Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump) BACnet points list
Updated 4 November 2026
The SXWTRC6500 is a SpaceLogic touchscreen room controller for rooftop units and heat pumps, sold under the Schneider Electric brand. It is a BACnet application-specific controller (B-ASC) on BACnet MS/TP. Besides the rooftop points (setpoints, system and fan mode, Y/W/G stage outputs, economizer settings) it carries display settings, Lua script parameters, Wi-Fi status and objects for up to 20 paired ZigBee wireless sensors.
This page lists 457 BACnet objects for the Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump) — 297 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
- Equipment
- Rooftop unit controller (room thermostat, rooftop or heat-pump units)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 457 (297 writable)
- Transport
- BACnet MS/TP
- Firmware
- 1.0
- Also known as
- SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Command occupancy with MV 10, mode with MV 16 and fan mode with MV 17, and write the occupied setpoints AV 39/AV 40. Read AV 100 room temperature, MI 33 effective occupancy, MV 112 control status and MI 326 fan speed. Write at priorities 4-16 for live control; avoid 1-3.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 10 | Occupancy Command | BMS occupancy: local, occupied or unoccupied | Command |
| MV 16 | System Mode | Off / auto / cool / heat | Command |
| MV 17 | Fan Mode | Fan mode: on / auto / smart | Command |
| AV 39 | Occupied Heat Setpoint | Occupied heating setpoint | Command |
| AV 40 | Occupied Cool Setpoint | Occupied cooling setpoint | Command |
| MV 112 | Control Status | Current state: off, cooling or heating | Command |
| MI 326 | Fan Speed Status | Fan speed status: off / low / medium / high | Read |
| MI 33 | Effective Occupancy | Actual occupancy state | Read |
| AV 100 | Room Temperature | Space temperature used for control | Command |
| BV 37 | Service Alarm | Service alarm from an input set to Service | Command |
Enable & remote start
The BMS writes MV 10 Occupancy Command (1 = Loc occ., local occupancy; 2 = Occupied; 3 = Unocc.) and MV 16 System Mode. MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.
Sensors & values from the BMS
The guide does not describe feeding room temperature from the BMS. MV 150 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. AI present values can only be written with Out_Of_Service set TRUE.
Network setup
- BACnet MS/TP baud rate is MV 8 (9600 to 115200 or Auto; default Auto). AV 10 COM Address holds the MS/TP address (default 254, range 0-254).
- Max_Master is writable, 0-127, default 127. Device Object_Identifier and Object_Name are writable.
- The controller is a B-ASC with COV, time synchronization and an internal schedule (SCHED-I-B); it does not support segmented requests or responses.
Watch out for
- Priorities 1-3 are stored in EEPROM and lock the value at the controller even after a power cycle, until released at the same priority or factory defaults are restored. Use them only for fixed configuration.
- Priorities 4-16 are held in RAM and lost on a power cycle, so the BMS has to write them again after a restart.
- The relinquish default (priority 17) is what the occupant changes at the screen; it survives power cycles.
- Keep Read Property Multiple requests small; segmentation is not supported.
- MV 119 Application (rooftop or heat pump), AV 75/AV 87 stage counts and the UI/DO configuration objects are commissioning settings; do not write them cyclically.
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | UI1 Raw Value | Range 0 to 4095 | Read | ||
| AI | 2 | UI2 Raw Value | Range 0 to 4095 | Read | ||
| AI | 3 | UI3 Raw Value | Range 0 to 4095 | Read | ||
| AI | 4 | UI4 Raw Value | Range 0 to 4095 | Read | ||
| AI | 5 | UI5 Raw Value | Range 0 to 4095 | Read | ||
| AI | 6 | UI6 Raw Value | Range 0 to 4095 | Read | ||
| AI | 7 | UI7 Raw Value | Range 0 to 4095 | Read | ||
| AI | 8 | UI8 Raw Value | Range 0 to 4095 | Read | ||
| AI | 20 | Light Sensor Level | Range 0 to 30000 | Read | ||
| AI | 40 | Relative Humidity Raw Value | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 315 | Wireless Device 1 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 316 | Wireless Device 2 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 317 | Wireless Device 3 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 318 | Wireless Device 4 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 319 | Wireless Device 5 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 320 | Wireless Device 6 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 321 | Wireless Device 7 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 322 | Wireless Device 8 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 323 | Wireless Device 9 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 324 | Wireless Device 10 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 329 | Effective Setpoint | Default 0 °F (-18 °C); range 40 to 100 °F (4 to 38 °C) | °F | Read | |
| AI | 330 | Paired ZigBee Devices | Range 0 to 20 | Read | ||
| AI | 32 | RH Temperature Raw Value | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Read | |
| AI | 342 | Wi-Fi Network Signal Strength | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 355 | Wireless Device 11 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 356 | Wireless Device 12 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 357 | Wireless Device 13 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 358 | Wireless Device 14 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 359 | Wireless Device 15 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 360 | Wireless Device 16 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 361 | Wireless Device 17 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 362 | Wireless Device 18 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 363 | Wireless Device 19 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 364 | Wireless Device 20 - Temperature | Default -40 °F (-40 °C); range -40 to 185 °F (-40 to 85 °C) | °F | Read | |
| AI | 365 | Wireless Device 1 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 366 | Wireless Device 2 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 367 | Wireless Device 3 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 368 | Wireless Device 4 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 369 | Wireless Device 5 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 370 | Wireless Device 6 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 371 | Wireless Device 7 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 372 | Wireless Device 8 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 373 | Wireless Device 9 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 374 | Wireless Device 10 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 375 | Wireless Device 11 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 376 | Wireless Device 12 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 377 | Wireless Device 13 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 378 | Wireless Device 14 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 379 | Wireless Device 15 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 380 | Wireless Device 16 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 381 | Wireless Device 17 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 382 | Wireless Device 18 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 383 | Wireless Device 19 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 384 | Wireless Device 20 - Humidity | Default 0 %; range 0 to 100 % | % | Read | |
