Fan coil unit controller (room thermostat) · BACnet points list

Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil) BACnet points list

Updated 4 November 2026

Short answer

The SXWTRC3500 is a SpaceLogic touchscreen room controller for fan coil units, sold under the Schneider Electric brand. It is a BACnet application-specific controller (B-ASC) on BACnet MS/TP. Besides the fan coil points (setpoints, system and fan mode, valves, fan speeds) it carries display settings, Lua script parameters, Wi-Fi status and objects for up to 20 paired ZigBee wireless sensors.

This page lists 437 BACnet objects for the Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil) — 277 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.

Manufacturer
Schneider Electric
Model
SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Equipment
Fan coil unit controller (room thermostat)
Equipment type
VAV boxes & fan coils
BACnet objects
437 (277 writable)
Transport
BACnet MS/TP
Firmware
1.0
Also known as
SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil
Source document
SpaceLogic Touchscreen Room Controllers SXWTRCn500 BACnet Integration Guide, Firmware Revision 1.0, Version 1 · 998-23139901-1 · rev. May 2024
Download CSV 437 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.

BMS integration notes: Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)

Integration in brief

Command occupancy with MV 10, mode with MV 16 and fan mode with MV 17, and write the occupied setpoints AV 39/AV 40. Read AV 100 room temperature, MI 33 effective occupancy, MV 112 control status and MI 326 fan speed. Write at priorities 4-16 for live control; avoid 1-3.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 10Occupancy CommandBMS occupancy: local, occupied or unoccupiedCommand
MV 16System ModeOff / auto / cool / heatCommand
MV 17Fan ModeFan mode: on / auto / smart / low / medium / highCommand
AV 39Occupied Heat SetpointOccupied heating setpointCommand
AV 40Occupied Cool SetpointOccupied cooling setpointCommand
MV 112Control StatusCurrent state: off, cooling or heatingCommand
MI 326Fan Speed StatusFan speed status: off / low / medium / highRead
MI 33Effective OccupancyActual occupancy stateRead
AV 100Room TemperatureSpace temperature used for controlCommand
BV 37Service AlarmService alarm from an input set to ServiceCommand

Enable & remote start

The BMS writes MV 10 Occupancy Command (1 = Loc occ., local occupancy; 2 = Occupied; 3 = Unocc.) and MV 16 System Mode. MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.

Sensors & values from the BMS

The guide does not describe feeding room temperature from the BMS. MV 150 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. AI present values can only be written with Out_Of_Service set TRUE.

