Variable frequency drive (HVAC) · BACnet points list

Schneider Electric Altivar 212 (embedded BACnet MS/TP) BACnet points list

Updated 28 October 2026

Short answer

The Altivar 212 has BACnet MS/TP built in; F829 = 4 selects it on the open-style RS-485 terminals. The fixed list of 48 objects covers relay and logic input status, run/stop, direction and fault reset commands, a % speed reference, three preset speeds, motor monitors, the last three fault codes and a mailbox (MBOX) for reading or writing any drive parameter. BV21/BV22 give BACnet priority over the local reference and command sources.

This page lists 48 BACnet objects for the Schneider Electric Altivar 212 (embedded BACnet MS/TP) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.

Manufacturer
Schneider Electric
Model
Altivar 212 (embedded BACnet MS/TP)
Equipment
Variable frequency drive (HVAC)
Equipment type
VFDs & pumps
BACnet objects
48 (20 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
0
Also known as
ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845
Source document
Altivar 212 BACnet Communication Manual · S1A53845 (04) · rev. 2020-07
Download CSV 48 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Schneider Electric Altivar 212 (embedded BACnet MS/TP)

Integration in brief

Set F829 = 4 (BACnet), F807 = 1 (open style), the MAC address in F890 and the device instance in F893/F894, then power-cycle. Set CMOd = 2 and FMOd = 4 so BACnet supplies commands and the speed reference, or leave them on terminals and use BV22 CMDSEL / BV21 STPSEL to give BACnet priority. Write BV10 RUN/STOP CMD and AV16 INPUT REF 1 and pick the comm-loss action in F851.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10RUN/STOP CMDStart/stop from the BMSCommand
AV 16INPUT REF 1Speed reference in %Command
BV 14FAULT RESETReset a tripped driveCommand
BV 0RUN/STOP ACTRunning statusRead
BV 4HAND/AUTO ACTShows if the drive is in HandRead
AV 1OUTPUT FREQOutput frequency in HzRead
AV 4CURRENTMotor ampsRead
AV 6POWERMotor power in %Read
BV 2FAULT ACTAny active drive faultRead
AV 18LAST FLTWhich fault is activeRead

Enable & remote start

Full BACnet control: CMOd Command mode sel = 2 (Communication) and FMOd Frequency mode sel = 4 (Serial com ref); F207 = 4 does the same for the second reference. Alternatively keep terminal control and turn on BV22 CMDSEL (command priority) and BV21 STPSEL (setpoint priority) to hand commands and the reference to BACnet. The LOC/REM key and logic inputs set to Forced local (48) or Frequency source (38) can take control back locally.

Heartbeat & communication loss

F892 Network time out (20-600 = 2-60 s, default 100 = 10 s) is the trip time once communication has been established. F851 Com. fault setting picks the reaction: 0 ramp to stop and hand control back to CMOd/FMOd, 1 no action (last command continues), 2 ramp stop keeping serial control, 3 freewheel, 4 ramp stop with Err8 Network error fault (default).

Sensors & values from the BMS

The object list has no writable process value; AV10 PRC PID FBCK is read-only. BV23 DAMPER FB lets the BMS supply the damper-open feedback when F580 = 3 or 4.

Network setup

Watch out for

Schneider Electric Altivar 212 (embedded BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