| AI | 385 | Wireless Device 1 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 386 | Wireless Device 2 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 387 | Wireless Device 3 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 388 | Wireless Device 4 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 389 | Wireless Device 5 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 390 | Wireless Device 6 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 391 | Wireless Device 7 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 392 | Wireless Device 8 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 393 | Wireless Device 9 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 394 | Wireless Device 10 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 395 | Wireless Device 11 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 396 | Wireless Device 12 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 397 | Wireless Device 13 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 398 | Wireless Device 14 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 399 | Wireless Device 15 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 400 | Wireless Device 16 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 401 | Wireless Device 17 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 402 | Wireless Device 18 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 403 | Wireless Device 19 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 404 | Wireless Device 20 - CO2 | Default 0 ppm; range 0 to 5000 ppm | ppm | Read | |
| AI | 11 | Thermistor 1 | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Read | |
| AI | 12 | Thermistor 2 | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Read | |
| AI | 13 | Thermistor 3 | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Read | |
| AI | 14 | Thermistor 4 | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Read | |
| AI | 15 | Thermistor 5 | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Read | |
| AI | 16 | MCU Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Read | |
| AO | 21 | PI Heating Demand | Default 0 %; range 0 to 100 % | % | Command | |
| AO | 22 | PI Cooling Demand | Default 0 %; range 0 to 100 % | % | Command | |
| AO | 23 | Economizer Demand | Default 0 %; range 0 to 100 % | % | Command | |
| AO | 24 | Analog Output Heat Demand | Default 0 %; range 0 to 100 % | % | Command | |
| AO | 101 | AO1 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AO | 102 | AO2 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AO | 103 | AO3 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AO | 104 | AO4 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AVmin | 100 | Room Temperature | Default 0 °F (-18 °C); range -40 to 122 °F (-40 to 50 °C) | °F | Command | |
| AV | 101 | Outdoor Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AV | 102 | Supply Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AV | 103 | Room Humidity | Default 0 %; range 0 to 100 % | % | Command | |
| AV | 105 | Wired Temperature Sensor | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AV | 106 | CO2 Level | Default 0 ppm; range 0 to 5000 ppm | ppm | Command | |
| AV | 107 | Airflow Level | Range 0 to 20000 | Command | ||
| AV | 111 | UI1 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AV | 112 | UI2 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AV | 113 | UI3 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AV | 114 | UI4 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AV | 115 | UI5 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AV | 116 | UI6 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AV | 117 | UI7 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AV | 118 | UI8 Voltage | Default 0 v; range 0 to 10 v | V | Command | |
| AV | 121 | UI1 Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AV | 122 | UI2 Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AV | 123 | UI3 Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AV | 124 | UI4 Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AV | 125 | UI5 Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AV | 126 | UI6 Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AV | 127 | UI7 Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AV | 128 | UI8 Temperature | Default 0 °F (-18 °C); range -40 to 180 °F (-40 to 82 °C) | °F | Command | |
| AVmin | 40 | Occupied Cool Setpoint | Default 75 °F (24 °C); range 54 to 100 °F (12 to 38 °C) | °F | Command | |
| AVmin | 39 | Occupied Heat Setpoint | Default 72 °F (22 °C); range 40 to 90 °F (4 to 32 °C) | °F | Command | |
| AV | 44 | Unoccupied Cool Setpoint | Default 80 °F (27 °C); range 54 to 100 °F (12 to 38 °C) | °F | Command | |
| AV | 43 | Unoccupied Heat Setpoint | Default 62 °F (17 °C); range 40 to 90 °F (4 to 32 °C) | °F | Command | |
| AV | 58 | Maximum Heating Setpoint Limit | Default 90 °F (32 °C); range 40 to 90 °F (4 to 32 °C) | °F | Command | |
| AV | 59 | Minimum Cooling Setpoint Limit | Default 54 °F (12 °C); range 54 to 100 °F (12 to 38 °C) | °F | Command | |
| AV | 7 | Calibrate Room Temperature Sensor | Default 0 °F Delta (0 °C); range -5 to 5 °F Delta (-3 to 3 °C) | Δ°F | Command | |
| AV | 42 | Standby Cool Setpoint | Default 78 °F (26 °C); range 54 to 100 °F (12 to 38 °C) | °F | Command | |
| AV | 41 | Standby Heat Setpoint | Default 69 °F (21 °C); range 40 to 90 °F (4 to 32 °C) | °F | Command | |
| AV | 71 | Dehumidification Setpoint | Default 50 %; range 30 to 95 % | % | Command | |
| AV | 8 | Calibrate Humidity Sensor | Default 0 %; range -15 to 15 % | % | Command | |
| AV | 72 | Dehumidification Hysteresis | Default 5 %; range 2 to 20 % | % | Command | |
| AV | 10 | COM Address | Default 254; range 0 to 254 | Command | ||
| AV | 63 | Minimum Deadband | Default 3 °F Delta (2 °C); range 1.8 to 5 °F Delta (1 to 3 °C) | Δ°F | Command | |
| AV | 84 | Heating CPH | Default 4; range 3 to 8 | Command | ||
| AV | 85 | Cooling CPH | Default 4; range 3 to 4 | Command | ||
| AV | 68 | Unoccupied Time | Default 0 h; range 0 to 24 h | h | Command | |
| AV | 62 | Temporary Occupancy Time | Default 2 h; range 0 to 24 h | h | Command | |
| AV | 67 | Standby Time | Default 0.5 h; range 0.5 to 24 h | h | Command | |
| AV | 65 | Proportional Band | Default 3 °F Delta (2 °C); range 3 to 10 °F Delta (2 to 6 °C) | Δ°F | Command | |
| AV | 89 | Cooling Demand Limit | Default 100 %; range 0 to 100 % | % | Command | |
| AV | 88 | Heating Demand Limit | Default 100 %; range 0 to 100 % | % | Command | |
| AV | 3 | Low Backlight | Default 60 %; range 0 to 100 % | % | Command | |
| AV | 4 | Night Backlight | Default 5 %; range 0 to 100 % | % | Command | |
| AV | 46 | Standby Temperature Differential | Default 4 °F Delta (2 °C); range 1 to 5 °F Delta (1 to 3 °C) | Δ°F | Command | |
| AV | 45 | Default Cooling Setpoint | Default 75 °F (24 °C); range 54 to 100 °F (12 to 38 °C) | °F | Command | |
| AV | 47 | Default Heating Setpoint | Default 72 °F (22 °C); range 40 to 90 °F (4 to 32 °C) | °F | Command | |
| AV | 86 | Anti Short Cycle Time | Default 2 m; range 0 to 5 m | min | Command | |
| AV | 87 | Number of Heating Stages | Default 2; range 0 to 2 | Command | ||
| AV | 75 | Number of Cooling Stages | Default 2; range 1 to 2 | Command | ||
| AV | 76 | Power-up Delay | Default 10; range 10 to 120 | Command | ||
| AV | 74 | Calibrate Outside Temperature Sensor | Default 0 °F Delta (0 °C); range -5 to 5 °F Delta (-3 to 3 °C) | Δ°F | Command | |
| AV | 91 | Heating Lockout from Outside Air Temperature | Default 120 °F (49 °C); range -15 to 120 °F (-26 to 49 °C) | °F | Command | |
| AV | 93 | Cooling Lockout | Default -40 °F (-40 °C); range -40 to 95 °F (-40 to 35 °C) | °F | Command | |
| AV | 94 | Supply Air Temperature Setpoint | Default 55 °F (13 °C); range 50 to 90 °F (10 to 32 °C) | °F | Command | |
