactive PowerAI133753phase meter Total Demand Min Reactive PowerAI133763phase meter Total Demand Max Reactive PowerAI133773phase meter Total Demand Avg CurrentAI133783phase meter Total Demand Min CurrentAI133793phase meter Total Demand Max CurrentAI133803 phase meter Phase n Demand Daily Peak PowerAI133833 phase meter Phase n Demand Peak PowerAI133863 phase meter All Phase Demand Daily Peak PowerAI133873 phase meter All Phase Demand Peak PowerAI13388Cct n Demand Avg PowerAI13580Cct n Demand Daily Peak PowerAI13772Cct n Demand Peak PowerAI139643 phase meter Phase n kVAh totalAI139673 phase meter All Phase kVAh totalAI139683 phase meter Phase n kVAh exportAI139713 phase meter All Phase kVAh exportAI139723 phase meter Phase n kVAh importAI139753 phase meter All Phase kVAh importAI139763 phase meter I imbalanceAI139773 phase meter V imbalanceAI139783 phase meter I total demand distortionAI139793 phase meter 2 I imbalanceAI139803 phase meter 2 V imbalanceAI139813 phase meter 2 I total demand distortionAI13982Phase n DPFAI139853 phase meter Ch n Demand Min VLNAI139883 phase meter Ch n Demand Max VLNAI139913 phase meter Ch n Demand Avg VLNAI139943 phase meter Ch n Demand Min VLLAI139973 phase meter Ch n Demand Max VLLAI140003 phase meter Ch n Demand Avg VLLAI140033 phase meter 2 Ch n Demand Avg PowerAI140063 phase meter 2 Ch n Demand Min PowerAI140093 phase meter 2 Ch n Demand Max PowerAI140123 phase meter 2 Ch n Demand Avg Apparent PowerAI140153 phase meter 2 Ch n Demand Min Apparent PowerAI140183 phase meter 2 Ch n Demand Max Apparent PowerAI140213 phase meter 2 Ch n Demand Avg Reactive PowerAI140243 phase meter 2 Ch n Demand Min Reactive PowerAI140273 phase meter 2 Ch n Demand Max Reactive PowerAI140303 phase meter 2 Ch n Demand Avg CurrentAI140333 phase meter 2 Ch n Demand Min CurrentAI140363 phase meter 2 Ch n Demand Max CurrentAI140393phase meter 2 Total Demand Avg PowerAI140403phase meter 2 Total Demand Min PowerAI140413phase meter 2 Total Demand Max PowerAI140423phase meter 2 Total Demand Avg Apparent PowerAI140433phase meter 2 Total Demand Min Apparent PowerAI140443phase meter 2 Total Demand Max Apparent PowerAI140453phase meter 2 Total Demand Avg Reactive PowerAI140463phase meter 2 Total Demand Min Reactive PowerAI140473phase meter 2 Total Demand Max Reactive PowerAI140483phase meter 2 Total Demand Avg CurrentAI140493phase meter 2 Total Demand Min CurrentAI140503phase meter 2 Total Demand Max CurrentAI140513 phase meter 3 Ch n Demand Avg PowerAI140543 phase meter 3 Ch n Demand Min PowerAI140573 phase meter 3 Ch n Demand Max PowerAI140603 phase meter 3 Ch n Demand Avg Apparent PowerAI140633 phase meter 3 Ch n Demand Min Apparent PowerAI140663 phase meter 3 Ch n Demand Max Apparent PowerAI140693 phase meter 3 Ch n Demand Avg Reactive PowerAI140723 phase meter 3 Ch n Demand Min Reactive PowerAI140753 phase meter 3 Ch n Demand Max Reactive PowerAI140783 phase meter 3 Ch n Demand Avg CurrentAI140813 phase meter 3 Ch n Demand Min CurrentAI140843 phase meter 3 Ch n Demand Max CurrentAI140873phase meter 3 Total Demand Avg PowerAI140883phase meter 3 Total Demand Min PowerAI140893phase meter 3 Total Demand Max PowerAI140903phase meter 3 Total Demand Avg Apparent