Zone controller (room thermostat) · BACnet points list

Schneider Electric SE7200 Series PIR Ready Zoning Controller BACnet points list

Updated 4 November 2026

Short answer

The SE7200 is a 24 Vac PIR-ready room controller for zoning (on/off or floating outputs). With the BACnet module it is a BACnet MS/TP application specific controller (B-ASC) with about 55 objects: room and outdoor temperature, setpoints, system mode, occupancy, PI demands, output status and configuration objects.

This page lists 57 BACnet objects for the Schneider Electric SE7200 Series PIR Ready Zoning Controller — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.

Manufacturer
Schneider Electric
Model
SE7200 Series PIR Ready Zoning Controller
Equipment
Zone controller (room thermostat)
Equipment type
Thermostats, sensors & meters
BACnet objects
57 (37 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
72000 + MAC address
Also known as
SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B
Source document
BACnet Integration Manual: PIR Ready SE7200, SE7300 & SER7300 Series (24 Vac zoning, fan coil and line-voltage fan coil controllers) · IG-SE7000-BNET24VAC-A4.EN.4.2013.v1 · rev. April 2013
Download CSV 57 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.

BMS integration notes: Schneider Electric SE7200 Series PIR Ready Zoning Controller

Integration in brief

Command occupancy with MV 18 and the mode with MV 16, and write the occupied setpoints AV 39/AV 40. Read AV 7 room temperature, MV 33 effective occupancy and the PI demands AV 21/AV 22. The BMS can also send outdoor temperature to AV 9.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 18Occupancy CommandBMS occupancy: local, occupied or unoccupiedCommand
MV 16System ModeOff / auto / cool / heatCommand
AV 39Occupied Heat SetpointOccupied heating setpointCommand
AV 40Occupied Cool SetpointOccupied cooling setpointCommand
MV 33Effective OccupancyActual occupancy stateRead
AV 7Room TemperatureSpace temperatureCommand
AV 21PI Heating DemandHeating demand, 0-100 %Read
AV 22PI Cooling DemandCooling demand, 0-100 %Read
BI 38Service AlarmService alarm from an input set to ServiceRead

Enable & remote start

BACnet stays off until the MAC address is changed from the factory 254 to 0-127. MV 18 Occupancy Command: 1 = Local Occupancy, 2 = Occupied, 3 = Unoccupied.

Sensors & values from the BMS

The BMS can write Outdoor Temperature (AV 9) and, for testing or override, Room Temperature (AV 7); AV 7 only accepts writes while BV 8 Room Temp Override is set to Override. Written room temperature, outdoor temperature and occupancy are released if the controller goes offline.

Network setup

Watch out for

Schneider Electric SE7200 Series PIR Ready Zoning Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