| AV | 95 | Changeover Setpoint | Default 55 °F (13 °C); range 14 to 70 °F (-10 to 21 °C) | °F | Command | |
| AV | 78 | Economizer Minimum Position | Default 0 %; range 0 to 99 % | % | Command | |
| AV | 81 | Economizer Maximum Position | Default 100 %; range 1 to 100 % | % | Command | |
| AV | 96 | Fresh Air Range Upper Limit | Range 0 to 20000 | Command | ||
| AV | 97 | Minimum Supply Heat | Default 64 °F (18 °C); range 50 to 72 °F (10 to 22 °C) | °F | Command | |
| AV | 98 | Supply Heat Lockout | Default 32 °F (0 °C); range -15 to 120 °F (-26 to 49 °C) | °F | Command | |
| AV | 99 | Supply Temperature High Limit | Default 120 °F (49 °C); range 70 to 150 °F (21 to 66 °C) | °F | Command | |
| AV | 20 | Supply Temperature Low Limit | Default 45 °F (7 °C); range 35 to 65 °F (2 to 18 °C) | °F | Command | |
| AV | 21 | Minimum Fresh Air | Range 0 to 20000 | Command | ||
| AV | 22 | Maximum Fresh Air | Range 0 to 20000 | Command | ||
| AV | 23 | Minimum CO2 | Default 800 ppm; range 0 to 4800 ppm | ppm | Command | |
| AV | 24 | Maximum CO2 | Default 1200 ppm; range 200 to 5000 ppm | ppm | Command | |
| AV | 25 | Lua Parameter A (AV25) | Range -32768 to 32767 | Command | ||
| AV | 26 | Lua Parameter B (AV26) | Range -32768 to 32767 | Command | ||
| AV | 27 | Lua Parameter C (AV27) | Range -32768 to 32767 | Command | ||
| AV | 28 | Lua Parameter D (AV28) | Range -32768 to 32767 | Command | ||
| AV | 29 | Lua Parameter E (AV29) | Range -32768 to 32767 | Command | ||
| AV | 30 | Lua Parameter F (AV30) | Range -32768 to 32767 | Command | ||
| AV | 82 | High balance point | Default 90 °F (32 °C); range 34 to 90 °F (1 to 32 °C) | °F | Command | |
| AV | 83 | Low balance point | Default -12 °F (-24 °C); range -40 to 30 °F (-40 to -1 °C) | °F | Command | |
| AV | 209 | Ambient Low Temperature Threshold | Default 40 °F (4 °C); range 32 to 50 °F (0 to 10 °C) | °F | Command | |
| AV | 210 | Temperature Alarm Hysteresis | Default 2 °F Delta (1 °C); range 0 to 10 °F Delta (0 to 6 °C) | Δ°F | Command | |
| AV | 280 | ADR Setpoint Offset - Load Shedding | Default 4 °F Delta (2 °C); range 1 to 10 °F Delta (1 to 6 °C) | Δ°F | Command | |
| AV | 31 | Lua Parameter G (AV31) | Range -32768 to 32767 | Command | ||
| AV | 32 | Lua Parameter H (AV32) | Range -32768 to 32767 | Command | ||
| AV | 33 | Lua Parameter I (AV33) | Range -32768 to 32767 | Command | ||
| AV | 34 | Lua Parameter J (AV34) | Range -32768 to 32767 | Command | ||
| AV | 35 | Lua Parameter K (AV35) | Range -32768 to 32767 | Command | ||
| AV | 36 | Lua Parameter L (AV36) | Range -32768 to 32767 | Command | ||
| AV | 275 | Ambient High Temperature Threshold | Default 86 °F (30 °C); range 32 to 122 °F (0 to 50 °C) | °F | Command | |
| AV | 276 | Refrigeration High Temperature Threshold | Default 40 °F (4 °C); range 32 to 60 °F (0 to 16 °C) | °F | Command | |
| AV | 277 | Refrigeration Low Temperature Threshold | Default 32 °F (0 °C); range 32 to 50 °F (0 to 10 °C) | °F | Command | |
| AV | 278 | Freezer High Temperature Threshold | Default 0 °F (-18 °C); range -40 to 32 °F (-40 to 0 °C) | °F | Command | |
| AV | 60 | Minimum Occupied Heating Setpoint Limit | Default 40 °F (4 °C); range 40 to 90 °F (4 to 32 °C) | °F | Command | |
| AV | 61 | Maximum Occupied Cooling Setpoint Limit | Default 100 °F (38 °C); range 54 to 100 °F (12 to 38 °C) | °F | Command | |
| AV | 231 | Inactivity Time | Default 3 m; range 1 to 10 m | min | Command | |
| AV | 232 | Backlight Brightness | Default 60 %; range 0 to 100 % | % | Command | |
| AV | 281 | ADR Setpoint Offset - Pricing | Default 4 °F Delta (2 °C); range 1 to 10 °F Delta (1 to 6 °C) | Δ°F | Command | |
| AV | 282 | Temperature compensation matrix | Default 0 °F (-18 °C); range -100 to 100 °F (-73 to 38 °C) | °F | Command | |
| AV | 16 | BACnet Stack Poll Rate | Default 4; range 1 to 5 | Command | ||
| BI | 1 | UI1 Binary | Default 0=Activated; screen: Terminals | Read | 0=Activated, 1=Not activated | |
| BI | 2 | UI2 Binary | Default 0=Activated; screen: Terminals | Read | 0=Activated, 1=Not activated | |
| BI | 3 | UI3 Binary | Default 0=Activated; screen: Terminals | Read | 0=Activated, 1=Not activated | |
| BI | 4 | UI4 Binary | Default 0=Activated; screen: Terminals | Read | 0=Activated, 1=Not activated | |
| BI | 5 | UI5 Binary | Default 0=Activated; screen: Terminals | Read | 0=Activated, 1=Not activated | |
| BI | 6 | UI6 Binary | Default 0=Activated; screen: Terminals | Read | 0=Activated, 1=Not activated | |
| BI | 7 | UI7 Binary | Default 0=Activated; screen: Terminals | Read | 0=Activated, 1=Not activated | |
| BI | 8 | UI8 Binary | Default 0=Activated; screen: Terminals | Read | 0=Activated, 1=Not activated | |
| BO | 1 | DO1 Occupancy Output | Default 0=Off; screen: Terminals | Command | 0=Off, 1=On | |
| BO | 2 | Y2 Status | Default 0=Off; screen: Terminals | Command | 0=Off, 1=On | |
| BO | 3 | Y1 Status | Default 0=Off; screen: Terminals | Command | 0=Off, 1=On | |
| BO | 4 | G Fan Status | Default 0=Off; screen: Terminals | Command | 0=Off, 1=On | |
| BO | 5 | W1 Status | Default 0=Off; screen: Terminals | Command | 0=Off, 1=On | |
| BO | 6 | W2-OB Status | Default 0=Off; screen: Terminals | Command | 0=Off, 1=On | |
| BO | 7 | DO7 Binary Output | Default 0=Off; screen: Terminals | Command | 0=Off, 1=On | |
| BO | 8 | DO8 Binary Output | Default 0=Off; screen: Terminals | Command | 0=Off, 1=On | |
| BO | 9 | DO9 Binary Output | Default 0=Off; screen: Terminals | Command | 0=Off, 1=On | |
| BV | 36 | Filter Alarm | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BVmin | 37 | Service Alarm | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BV | 35 | Window Alarm | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BV | 32 | PIR Local Motion | Default 0=No motion; screen: Operating Status | Command | 0=No motion, 1=Motion | |
| BV | 38 | Dehumidification Status | Default 0=Off; screen: System Status | Command | 0=Off, 1=On | |
| BV | 5 | Low Battery Alarm | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BV | 4 | Window Contact Installed | Default 0=No; screen: Environment | Command | 0=No, 1=Yes | |
| BV | 3 | Window Contact Status | Default 0=Closed; screen: Operating Status | Command | 0=Closed, 1=Opened | |
| BV | 2 | Door Contact Installed | Default 0=No; screen: Environment | Command | 0=No, 1=Yes | |
| BV | 1 | Door Contact Status | Default 0=Closed; screen: Operating Status | Command | 0=Closed, 1=Opened | |
| BV | 39 | Fan Lock Alarm | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BV | 40 | Smart Recovery Status | Default 0=Off; screen: System Status | Command | 0=Off, 1=On | |
| BV | 10 | Exception Status | Default 0=Off | Command | 0=Off, 1=On | |
| BV | 41 | CO2 Alarm | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BV | 42 | Low Fresh Air Alarm | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BV | 43 | Frost Protection Alarm | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BV | 200 | ZigBee PIR Sensor Installed | Default 0=Off | Command | 0=Off, 1=On | |
| BV | 201 | ZigBee Sensor Motion | Default 0=No motion | Command | 0=No motion, 1=Motion | |
| BV | 8 | Clock Alarm | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BV | 50 | Wireless Sensor Communication Alarm | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BV | 44 | Water Leak | Default 0=Off; screen: Alarms | Command | 0=Off, 1=On | |
| BV | 45 | Water Leak Sensor Installed | Default 0=No; screen: Environment | Command | 0=No, 1=Yes | |
| BV | 46 | Water leak sensor status | Default 0=Normal; screen: Operating Status | Command | 0=Normal, 1=Leak | |
| BV | 47 | Low Temperature | Default 0=Off; screen: Rooftop | Command | 0=Off, 1=On | |
| BV | 80 | ADR Utility Signal - Load Shedding | Default 0=Off; screen: ADR | Command | 0=Off, 1=On | |
| BV | 81 | ADR Status - Load Shedding | Default 0=Off; screen: ADR | Command | 0=Off, 1=On | |
