Pressure-dependent VAV zone controller · BACnet points list
Schneider Electric SEZ7260 Zoning System Zone Controller BACnet points list
Updated 7 November 2026
The SEZ7260 is the zone (damper) controller of the Schneider Electric SEZ7000 zoning system. It shares a BACnet MS/TP network with its SEZ7656 rooftop controller and exchanges demands, occupancy and outdoor temperature with it on its own, so no BMS bindings are needed. Objects cover room temperature and setpoints, damper position and limits, PI demands sent to the rooftop controller, reheat and output configuration, and CO2 values.
This page lists 64 BACnet objects for the Schneider Electric SEZ7260 Zoning System Zone Controller — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- SEZ7260 Zoning System Zone Controller
- Equipment
- Pressure-dependent VAV zone controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 64 (41 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 72000 + zone MAC address (AV 23, range 72000-72255)
- Also known as
- SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric SEZ7260 Zoning System Zone Controller
The zone runs with its SEZ7656 without any BMS. To command it, set MV 7 Cfg Network Handle to 2 or 3, then write occupancy MV 9 and the occupied setpoints AV 11 / AV 12. Read room temperature AV 21, damper position AI 1 and the PI demands AV 24 / AV 25.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 9 | GUI Occupancy | Occupancy command (needs MV 7 set to 2 or 3) | Write |
| AV 11 | GUI Occupied Heat Spt | Occupied heating setpoint | Write |
| AV 12 | GUI Occupied Cool Spt | Occupied cooling setpoint | Write |
| MV 11 | GUI Effective Occupancy | Occupied / unoccupied / temporary / stand-by | Read |
| AV 21 | GUI Room Temperature | Room temperature | Read |
| AI 1 | GUI Damper Position | Zone damper position, % (F models) | Read |
| AV 24 | GUI PI Heat Demand | PI heating demand, % | Read |
| AV 25 | GUI PI Cool Demand | PI cooling demand, % | Read |
Enable & remote start
MV 7 Cfg Network Handle: 1 = default (occupancy, mode and outdoor temperature come from the SEZ7656), 2 = zone handling minus occupancy, 3 = full release (zone runs without the SEZ7656). The BMS can hold occupancy MV 9 only at 2 or 3.
Sensors & values from the BMS
Room temperature AV 21 can be written only while BV 10 Room Temp Override is on. Outdoor temperature AV 22 normally comes from the SEZ7656. Room CO2 AV 32 is writable.
Network setup
- Each zone controller has a zone MAC (AV 1) and points to its rooftop controller MAC (AV 2).
- Default device instance is 72000 + MAC (AV 23).
Watch out for
- If the controller goes offline, BMS-written room temperature, outdoor temperature and occupancy are released.
- Schneider recommends removing configuration (Cfg) objects from the BAS after setup to cut polling.