Network setup

Watch out for

Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

437 of 437 shown
Type
Access
Show
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil) BACnet Points List
DescriptionStates
AI1UI1 Raw ValueRange 0 to 4095Read
AI2UI2 Raw ValueRange 0 to 4095Read
AI3UI3 Raw ValueRange 0 to 4095Read
AI4UI4 Raw ValueRange 0 to 4095Read
AI5UI5 Raw ValueRange 0 to 4095Read
AI6UI6 Raw ValueRange 0 to 4095Read
AI7UI7 Raw ValueRange 0 to 4095Read
AI8UI8 Raw ValueRange 0 to 4095Read
AI20Light Sensor LevelRange 0 to 30000Read
AI40Relative Humidity Raw ValueDefault 0 %; range 0 to 100 %%Read
AI315Wireless Device 1 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI316Wireless Device 2 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI317Wireless Device 3 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI318Wireless Device 4 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI319Wireless Device 5 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI320Wireless Device 6 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI321Wireless Device 7 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI322Wireless Device 8 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI323Wireless Device 9 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI324Wireless Device 10 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI329Effective SetpointDefault 0 °F (-18 °C); range 40 to 100 °F (4 to 38 °C)°FRead
AI330Paired ZigBee DevicesRange 0 to 20Read
AI32RH Temperature Raw ValueDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FRead
AI342Wi-Fi Network Signal StrengthDefault 0 %; range 0 to 100 %%Read
AI355Wireless Device 11 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI356Wireless Device 12 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI357Wireless Device 13 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI358Wireless Device 14 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI359Wireless Device 15 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI360Wireless Device 16 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI361Wireless Device 17 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI362Wireless Device 18 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI363Wireless Device 19 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI364Wireless Device 20 - TemperatureDefault -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C)°FRead
AI365Wireless Device 1 - HumidityDefault 0 %; range 0 to 100 %%Read
AI366Wireless Device 2 - HumidityDefault 0 %; range 0 to 100 %%Read
AI367Wireless Device 3 - HumidityDefault 0 %; range 0 to 100 %%Read
AI368Wireless Device 4 - HumidityDefault 0 %; range 0 to 100 %%Read
AI369Wireless Device 5 - HumidityDefault 0 %; range 0 to 100 %%Read
AI370Wireless Device 6 - HumidityDefault 0 %; range 0 to 100 %%Read
AI371Wireless Device 7 - HumidityDefault 0 %; range 0 to 100 %%Read
AI372Wireless Device 8 - HumidityDefault 0 %; range 0 to 100 %%Read
AI373Wireless Device 9 - HumidityDefault 0 %; range 0 to 100 %%Read
AI374Wireless Device 10 - HumidityDefault 0 %; range 0 to 100 %%Read
AI375Wireless Device 11 - HumidityDefault 0 %; range 0 to 100 %%Read
AI376Wireless Device 12 - HumidityDefault 0 %; range 0 to 100 %%Read
AI377Wireless Device 13 - HumidityDefault 0 %; range 0 to 100 %%Read
AI378Wireless Device 14 - HumidityDefault 0 %; range 0 to 100 %%Read
AI379Wireless Device 15 - HumidityDefault 0 %; range 0 to 100 %%Read
AI380Wireless Device 16 - HumidityDefault 0 %; range 0 to 100 %%Read
AI381Wireless Device 17 - HumidityDefault 0 %; range 0 to 100 %%Read
AI382Wireless Device 18 - HumidityDefault 0 %; range 0 to 100 %%Read
AI383Wireless Device 19 - HumidityDefault 0 %; range 0 to 100 %%Read
AI384Wireless Device 20 - HumidityDefault 0 %; range 0 to 100 %%Read
AI385Wireless Device 1 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI386Wireless Device 2 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI387Wireless Device 3 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI388Wireless Device 4 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI389Wireless Device 5 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI390Wireless Device 6 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI391Wireless Device 7 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI392Wireless Device 8 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI393Wireless Device 9 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI394Wireless Device 10 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI395Wireless Device 11 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI396Wireless Device 12 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI397Wireless Device 13 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI398Wireless Device 14 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI399Wireless Device 15 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI400Wireless Device 16 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI401Wireless Device 17 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI402Wireless Device 18 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI403Wireless Device 19 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI404Wireless Device 20 - CO2Default 0 ppm; range 0 to 5000 ppmppmRead
AI11Thermistor 1Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FRead
AI12Thermistor 2Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FRead
AI13Thermistor 3Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FRead
AI14Thermistor 4Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FRead
AI15Thermistor 5Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FRead
