Pressure-dependent VAV zone controller · BACnet points list

Schneider Electric SEZ7260 Zoning System Zone Controller BACnet points list

Updated 7 November 2026

Short answer

The SEZ7260 is the zone (damper) controller of the Schneider Electric SEZ7000 zoning system. It shares a BACnet MS/TP network with its SEZ7656 rooftop controller and exchanges demands, occupancy and outdoor temperature with it on its own, so no BMS bindings are needed. Objects cover room temperature and setpoints, damper position and limits, PI demands sent to the rooftop controller, reheat and output configuration, and CO2 values.

This page lists 64 BACnet objects for the Schneider Electric SEZ7260 Zoning System Zone Controller — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.

Manufacturer
Schneider Electric
Model
SEZ7260 Zoning System Zone Controller
Equipment
Pressure-dependent VAV zone controller
Equipment type
VAV boxes & fan coils
BACnet objects
64 (41 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
72000 + zone MAC address (AV 23, range 72000-72255)
Also known as
SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B
Source document
BACnet Integration Manual - Zoning Product Series SEZ7260 & SEZ7656 Series · IG-SE7000-BNETSEZ7XXX-US.EN.4.2013.v1 · rev. 2013-04
Download CSV 64 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.

BMS integration notes: Schneider Electric SEZ7260 Zoning System Zone Controller

Integration in brief

The zone runs with its SEZ7656 without any BMS. To command it, set MV 7 Cfg Network Handle to 2 or 3, then write occupancy MV 9 and the occupied setpoints AV 11 / AV 12. Read room temperature AV 21, damper position AI 1 and the PI demands AV 24 / AV 25.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 9GUI OccupancyOccupancy command (needs MV 7 set to 2 or 3)Write
AV 11GUI Occupied Heat SptOccupied heating setpointWrite
AV 12GUI Occupied Cool SptOccupied cooling setpointWrite
MV 11GUI Effective OccupancyOccupied / unoccupied / temporary / stand-byRead
AV 21GUI Room TemperatureRoom temperatureRead
AI 1GUI Damper PositionZone damper position, % (F models)Read
AV 24GUI PI Heat DemandPI heating demand, %Read
AV 25GUI PI Cool DemandPI cooling demand, %Read

Enable & remote start

MV 7 Cfg Network Handle: 1 = default (occupancy, mode and outdoor temperature come from the SEZ7656), 2 = zone handling minus occupancy, 3 = full release (zone runs without the SEZ7656). The BMS can hold occupancy MV 9 only at 2 or 3.

Sensors & values from the BMS

Room temperature AV 21 can be written only while BV 10 Room Temp Override is on. Outdoor temperature AV 22 normally comes from the SEZ7656. Room CO2 AV 32 is writable.

Network setup

Watch out for

Schneider Electric SEZ7260 Zoning System Zone Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

