Fan coil unit controller (room thermostat) · BACnet points list
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller BACnet points list
Updated 4 November 2026
The SER8350 is a line-voltage touchscreen room controller for fan coil units, from the Schneider Electric SpaceLogic SE8000 line. It is a BACnet application-specific controller (B-ASC) on BACnet MS/TP, and the object list also includes Wi-Fi module and BACnet IP status objects, some set from the controller's configuration web page. Besides the fan coil points it carries display settings, Lua script parameters and objects for up to 20 paired ZigBee wireless sensors.
This page lists 407 BACnet objects for the Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller — 227 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- SpaceLogic SER8350 Line Voltage Fan Coil Controller
- Equipment
- Fan coil unit controller (room thermostat)
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 407 (227 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- 2.6
- Also known as
- SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Command occupancy with MV 10, mode with MV 16 and fan mode with MV 17, and write the occupied setpoints AV 39/AV 40. Read AV 100 room temperature, MI 33 effective occupancy, MV 112 control status and MI 326 fan speed. Write at priorities 4-16 for live control; avoid 1-3.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 10 | Occupancy Command | BMS occupancy: local, occupied or unoccupied | Command |
| MV 16 | System Mode | Off / auto / cool / heat | Command |
| MV 17 | Fan Mode | Fan mode: low / medium / high / auto / on | Command |
| AV 39 | Occupied Heat Setpoint | Occupied heating setpoint | Command |
| AV 40 | Occupied Cool Setpoint | Occupied cooling setpoint | Command |
| MV 112 | Control Status | Current state: off, cooling or heating | Command |
| MI 326 | Fan Speed Status | Fan speed status: off / low / medium / high | Read |
| MI 33 | Effective Occupancy | Actual occupancy state | Read |
| AV 100 | Room Temperature | Space temperature used for control | Command |
| BV 37 | Service Alarm | Service alarm from an input set to Service | Command |
Enable & remote start
The BMS writes MV 10 Occupancy Command (1 = Loc. occ, local occupancy; 2 = Occupied; 3 = Unoccupied) and MV 16 System Mode. MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.
Sensors & values from the BMS
The guide does not describe feeding room temperature from the BMS. MV 145 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. AI present values are only writable with Out_Of_Service set TRUE.
Network setup
- The Device Object_Identifier and Object_Name are writable; no default device instance is printed in the guide.
- BACnet MS/TP baud rate is MV 8 (9600, 19200, 38400, 57600, 76800, 115200 or Auto; default Auto). Max_Master is writable, 0-127, default 127.
- MI 317 shows whether BACnet IP is enabled; the guide lists it on the BACnet/IP page of the configuration web page.
- COV subscriptions are supported (DS-COV-B), along with an internal schedule (SCHED-I-B) and time synchronization.
Watch out for
- Priorities 1-3 are stored in EEPROM and lock the value at the thermostat, even after a power cycle, until it is released at the same priority or factory defaults are restored. Use them only for fixed configuration.
- Priorities 4-16 are held in RAM and are lost on a power cycle, so the BMS has to write them again after the controller restarts.
- The relinquish default (priority 17) is the value the occupant changes at the thermostat, which is kept through power cycles. Writes at 4-16 override local changes to setpoints and modes.
- The controller does not support segmented requests or responses; keep Read Property Multiple requests small.
- MV 15 Sequence of Operation, AV 52 Number of Pipes and the input configuration objects are commissioning settings; do not write them cyclically.
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 2 | Light Sensor Level | Default 0; range 0 to 30000 | Read | ||
| AI | 4 | Relative Humidity Raw Value | Default 0; range 0 to 1000 | Read | ||
| AI | 32 | Temperature Raw Value | Default 0; range -400 to 1220 | Read | ||
| AI | 33 | UI16 Raw Value | Default 0; range 0 to 4095 | Read | ||
| AI | 34 | UI17 Raw Value | Default 0; range 0 to 4095 | Read | ||
| AI | 310 | Wireless IO 1 IEEE Address | Default 0; range -32768 to 32767; screen: Wireless IO 1 Screen | Read | ||
| AI | 311 | Wireless IO 2 IEEE Address | Default 0; range -32768 to 32767; screen: Wireless IO 2 Screen | Read | ||
| AI | 312 | Wireless IO 3 IEEE Address | Default 0; range -32768 to 32767; screen: Wireless IO 3 Screen | Read | ||
| AI | 313 | Paired Wireless IO | Default 0; range 0 to 3; screen: Wireless IO Settings Screen | Read | ||
| AI | 315 | Wireless Device 1 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 1 Screen | °F/°C | Read | |
| AI | 316 | Wireless Device 2 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 2 Screen | °F/°C | Read | |
| AI | 317 | Wireless Device 3 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 3 Screen | °F/°C | Read | |
| AI | 318 | Wireless Device 4 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 4 Screen | °F/°C | Read | |
| AI | 319 | Wireless Device 5 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 5 Screen | °F/°C | Read | |
| AI | 320 | Wireless Device 6 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 6 Screen | °F/°C | Read | |
| AI | 321 | Wireless Device 7 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 7 Screen | °F/°C | Read | |
| AI | 322 | Wireless Device 8 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 8 Screen | °F/°C | Read | |
| AI | 323 | Wireless Device 9 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 9 Screen | °F/°C | Read | |
| AI | 324 | Wireless Device 10 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 10 Screen | °F/°C | Read | |
| AI | 325 | Wireless IO Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 122°F (50°C) | °F/°C | Read | |
| AI | 329 | Effective Setpoint | Default 0°F (-18°C); range 40°F (4.5°C) to 100°F (38°C); screen: 6/7 Service View Screen | °F/°C | Read | |
| AI | 330 | Paired ZigBee Devices | Default 0; range 0 to 20; screen: Ecosystem Settings Screen | Read | ||
| AI | 340 | Therm. Raw Value | Default 0; range -400 to 1220 | Read | ||
| AI | 341 | SH Therm. Raw Value | Default 0; range -400 to 1220 | Read | ||
| AI | 343 | Wi-Fi Module Boot Count | Default 0; range 0 to 32767 | Read | ||
| AI | 355 | Wireless Device 11 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 11 Screen | °F/°C | Read | |
| AI | 356 | Wireless Device 12 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 12 Screen | °F/°C | Read | |
| AI | 357 | Wireless Device 13 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 13 Screen | °F/°C | Read | |
| AI | 358 | Wireless Device 14 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 14 Screen | °F/°C | Read | |
| AI | 359 | Wireless Device 15 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 15 Screen | °F/°C | Read | |
| AI | 360 | Wireless Device 16 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 16 Screen | °F/°C | Read | |
| AI | 361 | Wireless Device 17 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 17 Screen | °F/°C | Read | |
| AI | 362 | Wireless Device 18 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 18 Screen | °F/°C | Read | |
| AI | 363 | Wireless Device 19 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 19 Screen | °F/°C | Read | |
| AI | 364 | Wireless Device 20 - Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 185°F (85°C); screen: Device 20 Screen | °F/°C | Read | |
| AI | 365 | Wireless Device 1 - Humidity | Default 0; range 0 to 100; screen: Device 1 Screen | %RH | Read | |
| AI | 366 | Wireless Device 2 - Humidity | Default 0; range 0 to 100; screen: Device 2 Screen | %RH | Read | |
| AI | 367 | Wireless Device 3 - Humidity | Default 0; range 0 to 100; screen: Device 3 Screen | %RH | Read | |
| AI | 368 | Wireless Device 4 - Humidity | Default 0; range 0 to 100; screen: Device 4 Screen | %RH | Read | |
| AI | 369 | Wireless Device 5 - Humidity | Default 0; range 0 to 100; screen: Device 5 Screen | %RH | Read | |
| AI | 370 | Wireless Device 6 - Humidity | Default 0; range 0 to 100; screen: Device 6 Screen | %RH | Read | |
| AI | 371 | Wireless Device 7 - Humidity | Default 0; range 0 to 100; screen: Device 7 Screen | %RH | Read | |
| AI | 372 | Wireless Device 8 - Humidity | Default 0; range 0 to 100; screen: Device 8 Screen | %RH | Read | |