57 of 57 shown
Type
Multi-stateOther
Access
Show
Schneider Electric SE7200 Series PIR Ready Zoning Controller BACnet Points List
DescriptionStates
AVmin7Room TemperatureRange -39.9°F (-40°C) to 121.9°F (50°C)°F/°CCommand
BV8Room Temp OverrideDefault NormalCommand0=Normal, 1=Override
AV9Outdoor TemperatureRange -39°F (-40°C) to 121.9°F (50°C)°F/°CCommand
AI12Supply TemperatureRange -39.9°F (-40°C) to 121.9°F (50°C)°F/°CRead
BV14AUX CommandDefault OffCommand0=Off, 1=On
MV15Sequence of OperationCommand1=Cooling Only, 2=Heating Only, 3=Cooling & Reheat, 4=Heating & Reheat, 5=Cool/Heat4P, 6=Cool/Heat4P&Reht
MVmin16System ModeCommand1=Off, 2=Auto, 3=Cool, 4=Heat
MVmin18Occupancy CommandCommand1=Local Occupancy, 2=Occupied, 3=Unoccupied
MV19Keypad LockoutCommand1=Level 0, 2=Level 1, 3=Level 2, 4=Level 3, 5=Level 4, 6=Level 5
Other20Control OutputGroup object (bundles related objects)Read
AVmin21PI Heating DemandRange 0% to 100%; default 0%%Read
AVmin22PI Cooling DemandRange 0% to 100%; default 0%%Read
Other24Controller StatusGroup object (bundles related objects)Read
BI25AUX StatusDefault OffRead0=Off, 1=On
MV26Output 2Read
MV27Output 1Read
MV28Fan StatusRead1=Off, 2=Low, 3=Med, 4=High
BI30BI 2 StatusDefault DeactivatedRead0=Deactivated, 1=Activated
BI31UI 3 StatusDefault DeactivatedRead0=Deactivated, 1=Activated
BI32Local MotionDefault No MotionRead0=No Motion, 1=Motion
MVmin33Effective OccupancyRead1=Occupied, 2=Unoccupied, 3=Temporary Occupied, 4=Stand-by
Other34Controller AlarmsGroup object (bundles related objects)Read
BI36Window AlarmRead
BI37Filter AlarmRead
BImin38Service AlarmRead
Other38Temperature SetpointsGroup object (bundles related objects)Read
AVmin39Occupied Heat SetpointRange 40°F (4.5°C) to 90°F (32°C); default 72°F (22°C)°F/°CCommand
AVmin40Occupied Cool SetpointRange 54°F (12°C) to 100°F (37.5°C); default 74°F (24°C)°F/°CCommand
AV41Stand-by Heat SetpointRange 40°F (4.5°C) to 90°F (32°C); default 72°F (22°C)°F/°CCommand
AV42Stand-by Cool SetpointRange 54°F (12°C) to 100°F (37.5°C); default 74°F (24°C)°F/°CCommand
AV43Unoccupied Heat SetpointRange 40°F (4.5°C) to 90°F (32°C); default 62°F (16.5°C)°F/°CCommand
AV44Unoccupied Cool SetpointRange 54°F (12°C) to 100°F (37.5°C); default 80°F (26.5°C)°F/°CCommand
Other45General Options 1Group object (bundles related objects)Read
MV46BI 1 ConfigurationCommand1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window
MV47BI 2 ConfigurationCommand1=None, 2=Door Dry, 3=Override, 4=Filter, 5=Service
MV48UI 3 configurationCommand1=None, 2=COC/NH, 3=COC/NC, 4=COS, 5=SS
BV49Menu ScrollDefault Scroll ActiveCommand0=No Scroll, 1=Scroll Active
BV50Auto Mode EnableDefault EnabledCommand0=Disabled, 1=Enabled
BV51Temperature ScaleDefault °FCommand0=°C, 1=°F
MV52Pipe NumberCommand
MV53Out#1 ConfigCommand
MV54AUX ConfigurationCommand1=Not used, 2=NO with Occ, 3=NC with Occ, 4=NO with Occ & Fan, 5=NC with Occ & Fan, 6=Network controlled
AV56Password ValueRange 0 to 1000Command
AV58Heating Setpoint LimitRange 40°F (4.5°C) to 90°F (32°C); default 90°F (32°C)°F/°CCommand
AV59Cooling Setpoint LimitRange 54°F (12°C) to 100°F (37.5°C); default 54°F (12°C)°F/°CCommand
BV60Setpoint TypeDefault PermanentCommand0=Permanent, 1=Temporary
MV62Temporary Occupancy TimeCommand1=0 hour, 2=1 hour, 3=2 hours, 4=3 hours, 5=4 hours, 6=5 hours, 7=6 hours, 8=7 hours, 9=8 hours, 10=9 hours, 11=10 hours, 12=11 hours, 13=12 hours, 14=13 hours, 15=14 hours, 16=15 hours, 17=16 hours, 18=17 hours, 19=18 hours, 20=19 hours, 21=20 hours, 22=21 hours, 23=22 hours, 24=23 hours, 25=24 hours
AV63DeadbandRange 2°F (1°C) to 5°F (2.5°C); default 2°F (1°C)°F/°CCommand
BV64Reheat Time BaseDefault 15 minutesCommand0=15 minutes, 1=10 seconds
MV65Proportional BandCommand1=3 °F (1.2 °C), 2=4 °F (1.7 °C), 3=5 °F (2.2 °C), 4=6 °F (2.8 °C), 5=7 °F (3.3 °C), 6=8 °F (3.9 °C), 7=9 °F (5.0 °C), 8=10 °F (5.6 °C)
AV67Stand-by TimeRange 0.5 Hours to 24.0 Hours; default 0.5 HourshCommand
AV68Unoccupied TimeRange 0.0 Hours to 24.0 Hours; default 0.0 HourshCommand
Other74Output Configuration OptionsGroup object (bundles related objects)Read
BV75Control typeDefault On/Off; only SE7200Command0=On/Off, 1=Floating
MV76Floating Motor timingonly SE7200Command1=0.5 minute, 2=1 minute, 3=1.5 minutes, 4=2 minutes, 5=2.5 minutes, 6=3 minutes, 7=3.5 minutes, 8=4 minutes, 9=4.5 minutes, 10=5 minutes, 11=5.5 minutes, 12=6 minutes, 13=6.5 minutes, 14=7 minutes, 15=7.5 minutes, 16=8 minutes, 17=8.5 minutes, 18=9 minutes
MV77On Off Control CPHonly SE7200Command1=3 CPH, 2=4 CPH, 3=5 CPH, 4=6 CPH, 5=7 CPH, 6=8 CPH
BV78Direct Reverse ActingDefault Direct Acting; only SE7200Command0=Direct Acting, 1=Reverse Acting
Object ID lookup: Schneider Electric SE7200 Series PIR Ready Zoning Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SE7200 Series PIR Ready Zoning Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Schneider Electric SE7200 Series PIR Ready Zoning Controller