Schneider Electric SEZ7260 Zoning System Zone Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | GUI Damper Position | Range 0% to 100%; only SEZ7260F5x45B | % | Read | |
| AV | 1 | Cfg Zone MAC | Range 1 to 255, default 255 | Read | ||
| AV | 2 | Cfg RTC MAC | Range 1 to 127, default 4 | Write | ||
| AV | 3 | Cfg AO2 OA Lock Spt | Range -40°F (-40°C) to 122°F (50°C), default 55°F (13°C); only SEZ7260F5x45B | °F | Write | |
| AV | 4 | Cfg BO5 OA Lock Spt | Range -40°F (-40°C) to 122°F (50°C), default 32°F (0°C) | °F | Write | |
| AV | 5 | Cfg Damper Min Pos | Range 0% to 100%, default 10% | % | Write | |
| AV | 6 | Cfg Damper Max Pos | Range 0% to 100%, default 100% | % | Write | |
| AV | 7 | Cfg Damper Max Heat Pos | Range 0% to 100%, default 30% | % | Write | |
| AV | 8 | Cfg Heating Stpt Limit | Range 40°F (4.5°C) to 90°F (32°C), default 90°F (32°C) | °F | Write | |
| AV | 9 | Cfg Cooling Spt Limit | Range 54°F (12°C) to 100°F (37.5), default 54°F (12°C) | °F | Write | |
| AV | 10 | Cfg Deadband | Range 2°F (1°C) to 5°F (2.5°C), default 2°F (1°C) | °F | Write | |
| AVmin | 11 | GUI Occupied Heat Spt | Range 40°F (4.5°C) to 90°F (32°C), default 72°F (22°C) | °F | Write | |
| AVmin | 12 | GUI Occupied Cool Spt | Range 54°F (12°C) to 100°F (37.5°C), default 74°F (24°C) | °F | Write | |
| AV | 13 | GUI Unoccupied Heat Spt | Range 40°F (4.5°C) to 90°F (32°C), default 72°F (22°C) | °F | Write | |
| AV | 14 | GUI Unoccupied Cool Spt | Range 54°F (12°C) to 100°F (37.5°C), default 74°F (24°C) | °F | Write | |
| AV | 15 | GUI Stand-By Heat Spt | Range 40°F (4.5°C) to 90°F (32°C), default 62°F (16.5°C) | °F | Write | |
| AV | 16 | GUI Stand-By Cool Spt | Range 54°F (12°C) to 100°F (37.5°C), default 80°F (26.5°C) | °F | Write | |
| AV | 17 | GUI AO2 Status | Range 0% to 100%; only SEZ7260F5x45B | % | Read | |
| AV | 18 | GUI UI3 Status | Range -40°F (-40°C) to 122°F (50°C) | °F | Read | |
| AV | 19 | GUI PI Heat Weighted Demand | Range 0% to 100% | % | Read | |
| AV | 20 | GUI PI Cool Weighted Demand | Range 0% to 100% | % | Read | |
| AVmin | 21 | GUI Room Temperature | Range -40°F (-40°C) to 122°F (50°C); writable only while BV 10 is Override | °F | Read | |
| AV | 22 | GUI Outdoor Temperature | Range -40°F (-40°C) to 122°F (50°C) | °F | Write | |
| AV | 23 | Cfg Device Instance | Range 72000 to 72255 | Read | ||
| AVmin | 24 | GUI PI Heat Demand | Range 0% to 100% | % | Read | |
| AVmin | 25 | GUI PI Cool Demand | Range 0% to 100% | % | Read | |
| AV | 26 | Cfg Password | Range 0 to 1000 | Write | ||
| AV | 27 | Cfg Stand-by Time | Range 0.5 hours to 24 hours, default 0.5 hours | h | Write | |
| AV | 28 | Cfg Unoccupied Time | Range 0 hours to 24 hours, default 0 hours | h | Write | |
| AV | 29 | GUI Heating Performance | Range 32°F (0°C) to 100°F (37.5°C) | °F | Read | |
| AV | 30 | GUI Cooling Performance | Range 32°F (0°C) to 100°F (37.5°C) | °F | Read | |
| AV | 31 | Cfg BO3-BO4 OA Lock Spt | Range -40°F (-40°C) to 122°F (50°C); only SEZ7260C5x45B | °F | Write | |
| AV | 32 | GUI Room CO2 Level | Range 0 PPM to 2000 PPM | ppm | Write | |
| AV | 33 | GUI Transferred CO2 Value | Range 0 PPM to 2000 PPM | ppm | Write | |
| AV | 34 | GUI AI4 Value | Range 0 VDC to 10 VDC | V | Read | |