| AI | 373 | Wireless Device 9 - Humidity | Default 0; range 0 to 100; screen: Device 9 Screen | %RH | Read | |
| AI | 374 | Wireless Device 10 - Humidity | Default 0; range 0 to 100; screen: Device 10 Screen | %RH | Read | |
| AI | 375 | Wireless Device 11 - Humidity | Default 0; range 0 to 100; screen: Device 11 Screen | %RH | Read | |
| AI | 376 | Wireless Device 12 - Humidity | Default 0; range 0 to 100; screen: Device 12 Screen | %RH | Read | |
| AI | 377 | Wireless Device 13 - Humidity | Default 0; range 0 to 100; screen: Device 13 Screen | %RH | Read | |
| AI | 378 | Wireless Device 14 - Humidity | Default 0; range 0 to 100; screen: Device 14 Screen | %RH | Read | |
| AI | 379 | Wireless Device 15 - Humidity | Default 0; range 0 to 100; screen: Device 15 Screen | %RH | Read | |
| AI | 380 | Wireless Device 16 - Humidity | Default 0; range 0 to 100; screen: Device 16 Screen | %RH | Read | |
| AI | 381 | Wireless Device 17 - Humidity | Default 0; range 0 to 100; screen: Device 17 Screen | %RH | Read | |
| AI | 382 | Wireless Device 18 - Humidity | Default 0; range 0 to 100; screen: Device 18 Screen | %RH | Read | |
| AI | 383 | Wireless Device 19 - Humidity | Default 0; range 0 to 100; screen: Device 19 Screen | %RH | Read | |
| AI | 384 | Wireless Device 20 - Humidity | Default 0; range 0 to 100; screen: Device 20 Screen | %RH | Read | |
| AI | 385 | Wireless Device 1 - CO2 | Default 0; range 0 to 5000; screen: Device 1 Screen | ppm | Read | |
| AI | 386 | Wireless Device 2 - CO2 | Default 0; range 0 to 5000; screen: Device 2 Screen | ppm | Read | |
| AI | 387 | Wireless Device 3 - CO2 | Default 0; range 0 to 5000; screen: Device 3 Screen | ppm | Read | |
| AI | 388 | Wireless Device 4 - CO2 | Default 0; range 0 to 5000; screen: Device 4 Screen | ppm | Read | |
| AI | 389 | Wireless Device 5 - CO2 | Default 0; range 0 to 5000; screen: Device 5 Screen | ppm | Read | |
| AI | 390 | Wireless Device 6 - CO2 | Default 0; range 0 to 5000; screen: Device 6 Screen | ppm | Read | |
| AI | 391 | Wireless Device 7 - CO2 | Default 0; range 0 to 5000; screen: Device 7 Screen | ppm | Read | |
| AI | 392 | Wireless Device 8 - CO2 | Default 0; range 0 to 5000; screen: Device 8 Screen | ppm | Read | |
| AI | 393 | Wireless Device 9 - CO2 | Default 0; range 0 to 5000; screen: Device 9 Screen | ppm | Read | |
| AI | 394 | Wireless Device 10 - CO2 | Default 0; range 0 to 5000; screen: Device 10 Screen | ppm | Read | |
| AI | 395 | Wireless Device 11 - CO2 | Default 0; range 0 to 5000; screen: Device 11 Screen | ppm | Read | |
| AI | 396 | Wireless Device 12 - CO2 | Default 0; range 0 to 5000; screen: Device 12 Screen | ppm | Read | |
| AI | 397 | Wireless Device 13 - CO2 | Default 0; range 0 to 5000; screen: Device 13 Screen | ppm | Read | |
| AI | 398 | Wireless Device 14 - CO2 | Default 0; range 0 to 5000; screen: Device 14 Screen | ppm | Read | |
| AI | 399 | Wireless Device 15 - CO2 | Default 0; range 0 to 5000; screen: Device 15 Screen | ppm | Read | |
| AI | 400 | Wireless Device 16 - CO2 | Default 0; range 0 to 5000; screen: Device 16 Screen | ppm | Read | |
| AI | 401 | Wireless Device 17 - CO2 | Default 0; range 0 to 5000; screen: Device 17 Screen | ppm | Read | |
| AI | 402 | Wireless Device 18 - CO2 | Default 0; range 0 to 5000; screen: Device 18 Screen | ppm | Read | |
| AI | 403 | Wireless Device 19 - CO2 | Default 0; range 0 to 5000; screen: Device 19 Screen | ppm | Read | |
| AI | 404 | Wireless Device 20 - CO2 | Default 0; range 0 to 5000; screen: Device 20 Screen | ppm | Read | |
| AO | 21 | PI Heating Demand | Default 0; range 0 to 100; screen: 2/7 Service View Screen | % | Command | |
| AO | 22 | PI Cooling Demand | Default 0; range 0 to 100; screen: 2/7 Service View Screen | % | Command | |
| AO | 90 | Pulsed Heating Demand | Default 0; range 0 to 100; screen: 2/2 Test Outputs Screen | % | Command | |
| AO | 124 | UO12 Analog Output | Default 0; range 0 to 10; screen: 2/2 Test Outputs Screen | V | Command | |
| AV | 2 | User HMI | Default 0; range 0 to 12; screen: 1/3 Display Screen | Command | ||
| AV | 3 | Low Backlight | Default 60; range 0 to 100; screen: 2/3 Display Screen | % | Command | |
| AV | 4 | Night Backlight | Default 5; range 0 to 100; screen: 2/3 Display Screen | % | Command | |
| AV | 5 | Purge Sample Period | Default 2; range 0 to 4; screen: 6/9 Configuration Screen | h | Command | |
| AV | 6 | Purge Open | Default 2; range 1 to 3; screen: 6/9 Configuration Screen | min | Command | |
| AV | 7 | Calibrate Room Temperature Sensor | Default 0°F (0.0°C); range -5°F (-2.5°C) to 5°F (2.5°C); screen: 8/9 Configuration Screen | Δ°F/Δ°C | Command | |
| AV | 8 | Calibrate Humidity Sensor | Default 0; range -15 to 15; screen: 8/9 Configuration Screen | %RH | Command | |
| AV | 10 | COM Address | Default 254; range 0 to 254; screen: 2/3 ZigBee Network Screen | Command | ||
| AV | 16 | BACnet Stack Poll Rate | Default 4; range 1 to 5; screen: 1/2 BACnet Network Screen | Command | ||
| AV | 25 | Lua Parameter A (AV25) | Default 0; range -32768 to 32767; screen: 3/4 Lua Screen | Command | ||
| AV | 26 | Lua Parameter B (AV26) | Default 0; range -32768 to 32767; screen: 3/4 Lua Screen | Command | ||
| AV | 27 | Lua Parameter C (AV27) | Default 0; range -32768 to 32767; screen: 3/4 Lua Screen | Command | ||
| AV | 28 | Lua Parameter D (AV28) | Default 0; range -32768 to 32767; screen: 3/4 Lua Screen | Command | ||
| AV | 29 | Lua Parameter E (AV29) | Default 0; range -32768 to 32767; screen: 3/4 Lua Screen | Command | ||
| AV | 30 | Lua Parameter F (AV30) | Default 0; range -32768 to 32767; screen: 3/4 Lua Screen | Command | ||
| AVmin | 39 | Occupied Heat Setpoint | Default 72°F (22°C); range 40°F (4.5°C) to 90°F (32°C); screen: 1/2 Setpoints Screen | °F/°C | Command | |
| AVmin | 40 | Occupied Cool Setpoint | Default 75°F (24°C); range 54°F (12°C) to 100°F (38°C); screen: 1/2 Setpoints Screen | °F/°C | Command | |
| AV | 41 | Standby Heat Setpoint | Default 69°F (21°C); range 40°F (4.5°C) to 90°F (32°C); screen: 1/2 Setpoints Screen | °F/°C | Command | |
| AV | 42 | Standby Cool Setpoint | Default 78°F (21°C); range 54°F (12°C) to 100°F (38°C); screen: 1/2 Setpoints Screen | °F/°C | Command | |
| AV | 43 | Unoccupied Heat Setpoint | Default 62°F (17°C); range 40°F (4.5°C) to 90°F (32°C); screen: 1/2 Setpoints Screen | °F/°C | Command | |
| AV | 44 | Unoccupied Cool Setpoint | Default 80°F (27°C); range 54°F (12°C) to 100°F (38°C); screen: 1/2 Setpoints Screen | °F/°C | Command | |
| AV | 45 | Default Heating Setpoint | Default 72°F (22°C); range 65°F (18°C) to 80°F (27°C); screen: 2/2 Setpoints Screen | °F/°C | Command | |
| AV | 46 | Standby Temperature Differential | Default 4°F (2.0°C); range 1°F (0.5°C) to 5°F (2.5°C); screen: 2/9 Configuration Screen | Δ°F/Δ°C | Command | |
| AV | 52 | Number of Pipes | Number of pipes; default 2; range 2 to 4; screen: 6/9 Configuration Screen | Command | ||
| AV | 56 | Main Password | Default 0; range 0 to 9999; screen: 7/9 Configuration Screen | Command | ||
| AV | 57 | User Password | Default 0; range 0 to 9999; screen: 7/9 Configuration Screen | Command | ||
| AV | 58 | Heating Setpoint Limit | Default 90°F (32°C); range 40°F (4.5°C) to 90°F (32°C); screen: 2/2 Setpoints Screen | °F/°C | Command | |
| AV | 59 | Cooling Setpoint Limit | Default 54°F (12°C); range 54°F (12°C) to 100°F (38°C); screen: 2/2 Setpoints Screen | °F/°C | Command | |
| AV | 62 | Temporary Occupancy Time | Default 2; range 0 to 24; screen: 4/9 Configuration Screen | h | Command | |
| AV | 63 | Minimum Deadband | Default 3°F (1.5°C); range 2°F (1.0°C) to 5°F (2.5°C); screen: 2/2 Setpoints Screen | Δ°F/Δ°C | Command | |
| AV | 65 | Proportional Band | Default 3; range 3 to 10; screen: 6/9 Configuration Screen | Command | ||
| AV | 67 | Standby Time | Default 0.5; range 0.5 to 24; screen: 4/9 Configuration Screen | h | Command | |
| AV | 68 | Unoccupied Time | Default 0; range 0 to 24; screen: 4/9 Configuration Screen | h | Command | |
| AV | 71 | Dehumidification Setpoint | Default 50; range 30 to 95; screen: 2/2 Setpoints Screen | %RH | Command | |
| AV | 72 | Dehumidification Hysteresis | Default 5; range 2 to 20; screen: 4/9 Configuration Screen | %RH | Command | |
| AV | 73 | Dehumidification Max Cooling Limit | Default 100; range 20 to 100; screen: 4/9 Configuration Screen | % | Command | |
| AV | 84 | Heating CPH | Default 4; range 3 to 8; screen: 5/9 Configuration Screen | cycles/h | Command | |