64 of 64 shown
Type
Multi-state
Access
Show
Schneider Electric SEZ7260 Zoning System Zone Controller BACnet Points List
DescriptionStates
AImin1GUI Damper PositionRange 0% to 100%; only SEZ7260F5x45B%Read
AV1Cfg Zone MACRange 1 to 255, default 255Read
AV2Cfg RTC MACRange 1 to 127, default 4Write
AV3Cfg AO2 OA Lock SptRange -40°F (-40°C) to 122°F (50°C), default 55°F (13°C); only SEZ7260F5x45B°FWrite
AV4Cfg BO5 OA Lock SptRange -40°F (-40°C) to 122°F (50°C), default 32°F (0°C)°FWrite
AV5Cfg Damper Min PosRange 0% to 100%, default 10%%Write
AV6Cfg Damper Max PosRange 0% to 100%, default 100%%Write
AV7Cfg Damper Max Heat PosRange 0% to 100%, default 30%%Write
AV8Cfg Heating Stpt LimitRange 40°F (4.5°C) to 90°F (32°C), default 90°F (32°C)°FWrite
AV9Cfg Cooling Spt LimitRange 54°F (12°C) to 100°F (37.5), default 54°F (12°C)°FWrite
AV10Cfg DeadbandRange 2°F (1°C) to 5°F (2.5°C), default 2°F (1°C)°FWrite
AVmin11GUI Occupied Heat SptRange 40°F (4.5°C) to 90°F (32°C), default 72°F (22°C)°FWrite
AVmin12GUI Occupied Cool SptRange 54°F (12°C) to 100°F (37.5°C), default 74°F (24°C)°FWrite
AV13GUI Unoccupied Heat SptRange 40°F (4.5°C) to 90°F (32°C), default 72°F (22°C)°FWrite
AV14GUI Unoccupied Cool SptRange 54°F (12°C) to 100°F (37.5°C), default 74°F (24°C)°FWrite
AV15GUI Stand-By Heat SptRange 40°F (4.5°C) to 90°F (32°C), default 62°F (16.5°C)°FWrite
AV16GUI Stand-By Cool SptRange 54°F (12°C) to 100°F (37.5°C), default 80°F (26.5°C)°FWrite
AV17GUI AO2 StatusRange 0% to 100%; only SEZ7260F5x45B%Read
AV18GUI UI3 StatusRange -40°F (-40°C) to 122°F (50°C)°FRead
AV19GUI PI Heat Weighted DemandRange 0% to 100%%Read
AV20GUI PI Cool Weighted DemandRange 0% to 100%%Read
AVmin21GUI Room TemperatureRange -40°F (-40°C) to 122°F (50°C); writable only while BV 10 is Override°FRead
AV22GUI Outdoor TemperatureRange -40°F (-40°C) to 122°F (50°C)°FWrite
AV23Cfg Device InstanceRange 72000 to 72255Read
AVmin24GUI PI Heat DemandRange 0% to 100%%Read
AVmin25GUI PI Cool DemandRange 0% to 100%%Read
AV26Cfg PasswordRange 0 to 1000Write
AV27Cfg Stand-by TimeRange 0.5 hours to 24 hours, default 0.5 hourshWrite
AV28Cfg Unoccupied TimeRange 0 hours to 24 hours, default 0 hourshWrite
AV29GUI Heating PerformanceRange 32°F (0°C) to 100°F (37.5°C)°FRead
AV30GUI Cooling PerformanceRange 32°F (0°C) to 100°F (37.5°C)°FRead
AV31Cfg BO3-BO4 OA Lock SptRange -40°F (-40°C) to 122°F (50°C); only SEZ7260C5x45B°FWrite
AV32GUI Room CO2 LevelRange 0 PPM to 2000 PPMppmWrite
AV33GUI Transferred CO2 ValueRange 0 PPM to 2000 PPMppmWrite
AV34GUI AI4 ValueRange 0 VDC to 10 VDCVRead
BI1GUI BI1 StatusRead0=Not Activated, 1=Activated
BV1Cfg Temperature ScaleWrite0=°C, 1=°F
BV2Cfg Menu ScrollWrite0=No Scroll, 1=Scroll Active
BV4Cfg AO2 DA/RAonly SEZ7260F5x45BWrite0=Direct Acting, 1=Reverse Acting
BV5Cfg BO5 Time BaseWrite0=15 Minutes, 1=10 Seconds
BV6Cfg BO5 ConfWrite0=N.O., 1=N.C.
BV7GUI BO5 StatusRead0=Off, 1=On
BV8Sta AO2 Lock Statusonly SEZ7260F5x45BRead0=Not Activated, 1=Activated
BV9Sta BO5 Lock StatusRead0=Not Activated, 1=Activated
BV10GUI Room Temp OverrideWrite0=Normal, 1=Override
BV11Sta RTC Smart RecoveryRead0=Off, 1=On
BV12Cfg Setpoint TypeWrite0=Permanent, 1=Temporary
BV13Cfg Disable Min PosWrite0=Enabled, 1=Disabled
BV14Sta BO3-BO4 Lock Statusonly SEZ7260C5x45BRead0=Inactive, 1=Active
MV1Cfg Zone BaudRead1=9600 (Bps), 2=19200 (Bps), 3=38400 (Bps), 4=76800 (Bps), 5=Auto
MV2Cfg Reheat ConfigWrite1=None, 2=Analog Duct Heater Only, 3=On/Off Duct Heater Only, 4=On/Off Perimeter Heater Only, 5=Analog Duct Heater with On/Off Perimeter Heater
MV3Cfg BI1 ConfigurationWrite1=None, 2=Motion NO, 3=Motion NC
MV4Cfg PI Heat WeightWrite1=0 %, 2=25 %, 3=50 %, 4=75 %, 5=100 %
MV5Cfg PI Cool WeightWrite1=0 %, 2=25 %, 3=50 %, 4=75 %, 5=100 %
MV6Cfg Temporary Occupancy TimeRead1=0 hour, 2=1 hour, 3=2 hours, 4=3 hours, 5=4 hours, 6=5 hours, 7=6 hours, 8=7 hours, 9=8 hours, 10=9 hours, 11=10 hours, 12=11 hours, 13=12 hours
MV7Cfg Network HandleHow much the zone depends on its SEZ7656 rooftop controllerWrite1=Default Zone Handling, 2=Zone Handling minus Occupancy, 3=Full Release
MV8GUI Zone Keypad LockoutWrite1=Level 0, 2=Level 1, 3=Level 2, 4=Level 3
MVmin9GUI OccupancyWritable permanently only when MV 7 is 2 or 3Write1=Local Occupancy, 2=Occupied, 3=Unoccupied
MV10Sta RTC Zone SequencingRead1=Cool, 2=Heat
MVmin11GUI Effective OccupancyRead1=Occupied, 2=Unoccupied, 3=Temporary Occupied, 4=Stand-by
MV12Cfg BO1-BO2 Floating Timeonly SEZ7260C5x45BWrite1=0.5 minutes, 2=1 minute, 3=1.5 minutes, 4=2 minutes, 5=2.5 minutes, 6=3 minutes, 7=3.5 minutes, 8=4 minutes, 9=4.5 minutes, 10=5 minutes, 11=5.5 minutes, 12=6 minutes, 13=6.5 minutes, 14=7 minutes, 15=7.5 minutes, 16=8 minutes, 17=8.5 minutes, 18=9 minutes
MV13Cfg BO3-BO4 Floating Timeonly SEZ7260C5x45BWrite1=0.5 minutes, 2=1 minute, 3=1.5 minutes, 4=2 minutes, 5=2.5 minutes, 6=3 minutes, 7=3.5 minutes, 8=4 minutes, 9=4.5 minutes, 10=5 minutes, 11=5.5 minutes, 12=6 minutes, 13=6.5 minutes, 14=7 minutes, 15=7.5 minutes, 16=8 minutes, 17=8.5 minutes, 18=9 minutes
MV14Cfg AI4 ConfigurationWrite1=None, 2=CO2
MV15Cfg Proportional BandWrite1=3°F(1.7°C), 2=4°F(2.2°C), 3=5°F(2.8°C), 4=6°F(3.3°C), 5=7°F(3.9°C), 6=8°F(4.4°C), 7=9°F(5.0°C), 8=10°F(5.6°C)
Object ID lookup: Schneider Electric SEZ7260 Zoning System Zone Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SEZ7260 Zoning System Zone Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Schneider Electric SEZ7260 Zoning System Zone Controller

