Rooftop unit controller for zoning systems · BACnet points list
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller BACnet points list
Updated 7 November 2026
The SEZ7656 is the rooftop unit controller of the Schneider Electric SEZ7000 zoning system. It reads PI demands from its SEZ7260 zones over the shared BACnet MS/TP network and stages the rooftop unit, with bypass damper or VFD static pressure control and, on some models, economizer and CO2 functions. No BMS bindings are needed for the system to run.
This page lists 95 BACnet objects for the Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller — 51 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- SEZ7656 Zoning System Rooftop Unit Controller
- Equipment
- Rooftop unit controller for zoning systems
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 95 (51 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 76000 + MAC address (e.g. 76063 at MAC 63)
- Also known as
- SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Command occupancy with MV 14 and system mode with MV 15 (MV 17 on heat pump models). Read discharge and return air temperatures (AI 1, AI 2), the highest zone demands AV 17 / AV 18, fan status BI 1 and the bypass damper or VFD output AI 4. The BMS can supply outdoor temperature on AV 19.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 14 | GUI Occupancy | BMS occupancy command | Write |
| MV 15 | GUI System Mode | System mode: off / auto (non heat pump models) | Write |
| MV 17 | GUI System Mode HP | Off / auto / cool / heat / emergency heat | Write |
| BI 1 | GUI G Fan | Supply fan (G) output on / off | Read |
| AI 1 | GUI Discharge Air Temp | Discharge air temperature | Read |
| AI 2 | GUI Return Air Temp | Return air temperature | Read |
| AV 17 | GUI Highest PI Heat Demand | Highest zone PI heating demand | Read |
| AV 18 | GUI Highest PI Cool Demand | Highest zone PI cooling demand | Read |
| AI 4 | GUI By-Pass Damper / VFD | Bypass damper / VFD output | Read |
| BV 3 | Sta Comm Lost Status | Communication status: Down / Up | Read |
Sensors & values from the BMS
The BMS can write outdoor temperature (AV 19); BV 6 Outdoor Temp Override selects it.
Network setup
- Default device instance 76000 + MAC; default device name is the model number plus MAC. Both are writable.
- Baud rate auto-detects at power-up; after a network speed change the device keeps the old speed for 2.5 minutes unless re-powered.
- Each SEZ7260 zone points to its SEZ7656 by the RTC MAC address.
Watch out for
- If the controller goes offline, values the BMS wrote to room temperature, outdoor temperature and occupancy are released.
- Schneider recommends removing configuration (Cfg) objects from the BAS after setup to cut polling.
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | GUI Discharge Air Temp | Range -40°F (-40°C) to 150°F (65°C) | °F | Read | |
| AI | 5 | GUI Analog Heat Output | only SEZ7656F1045B | Read | ||