AI16MCU TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FRead
AO21PI Heating DemandDefault 0 %; range 0 to 100 %%Command
AO22PI Cooling DemandDefault 0 %; range 0 to 100 %%Command
AO101AO1 VoltageDefault 0 v; range 0 to 10 vVCommand
AO102AO2 VoltageDefault 0 v; range 0 to 10 vVCommand
AO103AO3 VoltageDefault 0 v; range 0 to 10 vVCommand
AO104AO4 VoltageDefault 0 v; range 0 to 10 vVCommand
AVmin100Room TemperatureDefault 0 °F (-18 °C); range -40 to 122 °F (-40 to 50 °C)°FCommand
AV101Outdoor TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV102Supply TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV103Room HumidityDefault 0 %; range 0 to 100 %%Command
AV104Changeover TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV105Wired Temperature SensorDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV106CO2 LevelDefault 0 ppm; range 0 to 5000 ppmppmCommand
AV111UI1 VoltageDefault 0 v; range 0 to 10 vVCommand
AV112UI2 VoltageDefault 0 v; range 0 to 10 vVCommand
AV113UI3 VoltageDefault 0 v; range 0 to 10 vVCommand
AV114UI4 VoltageDefault 0 v; range 0 to 10 vVCommand
AV115UI5 VoltageDefault 0 v; range 0 to 10 vVCommand
AV116UI6 VoltageDefault 0 v; range 0 to 10 vVCommand
AV117UI7 VoltageDefault 0 v; range 0 to 10 vVCommand
AV118UI8 VoltageDefault 0 v; range 0 to 10 vVCommand
AV121UI1 TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV122UI2 TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV123UI3 TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV124UI4 TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV125UI5 TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV126UI6 TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV127UI7 TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AV128UI8 TemperatureDefault 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C)°FCommand
AVmin40Occupied Cool SetpointDefault 75 °F (24 °C); range 54 to 100 °F (12 to 38 °C)°FCommand
AVmin39Occupied Heat SetpointDefault 72 °F (22 °C); range 40 to 90 °F (4 to 32 °C)°FCommand
AV44Unoccupied Cool SetpointDefault 80 °F (27 °C); range 54 to 100 °F (12 to 38 °C)°FCommand
AV43Unoccupied Heat SetpointDefault 62 °F (17 °C); range 40 to 90 °F (4 to 32 °C)°FCommand
AV58Maximum Heating Setpoint LimitDefault 90 °F (32 °C); range 40 to 90 °F (4 to 32 °C)°FCommand
AV59Minimum Cooling Setpoint LimitDefault 54 °F (12 °C); range 54 to 100 °F (12 to 38 °C)°FCommand
AV7Calibrate Room Temperature SensorDefault 0 °F Delta (0 °C); range -5 to 5 °F Delta (-3 to 3 °C)Δ°FCommand
AV42Standby Cool SetpointDefault 78 °F (26 °C); range 54 to 100 °F (12 to 38 °C)°FCommand
AV41Standby Heat SetpointDefault 69 °F (21 °C); range 40 to 90 °F (4 to 32 °C)°FCommand
AV73Dehumidification Max Cooling LimitDefault 100 %; range 20 to 100 %%Command
AV71Dehumidification SetpointDefault 50 %; range 30 to 95 %%Command
AV8Calibrate Humidity SensorDefault 0 %; range -15 to 15 %%Command
AV72Dehumidification HysteresisDefault 5 %; range 2 to 20 %%Command
AV10COM AddressDefault 254; range 0 to 254Command
AV63Minimum DeadbandDefault 3 °F Delta (2 °C); range 1.8 to 5 °F Delta (1 to 3 °C)Δ°FCommand
AV84Heating CPHDefault 4; range 3 to 8Command
AV85Cooling CPHDefault 4; range 3 to 8Command
AV52Number of PipesDefault 2; range 0 to 4Command
AV68Unoccupied TimeDefault 0 h; range 0 to 24 hhCommand
AV62Temporary Occupancy TimeDefault 2 h; range 0 to 24 hhCommand
AV67Standby TimeDefault 0.5 h; range 0.5 to 24 hhCommand
AV65Proportional BandDefault 3 °F Delta (2 °C); range 3 to 10 °F Delta (2 to 6 °C)Δ°FCommand
AV89Cooling Demand LimitDefault 100 %; range 0 to 100 %%Command
AV88Heating Demand LimitDefault 100 %; range 0 to 100 %%Command
AV3Low BacklightDefault 60 %; range 0 to 100 %%Command
AV4Night BacklightDefault 5 %; range 0 to 100 %%Command
AV5Purge Sample PeriodDefault 2 h; range 0 to 4 hhCommand
AV6Purge OpenDefault 2 m; range 1 to 3 mminCommand
AV46Standby Temperature DifferentialDefault 4 °F Delta (2 °C); range 1 to 5 °F Delta (1 to 3 °C)Δ°FCommand
AV45Default Cooling SetpointDefault 75 °F (24 °C); range 54 to 100 °F (12 to 38 °C)°FCommand
AV47Default Heating SetpointDefault 72 °F (22 °C); range 40 to 90 °F (4 to 32 °C)°FCommand
AV90Floating Actuator TimeDefault 1.5 m; range 0.5 to 9 mminCommand
AV74Calibrate Outside Temperature SensorDefault 0 °F Delta (0 °C); range -5 to 5 °F Delta (-3 to 3 °C)Δ°FCommand
AV25Lua Parameter A (AV25)Range -32768 to 32767Command
AV26Lua Parameter B (AV26)Range -32768 to 32767Command
AV27Lua Parameter C (AV27)Range -32768 to 32767Command
AV28Lua Parameter D (AV28)Range -32768 to 32767Command
AV29Lua Parameter E (AV29)Range -32768 to 32767Command
AV30Lua Parameter F (AV30)Range -32768 to 32767Command
AV209Ambient Low Temperature ThresholdDefault 40 °F (4 °C); range 32 to 50 °F (0 to 10 °C)°FCommand
AV210Temperature Alarm HysteresisDefault 2 °F Delta (1 °C); range 0 to 10 °F Delta (0 to 6 °C)Δ°FCommand
AV280ADR Setpoint Offset - Load SheddingDefault 4 °F Delta (2 °C); range 1 to 10 °F Delta (1 to 6 °C)Δ°FCommand
AV31Lua Parameter G (AV31)Range -32768 to 32767Command
AV32Lua Parameter H (AV32)Range -32768 to 32767Command
AV33Lua Parameter I (AV33)Range -32768 to 32767Command
AV34Lua Parameter J (AV34)Range -32768 to 32767Command
AV35Lua Parameter K (AV35)Range -32768 to 32767Command
AV36Lua Parameter L (AV36)Range -32768 to 32767Command
AV212ECM Fan Low VoltageDefault 2.2 v; range 0 to 9.8 vVCommand
AV213ECM Fan Medium VoltageDefault 6 v; range 0.1 to 9.9 vVCommand
AV214ECM Fan High VoltageDefault 8.6 v; range 0.2 to 10 vVCommand
AV275Ambient High Temperature ThresholdDefault 86 °F (30 °C); range 32 to 122 °F (0 to 50 °C)°FCommand
AV276Refrigeration High Temperature ThresholdDefault 40 °F (4 °C); range 32 to 60 °F (0 to 16 °C)°FCommand