| AV | 85 | Cooling CPH | Default 4; range 3 to 8; screen: 5/9 Configuration Screen | cycles/h | Command | |
| AV | 88 | Heating Demand Limit | Default 0; range 0 to 100; screen: 2/7 Service View Screen | % | Command | |
| AV | 89 | Cooling Demand Limit | Default 0; range 0 to 100; screen: 2/7 Service View Screen | % | Command | |
| AV | 92 | Keyboard Value | Default 0; range 0 to 35 | Command | ||
| AVmin | 100 | Room Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 122°F (50°C); screen: 1/7 Service View Screen | °F/°C | Command | |
| AV | 101 | Outdoor Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 180°F (82°C); screen: 1/7 Service View Screen | °F/°C | Command | |
| AV | 102 | Supply Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 180°F (82°C); screen: 1/7 Service View Screen | °F/°C | Command | |
| AV | 103 | Room Humidity | Default 0; range 0 to 100; screen: 1/7 Service View Screen | %RH | Command | |
| AV | 104 | Changeover Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 180°F (82°C); screen: 1/7 Service View Screen | °F/°C | Command | |
| AV | 106 | CO2 Level | Default 0; range 0 to 5000; screen: 5/7 Service View Screen | ppm | Command | |
| AV | 111 | UI16 Analog Input | Default 0; range 0 to 10 | V | Command | |
| AV | 112 | UI17 Analog Input | Default 0; range 0 to 10 | V | Command | |
| AV | 117 | UI16 Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 118 | UI17 Temperature | Default -40°F (-40°C); range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 207 | Input Source | Default 0; range 0 to 3; screen: Wireless IO Settings Screen | Command | ||
| AV | 209 | Ambient Low Temperature Threshold | Default 40°F (4°C); range 32°F (0°C) to 50°F (10°C); screen: 2/2 Temperature Screen | °F/°C | Command | |
| AV | 210 | Temperature Alarm Hysteresis | Default 2°F (1°C); range 0°F (0°C) to 10°F (5.5°C); screen: 1/2 Temperature Screen | Δ°F/Δ°C | Command | |
| AV | 211 | Load Shedding Offset | Default 4°F (2°C); range 4°F (2°C) to 10°F (5.5°C); screen: ADR Screen | Δ°F/Δ°C | Command | |
| AV | 212 | ECM Fan Low Voltage | Default 2.2; range 2.0 to 4.0; screen: 3/9 Configuration Screen | V | Command | |
| AV | 213 | ECM Fan Medium Voltage | Default 6.0; range 4.1 to 7.0; screen: 3/9 Configuration Screen | V | Command | |
| AV | 214 | ECM Fan High Voltage | Default 8.6; range 7.1 to 10.0; screen: 3/9 Configuration Screen | V | Command | |
| AV | 225 | Lua Parameter G (AV225) | Default 0; range -32768 to 32767; screen: 4/4 Lua Screen | Command | ||
| AV | 226 | Lua Parameter H (AV226) | Default 0; range -32768 to 32767; screen: 4/4 Lua Screen | Command | ||
| AV | 227 | Lua Parameter I (AV227) | Default 0; range -32768 to 32767; screen: 4/4 Lua Screen | Command | ||
| AV | 228 | Lua Parameter J (AV228) | Default 0; range -32768 to 32767; screen: 4/4 Lua Screen | Command | ||
| AV | 229 | Lua Parameter K (AV229) | Default 0; range -32768 to 32767; screen: 4/4 Lua Screen | Command | ||
| AV | 230 | Lua Parameter L (AV230) | Default 0; range -32768 to 32767; screen: 4/4 Lua Screen | Command | ||
| AV | 270 | Standby Screen Delay | Default 150; range 5 to 300 | s | Command | |
| AV | 275 | Ambient High Temperature Threshold | Default 86°F (30°C); range 32°F (0°C) to 122°F (50°C); screen: 2/2 Temperature Screen | °F/°C | Command | |
| AV | 276 | Refrigeration High Temperature Threshold | Default 40°F (4°C); range 32°F (0°C) to 60°F (16°C); screen: 2/2 Temperature Screen | °F/°C | Command | |
| AV | 277 | Refrigeration Low Temperature Threshold | Default 32°F (0°C); range 32°F (0°C) to 50°F (10°C); screen: 2/2 Temperature Screen | °F/°C | Command | |
| AV | 278 | Freezer High Temperature Threshold | Default 0°F (-18°C); range -40°F (-40°C) to 32°F (0°C); screen: 2/2 Temperature Screen | °F/°C | Command | |
| BI | 29 | UI16 Binary Input | Default 0; screen: 3/7 Service View Screen | Read | 0=Activated, 1=Not activ. | |
| BI | 30 | UI17 Binary Input | Default 0; screen: 3/7 Service View Screen | Read | 0=Activated, 1=Not activ. | |
| BI | 91 | RUI1 Binary Input | Default 0; screen: 3/7 Service View Screen | Read | 0=Activated, 1=Not activ. | |
| BI | 92 | RUI2 Binary Input | Default 0; screen: 3/7 Service View Screen | Read | 0=Activated, 1=Not activ. | |
| BO | 93 | Cooling Output | Default 0; screen: 1/2 Test Outputs Screen | Command | 0=Off, 1=On | |
| BO | 94 | Heating Output | Default 0; screen: 1/2 Test Outputs Screen | Command | 0=Off, 1=On | |
| BO | 95 | High Speed Fan Output | Default 0; screen: 1/2 Test Outputs Screen | Command | 0=Off, 1=On | |
| BO | 96 | Medium Speed Fan Output | Default 0; screen: 1/2 Test Outputs Screen | Command | 0=Off, 1=On | |
| BO | 97 | Low Speed Fan Output | Default 0; screen: 1/2 Test Outputs Screen | Command | 0=Off, 1=On | |
| BV | 1 | Door Contact Status | Default 0; screen: Device X Screen | Command | 0=Closed, 1=Open | |
| BV | 2 | Door Contact Installed | Default 0; screen: Device Groups Screen | Command | 0=No, 1=Yes | |
| BV | 3 | Window Contact Status | Default 0; screen: Device X Screen | Command | 0=Closed, 1=Open | |
| BV | 4 | Window Contact Installed | Default 0; screen: Device Groups Screen | Command | 0=No, 1=Yes | |
| BV | 5 | Low Battery Alarm | Default 0; screen: Alarms Screen | Command | 0=Off, 1=On | |
| BV | 6 | Force High Backlight | Default 0 | Command | 0=Off, 1=On | |
| BV | 7 | Display Long Screen Message | Default 0 | Command | 0=Off, 1=On | |
| BV | 8 | Clock Alarm | Default 0 | Command | 0=Off, 1=On | |
| BV | 10 | Exception Status | Default 0 | Command | 0=Off, 1=On | |
| BV | 32 | PIR Local Motion | Default 0; screen: 4/7 Service View Screen | Command | 0=No motion, 1=Motion | |
| BV | 35 | Window Alarm | Default 0; screen: 4/7 Service View Screen | Command | 0=Off, 1=On | |
| BV | 36 | Filter Alarm | Default 0; screen: 4/7 Service View Screen | Command | 0=Off, 1=On | |
| BVmin | 37 | Service Alarm | Default 0; screen: 4/7 Service View Screen | Command | 0=Off, 1=On | |
| BV | 38 | Dehumidification Status | Default 0; screen: 4/7 Service View Screen | Command | 0=Off, 1=On | |
| BV | 40 | Smart Recovery Status | Default 0; screen: 4/7 Service View Screen | Command | 0=Off, 1=On | |
| BV | 44 | Water Leak | Default 0; screen: Alarms Screen | Command | 0=Off, 1=On | |
| BV | 45 | Water Leak Sensor Installed | Default 0; screen: Device Groups Screen | Command | 0=No, 1=Yes | |
| BV | 46 | Water leak sensor status | Default 0; screen: Device X Screen | Command | 0=Normal, 1=Leak | |
| BV | 47 | Low Temperature | Default 0; screen: Alarms Screen | Command | 0=Off, 1=On | |
| BV | 48 | Load Shedding Demand | Default 0; screen: ADR Screen | Command | 0=Off, 1=On | |
| BV | 49 | Load Shedding Status | Default 0; screen: ADR Screen | Command | 0=Off, 1=On | |
| BV | 50 | Load Shedding Override | Default 0; screen: ADR Screen | Command | 0=Off, 1=On | |
| BV | 53 | High Temperature | Default 0; screen: Alarms Screen | Command | 0=Off, 1=On | |
| BV | 200 | ZigBee PIR Sensor Installed | Default 0; screen: 3/7 Service View Screen | Command | 0=Off, 1=On | |
| BV | 201 | ZigBee Sensor Motion | Default 0; screen: 3/7 Service View Screen | Command | 0=No motion, 1=Motion | |
| CSV | 1 | Short Screen Message Text | Characters | Write | ||
| CSV | 2 | Long Screen Message Text | Characters | Write | ||
| CSV | 3 | External Memory Revision | Write | |||
| CSV | 4 | Wi-Fi Device Name | Screen: 1/5 Wi-Fi Screen, Admin - Config Web Page | Write | ||
| CSV | 5 | Wi-Fi Firmware Version | Screen: 1/5 Wi-Fi Screen | Write | ||
| CSV | 6 | MAC Address | Screen: 1/5 Wi-Fi Screen | Write | ||
| CSV | 7 | Wi-Fi Network SSID | Screen: 3/5 Wi-Fi Network Screen, Network - Config Web Page | Write | ||
| CSV | 8 | Wi-Fi Network IP Address | Screen: 3/5 Wi-Fi Network Screen, Network - Config Web Page | Write | ||
| CSV | 9 | Zigbee Firmware Revision | Screen: 2/3 ZigBee Network Screen | Write | ||
| CSV | 10 | Zigbee IEEE Address | Screen: 2/3 ZigBee Network Screen | Write | ||
| CSV | 11 | Wireless Device 1 - Address | Screen: Device 1 Screen | Write | ||
| CSV | 12 | Wireless Device 2 - Address | Screen: Device 2 Screen | Write | ||
| CSV | 13 | Wireless Device 3 - Address | Screen: Device 3 Screen | Write | ||
| CSV | 14 | Wireless Device 4 - Address | Screen: Device 4 Screen | Write | ||
| CSV | 15 | Wireless Device 5 - Address | Screen: Device 5 Screen | Write | ||
| CSV | 16 | Wireless Device 6 - Address | Screen: Device 6 Screen | Write | ||
| CSV | 17 | Wireless Device 7 - Address | Screen: Device 7 Screen | Write | ||