How many BACnet points does the Schneider Electric SEZ7260 Zoning System Zone Controller have?

This list has 64 BACnet objects: 1 analog input, 34 analog values, 1 binary input, 13 binary values, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Schneider Electric SEZ7260 Zoning System Zone Controller BACnet points are writable?

41 of the 64 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Schneider Electric SEZ7260 Zoning System Zone Controller BACnet documentation?

The source is BACnet Integration Manual - Zoning Product Series SEZ7260 & SEZ7656 Series (IG-SE7000-BNETSEZ7XXX-US.EN.4.2013.v1), revision 2013-04, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=IG-SE7000-BNETSEZ7XXX-A4.

What are the minimum BACnet points to integrate the Schneider Electric SEZ7260 Zoning System Zone Controller?

Start with MV 9 GUI Occupancy (Occupancy command (needs MV 7 set to 2 or 3)); AV 11 GUI Occupied Heat Spt (Occupied heating setpoint); AV 12 GUI Occupied Cool Spt (Occupied cooling setpoint); MV 11 GUI Effective Occupancy (Occupied / unoccupied / temporary / stand-by); AV 21 GUI Room Temperature (Room temperature); AI 1 GUI Damper Position (Zone damper position, % (F models)); AV 24 GUI PI Heat Demand (PI heating demand, %); AV 25 GUI PI Cool Demand (PI cooling demand, %).

How do I enable BMS control of the Schneider Electric SEZ7260 Zoning System Zone Controller?

MV 7 Cfg Network Handle: 1 = default (occupancy, mode and outdoor temperature come from the SEZ7656), 2 = zone handling minus occupancy, 3 = full release (zone runs without the SEZ7656). The BMS can hold occupancy MV 9 only at 2 or 3.

Can the BMS supply sensor values to the Schneider Electric SEZ7260 Zoning System Zone Controller?

Room temperature AV 21 can be written only while BV 10 Room Temp Override is on. Outdoor temperature AV 22 normally comes from the SEZ7656. Room CO2 AV 32 is writable.

How do I check these points on the real SEZ7260 Zoning System Zone Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Schneider Electric BACnet points lists

Source: BACnet Integration Manual - Zoning Product Series SEZ7260 & SEZ7656 Series · IG-SE7000-BNETSEZ7XXX-US.EN.4.2013.v1 · rev. 2013-04. Object names, instances and units are reproduced as published; descriptions are our own.