| BV | 82 | ADR Override - Load Shedding | Default 0=Off; screen: ADR | Command | 0=Off, 1=On | |
| BV | 48 | High Temperature | Default 0=Off; screen: Rooftop | Command | 0=Off, 1=On | |
| BV | 60 | Purge Status | Default 0=Off; screen: Operating Status | Command | 0=Off, 1=On | |
| BV | 33 | PIR Local Proximity | Default 0=No proximity | Command | 0=No proximity, 1=Proximity | |
| BV | 65 | Activity Status | Default 0=Inactive | Command | 0=Inactive, 1=Active | |
| BV | 83 | ADR Utility Signal - Pricing | Default 0=Off; screen: ADR | Command | 0=Off, 1=On | |
| BV | 84 | ADR Status - Pricing | Default 0=Off; screen: ADR | Command | 0=Off, 1=On | |
| BV | 85 | ADR Override - Pricing | Default 0=Off; screen: ADR | Command | 0=Off, 1=On | |
| CSV | 1 | Short Screen Message Text | Text, length 0 to 160 | Write | ||
| CSV | 2 | Long Screen Message Text | Text, length 0 to 480 | Write | ||
| CSV | 4 | Wi-Fi Device Name | Text, length 0 to 63 | Write | ||
| CSV | 5 | Wi-Fi Firmware Version | Text, length 0 to 63 | Write | ||
| CSV | 6 | MAC Address | Text, length 0 to 18 | Write | ||
| CSV | 7 | Wi-Fi Network SSID | Text, length 0 to 33 | Write | ||
| CSV | 8 | Wi-Fi Network IP Address | Text, length 0 to 46 | Write | ||
| CSV | 10 | Zigbee IEEE Address | Text, length 0 to 18 | Write | ||
| CSV | 11 | Wireless Device 1 - Address | Text, length 0 to 18 | Write | ||
| CSV | 12 | Wireless Device 2 - Address | Text, length 0 to 18 | Write | ||
| CSV | 13 | Wireless Device 3 - Address | Text, length 0 to 18 | Write | ||
| CSV | 14 | Wireless Device 4 - Address | Text, length 0 to 18 | Write | ||
| CSV | 15 | Wireless Device 5 - Address | Text, length 0 to 18 | Write | ||
| CSV | 16 | Wireless Device 6 - Address | Text, length 0 to 18 | Write | ||
| CSV | 17 | Wireless Device 7 - Address | Text, length 0 to 18 | Write | ||
| CSV | 18 | Wireless Device 8 - Address | Text, length 0 to 18 | Write | ||
| CSV | 19 | Wireless Device 9 - Address | Text, length 0 to 18 | Write | ||
| CSV | 20 | Wireless Device 10 - Address | Text, length 0 to 18 | Write | ||
| CSV | 21 | Wireless Device 11 - Address | Text, length 0 to 18 | Write | ||
| CSV | 22 | Wireless Device 12 - Address | Text, length 0 to 18 | Write | ||
| CSV | 23 | Wireless Device 13 - Address | Text, length 0 to 18 | Write | ||
| CSV | 24 | Wireless Device 14 - Address | Text, length 0 to 18 | Write | ||
| CSV | 25 | Wireless Device 15 - Address | Text, length 0 to 18 | Write | ||
| CSV | 26 | Wireless Device 16 - Address | Text, length 0 to 18 | Write | ||
| CSV | 27 | Wireless Device 17 - Address | Text, length 0 to 18 | Write | ||
| CSV | 28 | Wireless Device 18 - Address | Text, length 0 to 18 | Write | ||
| CSV | 29 | Wireless Device 19 - Address | Text, length 0 to 18 | Write | ||
| CSV | 30 | Wireless Device 20 - Address | Text, length 0 to 18 | Write | ||
| CSV | 31 | Active User Id | Text, length 0 to 33 | Write | ||
| CSV | 32 | Wi-Fi Network Netmask | Text, length 0 to 46 | Write | ||
| CSV | 33 | Wi-Fi Network Gateway | Text, length 0 to 46 | Write | ||
| CSV | 34 | Wi-Fi Network DNS | Text, length 0 to 46 | Write | ||
| CSV | 35 | Location | Text, length 0 to 49 | Write | ||
| CSV | 36 | Install Code | Text, length 0 to 46 | Write | ||
| CSV | 37 | WiFi STA static IP address | Text, length 0 to 46 | Write | ||
| CSV | 38 | WiFi STA static netmask address | Text, length 0 to 46 | Write | ||
| CSV | 39 | WiFi STA static gateway address | Text, length 0 to 46 | Write | ||
| CSV | 40 | Timezone | Text, length 0 to 32 | Write | ||
| CSV | 41 | Custom Standby Heading Text | Text, length 0 to 65 | Write | ||
| CSV | 42 | Custom Standby Body Text | Text, length 0 to 161 | Write | ||
| MImin | 33 | Effective Occupancy | Default 1=Occupied; screen: Operating Status | Read | 1=Occupied, 2=Unoccupied, 3=Override, 4=Standby | |
| MI | 2 | ZigBee Network Status | Default 1=Not det. | Read | 1=Not det., 2=Pwr on, 3=No NWK, 4=Joined, 5=Online | |
| MI | 210 | Wireless Device 1 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 220 | Wireless Device 2 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 230 | Wireless Device 3 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 240 | Wireless Device 4 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 250 | Wireless Device 5 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 260 | Wireless Device 6 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 270 | Wireless Device 7 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 280 | Wireless Device 8 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 290 | Wireless Device 9 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 300 | Wireless Device 10 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 211 | Wireless Device 1 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 221 | Wireless Device 2 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 231 | Wireless Device 3 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 241 | Wireless Device 4 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 251 | Wireless Device 5 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 261 | Wireless Device 6 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 271 | Wireless Device 7 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 281 | Wireless Device 8 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 291 | Wireless Device 9 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 301 | Wireless Device 10 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 212 | Wireless Device 1 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 222 | Wireless Device 2 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 232 | Wireless Device 3 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 242 | Wireless Device 4 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 252 | Wireless Device 5 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 262 | Wireless Device 6 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 272 | Wireless Device 7 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 282 | Wireless Device 8 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 292 | Wireless Device 9 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 302 | Wireless Device 10 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 324 | CO2 Effective Source | Default 1=None; screen: Environment | Read | 1=None, 2=Internal, 3=Error, 4=Wired, 5=Wireless Sensor 1, 6=Wireless Sensor 2, 7=Wireless Sensor 3, 8=Wireless Sensor 4, 9=Wireless Sensor 5, 10=Wireless Sensor 6, 11=Wireless Sensor 7, 12=Wireless Sensor 8, 13=Wireless Sensor 9, 14=Wireless Sensor 10, 15=Wireless Sensor 11, 16=Wireless Sensor 12, 17=Wireless Sensor 13, 18=Wireless Sensor 14, 19=Wireless Sensor 15, 20=Wireless Sensor 16, 21=Wireless Sensor 17, 22=Wireless Sensor 18, 23=Wireless Sensor 19, 24=Wireless Sensor 20 | |
| MI | 309 | Effective temperature sensor | Default 1=Wired; screen: Environment | Read | 1=Wired, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20 | |
| MI | 313 | Effective relative humidity sensor | Default 1=None; screen: Environment | Read | 1=None, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20 | |
| MI | 314 | Effective System Mode | Default 1=Cool; screen: Operating Status | Read | 1=Cool, 2=Heat | |
| MI | 315 | IP Status | Default 1=Offline; screen: BACnet | Read | 1=Offline, 2=Initializing, 3=Ready, 4=Booting, 5=Resetting, 6=Fail, 7=Testing | |
| MI | 316 | Wi-Fi Network Status | Default 1=Offline; screen: BACnet | Read | 1=Offline, 2=Associate, 3=Online, 4=Failure | |
| MI | 318 | SMTP Server Status | Default 1=Unknown; screen: BACnet | Read | 1=Unknown, 2=Disabled, 3=Offline, 4=Online | |