| BI | 1 | GUI BI1 Status | Read | 0=Not Activated, 1=Activated | ||
| BV | 1 | Cfg Temperature Scale | Write | 0=°C, 1=°F | ||
| BV | 2 | Cfg Menu Scroll | Write | 0=No Scroll, 1=Scroll Active | ||
| BV | 4 | Cfg AO2 DA/RA | only SEZ7260F5x45B | Write | 0=Direct Acting, 1=Reverse Acting | |
| BV | 5 | Cfg BO5 Time Base | Write | 0=15 Minutes, 1=10 Seconds | ||
| BV | 6 | Cfg BO5 Conf | Write | 0=N.O., 1=N.C. | ||
| BV | 7 | GUI BO5 Status | Read | 0=Off, 1=On | ||
| BV | 8 | Sta AO2 Lock Status | only SEZ7260F5x45B | Read | 0=Not Activated, 1=Activated | |
| BV | 9 | Sta BO5 Lock Status | Read | 0=Not Activated, 1=Activated | ||
| BV | 10 | GUI Room Temp Override | Write | 0=Normal, 1=Override | ||
| BV | 11 | Sta RTC Smart Recovery | Read | 0=Off, 1=On | ||
| BV | 12 | Cfg Setpoint Type | Write | 0=Permanent, 1=Temporary | ||
| BV | 13 | Cfg Disable Min Pos | Write | 0=Enabled, 1=Disabled | ||
| BV | 14 | Sta BO3-BO4 Lock Status | only SEZ7260C5x45B | Read | 0=Inactive, 1=Active | |
| MV | 1 | Cfg Zone Baud | Read | 1=9600 (Bps), 2=19200 (Bps), 3=38400 (Bps), 4=76800 (Bps), 5=Auto | ||
| MV | 2 | Cfg Reheat Config | Write | 1=None, 2=Analog Duct Heater Only, 3=On/Off Duct Heater Only, 4=On/Off Perimeter Heater Only, 5=Analog Duct Heater with On/Off Perimeter Heater | ||
| MV | 3 | Cfg BI1 Configuration | Write | 1=None, 2=Motion NO, 3=Motion NC | ||
| MV | 4 | Cfg PI Heat Weight | Write | 1=0 %, 2=25 %, 3=50 %, 4=75 %, 5=100 % | ||
| MV | 5 | Cfg PI Cool Weight | Write | 1=0 %, 2=25 %, 3=50 %, 4=75 %, 5=100 % | ||
| MV | 6 | Cfg Temporary Occupancy Time | Read | 1=0 hour, 2=1 hour, 3=2 hours, 4=3 hours, 5=4 hours, 6=5 hours, 7=6 hours, 8=7 hours, 9=8 hours, 10=9 hours, 11=10 hours, 12=11 hours, 13=12 hours | ||
| MV | 7 | Cfg Network Handle | How much the zone depends on its SEZ7656 rooftop controller | Write | 1=Default Zone Handling, 2=Zone Handling minus Occupancy, 3=Full Release | |
| MV | 8 | GUI Zone Keypad Lockout | Write | 1=Level 0, 2=Level 1, 3=Level 2, 4=Level 3 | ||
| MVmin | 9 | GUI Occupancy | Writable permanently only when MV 7 is 2 or 3 | Write | 1=Local Occupancy, 2=Occupied, 3=Unoccupied | |
| MV | 10 | Sta RTC Zone Sequencing | Read | 1=Cool, 2=Heat | ||
| MVmin | 11 | GUI Effective Occupancy | Read | 1=Occupied, 2=Unoccupied, 3=Temporary Occupied, 4=Stand-by | ||
| MV | 12 | Cfg BO1-BO2 Floating Time | only SEZ7260C5x45B | Write | 1=0.5 minutes, 2=1 minute, 3=1.5 minutes, 4=2 minutes, 5=2.5 minutes, 6=3 minutes, 7=3.5 minutes, 8=4 minutes, 9=4.5 minutes, 10=5 minutes, 11=5.5 minutes, 12=6 minutes, 13=6.5 minutes, 14=7 minutes, 15=7.5 minutes, 16=8 minutes, 17=8.5 minutes, 18=9 minutes | |
| MV | 13 | Cfg BO3-BO4 Floating Time | only SEZ7260C5x45B | Write | 1=0.5 minutes, 2=1 minute, 3=1.5 minutes, 4=2 minutes, 5=2.5 minutes, 6=3 minutes, 7=3.5 minutes, 8=4 minutes, 9=4.5 minutes, 10=5 minutes, 11=5.5 minutes, 12=6 minutes, 13=6.5 minutes, 14=7 minutes, 15=7.5 minutes, 16=8 minutes, 17=8.5 minutes, 18=9 minutes | |
| MV | 14 | Cfg AI4 Configuration | Write | 1=None, 2=CO2 | ||
| MV | 15 | Cfg Proportional Band | Write | 1=3°F(1.7°C), 2=4°F(2.2°C), 3=5°F(2.8°C), 4=6°F(3.3°C), 5=7°F(3.9°C), 6=8°F(4.4°C), 7=9°F(5.0°C), 8=10°F(5.6°C) |
No points match these filters.