| AImin | 4 | GUI By-Pass Damper / VFD | Range 0% to 100% | % | Read | |
| AImin | 2 | GUI Return Air Temp | Range -40°F (-40°C) to 122°F (50°C) | °F | Read | |
| AI | 3 | GUI Static Pressure | Duct static pressure, 0 to 5 in. WC (0-1250 Pa) | in. WC | Read | |
| AV | 1 | Cfg RTC MAC | Range 1 to 255, default 4 | Read | ||
| AV | 21 | Cfg Device Instance | Range 76000 to 76255 | Read | ||
| AVmin | 18 | GUI Highest PI Cool Demand | Range 0% to 100% | % | Read | |
| AVmin | 17 | GUI Highest PI Heat Demand | Range 0% to 100% | % | Read | |
| AV | 40 | GUI CO2 Level | Range 0 PPM to 2000 PPM; only SEZ7656E1045B | ppm | Read | |
| AV | 12 | GUI Current Zone PI Cool Demand | Range 0% to 100% | % | Read | |
| AV | 11 | GUI Current Zone PI Heat Demand | Range 0% to 100% | % | Read | |
| AV | 42 | GUI Economizer Output | Range 0% to 100%; only SEZ7656E1045B | % | Read | |
| AV | 39 | GUI Fresh Air Level | Range 0 CFM (0 l/s) to 20000 CFM (9440 l/s); only SEZ7656E1045B | CFM | Read | |
| AV | 41 | GUI Highest CO2 Zone | Range 1 to 127; only SEZ7656E1045B | Read | ||
| AV | 16 | GUI Highest PI Cool Zone | Range 0 to 255 | Read | ||
| AV | 15 | GUI Highest PI Heat Zone | Range 0 to 255 | Read | ||
| AV | 28 | GUI Supply PI Heat Demand | Range 0% to 100%; only SEZ7656F1045B | % | Read | |
| AV | 14 | GUI Transferred PI Cool Demand | Range 0% to 100% | % | Read | |
| AV | 13 | GUI Transferred PI Heat Demand | Range 0% to 100% | % | Read | |
| AV | 30 | Cfg Changeover Setpoint | Range 14°F to 70°F, default 55°F (13°C); only SEZ7656E1045B | °F | Write | |
| AV | 3 | Cfg Cooling Lockout Temp | Range -40°F (-40°C) to 95°F (35°C), default -40°F (-40°C) | °F | Write | |
| AV | 22 | Cfg Deadband | Range 2°F (1°C) to 4°F (2°C), default 2°F (1°C) | °F | Write | |
| AV | 5 | Cfg Discharge High Limit Spt | Range 70°F (21°C) to 150°F (65°C), default 120°F (49°C) | °F | Write | |
| AV | 6 | Cfg Discharge Low Limit Spt | Range 35°F (2°C) to 65°F (19°C), default 45°F (7°C) | °F | Write | |
| AV | 33 | Cfg Economizer Max Position | Range 0% to 100%, default 100%; only SEZ7656E1045B | % | Write | |
| AV | 32 | Cfg Economizer Min Position | Range 0% to 100%, default 0%; only SEZ7656E1045B | % | Write | |
| AV | 34 | Cfg Fresh Air Max Range | Fresh air sensor full-scale range, 0 to 20000 CFM, default 0; only SEZ7656E1045B | CFM | Write | |
| AV | 2 | Cfg Heating Lockout Temp | Range -15°F (-26°C) to 120°F (49°C), default 120°F (49°C) | °F | Write | |
| AV | 24 | Cfg High Balance Point | Range 34°F(1°C) to 90°F(32°C), default 90°F(32°C); only SEZ7656H1045B | °F | Write | |
| AV | 25 | Cfg Low Balance Point | Heat pump low balance point, default -40°F; only SEZ7656H1045B | °F | Write | |
| AV | 38 | Cfg Maximum CO2 Level | Range 0 PPM to 2000 PPM, default 1200 PPM; only SEZ7656E1045B | ppm | Write | |
| AV | 36 | Cfg Maximum Fresh Air | Maximum fresh air flow, 0 to 20000 CFM, default 0; only SEZ7656E1045B | CFM | Write | |