AV277Refrigeration Low Temperature ThresholdDefault 32 °F (0 °C); range 32 to 50 °F (0 to 10 °C)°FCommand
AV278Freezer High Temperature ThresholdDefault 0 °F (-18 °C); range -40 to 32 °F (-40 to 0 °C)°FCommand
AV60Minimum Occupied Heating Setpoint LimitDefault 40 °F (4 °C); range 40 to 90 °F (4 to 32 °C)°FCommand
AV61Maximum Occupied Cooling Setpoint LimitDefault 100 °F (38 °C); range 54 to 100 °F (12 to 38 °C)°FCommand
AV231Inactivity TimeDefault 3 m; range 1 to 10 mminCommand
AV232Backlight BrightnessDefault 60 %; range 0 to 100 %%Command
AV281ADR Setpoint Offset - PricingDefault 4 °F Delta (2 °C); range 1 to 10 °F Delta (1 to 6 °C)Δ°FCommand
AV282Temperature compensation matrixDefault 0 °F (-18 °C); range -100 to 100 °F (-73 to 38 °C)°FCommand
AV16BACnet Stack Poll RateDefault 4; range 1 to 5Command
BI1UI1 BinaryDefault 0=Activated; screen: TerminalsRead0=Activated, 1=Not activated
BI2UI2 BinaryDefault 0=Activated; screen: TerminalsRead0=Activated, 1=Not activated
BI3UI3 BinaryDefault 0=Activated; screen: TerminalsRead0=Activated, 1=Not activated
BI4UI4 BinaryDefault 0=Activated; screen: TerminalsRead0=Activated, 1=Not activated
BI5UI5 BinaryDefault 0=Activated; screen: TerminalsRead0=Activated, 1=Not activated
BI6UI6 BinaryDefault 0=Activated; screen: TerminalsRead0=Activated, 1=Not activated
BI7UI7 BinaryDefault 0=Activated; screen: TerminalsRead0=Activated, 1=Not activated
BI8UI8 BinaryDefault 0=Activated; screen: TerminalsRead0=Activated, 1=Not activated
BO1DO1 Binary OutputDefault 0=Off; screen: TerminalsCommand0=Off, 1=On
BO2DO2 Low Speed Fan OutputDefault 0=Off; screen: TerminalsCommand0=Off, 1=On
BO3DO3 Medium Speed Fan OutputDefault 0=Off; screen: TerminalsCommand0=Off, 1=On
BO4DO4 High Speed Fan OutputDefault 0=Off; screen: TerminalsCommand0=Off, 1=On
BO5DO5 Auxiliary Binary OutputDefault 0=Off; screen: TerminalsCommand0=Off, 1=On
BO6DO6 Binary OutputDefault 0=Off; screen: TerminalsCommand0=Off, 1=On
BO7DO7 Binary OutputDefault 0=Off; screen: TerminalsCommand0=Off, 1=On
BO8DO8 Binary OutputDefault 0=Off; screen: TerminalsCommand0=Off, 1=On
BO9DO9 Binary OutputDefault 0=Off; screen: TerminalsCommand0=Off, 1=On
BV36Filter AlarmDefault 0=Off; screen: AlarmsCommand0=Off, 1=On
BVmin37Service AlarmDefault 0=Off; screen: AlarmsCommand0=Off, 1=On
BV35Window AlarmDefault 0=Off; screen: AlarmsCommand0=Off, 1=On
BV32PIR Local MotionDefault 0=No motion; screen: Operating StatusCommand0=No motion, 1=Motion
BV38Dehumidification StatusDefault 0=Off; screen: System StatusCommand0=Off, 1=On
BV5Low Battery AlarmDefault 0=Off; screen: AlarmsCommand0=Off, 1=On
BV4Window Contact InstalledDefault 0=No; screen: EnvironmentCommand0=No, 1=Yes
BV3Window Contact StatusDefault 0=Closed; screen: Operating StatusCommand0=Closed, 1=Opened
BV2Door Contact InstalledDefault 0=No; screen: EnvironmentCommand0=No, 1=Yes
BV1Door Contact StatusDefault 0=Closed; screen: Operating StatusCommand0=Closed, 1=Opened
BV40Smart Recovery StatusDefault 0=Off; screen: System StatusCommand0=Off, 1=On
BV10Exception StatusDefault 0=OffCommand0=Off, 1=On
BV200ZigBee PIR Sensor InstalledDefault 0=OffCommand0=Off, 1=On
BV201ZigBee Sensor MotionDefault 0=No motionCommand0=No motion, 1=Motion
BV8Clock AlarmDefault 0=Off; screen: AlarmsCommand0=Off, 1=On
BV50Wireless Sensor Communication AlarmDefault 0=Off; screen: AlarmsCommand0=Off, 1=On
BV44Water LeakDefault 0=Off; screen: AlarmsCommand0=Off, 1=On
BV45Water Leak Sensor InstalledDefault 0=No; screen: EnvironmentCommand0=No, 1=Yes
BV46Water leak sensor statusDefault 0=Normal; screen: Operating StatusCommand0=Normal, 1=Leak
BV47Low TemperatureDefault 0=Off; screen: RooftopCommand0=Off, 1=On
BV80ADR Utility Signal - Load SheddingDefault 0=Off; screen: ADRCommand0=Off, 1=On
BV81ADR Status - Load SheddingDefault 0=Off; screen: ADRCommand0=Off, 1=On
BV82ADR Override - Load SheddingDefault 0=Off; screen: ADRCommand0=Off, 1=On
BV48High TemperatureDefault 0=Off; screen: RooftopCommand0=Off, 1=On
BV60Purge StatusDefault 0=Off; screen: Operating StatusCommand0=Off, 1=On
BV33PIR Local ProximityDefault 0=No proximityCommand0=No proximity, 1=Proximity
BV65Activity StatusDefault 0=InactiveCommand0=Inactive, 1=Active
BV83ADR Utility Signal - PricingDefault 0=Off; screen: ADRCommand0=Off, 1=On
BV84ADR Status - PricingDefault 0=Off; screen: ADRCommand0=Off, 1=On
BV85ADR Override - PricingDefault 0=Off; screen: ADRCommand0=Off, 1=On
CSV1Short Screen Message TextText, length 0 to 160Write
CSV2Long Screen Message TextText, length 0 to 480Write
CSV4Wi-Fi Device NameText, length 0 to 63Write
CSV5Wi-Fi Firmware VersionText, length 0 to 63Write
CSV6MAC AddressText, length 0 to 18Write
CSV7Wi-Fi Network SSIDText, length 0 to 33Write
CSV8Wi-Fi Network IP AddressText, length 0 to 46Write
CSV10Zigbee IEEE AddressText, length 0 to 18Write
CSV11Wireless Device 1 - AddressText, length 0 to 18Write
CSV12Wireless Device 2 - AddressText, length 0 to 18Write
CSV13Wireless Device 3 - AddressText, length 0 to 18Write
CSV14Wireless Device 4 - AddressText, length 0 to 18Write
CSV15Wireless Device 5 - AddressText, length 0 to 18Write
CSV16Wireless Device 6 - AddressText, length 0 to 18Write
CSV17Wireless Device 7 - AddressText, length 0 to 18Write
CSV18Wireless Device 8 - AddressText, length 0 to 18Write
CSV19Wireless Device 9 - AddressText, length 0 to 18Write
CSV20Wireless Device 10 - AddressText, length 0 to 18Write
CSV21Wireless Device 11 - AddressText, length 0 to 18Write
CSV22Wireless Device 12 - AddressText, length 0 to 18Write
CSV23Wireless Device 13 - AddressText, length 0 to 18Write
CSV24Wireless Device 14 - AddressText, length 0 to 18Write
