Zone controller (room thermostat) · BACnet points list
Schneider Electric SE7200 Series PIR Ready Zoning Controller BACnet points list
Updated 4 November 2026
The SE7200 is a 24 Vac PIR-ready room controller for zoning (on/off or floating outputs). With the BACnet module it is a BACnet MS/TP application specific controller (B-ASC) with about 55 objects: room and outdoor temperature, setpoints, system mode, occupancy, PI demands, output status and configuration objects.
This page lists 57 BACnet objects for the Schneider Electric SE7200 Series PIR Ready Zoning Controller — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- SE7200 Series PIR Ready Zoning Controller
- Equipment
- Zone controller (room thermostat)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 57 (37 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 72000 + MAC address
- Also known as
- SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric SE7200 Series PIR Ready Zoning Controller
Command occupancy with MV 18 and the mode with MV 16, and write the occupied setpoints AV 39/AV 40. Read AV 7 room temperature, MV 33 effective occupancy and the PI demands AV 21/AV 22. The BMS can also send outdoor temperature to AV 9.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 18 | Occupancy Command | BMS occupancy: local, occupied or unoccupied | Command |
| MV 16 | System Mode | Off / auto / cool / heat | Command |
| AV 39 | Occupied Heat Setpoint | Occupied heating setpoint | Command |
| AV 40 | Occupied Cool Setpoint | Occupied cooling setpoint | Command |
| MV 33 | Effective Occupancy | Actual occupancy state | Read |
| AV 7 | Room Temperature | Space temperature | Command |
| AV 21 | PI Heating Demand | Heating demand, 0-100 % | Read |
| AV 22 | PI Cooling Demand | Cooling demand, 0-100 % | Read |
| BI 38 | Service Alarm | Service alarm from an input set to Service | Read |
Enable & remote start
BACnet stays off until the MAC address is changed from the factory 254 to 0-127. MV 18 Occupancy Command: 1 = Local Occupancy, 2 = Occupied, 3 = Unoccupied.
Sensors & values from the BMS
The BMS can write Outdoor Temperature (AV 9) and, for testing or override, Room Temperature (AV 7); AV 7 only accepts writes while BV 8 Room Temp Override is set to Override. Written room temperature, outdoor temperature and occupancy are released if the controller goes offline.
Network setup
- Controllers ship with MAC address 254, which keeps BACnet communication off. Set the MAC address (0-127) at the controller to enable BACnet MS/TP.
- Default Device ID is 72000 + MAC address.
- Baud rate auto-detects (9600, 19200, 38400, 76800) at power-up; after a network speed change the device keeps the old speed for 10 minutes unless re-powered.
- Default Device Name is the model number plus the MAC address; Device Name and Device ID are writable.
- No COV support: poll at 5 seconds or slower and write on change ('if once' or every few minutes), not every program scan.
Watch out for
- If the controller goes offline, values the BMS wrote to Room Temperature, Outdoor Temperature and Occupancy are released.
- Segmented requests and responses are not supported; keep Read Property Multiple requests small.
- The device object has no Local_Time or Local_Date, so the controller cannot claim DM-TS-B even though time sync over the network works.
Schneider Electric SE7200 Series PIR Ready Zoning Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 7 | Room Temperature | Range -39.9°F (-40°C) to 121.9°F (50°C) | °F/°C | Command | |
| BV | 8 | Room Temp Override | Default Normal | Command | 0=Normal, 1=Override | |
| AV | 9 | Outdoor Temperature | Range -39°F (-40°C) to 121.9°F (50°C) | °F/°C | Command | |