Object ID lookup: Schneider Electric SEZ7260 Zoning System Zone Controller point IDs by name
AI1GUI Damper PositionAV1Cfg Zone MACAV2Cfg RTC MACAV3Cfg AO2 OA Lock SptAV4Cfg BO5 OA Lock SptAV5Cfg Damper Min PosAV6Cfg Damper Max PosAV7Cfg Damper Max Heat PosAV8Cfg Heating Stpt LimitAV9Cfg Cooling Spt LimitAV10Cfg DeadbandAV11GUI Occupied Heat SptAV12GUI Occupied Cool SptAV13GUI Unoccupied Heat SptAV14GUI Unoccupied Cool SptAV15GUI Stand-By Heat SptAV16GUI Stand-By Cool SptAV17GUI AO2 StatusAV18GUI UI3 StatusAV19GUI PI Heat Weighted DemandAV20GUI PI Cool Weighted DemandAV21GUI Room TemperatureAV22GUI Outdoor TemperatureAV23Cfg Device InstanceAV24GUI PI Heat DemandAV25GUI PI Cool DemandAV26Cfg PasswordAV27Cfg Stand-by TimeAV28Cfg Unoccupied TimeAV29GUI Heating PerformanceAV30GUI Cooling PerformanceAV31Cfg BO3-BO4 OA Lock SptAV32GUI Room CO2 LevelAV33GUI Transferred CO2 ValueAV34GUI AI4 ValueBI1GUI BI1 StatusBV1Cfg Temperature ScaleBV2Cfg Menu ScrollBV4Cfg AO2 DA/RABV5Cfg BO5 Time BaseBV6Cfg BO5 ConfBV7GUI BO5 StatusBV8Sta AO2 Lock StatusBV9Sta BO5 Lock StatusBV10GUI Room Temp OverrideBV11Sta RTC Smart RecoveryBV12Cfg Setpoint TypeBV13Cfg Disable Min PosBV14Sta BO3-BO4 Lock StatusMV1Cfg Zone BaudMV2Cfg Reheat ConfigMV3Cfg BI1 ConfigurationMV4Cfg PI Heat WeightMV5Cfg PI Cool WeightMV6Cfg Temporary Occupancy TimeMV7Cfg Network HandleMV8GUI Zone Keypad LockoutMV9GUI OccupancyMV10Sta RTC Zone SequencingMV11GUI Effective OccupancyMV12Cfg BO1-BO2 Floating TimeMV13Cfg BO3-BO4 Floating TimeMV14Cfg AI4 ConfigurationMV15Cfg Proportional Band
Integration notes
- The guide marks each object for the SEZ7260F and SEZ7260C; objects on only one model say so in the description.
- Ranges and state texts come from the guide's range and enumeration tables (matched by type and instance).
- Access is from the guide's R / R/W column (R/W shown as W); the guide does not mention a priority array.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SEZ7260 Zoning System Zone Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric SEZ7260 Zoning System Zone Controller
How many BACnet points does the Schneider Electric SEZ7260 Zoning System Zone Controller have?