CSV25Wireless Device 15 - AddressText, length 0 to 18Write
CSV26Wireless Device 16 - AddressText, length 0 to 18Write
CSV27Wireless Device 17 - AddressText, length 0 to 18Write
CSV28Wireless Device 18 - AddressText, length 0 to 18Write
CSV29Wireless Device 19 - AddressText, length 0 to 18Write
CSV30Wireless Device 20 - AddressText, length 0 to 18Write
CSV31Active User IdText, length 0 to 33Write
CSV32Wi-Fi Network NetmaskText, length 0 to 46Write
CSV33Wi-Fi Network GatewayText, length 0 to 46Write
CSV34Wi-Fi Network DNSText, length 0 to 46Write
CSV35LocationText, length 0 to 49Write
CSV36Install CodeText, length 0 to 46Write
CSV37WiFi STA static IP addressText, length 0 to 46Write
CSV38WiFi STA static netmask addressText, length 0 to 46Write
CSV39WiFi STA static gateway addressText, length 0 to 46Write
CSV40TimezoneText, length 0 to 32Write
CSV41Custom Standby Heading TextText, length 0 to 65Write
CSV42Custom Standby Body TextText, length 0 to 161Write
MImin33Effective OccupancyDefault 1=Occupied; screen: Operating StatusRead1=Occupied, 2=Unoccupied, 3=Override, 4=Standby
MI2ZigBee Network StatusDefault 1=Not det.Read1=Not det., 2=Pwr on, 3=No NWK, 4=Joined, 5=Online
MI210Wireless Device 1 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI220Wireless Device 2 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI230Wireless Device 3 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI240Wireless Device 4 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI250Wireless Device 5 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI260Wireless Device 6 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI270Wireless Device 7 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI280Wireless Device 8 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI290Wireless Device 9 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI300Wireless Device 10 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI211Wireless Device 1 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI221Wireless Device 2 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI231Wireless Device 3 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI241Wireless Device 4 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI251Wireless Device 5 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI261Wireless Device 6 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI271Wireless Device 7 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI281Wireless Device 8 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI291Wireless Device 9 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI301Wireless Device 10 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI212Wireless Device 1 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI222Wireless Device 2 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI232Wireless Device 3 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI242Wireless Device 4 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI252Wireless Device 5 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI262Wireless Device 6 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI272Wireless Device 7 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI282Wireless Device 8 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI292Wireless Device 9 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI302Wireless Device 10 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI324CO2 Effective SourceDefault 1=None; screen: EnvironmentRead1=None, 2=Internal, 3=Error, 4=Wired, 5=Wireless Sensor 1, 6=Wireless Sensor 2, 7=Wireless Sensor 3, 8=Wireless Sensor 4, 9=Wireless Sensor 5, 10=Wireless Sensor 6, 11=Wireless Sensor 7, 12=Wireless Sensor 8, 13=Wireless Sensor 9, 14=Wireless Sensor 10, 15=Wireless Sensor 11, 16=Wireless Sensor 12, 17=Wireless Sensor 13, 18=Wireless Sensor 14, 19=Wireless Sensor 15, 20=Wireless Sensor 16, 21=Wireless Sensor 17, 22=Wireless Sensor 18, 23=Wireless Sensor 19, 24=Wireless Sensor 20
MI309Effective temperature sensorDefault 1=Wired; screen: EnvironmentRead1=Wired, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20
MI313Effective relative humidity sensorDefault 1=None; screen: EnvironmentRead1=None, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20
MI314Effective System ModeDefault 1=Cool; screen: Operating StatusRead1=Cool, 2=Heat
MI315IP StatusDefault 1=Offline; screen: BACnetRead1=Offline, 2=Initializing, 3=Ready, 4=Booting, 5=Resetting, 6=Fail, 7=Testing
MI316Wi-Fi Network StatusDefault 1=Offline; screen: BACnetRead1=Offline, 2=Associate, 3=Online, 4=Failure
MI318SMTP Server StatusDefault 1=Unknown; screen: BACnetRead1=Unknown, 2=Disabled, 3=Offline, 4=Online
MI310Wireless Device 11 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI320Wireless Device 12 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI330Wireless Device 13 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI340Wireless Device 14 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI350Wireless Device 15 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI360Wireless Device 16 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI370Wireless Device 17 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI380Wireless Device 18 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI390Wireless Device 19 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI400Wireless Device 20 - StatusDefault 1=NoneRead1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak
MI311Wireless Device 11 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI321Wireless Device 12 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI331Wireless Device 13 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI341Wireless Device 14 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI351Wireless Device 15 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI361Wireless Device 16 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI371Wireless Device 17 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI381Wireless Device 18 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI391Wireless Device 19 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI401Wireless Device 20 - BatteryDefault 1=NoneRead1=None, 2=Normal, 3=Low
MI312Wireless Device 11 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI322Wireless Device 12 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI332Wireless Device 13 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI342Wireless Device 14 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI352Wireless Device 15 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI362Wireless Device 16 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI372Wireless Device 17 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI382Wireless Device 18 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI392Wireless Device 19 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI402Wireless Device 20 - Communication StatusDefault 1=Not pairedRead1=Not paired, 2=Online, 3=Invalid, 4=Offline
MI325Time sourceDefault 1=NoneRead1=None, 2=Local, 3=BACnet, 4=NTP, 5=Cloud
MImin326Fan Speed StatusDefault 1=Off; screen: Operating StatusRead1=Off, 2=Low, 3=Medium, 4=High
MI327Wi-Fi Network Signal StrengthDefault 1=PoorRead1=Poor, 2=Fair, 3=Good, 4=Excellent
MV51Temperature ScaleDefault 1=°CCommand1=°C, 2=°F
MV4Display LanguageDefault 1=English; screen: Preferences (main)Command1=English, 2=French, 3=Spanish, 4=Chinese, 5=Russian, 6=Arabic, 7=Danish, 8=Italian, 9=German, 10=Indonesian, 11=Polish, 12=Swedish, 13=Norwegian, 14=Finnish, 15=Hungarian, 16=Turkish, 17=Dutch, 18=Czech, 19=Portuguese, 20=Bulgarian, 21=Slovak, 22=Japanese, 23=Hebrew
MVmin17Fan ModeDefault 3=Smart; screen: HomeCommand1=On, 2=Auto, 3=Smart, 4=Low, 5=Medium, 6=High
MVmin16System ModeDefault 4=Heat; screen: HomeCommand1=Off, 2=Auto, 3=Cool, 4=Heat
MV205Default SetpointsDefault 1=Disabled; screen: Setpoint ConfigurationCommand1=Disabled, 2=Enabled
MV46UI1 ConfigurationDefault 1=None; screen: InputsCommand1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window, 6=Fan lock
MV47UI2 ConfigurationDefault 1=None; screen: InputsCommand1=None, 2=Door dry, 3=Override, 4=Filter, 5=Service
MV13Dehumidification EnabledDefault 1=Disabled; screen: DehumidifierCommand1=Disabled, 2=Enabled
MV57Fan SequenceDefault 5=Speeds-Smart; screen: FanCommand1=Auto, 2=Smart, 3=Auto-Smart, 4=Speeds-Auto, 5=Speeds-Smart, 6=Speeds-Auto-Smart
MV58Setpoint FunctionDefault 2=Attach SP; screen: Setpoint ConfigurationCommand1=Dual SP, 2=Attach SP
MV95Fan Control in Heating ModeDefault 1=Enabled; screen: FanCommand1=Enabled, 2=Forced Off-Auto/Smart, 3=Forced Off-All Modes
MV15Sequence of OperationDefault 2=Heating only; screen: Fan Coil UnitCommand1=Cooling only, 2=Heating only, 3=Reheat Only, 4=Cooling/Heating, 5=Cooling/Reheat, 6=Heating/Reheat, 7=Cooling/Heating/Reheat
MVmin10Occupancy CommandDefault 2=Occupied; screen: Occupancy ConfigurationCommand1=Loc occ., 2=Occupied, 3=Unocc.
MV6Network UnitsDefault 2=Imperial; screen: Preferences (main)Command1=SI, 2=Imperial
MV5Time FormatDefault 1=12 Hour (AM- PM); screen: Preferences (setup)Command1=12 Hour (AM-PM), 2=24 Hour
MV11Standby Mode ConfigurationDefault 1=Absolute; screen: Setpoint ConfigurationCommand1=Absolute, 2=Offset
MV2Color ThemeDefault 2=Dark; screen: Preferences (main)Command1=Light, 2=Dark
MV3Main DisplayDefault 1=Temp.Command1=Temp., 2=Setpoint
MV32Use Standby ScreenDefault 1=Disabled; screen: DisplayCommand1=Disabled, 2=Custom Image
MV81Valve 1 TypeDefault 2=Floating; screen: Fan Coil UnitCommand1=On/Off, 2=Floating, 3=0-10V Direct Acting, 4=0-10V Reverse Acting
MV91Reheat Time BaseDefault 1=On/Off (4 CPH); screen: Fan Coil UnitCommand1=On/Off (4 CPH), 2=PWM (10s Duty Cycle)
MV92Auxiliary OutputDefault 1=Reheat (Normally Open); screen: Fan Coil UnitCommand1=Reheat (Normally Open), 2=Occupancy (Normally Open), 3=Occupancy (Normally Closed), 4=Aux Fan (Normally Open), 5=Aux Fan (Normally Closed), 6=Reheat (Normally Closed)
MV49UI3 ConfigurationDefault 1=None; screen: InputsCommand1=None, 2=CO2, 3=COC/NH, 4=COC/NC, 5=COS
MV96DO6-AO1 ConfigurationDefault 2=Binary RC; screen: TerminalsCommand1=Analog, 2=Binary RC, 3=Binary RH
MV97DO7-AO2 ConfigurationDefault 2=Binary RC; screen: TerminalsCommand1=Analog, 2=Binary RC
MV98DO8-AO3 ConfigurationDefault 2=Binary RC; screen: TerminalsCommand1=Analog, 2=Binary RC
MV99DO9-AO4 ConfigurationDefault 2=Binary RC; screen: TerminalsCommand1=Analog, 2=Binary RC
MV71Enable Smart RecoveryDefault 1=Off; screen: Occupancy ConfigurationCommand1=Off, 2=On
MV101FrenchDefault 2=Enabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV102SpanishDefault 2=Enabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV103ChineseDefault 2=Enabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV104RussianDefault 2=Enabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV210Wireless Device 1 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV220Wireless Device 2 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV230Wireless Device 3 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV240Wireless Device 4 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV250Wireless Device 5 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV260Wireless Device 6 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV270Wireless Device 7 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV280Wireless Device 8 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV290Wireless Device 9 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV300Wireless Device 10 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV110Occupancy SourceDefault 1=Motion; screen: Occupancy ConfigurationCommand1=Motion, 2=Schedule, 3=Motion during Schedule, 4=Motion or Schedule