48 of 48 shown
Type
Access
Show
Schneider Electric Altivar 212 (embedded BACnet MS/TP) BACnet Points List
DescriptionStates
BI0RO 1 ACTStatus of relay FLRead
BI1RO 2 ACTStatus of relay RYRead
BI6DI 1 ACTValue of FRead
BI7DI 2 ACTValue of RRead
BI8DI 3 ACTValue of RESRead
BO0RO1 CMDFL relay out accessible if not assigned; F132 =38 or 39Command
BO1RO2 CMDRY relay out accessible if not assigned; F130 =40 or 41Command
AI0ANALOG INPUT 1VIA analogue; 0-100% (100%=1023)%Read
AI1ANALOG INPUT 2VIB analogue; 0-100% (100%=1023)%Read
AI2ANALOG OUTPUT 1 ACTFM actual value; 0-100% (100%=1023) [FMSL=18]%Read
AO0ANALOG OUTPUT 1Analogue output; 0-100% (100%=1023) [FMSL=18]%Command
BVmin0RUN/STOP ACTIndicates the drive statusRead
BV1FWD/REV ACTIndicates the motor rotation's directionRead
BVmin2FAULT ACTIndicates the drive's fault statusRead
BVmin4HAND/AUTO ACTIndicates if the drive is locally controlled or notRead
BV6MAINT REQMaintenance requiredRead
BV7DRIVE READYThe VSD is ready and waits a start commandRead
BV8AT SETPOINTThe VSD has reached the target speedRead
BVmin10RUN/STOP CMDCommands a drive startCommand
BV11FWD/REV CMDCommands a motor direction's changeCommand
BVmin14FAULT RESETClear the detected fault by resetting the driveCommand
BV15MBOX READCommand to read parameterWrite
BV16MBOX WRITECommand to write parameterWrite
BV18SP1PRESETPreset speed operation frequencies 1Command
BV19SP2PRESETPreset speed operation frequencies 2Command
BV20SP3PRESETPreset speed operation frequencies 3Command
BV21STPSELGives the BACnet speed reference priority (ON)Command
BV22CMDSELGives BACnet commands priority (ON)Command
BV23DAMPER FBDamper open feedback written over BACnetWrite
AV0OUTPUT SPEEDOutput speedrpmRead
AVmin1OUTPUT FREQOutput frequencyHzRead
AV2DC BUS VOLTDC bus voltageVRead
AV3OUTPUT VOLTMotor voltageVRead
AVmin4CURRENTMotor currentARead
AV5TORQUEMotor Torque%Read
AVmin6POWERMotor power, % of nominal%Read
AV7DRIVE TEMPDrive Thermal State%Read
AV8KWH (R)Energy counter; writing a value resets itkWhWrite
AV10PRC PID FBCKPID regulator feedback%Read
AV14RUN TIMEOperating timehRead
AVmin16INPUT REF 1Speed reference from BACnet, %%Command
AVmin18LAST FLTError codeRead
AV19PREV FLT 1Previous detected fault (occurred before LASTFLT)Read
AV20PREV FLT 2Previous detected fault (occurred before PREVFLT1)Read
AV23ACCEL1 TIMEAcceleration timesWrite
AV24DECEL1 TIMEDeceleration timesWrite
AV25MBOX PARAMParameter numberWrite
AV26MBOX DATAParameter valueWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Altivar 212 (embedded BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Schneider Electric Altivar 212 (embedded BACnet MS/TP)

How many BACnet points does the Schneider Electric Altivar 212 (embedded BACnet MS/TP) have?

This list has 48 BACnet objects: 3 analog inputs, 1 analog output, 19 analog values, 5 binary inputs, 2 binary outputs, 18 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Schneider Electric Altivar 212 (embedded BACnet MS/TP) BACnet points are writable?

20 of the 48 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Schneider Electric Altivar 212 (embedded BACnet MS/TP) BACnet documentation?

The source is Altivar 212 BACnet Communication Manual (S1A53845 (04)), revision 2020-07, published free by Schneider Electric at https://download.schneider-electric.com/files?p_Doc_Ref=S1A53845&p_enDocType=User+guide&p_File_Name=ATV212_BACnet_manual_EN_S1A53845_04.pdf.

What are the minimum BACnet points to integrate the Schneider Electric Altivar 212 (embedded BACnet MS/TP)?

Start with BV 10 RUN/STOP CMD (Start/stop from the BMS); AV 16 INPUT REF 1 (Speed reference in %); BV 14 FAULT RESET (Reset a tripped drive); BV 0 RUN/STOP ACT (Running status); BV 4 HAND/AUTO ACT (Shows if the drive is in Hand); AV 1 OUTPUT FREQ (Output frequency in Hz); AV 4 CURRENT (Motor amps); AV 6 POWER (Motor power in %); BV 2 FAULT ACT (Any active drive fault); AV 18 LAST FLT (Which fault is active).

How do I enable BMS control of the Schneider Electric Altivar 212 (embedded BACnet MS/TP)?

Full BACnet control: CMOd Command mode sel = 2 (Communication) and FMOd Frequency mode sel = 4 (Serial com ref); F207 = 4 does the same for the second reference. Alternatively keep terminal control and turn on BV22 CMDSEL (command priority) and BV21 STPSEL (setpoint priority) to hand commands and the reference to BACnet. The LOC/REM key and logic inputs set to Forced local (48) or Frequency source (38) can take control back locally.

Does the Schneider Electric Altivar 212 (embedded BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

F892 Network time out (20-600 = 2-60 s, default 100 = 10 s) is the trip time once communication has been established. F851 Com. fault setting picks the reaction: 0 ramp to stop and hand control back to CMOd/FMOd, 1 no action (last command continues), 2 ramp stop keeping serial control, 3 freewheel, 4 ramp stop with Err8 Network error fault (default).

Can the BMS supply sensor values to the Schneider Electric Altivar 212 (embedded BACnet MS/TP)?

The object list has no writable process value; AV10 PRC PID FBCK is read-only. BV23 DAMPER FB lets the BMS supply the damper-open feedback when F580 = 3 or 4.

How do I check these points on the real Altivar 212 (embedded BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Schneider Electric BACnet points lists

Source: Altivar 212 BACnet Communication Manual · S1A53845 (04) · rev. 2020-07. Object names, instances and units are reproduced as published; descriptions are our own.