| AI | 12 | Supply Temperature | Range -39.9°F (-40°C) to 121.9°F (50°C) | °F/°C | Read | |
| BV | 14 | AUX Command | Default Off | Command | 0=Off, 1=On | |
| MV | 15 | Sequence of Operation | Command | 1=Cooling Only, 2=Heating Only, 3=Cooling & Reheat, 4=Heating & Reheat, 5=Cool/Heat4P, 6=Cool/Heat4P&Reht | ||
| MVmin | 16 | System Mode | Command | 1=Off, 2=Auto, 3=Cool, 4=Heat | ||
| MVmin | 18 | Occupancy Command | Command | 1=Local Occupancy, 2=Occupied, 3=Unoccupied | ||
| MV | 19 | Keypad Lockout | Command | 1=Level 0, 2=Level 1, 3=Level 2, 4=Level 3, 5=Level 4, 6=Level 5 | ||
| Other | 20 | Control Output | Group object (bundles related objects) | Read | ||
| AVmin | 21 | PI Heating Demand | Range 0% to 100%; default 0% | % | Read | |
| AVmin | 22 | PI Cooling Demand | Range 0% to 100%; default 0% | % | Read | |
| Other | 24 | Controller Status | Group object (bundles related objects) | Read | ||
| BI | 25 | AUX Status | Default Off | Read | 0=Off, 1=On | |
| MV | 26 | Output 2 | Read | |||
| MV | 27 | Output 1 | Read | |||
| MV | 28 | Fan Status | Read | 1=Off, 2=Low, 3=Med, 4=High | ||
| BI | 30 | BI 2 Status | Default Deactivated | Read | 0=Deactivated, 1=Activated | |
| BI | 31 | UI 3 Status | Default Deactivated | Read | 0=Deactivated, 1=Activated | |
| BI | 32 | Local Motion | Default No Motion | Read | 0=No Motion, 1=Motion | |
| MVmin | 33 | Effective Occupancy | Read | 1=Occupied, 2=Unoccupied, 3=Temporary Occupied, 4=Stand-by | ||
| Other | 34 | Controller Alarms | Group object (bundles related objects) | Read | ||
| BI | 36 | Window Alarm | Read | |||
| BI | 37 | Filter Alarm | Read | |||
| BImin | 38 | Service Alarm | Read | |||
| Other | 38 | Temperature Setpoints | Group object (bundles related objects) | Read | ||
| AVmin | 39 | Occupied Heat Setpoint | Range 40°F (4.5°C) to 90°F (32°C); default 72°F (22°C) | °F/°C | Command | |
| AVmin | 40 | Occupied Cool Setpoint | Range 54°F (12°C) to 100°F (37.5°C); default 74°F (24°C) | °F/°C | Command | |
| AV | 41 | Stand-by Heat Setpoint | Range 40°F (4.5°C) to 90°F (32°C); default 72°F (22°C) | °F/°C | Command | |
| AV | 42 | Stand-by Cool Setpoint | Range 54°F (12°C) to 100°F (37.5°C); default 74°F (24°C) | °F/°C | Command | |
| AV | 43 | Unoccupied Heat Setpoint | Range 40°F (4.5°C) to 90°F (32°C); default 62°F (16.5°C) | °F/°C | Command | |
| AV | 44 | Unoccupied Cool Setpoint | Range 54°F (12°C) to 100°F (37.5°C); default 80°F (26.5°C) | °F/°C | Command | |
| Other | 45 | General Options 1 | Group object (bundles related objects) | Read | ||
| MV | 46 | BI 1 Configuration | Command | 1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window | ||
| MV | 47 | BI 2 Configuration | Command | 1=None, 2=Door Dry, 3=Override, 4=Filter, 5=Service | ||
| MV | 48 | UI 3 configuration | Command | 1=None, 2=COC/NH, 3=COC/NC, 4=COS, 5=SS | ||
| BV | 49 | Menu Scroll | Default Scroll Active | Command | 0=No Scroll, 1=Scroll Active | |
| BV | 50 | Auto Mode Enable | Default Enabled | Command | 0=Disabled, 1=Enabled | |
| BV | 51 | Temperature Scale | Default °F | Command | 0=°C, 1=°F | |
| MV | 52 | Pipe Number | Command | |||
| MV | 53 | Out#1 Config | Command | |||
| MV | 54 | AUX Configuration | Command | 1=Not used, 2=NO with Occ, 3=NC with Occ, 4=NO with Occ & Fan, 5=NC with Occ & Fan, 6=Network controlled | ||
| AV | 56 | Password Value | Range 0 to 1000 | Command | ||
| AV | 58 | Heating Setpoint Limit | Range 40°F (4.5°C) to 90°F (32°C); default 90°F (32°C) | °F/°C | Command | |
| AV | 59 | Cooling Setpoint Limit | Range 54°F (12°C) to 100°F (37.5°C); default 54°F (12°C) | °F/°C | Command | |