| AV | 37 | Cfg Minimum CO2 Level | Range 0 PPM to 2000 PPM, default 800 PPM; only SEZ7656E1045B | ppm | Write | |
| AV | 35 | Cfg Minimum Fresh Air | Minimum fresh air flow, 0 to 20000 CFM, default 0; only SEZ7656E1045B | CFM | Write | |
| AV | 26 | Cfg Minimum Supply Heat Setpoint | Range 50°F(1°C) to 72°F(32°C), default 64°F(18°C); only SEZ7656F1045B | °F | Write | |
| AV | 31 | Cfg Mixed Air Setpoint | Range 50°F(10°C) to 90°F(32°C), default 55°F(13°C); only SEZ7656E1045B | °F | Write | |
| AV | 23 | Cfg Password | Range 0 to 1000 | Write | ||
| AV | 20 | Cfg Power-up Delay | Range 10 Seconds to 120 Seconds, default 30 Seconds | Write | ||
| AV | 7 | Cfg Return Air Occ CL Spt | Range 54°F (12°C) to 100°F (37.5°C), default 74°F (24°C) | °F | Write | |
| AV | 9 | Cfg Return Air Occ HT Spt | Range 40°F (4.5°C) to 90°F (32°C), default 72°F (22°C) | °F | Write | |
| AV | 8 | Cfg Return Air Unocc CL Spt | Range 54°F (12°C) to 100°F (37.5°C), default 74°F (24°C) | °F | Write | |
| AV | 10 | Cfg Return Air Unocc HT Spt | Range 40°F (4.5°C) to 90°F (32°C), default 72°F (22°C) | °F | Write | |
| AV | 4 | Cfg Static Pressure Spt | Static pressure setpoint, 0 to 2 in. WC, default 0.8 in. WC | in. WC | Write | |
| AV | 27 | Cfg Supply Heat Lockout Temperature | Range -15°F(-26°C) to 120°F(49°C), default 32°F(0°C); only SEZ7656F1045B | °F | Write | |
| AV | 19 | GUI Outdoor Temperature | Range -40°F (-40°C) to 122°F (50°C) | °F | Write | |
| BI | 7 | GUI AUX Status | only SEZ7656R1045B/SEZ7656H1045B/SEZ7656F1045B | Read | 0=Off, 1=On | |
| BI | 6 | GUI BI Status | only SEZ7656R1045B/SEZ7656H1045B/SEZ7656F1045B | Read | 0=Not Activated, 1=Activated | |
| BImin | 1 | GUI G Fan | Read | 0=Off, 1=On | ||
| BI | 4 | GUI W1 Heat | only SEZ7656R1045B/SEZ7656H1045B/SEZ7656E1045B | Read | 0=Off, 1=On | |
| BI | 5 | GUI W2 Heat | only SEZ7656R1045B/SEZ7656E1045B | Read | 0=Off, 1=On | |
| BI | 16 | GUI Y1 Compressor | only SEZ7656H1045B | Read | 0=Off, 1=On | |
| BI | 2 | GUI Y1 Cool | only SEZ7656R1045B/SEZ7656F1045B/SEZ7656E1045B | Read | 0=Off, 1=On | |
| BI | 15 | GUI Y2 Compressor | only SEZ7656H1045B | Read | 0=Off, 1=On | |
| BI | 3 | GUI Y2 Cool | only SEZ7656R1045B/SEZ7656F1045B/SEZ7656E1045B | Read | 0=Off, 1=On | |
| BI | 12 | Sta Clock Alarm | Read | 0=Off, 1=On | ||
| BI | 9 | Sta Cooling Lockout Status | Read | 0=Not Activated, 1=Activated | ||
| BI | 13 | Sta Discharge Temp Alarm | Read | 0=Off, 1=On | ||
| BI | 11 | Sta Filter Alarm | Read | 0=Off, 1=On | ||
| BI | 17 | Sta Fresh Air Alarm | only SEZ7656E1045B | Read | 0=Off, 1=On | |
| BI | 8 | Sta Heating Lockout Status | Read | 0=Not Activated, 1=Activated | ||
| BI | 18 | Sta High CO2 Alarm | only SEZ7656E1045B | Read | 0=Off, 1=On | |
| BI | 14 | Sta Reversing Valve Status | only SEZ7656H1045B | Read | 0=Off, 1=On | |
| BI | 10 | Sta Service Alarm | Read | 0=Off, 1=On | ||
| BV | 7 | GUI Smart Recovery | Read | 0=Off, 1=Active | ||