PowerAI140913phase meter 3 Total Demand Min Apparent PowerAI140923phase meter 3 Total Demand Max Apparent PowerAI140933phase meter 3 Total Demand Avg Reactive PowerAI140943phase meter 3 Total Demand Min Reactive PowerAI140953phase meter 3 Total Demand Max Reactive PowerAI140963phase meter 3 Total Demand Avg CurrentAI140973phase meter 3 Total Demand Min CurrentAI140983phase meter 3 Total Demand Max CurrentAI14099Circuit c Current ImbalanceAV0Ch n CT factorAV120Ch n alarm breaker sizeAV240Phase n Vlo thresholdAV243Phase n Vhi thresholdAV246Tripped breaker currentAV2473phm SAGVAV2483phm OVAV2493phm OIAV2503phm OI hold-offAV251TAPs TB hold-offAV252TAPs TB trigger levelAV253123N circuit n total power limitAV3013phm total power limitAV302Ch n CT factorAV374Ch n alarm breaker sizeAV446Circuit c total power limitAV6383 phase meter 2 total power limitAV639CT Type n Hardware Version 1 FactorAV759CT Type n Hardware Version 2 FactorAV879Harmonic calculations nominal voltageAV880CT Type n Hardware Version 1 FactorAV1260CT Type n Hardware Version 2 FactorAV1640PT RatioAV1641Zero ThresholdAV1642Imbalance phasesPIV0Ch n circuitPIV120Ch n CTPIV240Ch n phasePIV360Ch n Exp phasePIV480Ch n warning thresholdPIV600Ch n alarm thresholdPIV720Ch n warning delayPIV840Ch n alarm delayPIV960Log n configuration countPIV970Log n modePIV980Log n max entriesPIV990Log n intervalPIV1000Log n offsetPIV1010Log n register list lengthPIV1020Voltage alarm delayPIV1021Tripped breaker timeframePIV1022Nr channelsPIV1023kWh scalePIV1024High power modePIV1025CPU serial nrPIV1026ANSI/IEC channel numberingPIV1027Nr channels on TAP nPIV1057Supply typePIV10583 phase meter current wave capture modePIV1059TAPs current wave capture modePIV1060Channel selected for I harmonicsPIV1061123N circuit n warning thresholdPIV1109123N circuit n alarm thresholdPIV1157123N circuit n warning delayPIV1205123N circuit n alarm delayPIV12533 phase meter warning thresholdPIV12543 phase meter alarm thresholdPIV12553 phase meter warning delayPIV12563 phase meter alarm delayPIV1257Ch n circuitPIV1329Ch n CTPIV1401Ch n phasePIV1473Ch n Exp phasePIV1545Ch n warning thresholdPIV1617Ch n alarm thresholdPIV1689Ch n warning delayPIV1761Ch n alarm delayPIV1833Log n configuration countPIV1844Log n modePIV1855Log n max entriesPIV1866Log n intervalPIV1877Log n offsetPIV1888Log n register list lengthPIV1899Circuit c warning thresholdPIV2091Circuit c alarm thresholdPIV2283Circuit c warning delayPIV2475Circuit c alarm delayPIV26673 phase meter 2 warning thresholdPIV26683 phase meter 2 alarm thresholdPIV26693 phase meter 2 warning delayPIV26703 phase meter 2 alarm delayPIV2671Ch n Load TypePIV2863CT Type n Hardware Version 1 PHCALPIV2983CT Type n Hardware Version 2 PHCALPIV3103Demand IntervalPIV3104Demand SubintervalPIV3105Last Demand IntervalPIV3106Last Demand SubintervalPIV3107Last Demand TimestampCSV0CT Type n NameCSV120Load Type n NameCSV140Circuit n NameCSV332Circuit n Identifier
Integration notes
- Each row is the first object (n = 1, or the first c, t or h) of a block; the description gives the variable range and the full instance range. Object k of a block is the first instance + (k - 1); harmonic blocks step over odd harmonics only, per the guide.