| BV | 60 | Setpoint Type | Default Permanent | Command | 0=Permanent, 1=Temporary | |
| MV | 62 | Temporary Occupancy Time | Command | 1=0 hour, 2=1 hour, 3=2 hours, 4=3 hours, 5=4 hours, 6=5 hours, 7=6 hours, 8=7 hours, 9=8 hours, 10=9 hours, 11=10 hours, 12=11 hours, 13=12 hours, 14=13 hours, 15=14 hours, 16=15 hours, 17=16 hours, 18=17 hours, 19=18 hours, 20=19 hours, 21=20 hours, 22=21 hours, 23=22 hours, 24=23 hours, 25=24 hours | ||
| AV | 63 | Deadband | Range 2°F (1°C) to 5°F (2.5°C); default 2°F (1°C) | °F/°C | Command | |
| BV | 64 | Reheat Time Base | Default 15 minutes | Command | 0=15 minutes, 1=10 seconds | |
| MV | 65 | Proportional Band | Command | 1=3 °F (1.2 °C), 2=4 °F (1.7 °C), 3=5 °F (2.2 °C), 4=6 °F (2.8 °C), 5=7 °F (3.3 °C), 6=8 °F (3.9 °C), 7=9 °F (5.0 °C), 8=10 °F (5.6 °C) | ||
| AV | 67 | Stand-by Time | Range 0.5 Hours to 24.0 Hours; default 0.5 Hours | h | Command | |
| AV | 68 | Unoccupied Time | Range 0.0 Hours to 24.0 Hours; default 0.0 Hours | h | Command | |
| Other | 74 | Output Configuration Options | Group object (bundles related objects) | Read | ||
| BV | 75 | Control type | Default On/Off; only SE7200 | Command | 0=On/Off, 1=Floating | |
| MV | 76 | Floating Motor timing | only SE7200 | Command | 1=0.5 minute, 2=1 minute, 3=1.5 minutes, 4=2 minutes, 5=2.5 minutes, 6=3 minutes, 7=3.5 minutes, 8=4 minutes, 9=4.5 minutes, 10=5 minutes, 11=5.5 minutes, 12=6 minutes, 13=6.5 minutes, 14=7 minutes, 15=7.5 minutes, 16=8 minutes, 17=8.5 minutes, 18=9 minutes | |
| MV | 77 | On Off Control CPH | only SE7200 | Command | 1=3 CPH, 2=4 CPH, 3=5 CPH, 4=6 CPH, 5=7 CPH, 6=8 CPH | |
| BV | 78 | Direct Reverse Acting | Default Direct Acting; only SE7200 | Command | 0=Direct Acting, 1=Reverse Acting |
No points match these filters.
Object ID lookup: Schneider Electric SE7200 Series PIR Ready Zoning Controller point IDs by name
AV7Room TemperatureBV8Room Temp OverrideAV9Outdoor TemperatureAI12Supply TemperatureBV14AUX CommandMV15Sequence of OperationMV16System ModeMV18Occupancy CommandMV19Keypad LockoutAV21PI Heating DemandAV22PI Cooling DemandBI25AUX StatusMV26Output 2MV27Output 1MV28Fan StatusBI30BI 2 StatusBI31UI 3 StatusBI32Local MotionMV33Effective OccupancyBI36Window AlarmBI37Filter AlarmBI38Service AlarmAV39Occupied Heat SetpointAV40Occupied Cool SetpointAV41Stand-by Heat SetpointAV42Stand-by Cool SetpointAV43Unoccupied Heat SetpointAV44Unoccupied Cool SetpointMV46BI 1 ConfigurationMV47BI 2 ConfigurationMV48UI 3 configurationBV49Menu ScrollBV50Auto Mode EnableBV51Temperature ScaleMV52Pipe NumberMV53Out#1 ConfigMV54AUX ConfigurationAV56Password ValueAV58Heating Setpoint LimitAV59Cooling Setpoint LimitBV60Setpoint TypeMV62Temporary Occupancy TimeAV63DeadbandBV64Reheat Time BaseMV65Proportional BandAV67Stand-by TimeAV68Unoccupied TimeBV75Control typeMV76Floating Motor timingMV77On Off Control CPHBV78Direct Reverse Acting
Integration notes
- Access comes from the objects table (Present_Value R or R,W). Writable AV, BV and MV objects are marked commandable 'C'.
- Group objects (GRP) are listed as type 'Other'; they only bundle related objects. Schneider suggests removing configuration objects from the BAS after setup to cut polling.
- State texts and ranges come from the guide's enumeration tables where the object name and instance match; a few enumeration rows use different instances than the objects table and were not applied.
- The PIR cover and the humidity sensor are model options: objects marked 'only ...' exist only on the listed part numbers.
- Fan Mode, Fan Mode Sequence and Auto Fan are SE7300-only and not listed here; the table still ticks MV 28 Fan Status for the SE7200.