| BVmin | 3 | Sta Comm Lost Status | Read | 0=Down, 1=Up | ||
| BV | 12 | Sta Supply Heat Lockout Status | only SEZ7656F1045B | Read | 0=Inactive, 1=Active | |
| BV | 4 | Cfg Aux Contact | only SEZ7656R1045B/SEZ7656H1045B/SEZ7656F1045B | Write | 0=N.O., 1=N.C. | |
| BV | 11 | Cfg Compressor Interlock | only SEZ7656H1045B | Write | 0=Off, 1=On | |
| BV | 9 | Cfg Emergency Heat Mode | only SEZ7656H1045B | Write | 0=Off, 1=On | |
| BV | 5 | Cfg Fan Purge Delay | Write | 0=Off, 1=On | ||
| BV | 2 | Cfg Progressive Recovery | Write | 0=Off, 1=Active | ||
| BV | 10 | Cfg Reversing Valve | only SEZ7656H1045B | Write | 0=Normally Cool, 1=Normally Heat | |
| BV | 8 | Cfg Static Pressure Ctrl Type | Write | 0=By-Pass Damper, 1=VFD | ||
| BV | 1 | Cfg Units | Write | 0=°C / SI Units, 1=°F / Imperial Units | ||
| BV | 6 | GUI Outdoor Temp Override | Write | 0=Normal, 1=Override | ||
| MV | 1 | Cfg RTC Baud | Read | 1=9600 ( Bps ), 2=19200 ( Bps ), 3=38400 ( Bps ), 4=76800 ( Bps ), 5=Auto | ||
| MV | 4 | GUI Zone Sequence | Read | 1=Off / Never used, 2=Cool, 3=Heat | ||
| MV | 11 | Cfg BI1 Configuration | only SEZ7656R1045B/SEZ7656H1045B/SEZ7656F1045B | Write | 1=None, 2=RemNSB, 3=RemOVR, 4=Filter, 5=Service | |
| MV | 18 | Cfg CO2 Control Type | only SEZ7656E1045B | Write | 1=Highest, 2=AV H3, 3=AV H5 | |
| MV | 2 | Cfg Control Type | Write | 1=Highest, 2=AV H3 /Average of Highest 3 Zones, 3=AV H5 /Average of Highest 5 Zones | ||
| MV | 9 | Cfg Cooling CPH | Write | 1=3 CPH, 2=4 CPH | ||
| MV | 7 | Cfg Cooling Stages | only SEZ7656R1045B/SEZ7656F1045B/SEZ7656E1045B | Write | 1=1 Stage, 2=2 Stages | |
| MV | 13 | Cfg Event Display | Write | 1=2 Events, 2=4 Events | ||
| MV | 16 | Cfg Heat Pump Stages | only SEZ7656H1045B | Write | 1=1 Stage, 2=2 Stages | |
| MV | 8 | Cfg Heating CPH | only SEZ7656R1045B/SEZ7656H1045B/SEZ7656E1045B | Write | 1=3 CPH, 2=4 CPH, 3=5 CPH, 4=6 CPH, 5=7 CPH, 6=8 CPH | |
| MV | 6 | Cfg Heating Stages | only SEZ7656R1045B/SEZ7656E1045B | Write | 1=1 Stage, 2=2 Stages | |
| MV | 3 | Cfg Local Keypad Lockout | Write | 1=Level 0 / No Lockout, 2=Level 1, 3=Level 2 | ||
| MV | 10 | Cfg Minimum On/Off Time | Write | 1=0 minute, 2=1 minute, 3=2 minutes, 4=3 minutes, 5=4 minutes, 6=5 minutes | ||
| MV | 5 | Cfg Static Pressure Transducer Range | Write | 1=0 to 1.5“ of WC, 2=0 to 2.0“ of WC, 3=0 to 3.0“ of WC, 4=0 to 4.0“ of WC, 5=0 to 5.0“ of WC | ||
| MV | 12 | Cfg Temporary Occupied Time | Write | 1=0 hour, 2=1 hour, 3=2 hours, 4=3 hours, 5=4 hours, 6=5 hours, 7=6 hours, 8=7 hours, 9=8 hours, 10=9 hours, 11=10 hours, 12=11 hours, 13=12 hours | ||
| MVmin | 15 | GUI System Mode | only SEZ7656R1045B/SEZ7656F1045B/SEZ7656E1045B | Write | 1=Off, 2=Auto | |
| MVmin | 17 | GUI System Mode HP | only SEZ7656H1045B | Write | 1=Off, 2=Auto, 3=Cool, 4=Heat, 5=Emergency Heat | |
| MVmin | 14 | GUI Occupancy | Write | 1=Local Occupancy, 2=Occupied, 3=Unoccupied | ||
| SCH | 1 | GUI Schedule | Read |
No points match these filters.