- Names are the printed patterns; on the device n, c, t, p, v or h is replaced by the channel, circuit, TAP, port, value or harmonic number.
- The guide prints some block starts wrongly: '3 phase meter 3 Ch n Demand Max Reactive Power' and '... Avg Current' as 17075 and 17078; by sequence they are 14075 and 14078 and are listed so. It also prints 13972-13984 for a 3-instance block (13972-13974) and overlapping ranges 1617-1689 / 1689-1760 for PIV channel alarm thresholds and warning delays.
- Present_Value is writable for AV, PIV, BitString and CharString Value objects per the PICS, but the guide says configuration is normally done through Modbus or the web interface.
- BitString Value objects (alarm and warning states, dry inputs) are listed as type Other. The environmental sensor block name prints '[3phm | TAP]'; shown here with a slash.
- BACnet is only on Ethernet; the RS-485 port is Modbus RTU. Source: HDPM6000 Protocol Guide ZL0192-0G (04/2026), Section 4.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PowerLogic HDPM6000 high-density power meter (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
How many BACnet points does the Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP) have?
This list has 386 BACnet objects: 277 analog inputs, 25 analog values, 4 characterstring values, 64 positive integer values, 16 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP) BACnet points are writable?
109 of the 386 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP) BACnet documentation?
The source is HDPM6000 Protocol Guide (ZL0192-0G), revision 2026-04, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=ZL0192.
What are the minimum BACnet points to integrate the Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)?
Start with AI 756 All Phase Watts total (Total power across all phases); AI 757 All Phase kWh total (Total energy across all phases); AI 360 Ch n Watts (Channel 1 power; channel n = 359 + n); AI 480 Ch n kWh (Channel 1 energy; channel n = 479 + n); AI 120 Ch n Irms (Channel 1 RMS current; channel n = 119 + n); AI 720 Phase n Vrms (Phase 1 RMS voltage (720-722)); Other 1 Alarms (Channel alarm state bits); Other 2 Tripped breakers (Channel tripped-breaker bits).
How do I enable BMS control of the Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)?
BACnet is enabled with a protocol flag in the head unit's network settings (web interface or Modbus); there is no BMS enable point.
How do I check these points on the real PowerLogic HDPM6000 high-density power meter (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Schneider Electric PowerLogic PM5300 series power meters with the Ethernet port (PM5320, PM5340, PM5341) using BACnet IP.
Also known as: PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Zone controller (room thermostat)
Schneider Electric SE7200 Series PIR Ready Zoning Controller
Schneider Electric PIR-ready SE7200 series 24 Vac zoning controllers (SE7200C5x45B, SE7200F5x45B).
Also known as: SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Schneider Electric PIR-ready SER7300 series line-voltage fan coil controllers: SER7300, SER7305, SER7350 and SER7355 (A versions).
Also known as: SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B - Pressure-dependent VAV zone controller
Schneider Electric SEZ7260 Zoning System Zone Controller
Schneider Electric SEZ7260 zone controllers (F model with floating damper and AO2, C model) used with SEZ7656 rooftop controllers in pressure-dependent zoning systems.
Also known as: SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B - Rooftop unit controller for zoning systems
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Schneider Electric SEZ7656 rooftop controllers (R conventional, H heat pump, F modulating heat, E economizer) that run a rooftop unit for a group of SEZ7260 zone controllers.
Also known as: SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Schneider Electric SpaceLogic SE8000-series SER8350 room controllers for line-voltage fan coil units.
Also known as: SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350 - Room humidity and temperature sensor (wall)
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Schneider Electric SpaceLogic SLP Series wall humidity/temperature sensors (with or without touchscreen) set to BACnet MS/TP.
Also known as: SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil - Rooftop unit controller (room thermostat, rooftop or heat-pump units)
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 6500 (rooftop unit / heat pump) version.
Also known as: SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump
Source: HDPM6000 Protocol Guide · ZL0192-0G · rev. 2026-04. Object names, instances and units are reproduced as published; descriptions are our own.