This list has 64 BACnet objects: 1 analog input, 34 analog values, 1 binary input, 13 binary values, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric SEZ7260 Zoning System Zone Controller BACnet points are writable?
41 of the 64 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Schneider Electric SEZ7260 Zoning System Zone Controller BACnet documentation?
The source is BACnet Integration Manual - Zoning Product Series SEZ7260 & SEZ7656 Series (IG-SE7000-BNETSEZ7XXX-US.EN.4.2013.v1), revision 2013-04, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=IG-SE7000-BNETSEZ7XXX-A4.
What are the minimum BACnet points to integrate the Schneider Electric SEZ7260 Zoning System Zone Controller?
Start with MV 9 GUI Occupancy (Occupancy command (needs MV 7 set to 2 or 3)); AV 11 GUI Occupied Heat Spt (Occupied heating setpoint); AV 12 GUI Occupied Cool Spt (Occupied cooling setpoint); MV 11 GUI Effective Occupancy (Occupied / unoccupied / temporary / stand-by); AV 21 GUI Room Temperature (Room temperature); AI 1 GUI Damper Position (Zone damper position, % (F models)); AV 24 GUI PI Heat Demand (PI heating demand, %); AV 25 GUI PI Cool Demand (PI cooling demand, %).
How do I enable BMS control of the Schneider Electric SEZ7260 Zoning System Zone Controller?
MV 7 Cfg Network Handle: 1 = default (occupancy, mode and outdoor temperature come from the SEZ7656), 2 = zone handling minus occupancy, 3 = full release (zone runs without the SEZ7656). The BMS can hold occupancy MV 9 only at 2 or 3.
Can the BMS supply sensor values to the Schneider Electric SEZ7260 Zoning System Zone Controller?
Room temperature AV 21 can be written only while BV 10 Room Temp Override is on. Outdoor temperature AV 22 normally comes from the SEZ7656. Room CO2 AV 32 is writable.
How do I check these points on the real SEZ7260 Zoning System Zone Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Multi-circuit branch power meter (high density)
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Schneider Electric (ex-Veris) PowerLogic HDPM6000 head units with busway, strip or retrofit measurement modules, on BACnet IP over Ethernet.
Also known as: HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Schneider Electric PowerLogic PM5300 series power meters with the Ethernet port (PM5320, PM5340, PM5341) using BACnet IP.
Also known as: PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Zone controller (room thermostat)
Schneider Electric SE7200 Series PIR Ready Zoning Controller
Schneider Electric PIR-ready SE7200 series 24 Vac zoning controllers (SE7200C5x45B, SE7200F5x45B).
Also known as: SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Schneider Electric PIR-ready SER7300 series line-voltage fan coil controllers: SER7300, SER7305, SER7350 and SER7355 (A versions).
Also known as: SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B - Rooftop unit controller for zoning systems
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Schneider Electric SEZ7656 rooftop controllers (R conventional, H heat pump, F modulating heat, E economizer) that run a rooftop unit for a group of SEZ7260 zone controllers.
Also known as: SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Schneider Electric SpaceLogic SE8000-series SER8350 room controllers for line-voltage fan coil units.
Also known as: SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350 - Room humidity and temperature sensor (wall)
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Schneider Electric SpaceLogic SLP Series wall humidity/temperature sensors (with or without touchscreen) set to BACnet MS/TP.
Also known as: SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil - Rooftop unit controller (room thermostat, rooftop or heat-pump units)
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 6500 (rooftop unit / heat pump) version.
Also known as: SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump
Source: BACnet Integration Manual - Zoning Product Series SEZ7260 & SEZ7656 Series · IG-SE7000-BNETSEZ7XXX-US.EN.4.2013.v1 · rev. 2013-04. Object names, instances and units are reproduced as published; descriptions are our own.