How many BACnet points does the Schneider Electric SE7200 Series PIR Ready Zoning Controller have?

This list has 57 BACnet objects: 1 analog input, 16 analog values, 7 binary inputs, 9 binary values, 18 multi-state values, 6 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Schneider Electric SE7200 Series PIR Ready Zoning Controller BACnet points are writable?

37 of the 57 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Schneider Electric SE7200 Series PIR Ready Zoning Controller BACnet documentation?

The source is BACnet Integration Manual: PIR Ready SE7200, SE7300 & SER7300 Series (24 Vac zoning, fan coil and line-voltage fan coil controllers) (IG-SE7000-BNET24VAC-A4.EN.4.2013.v1), revision April 2013, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=IG-SE7000-BNET24VAC-A4.

What are the minimum BACnet points to integrate the Schneider Electric SE7200 Series PIR Ready Zoning Controller?

Start with MV 18 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 33 Effective Occupancy (Actual occupancy state); AV 7 Room Temperature (Space temperature); AV 21 PI Heating Demand (Heating demand, 0-100 %); AV 22 PI Cooling Demand (Cooling demand, 0-100 %); BI 38 Service Alarm (Service alarm from an input set to Service).

How do I enable BMS control of the Schneider Electric SE7200 Series PIR Ready Zoning Controller?

BACnet stays off until the MAC address is changed from the factory 254 to 0-127. MV 18 Occupancy Command: 1 = Local Occupancy, 2 = Occupied, 3 = Unoccupied.

Can the BMS supply sensor values to the Schneider Electric SE7200 Series PIR Ready Zoning Controller?

The BMS can write Outdoor Temperature (AV 9) and, for testing or override, Room Temperature (AV 7); AV 7 only accepts writes while BV 8 Room Temp Override is set to Override. Written room temperature, outdoor temperature and occupancy are released if the controller goes offline.

How do I check these points on the real SE7200 Series PIR Ready Zoning Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.