- The objects table prints 'General Options 2' as GRP 45, the same instance as 'General Options 1'; the SER7300 table and the configuration section give GRP 55. It is listed once here as GRP 45 General Options 1.
- In this table the alarms are BI 36 Window, BI 37 Filter and BI 38 Service Alarm; the enumeration table and GUI list call them BI 35-37. Other slips: the GUI list gives Unoccupied Cool Setpoint as 'AV34' and Output 1 as 'MV28', Figure 1 calls System Mode 'AV16', and the sample program writes occupancy to 'MV13'; the objects table has AV 44, MV 27, MV 16 and MV 18.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SE7200 Series PIR Ready Zoning Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric SE7200 Series PIR Ready Zoning Controller
How many BACnet points does the Schneider Electric SE7200 Series PIR Ready Zoning Controller have?
This list has 57 BACnet objects: 1 analog input, 16 analog values, 7 binary inputs, 9 binary values, 18 multi-state values, 6 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric SE7200 Series PIR Ready Zoning Controller BACnet points are writable?
37 of the 57 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Schneider Electric SE7200 Series PIR Ready Zoning Controller BACnet documentation?
The source is BACnet Integration Manual: PIR Ready SE7200, SE7300 & SER7300 Series (24 Vac zoning, fan coil and line-voltage fan coil controllers) (IG-SE7000-BNET24VAC-A4.EN.4.2013.v1), revision April 2013, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=IG-SE7000-BNET24VAC-A4.
What are the minimum BACnet points to integrate the Schneider Electric SE7200 Series PIR Ready Zoning Controller?
Start with MV 18 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 33 Effective Occupancy (Actual occupancy state); AV 7 Room Temperature (Space temperature); AV 21 PI Heating Demand (Heating demand, 0-100 %); AV 22 PI Cooling Demand (Cooling demand, 0-100 %); BI 38 Service Alarm (Service alarm from an input set to Service).
How do I enable BMS control of the Schneider Electric SE7200 Series PIR Ready Zoning Controller?
BACnet stays off until the MAC address is changed from the factory 254 to 0-127. MV 18 Occupancy Command: 1 = Local Occupancy, 2 = Occupied, 3 = Unoccupied.
Can the BMS supply sensor values to the Schneider Electric SE7200 Series PIR Ready Zoning Controller?
The BMS can write Outdoor Temperature (AV 9) and, for testing or override, Room Temperature (AV 7); AV 7 only accepts writes while BV 8 Room Temp Override is set to Override. Written room temperature, outdoor temperature and occupancy are released if the controller goes offline.
How do I check these points on the real SE7200 Series PIR Ready Zoning Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Multi-circuit branch power meter (high density)
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Schneider Electric (ex-Veris) PowerLogic HDPM6000 head units with busway, strip or retrofit measurement modules, on BACnet IP over Ethernet.
Also known as: HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Schneider Electric PowerLogic PM5300 series power meters with the Ethernet port (PM5320, PM5340, PM5341) using BACnet IP.
Also known as: PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Schneider Electric PIR-ready SER7300 series line-voltage fan coil controllers: SER7300, SER7305, SER7350 and SER7355 (A versions).
Also known as: SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B - Pressure-dependent VAV zone controller
Schneider Electric SEZ7260 Zoning System Zone Controller
Schneider Electric SEZ7260 zone controllers (F model with floating damper and AO2, C model) used with SEZ7656 rooftop controllers in pressure-dependent zoning systems.
Also known as: SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B - Rooftop unit controller for zoning systems
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Schneider Electric SEZ7656 rooftop controllers (R conventional, H heat pump, F modulating heat, E economizer) that run a rooftop unit for a group of SEZ7260 zone controllers.
Also known as: SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Schneider Electric SpaceLogic SE8000-series SER8350 room controllers for line-voltage fan coil units.
Also known as: SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350 - Room humidity and temperature sensor (wall)
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Schneider Electric SpaceLogic SLP Series wall humidity/temperature sensors (with or without touchscreen) set to BACnet MS/TP.
Also known as: SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil - Rooftop unit controller (room thermostat, rooftop or heat-pump units)
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 6500 (rooftop unit / heat pump) version.
Also known as: SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump
Source: BACnet Integration Manual: PIR Ready SE7200, SE7300 & SER7300 Series (24 Vac zoning, fan coil and line-voltage fan coil controllers) · IG-SE7000-BNET24VAC-A4.EN.4.2013.v1 · rev. April 2013. Object names, instances and units are reproduced as published; descriptions are our own.