| CSV | 18 | Wireless Device 8 - Address | Screen: Device 8 Screen | Write | ||
| CSV | 19 | Wireless Device 9 - Address | Screen: Device 9 Screen | Write | ||
| CSV | 20 | Wireless Device 10 - Address | Screen: Device 10 Screen | Write | ||
| CSV | 21 | Wireless Device 11 - Address | Screen: Device 11 Screen | Write | ||
| CSV | 22 | Wireless Device 12 - Address | Screen: Device 12 Screen | Write | ||
| CSV | 23 | Wireless Device 13 - Address | Screen: Device 13 Screen | Write | ||
| CSV | 24 | Wireless Device 14 - Address | Screen: Device 14 Screen | Write | ||
| CSV | 25 | Wireless Device 15 - Address | Screen: Device 15 Screen | Write | ||
| CSV | 26 | Wireless Device 16 - Address | Screen: Device 16 Screen | Write | ||
| CSV | 27 | Wireless Device 17 - Address | Screen: Device 17 Screen | Write | ||
| CSV | 28 | Wireless Device 18 - Address | Screen: Device 18 Screen | Write | ||
| CSV | 29 | Wireless Device 19 - Address | Screen: Device 19 Screen | Write | ||
| CSV | 30 | Wireless Device 20 - Address | Screen: Device 20 Screen | Write | ||
| MI | 2 | ZigBee Network Status | Default 1; screen: 1/3 ZigBee Network, Ecosystem Settings Screen | Read | 1=Not det., 2=Pwr on, 3=No NWK, 4=Joined, 5=Online | |
| MImin | 33 | Effective Occupancy | Default 1; screen: 2/7 Service View Screen | Read | 1=Occupied, 2=Unoccupied, 3=Override, 4=Standby | |
| MI | 180 | Wireless Device 1 - Sensor Type | Default 1; screen: Device 1 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 181 | Wireless Device 2 - Sensor Type | Default 1; screen: Device 2 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 182 | Wireless Device 3 - Sensor Type | Default 1; screen: Device 3 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 183 | Wireless Device 4 - Sensor Type | Default 1; screen: Device 4 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 184 | Wireless Device 5 - Sensor Type | Default 1; screen: Device 5 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 185 | Wireless Device 6 - Sensor Type | Default 1; screen: Device 6 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 186 | Wireless Device 7 - Sensor Type | Default 1; screen: Device 7 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 187 | Wireless Device 8 - Sensor Type | Default 1; screen: Device 8 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 188 | Wireless Device 9 - Sensor Type | Default 1; screen: Device 9 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 189 | Wireless Device 10 - Sensor Type | Default 1; screen: Device 10 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 190 | Wireless Device 11 - Sensor Type | Default 1; screen: Device 11 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 191 | Wireless Device 12 - Sensor Type | Default 1; screen: Device 11 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 192 | Wireless Device 13 - Sensor Type | Default 1; screen: Device 13 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 193 | Wireless Device 14 - Sensor Type | Default 1; screen: Device 14 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 194 | Wireless Device 15 - Sensor Type | Default 1; screen: Device 15 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 195 | Wireless Device 16 - Sensor Type | Default 1; screen: Device 16 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 196 | Wireless Device 17 - Sensor Type | Default 1; screen: Device 17 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 197 | Wireless Device 18 - Sensor Type | Default 1; screen: Device 18 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 198 | Wireless Device 19 - Sensor Type | Default 1; screen: Device 19 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 199 | Wireless Device 20 - Sensor Type | Default 1; screen: Device 20 Screen | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | |
| MI | 210 | Wireless Device 1 - Status | Default 1; screen: Device 1 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 211 | Wireless Device 1 - Battery | Default 1; screen: Device 1 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 212 | Wireless Device 1 - Communication Status | Default 1; screen: Device 1 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 220 | Wireless Device 2 - Status | Default 1; screen: Device 2 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 221 | Wireless Device 2 - Battery | Default 1; screen: Device 2 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 222 | Wireless Device 2 - Communication Status | Default 1; screen: Device 2 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 230 | Wireless Device 3 - Status | Default 1; screen: Device 3 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 231 | Wireless Device 3 - Battery | Default 1; screen: Device 3 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 232 | Wireless Device 3 - Communication Status | Default 1; screen: Device 3 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 240 | Wireless Device 4 - Status | Default 1; screen: Device 4 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 241 | Wireless Device 4 - Battery | Default 1; screen: Device 4 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 242 | Wireless Device 4 - Communication Status | Default 1; screen: Device 4 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 250 | Wireless Device 5 - Status | Default 1; screen: Device 5 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 251 | Wireless Device 5 - Battery | Default 1; screen: Device 5 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 252 | Wireless Device 5 - Communication Status | Default 1; screen: Device 5 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 260 | Wireless Device 6 - Status | Default 1; screen: Device 6 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 261 | Wireless Device 6 - Battery | Default 1; screen: Device 6 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 262 | Wireless Device 6 - Communication Status | Default 1; screen: Device 6 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 270 | Wireless Device 7 - Status | Default 1; screen: Device 7 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 271 | Wireless Device 7 - Battery | Default 1; screen: Device 7 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 272 | Wireless Device 7 - Communication Status | Default 1; screen: Device 7 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 280 | Wireless Device 8 - Status | Default 1; screen: Device 8 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 281 | Wireless Device 8 - Battery | Default 1; screen: Device 8 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 282 | Wireless Device 8 - Communication Status | Default 1; screen: Device 8 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 290 | Wireless Device 9 - Status | Default 1; screen: Device 9 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 291 | Wireless Device 9 - Battery | Default 1; screen: Device 9 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 292 | Wireless Device 9 - Communication Status | Default 1; screen: Device 9 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 300 | Wireless Device 10 - Status | Default 1; screen: Device 10 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 301 | Wireless Device 10 - Battery | Default 1; screen: Device 10 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 302 | Wireless Device 10 - Communication Status | Default 1; screen: Device 10 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 303 | Wireless IO 1 Status | Default 1; screen: Wireless IO 1 Screen | Read | 1=Offline, 2=Online, 3=Busy | |
| MI | 304 | Wireless IO 2 Status | Default 1; screen: Wireless IO 2 Screen | Read | 1=Offline, 2=Online, 3=Busy | |
| MI | 305 | Wireless IO 3 Status | Default 1; screen: Wireless IO 3 Screen | Read | 1=Offline, 2=Online, 3=Busy | |
| MI | 306 | Wireless IO 1 Remove | Default 1; screen: Wireless IO 1 Screen | Read | 1=No, 2=Yes | |
| MI | 307 | Wireless IO 2 Remove | Default 1; screen: Wireless IO 2 Screen | Read | 1=No, 2=Yes | |
| MI | 308 | Wireless IO 3 Remove | Default 1; screen: Wireless IO 3 Screen | Read | 1=No, 2=Yes | |
| MI | 309 | Effective Temperature Sensor | Default 1; screen: 8/9 Configuration Screen | Read | 1=Wired, 2=Internal, 3=WL IO, 4=WL 1, 5=WL 2, 6=WL 3, 7=WL 4, 8=WL 5, 9=WL 6, 10=WL 7, 11=WL 8, 12=WL 9, 13=WL 10, 14=WL 11, 15=WL 12, 16=WL 13, 17=WL 14, 18=WL 15, 19=WL 16, 20=WL 17, 21=WL 18, 22=WL 19, 23=WL 20 | |