| MI | 310 | Wireless Device 11 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 320 | Wireless Device 12 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 330 | Wireless Device 13 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 340 | Wireless Device 14 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 350 | Wireless Device 15 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 360 | Wireless Device 16 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 370 | Wireless Device 17 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 380 | Wireless Device 18 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 390 | Wireless Device 19 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 400 | Wireless Device 20 - Status | Default 1=None | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | |
| MI | 311 | Wireless Device 11 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 321 | Wireless Device 12 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 331 | Wireless Device 13 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 341 | Wireless Device 14 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 351 | Wireless Device 15 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 361 | Wireless Device 16 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 371 | Wireless Device 17 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 381 | Wireless Device 18 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 391 | Wireless Device 19 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 401 | Wireless Device 20 - Battery | Default 1=None | Read | 1=None, 2=Normal, 3=Low | |
| MI | 312 | Wireless Device 11 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 322 | Wireless Device 12 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 332 | Wireless Device 13 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 342 | Wireless Device 14 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 352 | Wireless Device 15 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 362 | Wireless Device 16 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 372 | Wireless Device 17 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 382 | Wireless Device 18 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 392 | Wireless Device 19 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 402 | Wireless Device 20 - Communication Status | Default 1=Not paired | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | |
| MI | 325 | Time source | Default 1=None | Read | 1=None, 2=Local, 3=BACnet, 4=NTP, 5=Cloud | |
| MImin | 326 | Fan Speed Status | Default 1=Off; screen: Operating Status | Read | 1=Off, 2=Low, 3=Medium, 4=High | |
| MI | 327 | Wi-Fi Network Signal Strength | Default 1=Poor | Read | 1=Poor, 2=Fair, 3=Good, 4=Excellent | |
| MV | 51 | Temperature Scale | Default 1=°C | Command | 1=°C, 2=°F | |
| MV | 4 | Display Language | Default 1=English; screen: Preferences (main) | Command | 1=English, 2=French, 3=Spanish, 4=Chinese, 5=Russian, 6=Arabic, 7=Danish, 8=Italian, 9=German, 10=Indonesian, 11=Polish, 12=Swedish, 13=Norwegian, 14=Finnish, 15=Hungarian, 16=Turkish, 17=Dutch, 18=Czech, 19=Portuguese, 20=Bulgarian, 21=Slovak, 22=Japanese, 23=Hebrew | |
| MVmin | 17 | Fan Mode | Default 3=Smart; screen: Home | Command | 1=On, 2=Auto, 3=Smart | |
| MVmin | 16 | System Mode | Default 4=Heat; screen: Home | Command | 1=Off, 2=Auto, 3=Cool, 4=Heat | |
| MV | 205 | Default Setpoints | Default 1=Disabled; screen: Setpoint Configuration | Command | 1=Disabled, 2=Enabled | |
| MV | 46 | UI1 Configuration | Default 1=None; screen: Inputs | Command | 1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window, 6=Fan lock | |
| MV | 47 | UI2 Configuration | Default 1=None; screen: Inputs | Command | 1=None, 2=Door dry, 3=Override, 4=Filter, 5=Service | |
| MV | 13 | Dehumidification Enabled | Default 1=Disabled; screen: Dehumidifier | Command | 1=Disabled, 2=Enabled | |
| MV | 58 | Setpoint Function | Default 2=Attach SP; screen: Setpoint Configuration | Command | 1=Dual SP, 2=Attach SP | |
| MV | 95 | Fan Control in Heating Mode | Default 2=On; screen: Rooftop | Command | 1=Off, 2=On | |
| MVmin | 10 | Occupancy Command | Default 2=Occupied; screen: Occupancy Configuration | Command | 1=Loc occ., 2=Occupied, 3=Unocc. | |
| MV | 6 | Network Units | Default 2=Imperial; screen: Preferences (main) | Command | 1=SI, 2=Imperial | |
| MV | 5 | Time Format | Default 1=12 Hour (AM- PM); screen: Preferences (setup) | Command | 1=12 Hour (AM-PM), 2=24 Hour | |
| MV | 11 | Standby Mode Configuration | Default 1=Absolute; screen: Setpoint Configuration | Command | 1=Absolute, 2=Offset | |
| MV | 2 | Color Theme | Default 2=Dark; screen: Preferences (main) | Command | 1=Light, 2=Dark | |
| MV | 3 | Main Display | Default 1=Temp. | Command | 1=Temp., 2=Setpoint | |
| MV | 32 | Use Standby Screen | Default 1=Disabled; screen: Display | Command | 1=Disabled, 2=Custom Image | |
| MV | 92 | BO1 Auxiliary Output Configuration | Default 1=NO | Command | 1=NO, 2=NC | |
| MV | 49 | UI3 Configuration | Default 1=None; screen: Inputs | Command | 1=None, 2=CO2 | |
| MV | 96 | DO6-AO1 Configuration | Default 3=Binary RH; screen: Terminals | Command | 1=Analog, 2=Binary RC, 3=Binary RH | |
| MV | 97 | DO7-AO2 Configuration | Default 1=Analog; screen: Terminals | Command | 1=Analog, 2=Binary RC | |
| MV | 98 | DO8-AO3 Configuration | Default 1=Analog; screen: Terminals | Command | 1=Analog, 2=Binary RC | |
| MV | 99 | DO9-AO4 Configuration | Default 2=Binary RC; screen: Terminals | Command | 1=Analog, 2=Binary RC | |
| MV | 55 | Frost Protection | Default 1=Off; screen: Rooftop | Command | 1=Off, 2=On | |
| MV | 79 | Mechanical Cooling Allowed | Default 1=Off; screen: Economizer | Command | 1=Off, 2=On | |
| MV | 71 | Enable Smart Recovery | Default 1=Off; screen: Occupancy Configuration | Command | 1=Off, 2=On | |
| MV | 72 | Economizer Configuration | Default 1=Off; screen: Economizer | Command | 1=Off, 2=On | |
| MV | 101 | French | Default 2=Enabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 102 | Spanish | Default 2=Enabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 103 | Chinese | Default 2=Enabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 104 | Russian | Default 2=Enabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 12 | Fan Delay | Default 2=On; screen: Rooftop | Command | 1=Off, 2=On | |
| MV | 210 | Wireless Device 1 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 220 | Wireless Device 2 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 230 | Wireless Device 3 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 240 | Wireless Device 4 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 250 | Wireless Device 5 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 260 | Wireless Device 6 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 270 | Wireless Device 7 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 280 | Wireless Device 8 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 290 | Wireless Device 9 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 300 | Wireless Device 10 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 110 | Occupancy Source | Default 1=Motion; screen: Occupancy Configuration | Command | 1=Motion, 2=Schedule, 3=Motion during Schedule, 4=Motion or Schedule | |
| MVmin | 112 | Control Status | Default 1=Off | Command | 1=Off, 2=Cool, 3=Heat | |