MVmin112Control StatusDefault 1=OffCommand1=Off, 2=Cool, 3=Heat
MV120ArabicDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV122CzechDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV123DanishDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV124DutchDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV125FinnishDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV126GermanDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV127HungarianDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV128IndonesianDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV129ItalianDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV130NorwegianDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV131PolishDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV132PortugueseDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV133SlovakDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV134SwedishDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV135TurkishDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV119ApplicationDefault 3=; screen: HVAC ConfigurationCommand1=FCU
MV136Schedule TypeDefault 1=7 days; screen: Occupancy ScheduleCommand1=7 days, 2=5+2 days, 3=5+1+1 day
MV141UI1 TypeDefault 2=BinaryCommand1=Therm., 2=Binary, 3=Voltage
MV142UI2 TypeDefault 2=BinaryCommand1=Therm., 2=Binary, 3=Voltage
MV143UI3 TypeDefault 1=Therm.Command1=Therm., 2=Binary, 3=Voltage
MV144UI4 TypeDefault 1=Therm.Command1=Therm., 2=Binary, 3=Voltage
MV145UI5 TypeDefault 1=Therm.Command1=Therm., 2=Binary, 3=Voltage
MV146UI6 TypeDefault 1=Therm.Command1=Therm., 2=Binary, 3=Voltage
MV147UI7 TypeDefault 3=VoltageCommand1=Therm., 2=Binary, 3=Voltage
MV148UI8 TypeDefault 3=VoltageCommand1=Therm., 2=Binary, 3=Voltage
MV152CO2 AutocalibrationDefault 2=EnabledCommand1=Disabled, 2=Enabled
MV154Relative humidity sensorDefault 2=Internal; screen: InputsCommand1=None, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20
MV150Room Temperature SensorDefault 1=Wired; screen: InputsCommand1=Wired, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20
MV156Temperature Alarm EnabledDefault 1=OffCommand1=Off, 2=On
MV157ADR PermissionDefault 1=Disabled; screen: ADRCommand1=Disabled, 2=Enabled
MV158Fan TypeDefault 3=3 Speed (L-M-H); screen: FanCommand1=1 Speed (H), 2=2 Speed (L-H), 3=3 Speed (L-M-H), 4=ECM
MV159JapaneseDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV160HebrewDefault 1=Disabled; screen: Language SelectionCommand1=Disabled, 2=Enabled
MV82Valve 2 TypeDefault 2=FloatingCommand1=On/Off, 2=Floating, 3=0-10V Direct Acting, 4=0-10V Reverse Acting
MV310Wireless Device 11 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV320Wireless Device 12 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV330Wireless Device 13 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV340Wireless Device 14 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV350Wireless Device 15 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV360Wireless Device 16 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV370Wireless Device 17 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV380Wireless Device 18 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV390Wireless Device 19 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV400Wireless Device 20 - FunctionDefault 6=RemoveCommand1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer
MV155CO2 sourceDefault 2=Local; screen: EnvironmentCommand1=None, 2=Local, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20
MV183Enable Static IPDefault 1=DynamicCommand1=Dynamic, 2=Static
MV184Enable WIFIDefault 1=DisabledCommand1=Disabled, 2=Enabled
MV185Hidden WIFIDefault 1=DisabledCommand1=Disabled, 2=Enabled
MV186Notification TypeDefault 1=DisabledCommand1=Disabled, 2=Critical, 3=Warning, 4=Ok, 5=Informative
MV187Notification Display TypeDefault 3=All; screen: DisplayCommand1=Disabled, 2=Custom Only, 3=All
MV188Occupancy SensorDefault 4=High; screen: Occupancy ConfigurationCommand1=Off, 2=Low, 3=Medium, 4=High
MV189Proximity SensorDefault 4=HighCommand1=Off, 2=Low, 3=Medium, 4=High
MV190Custom Standby Text ColorDefault 1=WhiteCommand1=White, 2=Black
MV192HMI SetpointDefault 2=Slider; screen: DisplayCommand1=None, 2=Slider, 3=Buttons (Attached SP Only)
MV195Button 1Default 2=System Mode; screen: DisplayCommand1=Disabled, 2=System Mode, 3=Fan Mode
MV196Button 2Default 3=Fan Mode; screen: DisplayCommand1=Disabled, 2=System Mode, 3=Fan Mode
MV200Info Item 1Default 3=Humidity; screen: DisplayCommand1=Disabled, 2=Outdoor Air Temperature, 3=Humidity, 4=CO2 Level
MV201Info Item 2Default 4=CO2 Level; screen: DisplayCommand1=Disabled, 2=Outdoor Air Temperature, 3=Humidity, 4=CO2 Level
MV202Info Item 3Default 2=Outdoor Air Temperature; screen: DisplayCommand1=Disabled, 2=Outdoor Air Temperature, 3=Humidity, 4=CO2 Level
MV8BACnet Baud RateDefault 7=Auto; screen: BACnetCommand1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200, 7=Auto
MV193Remote Device AccessDefault 1=Disabled; screen: Lua StatusCommand1=Disabled, 2=Enabled
FILE1Custom Lua FileLUA4RC script file; read/write the scriptWrite
Other1Lua Program 1Program object that runs and monitors the LUA4RC scriptWrite
Object ID lookup: Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)