Object ID lookup: Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller point IDs by name
AI1GUI Discharge Air TempAI5GUI Analog Heat OutputAI4GUI By-Pass Damper / VFDAI2GUI Return Air TempAI3GUI Static PressureAV1Cfg RTC MACAV21Cfg Device InstanceAV18GUI Highest PI Cool DemandAV17GUI Highest PI Heat DemandAV40GUI CO2 LevelAV12GUI Current Zone PI Cool DemandAV11GUI Current Zone PI Heat DemandAV42GUI Economizer OutputAV39GUI Fresh Air LevelAV41GUI Highest CO2 ZoneAV16GUI Highest PI Cool ZoneAV15GUI Highest PI Heat ZoneAV28GUI Supply PI Heat DemandAV14GUI Transferred PI Cool DemandAV13GUI Transferred PI Heat DemandAV30Cfg Changeover SetpointAV3Cfg Cooling Lockout TempAV22Cfg DeadbandAV5Cfg Discharge High Limit SptAV6Cfg Discharge Low Limit SptAV33Cfg Economizer Max PositionAV32Cfg Economizer Min PositionAV34Cfg Fresh Air Max RangeAV2Cfg Heating Lockout TempAV24Cfg High Balance PointAV25Cfg Low Balance PointAV38Cfg Maximum CO2 LevelAV36Cfg Maximum Fresh AirAV37Cfg Minimum CO2 LevelAV35Cfg Minimum Fresh AirAV26Cfg Minimum Supply Heat SetpointAV31Cfg Mixed Air SetpointAV23Cfg PasswordAV20Cfg Power-up DelayAV7Cfg Return Air Occ CL SptAV9Cfg Return Air Occ HT SptAV8Cfg Return Air Unocc CL SptAV10Cfg Return Air Unocc HT SptAV4Cfg Static Pressure SptAV27Cfg Supply Heat Lockout TemperatureAV19GUI Outdoor TemperatureBI7GUI AUX StatusBI6GUI BI StatusBI1GUI G FanBI4GUI W1 HeatBI5GUI W2 HeatBI16GUI Y1 CompressorBI2GUI Y1 CoolBI15GUI Y2 CompressorBI3GUI Y2 CoolBI12Sta Clock AlarmBI9Sta Cooling Lockout StatusBI13Sta Discharge Temp AlarmBI11Sta Filter AlarmBI17Sta Fresh Air AlarmBI8Sta Heating Lockout StatusBI18Sta High CO2 AlarmBI14Sta Reversing Valve StatusBI10Sta Service AlarmBV7GUI Smart RecoveryBV3Sta Comm Lost StatusBV12Sta Supply Heat Lockout StatusBV4Cfg Aux ContactBV11Cfg Compressor InterlockBV9Cfg Emergency Heat ModeBV5Cfg Fan Purge DelayBV2Cfg Progressive RecoveryBV10Cfg Reversing ValveBV8Cfg Static Pressure Ctrl TypeBV1Cfg UnitsBV6GUI Outdoor Temp OverrideMV1Cfg RTC BaudMV4GUI Zone SequenceMV11Cfg BI1 ConfigurationMV18Cfg CO2 Control TypeMV2Cfg Control TypeMV9Cfg Cooling CPHMV7Cfg Cooling StagesMV13Cfg Event DisplayMV16Cfg Heat Pump StagesMV8Cfg Heating CPHMV6Cfg Heating StagesMV3Cfg Local Keypad LockoutMV10Cfg Minimum On/Off TimeMV5Cfg Static Pressure Transducer RangeMV12Cfg Temporary Occupied TimeMV15GUI System ModeMV17GUI System Mode HPMV14GUI OccupancySCH1GUI Schedule
Integration notes
- The guide marks each object for the R, H, F and E models; objects on only some models say so in the description.