| MV | 120 | Arabic | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 122 | Czech | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 123 | Danish | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 124 | Dutch | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 125 | Finnish | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 126 | German | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 127 | Hungarian | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 128 | Indonesian | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 129 | Italian | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 130 | Norwegian | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 131 | Polish | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 132 | Portuguese | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 133 | Slovak | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 134 | Swedish | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 135 | Turkish | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 116 | Comfort or economy mode | Default 1=Comfort | Command | 1=Comfort, 2=Economy | |
| MV | 117 | Reversing valve operation | Default 1=O | Command | 1=O, 2=B | |
| MV | 118 | Compressor - auxiliary interlock | Default 1=Off | Command | 1=Off, 2=On | |
| MV | 119 | Application | Default 1=Rooftop Unit; screen: HVAC Configuration | Command | 1=Rooftop Unit, 2=Heat Pump | |
| MV | 136 | Schedule Type | Default 1=7 days; screen: Occupancy Schedule | Command | 1=7 days, 2=5+2 days, 3=5+1+1 day | |
| MV | 141 | UI1 Type | Default 2=Binary | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 142 | UI2 Type | Default 2=Binary | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 143 | UI3 Type | Default 3=Voltage | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 144 | UI4 Type | Default 1=Therm. | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 145 | UI5 Type | Default 1=Therm. | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 146 | UI6 Type | Default 1=Therm. | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 147 | UI7 Type | Default 3=Voltage | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 148 | UI8 Type | Default 3=Voltage | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 152 | CO2 Autocalibration | Default 2=Enabled | Command | 1=Disabled, 2=Enabled | |
| MV | 154 | Relative humidity sensor | Default 2=Internal; screen: Inputs | Command | 1=None, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20 | |
| MV | 150 | Room Temperature Sensor | Default 1=Wired; screen: Inputs | Command | 1=Wired, 2=Internal, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20 | |
| MV | 156 | Temperature Alarm Enabled | Default 1=Off | Command | 1=Off, 2=On | |
| MV | 157 | ADR Permission | Default 1=Disabled; screen: ADR | Command | 1=Disabled, 2=Enabled | |
| MV | 159 | Japanese | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 160 | Hebrew | Default 1=Disabled; screen: Language Selection | Command | 1=Disabled, 2=Enabled | |
| MV | 310 | Wireless Device 11 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 320 | Wireless Device 12 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 330 | Wireless Device 13 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 340 | Wireless Device 14 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 350 | Wireless Device 15 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 360 | Wireless Device 16 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 370 | Wireless Device 17 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 380 | Wireless Device 18 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 390 | Wireless Device 19 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 400 | Wireless Device 20 - Function | Default 6=Remove | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 155 | CO2 source | Default 2=Local; screen: Environment | Command | 1=None, 2=Local, 3=Wireless Sensor 1, 4=Wireless Sensor 2, 5=Wireless Sensor 3, 6=Wireless Sensor 4, 7=Wireless Sensor 5, 8=Wireless Sensor 6, 9=Wireless Sensor 7, 10=Wireless Sensor 8, 11=Wireless Sensor 9, 12=Wireless Sensor 10, 13=Wireless Sensor 11, 14=Wireless Sensor 12, 15=Wireless Sensor 13, 16=Wireless Sensor 14, 17=Wireless Sensor 15, 18=Wireless Sensor 16, 19=Wireless Sensor 17, 20=Wireless Sensor 18, 21=Wireless Sensor 19, 22=Wireless Sensor 20 | |
| MV | 183 | Enable Static IP | Default 1=Dynamic | Command | 1=Dynamic, 2=Static | |
| MV | 184 | Enable WIFI | Default 1=Disabled | Command | 1=Disabled, 2=Enabled | |
| MV | 185 | Hidden WIFI | Default 1=Disabled | Command | 1=Disabled, 2=Enabled | |
| MV | 186 | Notification Type | Default 1=Disabled | Command | 1=Disabled, 2=Critical, 3=Warning, 4=Ok, 5=Informative | |
| MV | 187 | Notification Display Type | Default 3=All; screen: Display | Command | 1=Disabled, 2=Custom Only, 3=All | |
| MV | 188 | Occupancy Sensor | Default 4=High; screen: Occupancy Configuration | Command | 1=Off, 2=Low, 3=Medium, 4=High | |
| MV | 189 | Proximity Sensor | Default 4=High | Command | 1=Off, 2=Low, 3=Medium, 4=High | |
| MV | 190 | Custom Standby Text Color | Default 1=White | Command | 1=White, 2=Black | |
| MV | 192 | HMI Setpoint | Default 2=Slider; screen: Display | Command | 1=None, 2=Slider, 3=Buttons (Attached SP Only) | |
| MV | 195 | Button 1 | Default 2=System Mode; screen: Display | Command | 1=Disabled, 2=System Mode, 3=Fan Mode | |
| MV | 196 | Button 2 | Default 3=Fan Mode; screen: Display | Command | 1=Disabled, 2=System Mode, 3=Fan Mode | |
| MV | 200 | Info Item 1 | Default 3=Humidity; screen: Display | Command | 1=Disabled, 2=Outdoor Air Temperature, 3=Humidity, 4=CO2 Level | |
| MV | 201 | Info Item 2 | Default 4=CO2 Level; screen: Display | Command | 1=Disabled, 2=Outdoor Air Temperature, 3=Humidity, 4=CO2 Level | |
| MV | 202 | Info Item 3 | Default 2=Outdoor Air Temperature; screen: Display | Command | 1=Disabled, 2=Outdoor Air Temperature, 3=Humidity, 4=CO2 Level | |
| MV | 8 | BACnet Baud Rate | Default 7=Auto; screen: BACnet | Command | 1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200, 7=Auto | |
| MV | 193 | Remote Device Access | Default 1=Disabled; screen: Lua Status | Command | 1=Disabled, 2=Enabled | |
| FILE | 1 | Custom Lua File | LUA4RC script file; read/write the script | Write | ||
| Other | 1 | Lua Program 1 | Program object that runs and monitors the LUA4RC script | Write |
No points match these filters.
Object ID lookup: Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller point IDs by name
AI1UI1 Raw ValueAI2UI2 Raw ValueAI3UI3 Raw ValueAI4UI4 Raw ValueAI5UI5 Raw ValueAI6UI6 Raw ValueAI7UI7 Raw ValueAI8UI8 Raw ValueAI20Light Sensor LevelAI40Relative Humidity Raw ValueAI315Wireless Device 1 - TemperatureAI316Wireless Device 2 - TemperatureAI317Wireless Device 3 - TemperatureAI318Wireless Device 4 - TemperatureAI319Wireless Device 5 - TemperatureAI320Wireless Device 6 - TemperatureAI321Wireless Device 7 - TemperatureAI322Wireless Device 8 - TemperatureAI323Wireless Device 9 - TemperatureAI324Wireless Device 10 - TemperatureAI329Effective SetpointAI330Paired ZigBee DevicesAI32RH Temperature Raw ValueAI342Wi-Fi Network Signal StrengthAI355Wireless Device 11 - TemperatureAI356Wireless Device 12 - TemperatureAI357Wireless Device 13 - TemperatureAI358Wireless Device 14 - TemperatureAI359Wireless Device 15 - TemperatureAI360Wireless Device 16 - TemperatureAI361Wireless Device 17 - TemperatureAI362Wireless Device 18 - TemperatureAI363Wireless Device 19 - TemperatureAI364Wireless Device 20 - TemperatureAI365Wireless Device 1 - HumidityAI366Wireless Device 2 - HumidityAI367Wireless Device 3 - HumidityAI368Wireless Device 4 - HumidityAI369Wireless Device 5 - HumidityAI370Wireless Device 6 - HumidityAI371Wireless Device 7 - HumidityAI372Wireless Device 8 - HumidityAI373Wireless Device 9 - HumidityAI374Wireless Device 10 - HumidityAI375Wireless Device 11 - HumidityAI376Wireless Device 12 - HumidityAI377Wireless Device 13 - HumidityAI378Wireless Device 14 - HumidityAI379Wireless Device 15 - HumidityAI380Wireless Device 16 - HumidityAI381Wireless Device 17 - HumidityAI382Wireless Device 18 - HumidityAI383Wireless Device 19 - HumidityAI384Wireless Device 20 - HumidityAI385Wireless Device 1 - CO2AI386Wireless Device 2 - CO2AI387Wireless Device 3 - CO2AI388Wireless Device 4 - CO2AI389Wireless Device 5 - CO2AI390Wireless Device 6 - CO2AI391Wireless Device 7 - CO2AI392Wireless Device 8 - CO2AI393Wireless Device 9 - CO2AI394Wireless Device 10 - CO2AI395Wireless Device 11 - CO2AI396Wireless Device 12 - CO2AI397Wireless Device 13 - CO2AI398Wireless Device 14 - CO2AI399Wireless Device 15 - CO2AI400Wireless Device 16 - CO2AI401Wireless Device 17 - CO2AI402Wireless Device 18 - CO2AI403Wireless Device 19 - CO2AI404Wireless Device 20 - CO2AI11Thermistor 1AI12Thermistor 2AI13Thermistor 3AI14Thermistor 4AI15Thermistor 5AI16MCU TemperatureAO21PI Heating DemandAO22PI Cooling DemandAO23Economizer DemandAO24Analog Output Heat DemandAO101AO1 VoltageAO102AO2 VoltageAO103AO3 VoltageAO104AO4 VoltageAV100Room TemperatureAV101Outdoor TemperatureAV102Supply TemperatureAV103Room HumidityAV105Wired Temperature SensorAV106CO2 LevelAV107Airflow LevelAV111UI1 VoltageAV112UI2 VoltageAV113UI3 VoltageAV114UI4 VoltageAV115UI5 VoltageAV116UI6 VoltageAV117UI7 VoltageAV118UI8 VoltageAV121UI1 TemperatureAV122UI2 TemperatureAV123UI3 TemperatureAV124UI4 TemperatureAV125UI5 TemperatureAV126UI6 TemperatureAV127UI7 TemperatureAV128UI8 TemperatureAV40Occupied Cool SetpointAV39Occupied Heat SetpointAV44Unoccupied Cool SetpointAV43Unoccupied Heat SetpointAV58Maximum Heating Setpoint LimitAV59Minimum Cooling Setpoint LimitAV7Calibrate Room Temperature SensorAV42Standby Cool SetpointAV41Standby Heat SetpointAV71Dehumidification SetpointAV8Calibrate Humidity SensorAV72Dehumidification HysteresisAV10COM AddressAV63Minimum DeadbandAV84Heating CPHAV85Cooling CPHAV68Unoccupied TimeAV62Temporary Occupancy TimeAV67Standby TimeAV65Proportional BandAV89Cooling Demand LimitAV88Heating Demand LimitAV3Low BacklightAV4Night BacklightAV46Standby Temperature DifferentialAV45Default Cooling SetpointAV47Default Heating SetpointAV86Anti Short Cycle TimeAV87Number of Heating StagesAV75Number of Cooling StagesAV76Power-up DelayAV74Calibrate Outside Temperature SensorAV91Heating Lockout from Outside Air TemperatureAV93Cooling LockoutAV94Supply Air Temperature SetpointAV95Changeover SetpointAV78Economizer Minimum PositionAV81Economizer Maximum PositionAV96Fresh Air Range Upper LimitAV97Minimum Supply HeatAV98Supply Heat LockoutAV99Supply Temperature High LimitAV20Supply Temperature Low LimitAV21Minimum Fresh AirAV22Maximum Fresh AirAV23Minimum CO2AV24Maximum CO2AV25Lua Parameter A (AV25)AV26Lua Parameter B (AV26)AV27Lua Parameter C (AV27)AV28Lua Parameter D (AV28)AV29Lua Parameter E (AV29)AV30Lua Parameter F (AV30)AV82High balance pointAV83Low balance pointAV209Ambient Low Temperature ThresholdAV210Temperature Alarm HysteresisAV280ADR Setpoint Offset - Load SheddingAV31Lua Parameter G (AV31)AV32Lua Parameter H (AV32)AV33Lua Parameter I (AV33)AV34Lua Parameter J (AV34)AV35Lua Parameter K (AV35)AV36Lua Parameter L (AV36)AV275Ambient High Temperature ThresholdAV276Refrigeration High Temperature ThresholdAV277Refrigeration Low Temperature ThresholdAV278Freezer High Temperature ThresholdAV60Minimum Occupied Heating Setpoint LimitAV61Maximum Occupied Cooling Setpoint LimitAV231Inactivity TimeAV232Backlight BrightnessAV281ADR Setpoint Offset - PricingAV282Temperature compensation matrixAV16BACnet Stack Poll RateBI1UI1 BinaryBI2UI2 BinaryBI3UI3 BinaryBI4UI4 BinaryBI5UI5 BinaryBI6UI6 BinaryBI7UI7 BinaryBI8UI8 BinaryBO1DO1 Occupancy OutputBO2Y2 StatusBO3Y1 StatusBO4G Fan StatusBO5W1 StatusBO6W2-OB StatusBO7DO7 Binary OutputBO8DO8 Binary OutputBO9DO9 Binary OutputBV36Filter AlarmBV37Service AlarmBV35Window AlarmBV32PIR Local MotionBV38Dehumidification StatusBV5Low Battery AlarmBV4Window Contact InstalledBV3Window Contact StatusBV2Door Contact InstalledBV1Door Contact StatusBV39Fan Lock AlarmBV40Smart Recovery StatusBV10Exception StatusBV41CO2 AlarmBV42Low Fresh Air AlarmBV43Frost Protection AlarmBV200ZigBee PIR Sensor InstalledBV201ZigBee Sensor MotionBV8Clock AlarmBV50Wireless Sensor Communication AlarmBV44Water LeakBV45Water Leak Sensor InstalledBV46Water leak sensor statusBV47Low TemperatureBV80ADR Utility Signal - Load SheddingBV81ADR Status - Load SheddingBV82ADR Override - Load SheddingBV48High TemperatureBV60Purge StatusBV33PIR Local ProximityBV65Activity StatusBV83ADR Utility Signal - PricingBV84ADR Status - PricingBV85ADR Override - PricingCSV1Short Screen Message TextCSV2Long Screen Message TextCSV4Wi-Fi Device NameCSV5Wi-Fi Firmware VersionCSV6MAC AddressCSV7Wi-Fi Network SSIDCSV8Wi-Fi Network IP AddressCSV10Zigbee IEEE AddressCSV11Wireless Device 1 - AddressCSV12Wireless Device 2 - AddressCSV13Wireless Device 3 - AddressCSV14Wireless Device 4 - AddressCSV15Wireless Device 5 - AddressCSV16Wireless Device 6 - AddressCSV17Wireless Device 7 - AddressCSV18Wireless Device 8 - AddressCSV19Wireless Device 9 - AddressCSV20Wireless Device 10 - AddressCSV21Wireless Device 11 - AddressCSV22Wireless Device 12 - AddressCSV23Wireless Device 13 - AddressCSV24Wireless Device 14 - AddressCSV25Wireless Device 15 - AddressCSV26Wireless Device 16 - AddressCSV27Wireless Device 17 - AddressCSV28Wireless Device 18 - AddressCSV29Wireless Device 19 - AddressCSV30Wireless Device 20 - AddressCSV31Active User IdCSV32Wi-Fi Network NetmaskCSV33Wi-Fi Network GatewayCSV34Wi-Fi Network DNSCSV35LocationCSV36Install CodeCSV37WiFi STA static IP addressCSV38WiFi STA static netmask addressCSV39WiFi STA static gateway addressCSV40TimezoneCSV41Custom Standby Heading TextCSV42Custom Standby Body TextMI33Effective OccupancyMI2ZigBee Network StatusMI210Wireless Device 1 - StatusMI220Wireless Device 2 - StatusMI230Wireless Device 3 - StatusMI240Wireless Device 4 - StatusMI250Wireless Device 5 - StatusMI260Wireless Device 6 - StatusMI270Wireless Device 7 - StatusMI280Wireless Device 8 - StatusMI290Wireless Device 9 - StatusMI300Wireless Device 10 - StatusMI211Wireless Device 1 - BatteryMI221Wireless Device 2 - BatteryMI231Wireless Device 3 - BatteryMI241Wireless Device 4 - BatteryMI251Wireless Device 5 - BatteryMI261Wireless Device 6 - BatteryMI271Wireless Device 7 - BatteryMI281Wireless Device 8 - BatteryMI291Wireless Device 9 - BatteryMI301Wireless Device 10 - BatteryMI212Wireless Device 1 - Communication StatusMI222Wireless Device 2 - Communication StatusMI232Wireless Device 3 - Communication StatusMI242Wireless Device 4 - Communication StatusMI252Wireless Device 5 - Communication StatusMI262Wireless Device 6 - Communication StatusMI272Wireless Device 7 - Communication StatusMI282Wireless Device 8 - Communication StatusMI292Wireless Device 9 - Communication StatusMI302Wireless Device 10 - Communication StatusMI324CO2 Effective SourceMI309Effective temperature sensorMI313Effective relative humidity sensorMI314Effective System ModeMI315IP StatusMI316Wi-Fi Network StatusMI318SMTP Server StatusMI310Wireless Device 11 - StatusMI320Wireless Device 12 - StatusMI330Wireless Device 13 - StatusMI340Wireless Device 14 - StatusMI350Wireless Device 15 - StatusMI360Wireless Device 16 - StatusMI370Wireless Device 17 - StatusMI380Wireless Device 18 - StatusMI390Wireless Device 19 - StatusMI400Wireless Device 20 - StatusMI311Wireless Device 11 - BatteryMI321Wireless Device 12 - BatteryMI331Wireless Device 13 - BatteryMI341Wireless Device 14 - BatteryMI351Wireless Device 15 - BatteryMI361Wireless Device 16 - BatteryMI371Wireless Device 17 - BatteryMI381Wireless Device 18 - BatteryMI391Wireless Device 19 - BatteryMI401Wireless Device 20 - BatteryMI312Wireless Device 11 - Communication StatusMI322Wireless Device 12 - Communication StatusMI332Wireless Device 13 - Communication StatusMI342Wireless Device 14 - Communication StatusMI352Wireless Device 15 - Communication StatusMI362Wireless Device 16 - Communication StatusMI372Wireless Device 17 - Communication StatusMI382Wireless Device 18 - Communication StatusMI392Wireless Device 19 - Communication StatusMI402Wireless Device 20 - Communication StatusMI325Time sourceMI326Fan Speed StatusMI327Wi-Fi Network Signal StrengthMV51Temperature ScaleMV4Display LanguageMV17Fan ModeMV16System ModeMV205Default SetpointsMV46UI1 ConfigurationMV47UI2 ConfigurationMV13Dehumidification EnabledMV58Setpoint FunctionMV95Fan Control in Heating ModeMV10Occupancy CommandMV6Network UnitsMV5Time FormatMV11Standby Mode ConfigurationMV2Color ThemeMV3Main DisplayMV32Use Standby ScreenMV92BO1 Auxiliary Output ConfigurationMV49UI3 ConfigurationMV96DO6-AO1 ConfigurationMV97DO7-AO2 ConfigurationMV98DO8-AO3 ConfigurationMV99DO9-AO4 ConfigurationMV55Frost ProtectionMV79Mechanical Cooling AllowedMV71Enable Smart RecoveryMV72Economizer ConfigurationMV101FrenchMV102SpanishMV103ChineseMV104RussianMV12Fan DelayMV210Wireless Device 1 - FunctionMV220Wireless Device 2 - FunctionMV230Wireless Device 3 - FunctionMV240Wireless Device 4 - FunctionMV250Wireless Device 5 - FunctionMV260Wireless Device 6 - FunctionMV270Wireless Device 7 - FunctionMV280Wireless Device 8 - FunctionMV290Wireless Device 9 - FunctionMV300Wireless Device 10 - FunctionMV110Occupancy SourceMV112Control StatusMV120ArabicMV122CzechMV123DanishMV124DutchMV125FinnishMV126GermanMV127HungarianMV128IndonesianMV129ItalianMV130NorwegianMV131PolishMV132PortugueseMV133SlovakMV134SwedishMV135TurkishMV116Comfort or economy modeMV117Reversing valve operationMV118Compressor - auxiliary interlockMV119ApplicationMV136Schedule TypeMV141UI1 TypeMV142UI2 TypeMV143UI3 TypeMV144UI4 TypeMV145UI5 TypeMV146UI6 TypeMV147UI7 TypeMV148UI8 TypeMV152CO2 AutocalibrationMV154Relative humidity sensorMV150Room Temperature SensorMV156Temperature Alarm EnabledMV157ADR PermissionMV159JapaneseMV160HebrewMV310Wireless Device 11 - FunctionMV320Wireless Device 12 - FunctionMV330Wireless Device 13 - FunctionMV340Wireless Device 14 - FunctionMV350Wireless Device 15 - FunctionMV360Wireless Device 16 - FunctionMV370Wireless Device 17 - FunctionMV380Wireless Device 18 - FunctionMV390Wireless Device 19 - FunctionMV400Wireless Device 20 - FunctionMV155CO2 sourceMV183Enable Static IPMV184Enable WIFIMV185Hidden WIFIMV186Notification TypeMV187Notification Display TypeMV188Occupancy SensorMV189Proximity SensorMV190Custom Standby Text ColorMV192HMI SetpointMV195Button 1MV196Button 2MV200Info Item 1MV201Info Item 2MV202Info Item 3MV8BACnet Baud RateMV193Remote Device AccessFILE1Custom Lua File
Integration notes
- Access follows the guide's object-property tables: AV, AO, BV, BO and MSV present values are commandable, CSVs writable, and AI and MSI present values only writable while Out_Of_Service is TRUE.
- The guide gives no description column; descriptions here show the printed default and range (and the screen where the setting appears).
- Wireless Device 1-20 objects only report data for ZigBee sensors paired to the controller.
- The guide's tables carry a Model(s) column (All, 3500 or 6500); this entry lists the 'All' objects plus the ones marked for this model. The guide's intro mentions three models, but only 3500 and 6500 appear in the tables.
- Units follow MV 6 Network Units (SI or Imperial); the defaults are printed in °F with °C in brackets.
- BO 1-6 are the Y1, Y2, G, W1, W2-OB stage and occupancy outputs on this model; on the 3500 the same instances are the fan coil DO outputs.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
How many BACnet points does the Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump) have?
This list has 457 BACnet objects: 80 analog inputs, 8 analog outputs, 98 analog values, 8 binary inputs, 9 binary outputs, 34 binary values, 1 file, 72 multi-state inputs, 106 multi-state values, 40 characterstring values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump) BACnet points are writable?
297 of the 457 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump) BACnet documentation?
The source is SpaceLogic Touchscreen Room Controllers SXWTRCn500 BACnet Integration Guide, Firmware Revision 1.0, Version 1 (998-23139901-1), revision May 2024, published free by Schneider Electric at https://iportal.se.com/Contents/docs/998-23139901-1_TRCSE-BACNET-INTEGRATION-GUIDE_EN_CP20240508.PDF.
What are the minimum BACnet points to integrate the Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)?
Start with MV 10 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode: on / auto / smart); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 112 Control Status (Current state: off, cooling or heating); MI 326 Fan Speed Status (Fan speed status: off / low / medium / high); MI 33 Effective Occupancy (Actual occupancy state); AV 100 Room Temperature (Space temperature used for control); BV 37 Service Alarm (Service alarm from an input set to Service).
How do I enable BMS control of the Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)?
The BMS writes MV 10 Occupancy Command (1 = Loc occ., local occupancy; 2 = Occupied; 3 = Unocc.) and MV 16 System Mode. MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.
Can the BMS supply sensor values to the Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)?
The guide does not describe feeding room temperature from the BMS. MV 150 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. AI present values can only be written with Out_Of_Service set TRUE.
How do I check these points on the real SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Multi-circuit branch power meter (high density)
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Schneider Electric (ex-Veris) PowerLogic HDPM6000 head units with busway, strip or retrofit measurement modules, on BACnet IP over Ethernet.
Also known as: HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Schneider Electric PowerLogic PM5300 series power meters with the Ethernet port (PM5320, PM5340, PM5341) using BACnet IP.
Also known as: PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Zone controller (room thermostat)
Schneider Electric SE7200 Series PIR Ready Zoning Controller
Schneider Electric PIR-ready SE7200 series 24 Vac zoning controllers (SE7200C5x45B, SE7200F5x45B).
Also known as: SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Schneider Electric PIR-ready SER7300 series line-voltage fan coil controllers: SER7300, SER7305, SER7350 and SER7355 (A versions).
Also known as: SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B - Pressure-dependent VAV zone controller
Schneider Electric SEZ7260 Zoning System Zone Controller
Schneider Electric SEZ7260 zone controllers (F model with floating damper and AO2, C model) used with SEZ7656 rooftop controllers in pressure-dependent zoning systems.
Also known as: SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B - Rooftop unit controller for zoning systems
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Schneider Electric SEZ7656 rooftop controllers (R conventional, H heat pump, F modulating heat, E economizer) that run a rooftop unit for a group of SEZ7260 zone controllers.
Also known as: SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Schneider Electric SpaceLogic SE8000-series SER8350 room controllers for line-voltage fan coil units.
Also known as: SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350 - Room humidity and temperature sensor (wall)
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Schneider Electric SpaceLogic SLP Series wall humidity/temperature sensors (with or without touchscreen) set to BACnet MS/TP.
Also known as: SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil
Source: SpaceLogic Touchscreen Room Controllers SXWTRCn500 BACnet Integration Guide, Firmware Revision 1.0, Version 1 · 998-23139901-1 · rev. May 2024. Object names, instances and units are reproduced as published; descriptions are our own.