How many BACnet points does the Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil) have?

This list has 437 BACnet objects: 80 analog inputs, 6 analog outputs, 85 analog values, 8 binary inputs, 9 binary outputs, 30 binary values, 1 file, 72 multi-state inputs, 105 multi-state values, 40 characterstring values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil) BACnet points are writable?

277 of the 437 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil) BACnet documentation?

The source is SpaceLogic Touchscreen Room Controllers SXWTRCn500 BACnet Integration Guide, Firmware Revision 1.0, Version 1 (998-23139901-1), revision May 2024, published free by Schneider Electric at https://iportal.se.com/Contents/docs/998-23139901-1_TRCSE-BACNET-INTEGRATION-GUIDE_EN_CP20240508.PDF.

What are the minimum BACnet points to integrate the Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)?

Start with MV 10 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode: on / auto / smart / low / medium / high); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 112 Control Status (Current state: off, cooling or heating); MI 326 Fan Speed Status (Fan speed status: off / low / medium / high); MI 33 Effective Occupancy (Actual occupancy state); AV 100 Room Temperature (Space temperature used for control); BV 37 Service Alarm (Service alarm from an input set to Service).

How do I enable BMS control of the Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)?

The BMS writes MV 10 Occupancy Command (1 = Loc occ., local occupancy; 2 = Occupied; 3 = Unocc.) and MV 16 System Mode. MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.

Can the BMS supply sensor values to the Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)?

The guide does not describe feeding room temperature from the BMS. MV 150 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. AI present values can only be written with Out_Of_Service set TRUE.

How do I check these points on the real SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.