| MI | 310 | Wireless Device 11 - Status | Default 1; screen: Device 11 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 311 | Wireless Device 11 - Battery | Default 1; screen: Device 11 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 312 | Wireless Device 11 - Communication Status | Default 1; screen: Device 11 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 313 | Effective Relative Humidity Sensor | Default 1; screen: 8/9 Configuration Screen | Read | 1=None, 2=Internal, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20 | |
| MI | 314 | Effective System Mode | Default 1; screen: 6/7 Service View Screen | Read | 1=Cool, 2=Heat | |
| MI | 315 | Wi-Fi Module Status | Default 1; screen: 1/5 Wi-Fi Screen | Read | 1=Offline, 2=Initializing, 3=Ready, 4=Booting, 5=Resetting, 6=Fail, 7=Testing | |
| MI | 316 | Wi-Fi Status | Default 1; screen: 3/5 Wi-Fi Network Screen | Read | 1=Idle, 2=Associate, 3=Config., 4=Ready, 5=Online, 6=Disconn., 7=Failure | |
| MI | 317 | BACnet IP Status | Default 1; screen: BACnet/IP - Config Web Page | Read | 1=Disabled, 2=Enabled | |
| MI | 318 | SMTP Server Status | Default 1; screen: 3/5 Wi-Fi Network Screen, Notifications - Config Web Page | Read | 1=Unkown, 2=Disabled, 3=Offline, 4=Online | |
| MI | 319 | Facility Expert Enabled | Default 1; screen: 4/5 Wi-Fi: Facility Expert Screen | Read | 1=Disabled, 2=Enabled | |
| MI | 320 | Wireless Device 12 - Status | Default 1; screen: Device 12 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 321 | Wireless Device 12 - Battery | Default 1; screen: Device 12 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 322 | Wireless Device 12 - Communication Status | Default 1; screen: Device 12 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 323 | Facility Expert Status | Default 1; screen: 4/5 Wi-Fi: Facility Expert Screen | Read | 1=Disabled, 2=Offline, 3= Connect., 4= Online, 5=Failure, 6=Unknown | |
| MI | 324 | CO2 Effective Source | Default 1; screen: 5/7 Service View Screen | Read | 1=None, 2=Internal, 3=Error, 4=Wired, 5=WL 1, 6=WL 2, 7=WL 3, 8=WL 4, 9=WL 5, 10=WL 6, 11=WL 7, 12=WL 8, 13=WL 9, 14=WL 10, 15=WL 11, 16=WL 12, 17=WL 13, 18=WL 14, 19=WL 15, 20=WL 16, 21=WL 17, 22=WL 18, 23=WL 19, 24=WL 20 | |
| MI | 325 | Time source | Default 1; screen: 2/2 Clock Screen | Read | 1=None, 2=Local, 3=BACnet, 4=NTP, 5=Cloud | |
| MImin | 326 | Fan Speed Status | Default 1; screen: HMI Display | Read | 1=Off, 2=Low, 3=Medium, 4=High | |
| MI | 327 | Wi-Fi Network Signal Strength | Default 1; screen: 3/5 Wi-Fi Network Screen | Read | 1=Unknown, 2=Weak, 3=Fair, 4=Good, 5=Excellent | |
| MI | 330 | Wireless Device 13 - Status | Default 1; screen: Device 13 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 331 | Wireless Device 13 - Battery | Default 1; screen: Device 13 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 332 | Wireless Device 13 - Communication Status | Default 1; screen: Device 13 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 340 | Wireless Device 14 - Status | Default 1; screen: Device 14 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 341 | Wireless Device 14 - Battery | Default 1; screen: Device 14 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 342 | Wireless Device 14 - Communication Status | Default 1; screen: Device 14 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 350 | Wireless Device 15 - Status | Default 1; screen: Device 15 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 351 | Wireless Device 15 - Battery | Default 1; screen: Device 15 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 352 | Wireless Device 15 - Communication Status | Default 1; screen: Device 15 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 360 | Wireless Device 16 - Status | Default 1; screen: Device 16 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 361 | Wireless Device 16 - Battery | Default 1; screen: Device 16 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 362 | Wireless Device 16 - Communication Status | Default 1; screen: Device 16 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 370 | Wireless Device 17 - Status | Default 1; screen: Device 17 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 371 | Wireless Device 17 - Battery | Default 1; screen: Device 17 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 372 | Wireless Device 17 - Communication Status | Default 1; screen: Device 17 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 380 | Wireless Device 18 - Status | Default 1; screen: Device 18 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 381 | Wireless Device 18 - Battery | Default 1; screen: Device 18 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 382 | Wireless Device 18 - Communication Status | Default 1; screen: Device 18 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 390 | Wireless Device 19 - Status | Default 1; screen: Device 19 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 391 | Wireless Device 19 - Battery | Default 1; screen: Device 19 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 392 | Wireless Device 19 - Communication Status | Default 1; screen: Device 19 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 400 | Wireless Device 20 - Status | Default 1; screen: Device 20 Screen | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 401 | Wireless Device 20 - Battery | Default 1; screen: Device 20 Screen | Read | 1=None, 2=Normal, 3=Low | |
| MI | 402 | Wireless Device 20 - Communication Status | Default 1; screen: Device 20 Screen | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MV | 1 | Long Message Background Color | Default 1 | Command | 1=White, 2=Green, 3=Blue, 4=Grey, 5=Dark grey, 6=Pink, 7=Purple, 8=Red, 9=Orange, 10=Black, 11=Default | |
| MV | 2 | HMI Color | Default 1; screen: 1/3 Display Screen | Command | 1=White, 2=Green, 3=Blue, 4=Grey, 5=Dark grey, 6=Pink, 7=Purple, 8=Red, 9=Orange, 10=Black | |
| MV | 3 | Main Display | Default 1; screen: 1/3 Display Screen | Command | 1=Temp., 2=Setpoint | |
| MV | 4 | Display Language | Default 1; screen: 2/3 Display Screen | Command | 1=English, 2=French, 3=Spanish, 4=Chinese, 5=Russian, 6=Arabic, 7=Bulgarian, 8=Czech, 9=Danish, 10=Dutch, 11=Finnish, 12=German, 13=Hungarian, 14=Indonesian, 15=Italian, 16=Norwegian, 17=Polish, 18=Portuguese, 19=Slovak, 20=Swedish, 21=Turkish, 22=Japanese, 23=Hebrew | |
| MV | 5 | Time Format | Default 1; screen: 1/2 Clock Screen | Command | 1=AM-PM, 2=24 Hours | |
| MV | 6 | Network Units | Default 1; screen: 1/2 BACnet Network Screen | Command | 1=SI, 2=Imperial | |
| MV | 7 | Network Language | Default 1; screen: 1/2 BACnet Network Screen | Command | 1=English, 2=French, 3=Spanish | |
| MV | 8 | BACnet Baud Rate | Default 7; screen: 1/2 BACnet Network Screen | Command | 1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200, 7=Auto | |
| MV | 9 | No Activity Sleep Mode Time | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MVmin | 10 | Occupancy Command | Default 2; screen: Options Screen | Command | 1=Loc. occ, 2=Occupied, 3=Unocc. | |
| MV | 11 | Standby Mode Configuration | Default 1; screen: 2/9 Configuration Screen | Command | 1=Absolute, 2=Offset | |
| MV | 13 | Dehumidification Lockout | Default 1; screen: 4/9 Configuration Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 15 | Sequence of Operation | Default 2; screen: 6/9 Configuration Screen | Command | 1=Cool only, 2=Heat only, 3=Cool/Heat, 4=Heat-rht, 5=Reheat | |
| MVmin | 16 | System Mode | Default 4; screen: HMI Display | Command | 1=Off, 2=Auto, 3=Cool, 4=Heat | |
| MVmin | 17 | Fan Mode | Default 4; screen: HMI Display | Command | 1=Low, 2=Medium, 3=High, 4=Auto, 5=On | |
| MV | 32 | Use Standby Screen | Default 1; screen: 1/3 Display Screen | Command | 1=No, 2=Yes, 3=Occ. only, 4=Screen sav | |
| MV | 46 | BI1 Configuration | Default 1; screen: 1/9 Configuration Screen | Command | 1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window | |
| MV | 47 | BI2 Configuration | Default 1; screen: 1/9 Configuration Screen | Command | 1=None, 2=Door dry, 3=Override | |
| MV | 50 | Auto Mode Enable | Default 1; screen: 2/9 Configuration Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 51 | Temperature Scale | Default 1; screen: 2/3 Display Screen | Command | 1=°C, 2=°F | |
| MV | 57 | Fan Sequence | Default 5; screen: 3/9 Configuration Screen | Command | 1=L-M-H, 2=L-H, 3=L-M-H-A, 4=L-H-A, 5=On-Auto | |
| MV | 58 | Setpoint Function | Default 2; screen: 5/9 Configuration Screen | Command | 1=Dual SP, 2=Attach SP | |