- Ranges and state texts come from the guide's SEZ7656 range and enumeration tables (matched by type and instance).
- Access is from the guide's R / R/W column (R/W shown as W); the guide does not mention a priority array.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SEZ7656 Zoning System Rooftop Unit Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
How many BACnet points does the Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller have?
This list has 95 BACnet objects: 5 analog inputs, 41 analog values, 18 binary inputs, 12 binary values, 1 schedule, 18 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller BACnet points are writable?
51 of the 95 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller BACnet documentation?
The source is BACnet Integration Manual - Zoning Product Series SEZ7260 & SEZ7656 Series (IG-SE7000-BNETSEZ7XXX-US.EN.4.2013.v1), revision 2013-04, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=IG-SE7000-BNETSEZ7XXX-A4.
What are the minimum BACnet points to integrate the Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller?
Start with MV 14 GUI Occupancy (BMS occupancy command); MV 15 GUI System Mode (System mode: off / auto (non heat pump models)); MV 17 GUI System Mode HP (Off / auto / cool / heat / emergency heat); BI 1 GUI G Fan (Supply fan (G) output on / off); AI 1 GUI Discharge Air Temp (Discharge air temperature); AI 2 GUI Return Air Temp (Return air temperature); AV 17 GUI Highest PI Heat Demand (Highest zone PI heating demand); AV 18 GUI Highest PI Cool Demand (Highest zone PI cooling demand); AI 4 GUI By-Pass Damper / VFD (Bypass damper / VFD output); BV 3 Sta Comm Lost Status (Communication status: Down / Up).
Can the BMS supply sensor values to the Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller?
The BMS can write outdoor temperature (AV 19); BV 6 Outdoor Temp Override selects it.
How do I check these points on the real SEZ7656 Zoning System Rooftop Unit Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Multi-circuit branch power meter (high density)
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Schneider Electric (ex-Veris) PowerLogic HDPM6000 head units with busway, strip or retrofit measurement modules, on BACnet IP over Ethernet.
Also known as: HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Schneider Electric PowerLogic PM5300 series power meters with the Ethernet port (PM5320, PM5340, PM5341) using BACnet IP.
Also known as: PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Zone controller (room thermostat)
Schneider Electric SE7200 Series PIR Ready Zoning Controller
Schneider Electric PIR-ready SE7200 series 24 Vac zoning controllers (SE7200C5x45B, SE7200F5x45B).
Also known as: SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Schneider Electric PIR-ready SER7300 series line-voltage fan coil controllers: SER7300, SER7305, SER7350 and SER7355 (A versions).
Also known as: SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B - Pressure-dependent VAV zone controller
Schneider Electric SEZ7260 Zoning System Zone Controller
Schneider Electric SEZ7260 zone controllers (F model with floating damper and AO2, C model) used with SEZ7656 rooftop controllers in pressure-dependent zoning systems.
Also known as: SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Schneider Electric SpaceLogic SE8000-series SER8350 room controllers for line-voltage fan coil units.
Also known as: SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350 - Room humidity and temperature sensor (wall)
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Schneider Electric SpaceLogic SLP Series wall humidity/temperature sensors (with or without touchscreen) set to BACnet MS/TP.
Also known as: SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil - Rooftop unit controller (room thermostat, rooftop or heat-pump units)
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 6500 (rooftop unit / heat pump) version.
Also known as: SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump
Source: BACnet Integration Manual - Zoning Product Series SEZ7260 & SEZ7656 Series · IG-SE7000-BNETSEZ7XXX-US.EN.4.2013.v1 · rev. 2013-04. Object names, instances and units are reproduced as published; descriptions are our own.