| MV | 66 | Auto Mode Fan Function | Default 1; screen: 3/9 Configuration Screen | Command | 1=AS, 2=AS/SD | |
| MV | 70 | Room Humidity Display | Default 1; screen: 2/3 Display Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 71 | Enable Smart Recovery | Default 1; screen: 1/9 Configuration Screen | Command | 1=Off, 2=On | |
| MV | 73 | Schedule Menu | Default 2; screen: 7/9 Configuration Screen | Command | 1=Disabled, 2=Enabled, 3=Dis. no. clk., 4=En. no. clk. | |
| MV | 82 | RUI1 Configuration | Default 1; screen: 1/9 Configuration Screen | Command | 1=None, 2=Filter, 3=Service, 4=COC/NH, 5=COC/NC, 6=COS | |
| MV | 83 | RBI2 Configuration | Default 1; screen: 1/9 Configuration Screen | Command | 1=None, 2=Filter, 3=Service | |
| MV | 86 | Heating Valve | Default 2; screen: 5/9 Configuration Screen | Command | 1=NO, 2=NC | |
| MV | 87 | Cooling Valve | Default 2; screen: 5/9 Configuration Screen | Command | 1=NO, 2=NC | |
| MV | 90 | Pulsed Heating | Default 1; screen: 6/9 Configuration Screen | Command | 1=Off, 2=On, 3=Occ out | |
| MV | 95 | Fan Control in Heating Mode | Default 2; screen: 2/9 Configuration Screen | Command | 1=On, 2=Off-Auto, 3=Off-All | |
| MV | 101 | French | Default 2; screen: 1/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 102 | Spanish | Default 2; screen: 1/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 103 | Chinese | Default 2; screen: 1/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 104 | Russian | Default 2; screen: 1/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 110 | Occupancy Source | Default 1; screen: 1/9 Configuration Screen | Command | 1=Motion, 2=Schedule, 3=Mot. occ., 4=Mot. unoc. | |
| MV | 111 | Mode Button | Default 1; screen: 5/9 Configuration Screen | Command | 1=Normal, 2=Off-Auto | |
| MVmin | 112 | Control Status | Default 1; screen: HMI Display | Command | 1=Off, 2=Cool, 3=Heat | |
| MV | 114 | Custom button icon | Default 1 | Command | 1=Default Button, 2=No Button, 3=System Mode Heat/Cool, 4=System Mode On/Off, 5=Fan Mode, 6=Override Button, 7=Units Button, 8=Help Button, 9=Language Button, 10=Schedule Button, 11=Lighting Button, 12=Blind Button, 13=Lamp Button, 14=Energy Button, 15=Make Room Button, 16=Setting Button, 17=Timer Button | |
| MV | 115 | Custom button behavior | Default 1 | Command | 1=Default function, 2=No function, 3=System mode function, 4=Fan function, 5=Override function, 6=Schedule function, 7=Units function, 8=Help function, 9=Language function, 10=Configuration function, 11=Custom function, 12=Standby function | |
| MV | 120 | Arabic | Default 1; screen: 1/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 122 | Czech | Default 1; screen: 1/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 123 | Danish | Default 1; screen: 2/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 124 | Dutch | Default 1; screen: 2/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 125 | Finnish | Default 1; screen: 2/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 126 | German | Default 1; screen: 2/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 127 | Hungarian | Default 1; screen: 2/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 128 | Indonesian | Default 1; screen: 3/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 129 | Italian | Default 1; screen: 3/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 130 | Norwegian | Default 1; screen: 3/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 131 | Polish | Default 1; screen: 3/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 132 | Portuguese | Default 1; screen: 3/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 133 | Slovak | Default 1; screen: 4/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 134 | Swedish | Default 1; screen: 4/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 135 | Turkish | Default 1; screen: 4/4 Language Selection Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 136 | Schedule Type | Default 1; screen: Options Screen | Command | 1=7 days, 2=5+2 days, 3=5+1+1 day | |
| MV | 138 | UI16 Input Type | Default 2 | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 139 | UI17 Input Type | Default 2 | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 145 | Room Temperature Sensor | Default 1; screen: 8/9 Configuration Screen | Command | 1=Wired, 2=Internal, 3=WL IO, 4=WL 1, 5=WL 2, 6=WL 3, 7=WL 4, 8=WL 5, 9=WL 6, 10=WL 7, 11=WL 8, 12=WL 9, 13=WL 10, 14=WL 11, 15=WL 12, 16=WL 13, 17=WL 14, 18=WL 15, 19=WL 16, 20=WL 17, 21=WL 18, 22=WL 19, 23=WL 20 | |
| MV | 146 | CO2 Display | Default 2; screen: 2/3 Display Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 147 | CO2 Autocalibration | Default 2 | Command | 1=Disabled, 2=Enabled | |
| MV | 148 | Lock Screen | Default 1; screen: 1/3 Display Screen | Command | 1=No, 2=Yes | |
| MV | 149 | Relative Humidity Sensor | Default 2; screen: 8/9 Configuration Screen | Command | 1=None, 2=Internal, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20 | |
| MV | 150 | CO2 source | Default 2; screen: 8/9 Configuration Screen | Command | 1=None, 2=Local, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20 | |
| MV | 151 | Temperature Alarm Enabled | Default 1; screen: 1/2 Temperature Screen | Command | 1=Off, 2=On | |
| MV | 152 | ADR Permission | Default 1; screen: ADR Screen | Command | 1=Off, 2=On | |
| MV | 154 | Fan Type | Default 1; screen: 3/9 Configuration Screen | Command | 1=3 speed, 2=ECM | |
| MV | 155 | Japanese | Default 1; screen: 3/4 Language Selection Screen | Command | 1= Disabled, 2=Enabled | |
| MV | 156 | Hebrew | Default 1; screen: 2/4 Language Selection Screen | Command | 1= Disabled, 2=Enabled | |
| MV | 180 | Display the Fan Status icon | Default 2; screen: 3/3 Display Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 181 | Display the System Status icon | Default 2; screen: 3/3 Display Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 182 | Display the Help button | Default 2; screen: 3/3 Display Screen | Command | 1=Disabled, 2=Enabled | |
| MV | 210 | Wireless Device 1 - Function | Default 1; screen: Device 1 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 220 | Wireless Device 2 - Function | Default 1; screen: Device 2 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 230 | Wireless Device 3 - Function | Default 1; screen: Device 3 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 240 | Wireless Device 4 - Function | Default 1; screen: Device 4 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 250 | Wireless Device 5 - Function | Default 1; screen: Device 5 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 260 | Wireless Device 6 - Function | Default 1; screen: Device 6 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 270 | Wireless Device 7 - Function | Default 1; screen: Device 7 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 280 | Wireless Device 8 - Function | Default 1; screen: Device 8 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 290 | Wireless Device 9 - Function | Default 1; screen: Device 9 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 300 | Wireless Device 10 - Function | Default 1; screen: Device 10 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 310 | Wireless Device 11 - Function | Default 1; screen: Device 11 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 320 | Wireless Device 12 - Function | Default 1; screen: Device 12 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 330 | Wireless Device 13 - Function | Default 1; screen: Device 13 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 340 | Wireless Device 14 - Function | Default 1; screen: Device 14 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 350 | Wireless Device 15 - Function | Default 1; screen: Device 15 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 360 | Wireless Device 16 - Function | Default 1; screen: Device 16 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 370 | Wireless Device 17 - Function | Default 1; screen: Device 17 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 380 | Wireless Device 18 - Function | Default 1; screen: Device 18 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 390 | Wireless Device 19 - Function | Default 1; screen: Device 19 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 400 | Wireless Device 20 - Function | Default 1; screen: Device 20 Screen | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| Other | 1 | Lua Program 1 | Write |
No points match these filters.
Object ID lookup: Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller point IDs by name
AI2Light Sensor LevelAI4Relative Humidity Raw ValueAI32Temperature Raw ValueAI33UI16 Raw ValueAI34UI17 Raw ValueAI310Wireless IO 1 IEEE AddressAI311Wireless IO 2 IEEE AddressAI312Wireless IO 3 IEEE AddressAI313Paired Wireless IOAI315Wireless Device 1 - TemperatureAI316Wireless Device 2 - TemperatureAI317Wireless Device 3 - TemperatureAI318Wireless Device 4 - TemperatureAI319Wireless Device 5 - TemperatureAI320Wireless Device 6 - TemperatureAI321Wireless Device 7 - TemperatureAI322Wireless Device 8 - TemperatureAI323Wireless Device 9 - TemperatureAI324Wireless Device 10 - TemperatureAI325Wireless IO TemperatureAI329Effective SetpointAI330Paired ZigBee DevicesAI340Therm. Raw ValueAI341SH Therm. Raw ValueAI343Wi-Fi Module Boot CountAI355Wireless Device 11 - TemperatureAI356Wireless Device 12 - TemperatureAI357Wireless Device 13 - TemperatureAI358Wireless Device 14 - TemperatureAI359Wireless Device 15 - TemperatureAI360Wireless Device 16 - TemperatureAI361Wireless Device 17 - TemperatureAI362Wireless Device 18 - TemperatureAI363Wireless Device 19 - TemperatureAI364Wireless Device 20 - TemperatureAI365Wireless Device 1 - HumidityAI366Wireless Device 2 - HumidityAI367Wireless Device 3 - HumidityAI368Wireless Device 4 - HumidityAI369Wireless Device 5 - HumidityAI370Wireless Device 6 - HumidityAI371Wireless Device 7 - HumidityAI372Wireless Device 8 - HumidityAI373Wireless Device 9 - HumidityAI374Wireless Device 10 - HumidityAI375Wireless Device 11 - HumidityAI376Wireless Device 12 - HumidityAI377Wireless Device 13 - HumidityAI378Wireless Device 14 - HumidityAI379Wireless Device 15 - HumidityAI380Wireless Device 16 - HumidityAI381Wireless Device 17 - HumidityAI382Wireless Device 18 - HumidityAI383Wireless Device 19 - HumidityAI384Wireless Device 20 - HumidityAI385Wireless Device 1 - CO2AI386Wireless Device 2 - CO2AI387Wireless Device 3 - CO2AI388Wireless Device 4 - CO2AI389Wireless Device 5 - CO2AI390Wireless Device 6 - CO2AI391Wireless Device 7 - CO2AI392Wireless Device 8 - CO2AI393Wireless Device 9 - CO2AI394Wireless Device 10 - CO2AI395Wireless Device 11 - CO2AI396Wireless Device 12 - CO2AI397Wireless Device 13 - CO2AI398Wireless Device 14 - CO2AI399Wireless Device 15 - CO2AI400Wireless Device 16 - CO2AI401Wireless Device 17 - CO2AI402Wireless Device 18 - CO2AI403Wireless Device 19 - CO2AI404Wireless Device 20 - CO2AO21PI Heating DemandAO22PI Cooling DemandAO90Pulsed Heating DemandAO124UO12 Analog OutputAV2User HMIAV3Low BacklightAV4Night BacklightAV5Purge Sample PeriodAV6Purge OpenAV7Calibrate Room Temperature SensorAV8Calibrate Humidity SensorAV10COM AddressAV16BACnet Stack Poll RateAV25Lua Parameter A (AV25)AV26Lua Parameter B (AV26)AV27Lua Parameter C (AV27)AV28Lua Parameter D (AV28)AV29Lua Parameter E (AV29)AV30Lua Parameter F (AV30)AV39Occupied Heat SetpointAV40Occupied Cool SetpointAV41Standby Heat SetpointAV42Standby Cool SetpointAV43Unoccupied Heat SetpointAV44Unoccupied Cool SetpointAV45Default Heating SetpointAV46Standby Temperature DifferentialAV52Number of PipesAV56Main PasswordAV57User PasswordAV58Heating Setpoint LimitAV59Cooling Setpoint LimitAV62Temporary Occupancy TimeAV63Minimum DeadbandAV65Proportional BandAV67Standby TimeAV68Unoccupied TimeAV71Dehumidification SetpointAV72Dehumidification HysteresisAV73Dehumidification Max Cooling LimitAV84Heating CPHAV85Cooling CPHAV88Heating Demand LimitAV89Cooling Demand LimitAV92Keyboard ValueAV100Room TemperatureAV101Outdoor TemperatureAV102Supply TemperatureAV103Room HumidityAV104Changeover TemperatureAV106CO2 LevelAV111UI16 Analog InputAV112UI17 Analog InputAV117UI16 TemperatureAV118UI17 TemperatureAV207Input SourceAV209Ambient Low Temperature ThresholdAV210Temperature Alarm HysteresisAV211Load Shedding OffsetAV212ECM Fan Low VoltageAV213ECM Fan Medium VoltageAV214ECM Fan High VoltageAV225Lua Parameter G (AV225)AV226Lua Parameter H (AV226)AV227Lua Parameter I (AV227)AV228Lua Parameter J (AV228)AV229Lua Parameter K (AV229)AV230Lua Parameter L (AV230)AV270Standby Screen DelayAV275Ambient High Temperature ThresholdAV276Refrigeration High Temperature ThresholdAV277Refrigeration Low Temperature ThresholdAV278Freezer High Temperature ThresholdBI29UI16 Binary InputBI30UI17 Binary InputBI91RUI1 Binary InputBI92RUI2 Binary InputBO93Cooling OutputBO94Heating OutputBO95High Speed Fan OutputBO96Medium Speed Fan OutputBO97Low Speed Fan OutputBV1Door Contact StatusBV2Door Contact InstalledBV3Window Contact StatusBV4Window Contact InstalledBV5Low Battery AlarmBV6Force High BacklightBV7Display Long Screen MessageBV8Clock AlarmBV10Exception StatusBV32PIR Local MotionBV35Window AlarmBV36Filter AlarmBV37Service AlarmBV38Dehumidification StatusBV40Smart Recovery StatusBV44Water LeakBV45Water Leak Sensor InstalledBV46Water leak sensor statusBV47Low TemperatureBV48Load Shedding DemandBV49Load Shedding StatusBV50Load Shedding OverrideBV53High TemperatureBV200ZigBee PIR Sensor InstalledBV201ZigBee Sensor MotionCSV1Short Screen Message TextCSV2Long Screen Message TextCSV3External Memory RevisionCSV4Wi-Fi Device NameCSV5Wi-Fi Firmware VersionCSV6MAC AddressCSV7Wi-Fi Network SSIDCSV8Wi-Fi Network IP AddressCSV9Zigbee Firmware RevisionCSV10Zigbee IEEE AddressCSV11Wireless Device 1 - AddressCSV12Wireless Device 2 - AddressCSV13Wireless Device 3 - AddressCSV14Wireless Device 4 - AddressCSV15Wireless Device 5 - AddressCSV16Wireless Device 6 - AddressCSV17Wireless Device 7 - AddressCSV18Wireless Device 8 - AddressCSV19Wireless Device 9 - AddressCSV20Wireless Device 10 - AddressCSV21Wireless Device 11 - AddressCSV22Wireless Device 12 - AddressCSV23Wireless Device 13 - AddressCSV24Wireless Device 14 - AddressCSV25Wireless Device 15 - AddressCSV26Wireless Device 16 - AddressCSV27Wireless Device 17 - AddressCSV28Wireless Device 18 - AddressCSV29Wireless Device 19 - AddressCSV30Wireless Device 20 - AddressMI2ZigBee Network StatusMI33Effective OccupancyMI180Wireless Device 1 - Sensor TypeMI181Wireless Device 2 - Sensor TypeMI182Wireless Device 3 - Sensor TypeMI183Wireless Device 4 - Sensor TypeMI184Wireless Device 5 - Sensor TypeMI185Wireless Device 6 - Sensor TypeMI186Wireless Device 7 - Sensor TypeMI187Wireless Device 8 - Sensor TypeMI188Wireless Device 9 - Sensor TypeMI189Wireless Device 10 - Sensor TypeMI190Wireless Device 11 - Sensor TypeMI191Wireless Device 12 - Sensor TypeMI192Wireless Device 13 - Sensor TypeMI193Wireless Device 14 - Sensor TypeMI194Wireless Device 15 - Sensor TypeMI195Wireless Device 16 - Sensor TypeMI196Wireless Device 17 - Sensor TypeMI197Wireless Device 18 - Sensor TypeMI198Wireless Device 19 - Sensor TypeMI199Wireless Device 20 - Sensor TypeMI210Wireless Device 1 - StatusMI211Wireless Device 1 - BatteryMI212Wireless Device 1 - Communication StatusMI220Wireless Device 2 - StatusMI221Wireless Device 2 - BatteryMI222Wireless Device 2 - Communication StatusMI230Wireless Device 3 - StatusMI231Wireless Device 3 - BatteryMI232Wireless Device 3 - Communication StatusMI240Wireless Device 4 - StatusMI241Wireless Device 4 - BatteryMI242Wireless Device 4 - Communication StatusMI250Wireless Device 5 - StatusMI251Wireless Device 5 - BatteryMI252Wireless Device 5 - Communication StatusMI260Wireless Device 6 - StatusMI261Wireless Device 6 - BatteryMI262Wireless Device 6 - Communication StatusMI270Wireless Device 7 - StatusMI271Wireless Device 7 - BatteryMI272Wireless Device 7 - Communication StatusMI280Wireless Device 8 - StatusMI281Wireless Device 8 - BatteryMI282Wireless Device 8 - Communication StatusMI290Wireless Device 9 - StatusMI291Wireless Device 9 - BatteryMI292Wireless Device 9 - Communication StatusMI300Wireless Device 10 - StatusMI301Wireless Device 10 - BatteryMI302Wireless Device 10 - Communication StatusMI303Wireless IO 1 StatusMI304Wireless IO 2 StatusMI305Wireless IO 3 StatusMI306Wireless IO 1 RemoveMI307Wireless IO 2 RemoveMI308Wireless IO 3 RemoveMI309Effective Temperature SensorMI310Wireless Device 11 - StatusMI311Wireless Device 11 - BatteryMI312Wireless Device 11 - Communication StatusMI313Effective Relative Humidity SensorMI314Effective System ModeMI315Wi-Fi Module StatusMI316Wi-Fi StatusMI317BACnet IP StatusMI318SMTP Server StatusMI319Facility Expert EnabledMI320Wireless Device 12 - StatusMI321Wireless Device 12 - BatteryMI322Wireless Device 12 - Communication StatusMI323Facility Expert StatusMI324CO2 Effective SourceMI325Time sourceMI326Fan Speed StatusMI327Wi-Fi Network Signal StrengthMI330Wireless Device 13 - StatusMI331Wireless Device 13 - BatteryMI332Wireless Device 13 - Communication StatusMI340Wireless Device 14 - StatusMI341Wireless Device 14 - BatteryMI342Wireless Device 14 - Communication StatusMI350Wireless Device 15 - StatusMI351Wireless Device 15 - BatteryMI352Wireless Device 15 - Communication StatusMI360Wireless Device 16 - StatusMI361Wireless Device 16 - BatteryMI362Wireless Device 16 - Communication StatusMI370Wireless Device 17 - StatusMI371Wireless Device 17 - BatteryMI372Wireless Device 17 - Communication StatusMI380Wireless Device 18 - StatusMI381Wireless Device 18 - BatteryMI382Wireless Device 18 - Communication StatusMI390Wireless Device 19 - StatusMI391Wireless Device 19 - BatteryMI392Wireless Device 19 - Communication StatusMI400Wireless Device 20 - StatusMI401Wireless Device 20 - BatteryMI402Wireless Device 20 - Communication StatusMV1Long Message Background ColorMV2HMI ColorMV3Main DisplayMV4Display LanguageMV5Time FormatMV6Network UnitsMV7Network LanguageMV8BACnet Baud RateMV9No Activity Sleep Mode TimeMV10Occupancy CommandMV11Standby Mode ConfigurationMV13Dehumidification LockoutMV15Sequence of OperationMV16System ModeMV17Fan ModeMV32Use Standby ScreenMV46BI1 ConfigurationMV47BI2 ConfigurationMV50Auto Mode EnableMV51Temperature ScaleMV57Fan SequenceMV58Setpoint FunctionMV66Auto Mode Fan FunctionMV70Room Humidity DisplayMV71Enable Smart RecoveryMV73Schedule MenuMV82RUI1 ConfigurationMV83RBI2 ConfigurationMV86Heating ValveMV87Cooling ValveMV90Pulsed HeatingMV95Fan Control in Heating ModeMV101FrenchMV102SpanishMV103ChineseMV104RussianMV110Occupancy SourceMV111Mode ButtonMV112Control StatusMV114Custom button iconMV115Custom button behaviorMV120ArabicMV122CzechMV123DanishMV124DutchMV125FinnishMV126GermanMV127HungarianMV128IndonesianMV129ItalianMV130NorwegianMV131PolishMV132PortugueseMV133SlovakMV134SwedishMV135TurkishMV136Schedule TypeMV138UI16 Input TypeMV139UI17 Input TypeMV145Room Temperature SensorMV146CO2 DisplayMV147CO2 AutocalibrationMV148Lock ScreenMV149Relative Humidity SensorMV150CO2 sourceMV151Temperature Alarm EnabledMV152ADR PermissionMV154Fan TypeMV155JapaneseMV156HebrewMV180Display the Fan Status iconMV181Display the System Status iconMV182Display the Help buttonMV210Wireless Device 1 - FunctionMV220Wireless Device 2 - FunctionMV230Wireless Device 3 - FunctionMV240Wireless Device 4 - FunctionMV250Wireless Device 5 - FunctionMV260Wireless Device 6 - FunctionMV270Wireless Device 7 - FunctionMV280Wireless Device 8 - FunctionMV290Wireless Device 9 - FunctionMV300Wireless Device 10 - FunctionMV310Wireless Device 11 - FunctionMV320Wireless Device 12 - FunctionMV330Wireless Device 13 - FunctionMV340Wireless Device 14 - FunctionMV350Wireless Device 15 - FunctionMV360Wireless Device 16 - FunctionMV370Wireless Device 17 - FunctionMV380Wireless Device 18 - FunctionMV390Wireless Device 19 - FunctionMV400Wireless Device 20 - Function
Integration notes
- Access follows the guide's generic property tables: AV, AO, BV, BO and MSV present values are commandable, CSVs are writable, and AI/MSI present values can only be written while Out_Of_Service is TRUE.
- Object names in the guide carry the screen or web page where each setting appears, in brackets; those references are moved to the descriptions here.
- Universal inputs and outputs appear as several objects each (raw value, temperature, voltage, binary); which one is meaningful depends on the input type and configuration objects.
- Wireless Device 1-20 objects only report data for ZigBee sensors paired to the controller.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SpaceLogic SER8350 Line Voltage Fan Coil Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
How many BACnet points does the Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller have?
This list has 407 BACnet objects: 75 analog inputs, 4 analog outputs, 69 analog values, 4 binary inputs, 5 binary outputs, 25 binary values, 101 multi-state inputs, 93 multi-state values, 30 characterstring values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller BACnet points are writable?
227 of the 407 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller BACnet documentation?
The source is SpaceLogic SER8350 BACnet Integration Guide - Line Voltage Fan Coil Unit (FCU) - Firmware Revision 2.6, Version 7 (028-0553-07_IG-SER8350-BNET_A4_EN (Version 7)), revision 2022-05, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=IG-SER8300-BNET.
What are the minimum BACnet points to integrate the Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller?
Start with MV 10 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode: low / medium / high / auto / on); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 112 Control Status (Current state: off, cooling or heating); MI 326 Fan Speed Status (Fan speed status: off / low / medium / high); MI 33 Effective Occupancy (Actual occupancy state); AV 100 Room Temperature (Space temperature used for control); BV 37 Service Alarm (Service alarm from an input set to Service).
How do I enable BMS control of the Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller?
The BMS writes MV 10 Occupancy Command (1 = Loc. occ, local occupancy; 2 = Occupied; 3 = Unoccupied) and MV 16 System Mode. MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.
Can the BMS supply sensor values to the Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller?
The guide does not describe feeding room temperature from the BMS. MV 145 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. AI present values are only writable with Out_Of_Service set TRUE.
How do I check these points on the real SpaceLogic SER8350 Line Voltage Fan Coil Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Multi-circuit branch power meter (high density)
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Schneider Electric (ex-Veris) PowerLogic HDPM6000 head units with busway, strip or retrofit measurement modules, on BACnet IP over Ethernet.
Also known as: HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Schneider Electric PowerLogic PM5300 series power meters with the Ethernet port (PM5320, PM5340, PM5341) using BACnet IP.
Also known as: PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Zone controller (room thermostat)
Schneider Electric SE7200 Series PIR Ready Zoning Controller
Schneider Electric PIR-ready SE7200 series 24 Vac zoning controllers (SE7200C5x45B, SE7200F5x45B).
Also known as: SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Schneider Electric PIR-ready SER7300 series line-voltage fan coil controllers: SER7300, SER7305, SER7350 and SER7355 (A versions).
Also known as: SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B - Pressure-dependent VAV zone controller
Schneider Electric SEZ7260 Zoning System Zone Controller
Schneider Electric SEZ7260 zone controllers (F model with floating damper and AO2, C model) used with SEZ7656 rooftop controllers in pressure-dependent zoning systems.
Also known as: SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B - Rooftop unit controller for zoning systems
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Schneider Electric SEZ7656 rooftop controllers (R conventional, H heat pump, F modulating heat, E economizer) that run a rooftop unit for a group of SEZ7260 zone controllers.
Also known as: SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Room humidity and temperature sensor (wall)
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Schneider Electric SpaceLogic SLP Series wall humidity/temperature sensors (with or without touchscreen) set to BACnet MS/TP.
Also known as: SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil - Rooftop unit controller (room thermostat, rooftop or heat-pump units)
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 6500 (rooftop unit / heat pump) version.
Also known as: SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump
Source: SpaceLogic SER8350 BACnet Integration Guide - Line Voltage Fan Coil Unit (FCU) - Firmware Revision 2.6, Version 7 · 028-0553-07_IG-SER8350-BNET_A4_EN (Version 7) · rev. 2022-05. Object names, instances and units are reproduced as published; descriptions are our own.