- Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Power and energy meter (BACnet MS/TP) · BACnet points list
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP) BACnet points list
Updated 28 October 2026
The BACnet versions of the iEM3000 DIN-rail meters (iEM3165 63 A direct, iEM3265 CT-connected, iEM3365 125 A direct) are BACnet MS/TP B-ASC devices. They serve Analog Inputs for current, voltage, power, power factor, frequency, total, partial, per-phase and per-tariff energy, plus meter and I/O configuration readbacks; one Analog Value for commands; and seven Binary Inputs for I/O and the overload alarm. The iEM3165 and iEM3365 stop at AI 48; AI 49-55 (VT/CT settings) are iEM3265 only.
This page lists 64 BACnet objects for the Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
- Equipment
- Power and energy meter (BACnet MS/TP)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 64 (1 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN
BMS integration notes: Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
At the front panel set the MS/TP baud rate, MAC address and device ID, then read the energy import total (AI 27), total active power (AI 22), current, voltage and power factor. Read BI 05 if the overload alarm is used. Write AV00 only to reset partial counters or acknowledge alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 27 | AI27 - Total active energy import | Imported active energy, Wh | Read |
| AI 22 | AI22 - Active Power Total | Total active power, kW | Read |
| AI 25 | AI25 - Power Factor Total | Total power factor | Read |
| AI 10 | AI10 - Current Average | Average phase current, A | Read |
| AI 18 | AI18 - Voltage Average L-N | Average line-to-neutral voltage | Read |
| AI 26 | AI26 - Frequency | Supply frequency | Read |
| BI 5 | BI05 - Alarm Status | Overload alarm active | Read |
Network setup
- Set baud (9600, 19200, 38400, 57600 or 76800), MAC address (1-127) and device ID (0-4194303) at the front panel.
- The device ID can only be set at the front panel; Object_Name, Description and Location are writable over BACnet.
- Max_Master and Max_Info_Frames are writable; APDU timeout 1000-30000 ms.
- No segmentation; max APDU 480 bytes.
Watch out for
- Energy is reported in Wh, not kWh.
- AI 49-55 exist only on the CT-connected iEM3265.
- The comms LED flashes even when there is a communication error.
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | AI00 - BACnet MAC Address | MS/TP MAC address (set at the front panel) | Read | ||
| AI | 1 | AI01 - BACnet Baud Rate | MS/TP baud rate (set at the front panel) | Read | ||
| AI | 2 | AI02 - Pulse Duration | Energy pulse width of the digital output | ms | Read | |
| AI | 3 | AI03 - Pulse Weight | Pulses per unit, digital input in input-metering mode | Read | ||
| AI | 4 | AI04 - Pulse Constant | Pulses per kWh of the digital output | Read | ||
| AI | 5 | AI05 - Digital Input Mode | Digital input function | Read | 0=Normal (input status), 2=Multi Tariff control, 3=Input metering, 5=All partial energy logs reset | |
| AI | 6 | AI06 - Digital Output Mode | Digital output function | Read | 2=Alarm, 3=Energy, 65535=Disabled | |
| AI | 7 | AI07 - Current Phase 1 | A | Read | ||
| AI | 8 | AI08 - Current Phase 2 | A | Read | ||
| AI | 9 | AI09 - Current Phase 3 | A | Read | ||
| AImin | 10 | AI10 - Current Average | A | Read | ||
| AI | 11 | AI11 - Voltage L1-L2 | V | Read | ||
| AI | 12 | AI12 - Voltage L2-L3 | V | Read | ||
| AI | 13 | AI13 - Voltage L3-L1 | V | Read | ||
| AI | 14 | AI14 - Voltage Average L-L | V | Read | ||
| AI | 15 | AI15 - Voltage L1-N | V | Read | ||
| AI | 16 | AI16 - Voltage L2-N | V | Read | ||
| AI | 17 | AI17 - Voltage L3-N | V | Read | ||
| AImin | 18 | AI18 - Voltage Average L-N | V | Read | ||
| AI | 19 | AI19 - Active Power Phase 1 | kW | Read | ||
| AI | 20 | AI20 - Active Power Phase 2 | kW | Read | ||
| AI | 21 | AI21 - Active Power Phase 3 | kW | Read | ||
| AImin | 22 | AI22 - Active Power Total | kW | Read | ||
| AI | 23 | AI23 - Reactive Power Total | kVAR | Read | ||
| AI | 24 | AI24 - Apparent Power Total | kVA | Read | ||
| AImin | 25 | AI25 - Power Factor Total | Read | |||
| AImin | 26 | AI26 - Frequency | Hz | Read | ||
| AImin | 27 | AI27 - Total active energy import | Kept through power failures | Wh | Read | |
| AI | 28 | AI28 - Total active energy export | Kept through power failures | Wh | Read | |
| AI | 29 | AI29 - Total reactive energy import | Kept through power failures | Wh | Read | |
| AI | 30 | AI30 - Total reactive energy export | Kept through power failures | Wh | Read | |
| AI | 31 | AI31 - Partial active energy import | Resettable partial counter | Wh | Read | |
| AI | 32 | AI32 - Partial reactive energy import | Resettable partial counter | Wh | Read | |
| AI | 33 | AI33 - Active energy import phase 1 | Wh | Read | ||
| AI | 34 | AI34 - Active energy import phase 2 | Wh | Read | ||
| AI | 35 | AI35 - Active energy import phase 3 | Wh | Read | ||
| AI | 36 | AI36 - Accumulation | Input metering accumulation (pulse input) | Read | ||
| AI | 37 | AI37 - Tariff Energy Active Rate | Active tariff | Read | 0=Multi tariff disabled, 1=Rate A, 2=Rate B, 3=Rate C, 4=Rate D | |
| AI | 38 | AI38 - Rate A (Tariff 1) active energy import | Wh | Read | ||
| AI | 39 | AI39 - Rate B (Tariff 2) active energy import | Wh | Read | ||
| AI | 40 | AI40 - Rate C (Tariff 3) active energy import | Wh | Read | ||
| AI | 41 | AI41 - Rate D (Tariff 4) active energy import | Wh | Read | ||
| AI | 42 | AI42 - Pickup Setpoint | Active power alarm pickup setpoint | kW | Read | |
| AI | 43 | AI43 - Last Alarm Value | Value at the last alarm | kW | Read | |
| AI | 44 | AI44 - Meter operation time | Time since the meter last powered up | Seconds | Read | |
| AI | 45 | AI45 - Number of phases | 1 or 3 | Read | ||
| AI | 46 | AI46 - Number of wires | 2, 3 or 4 | Read | ||
| AI | 47 | AI47 - Power system type | Wiring configuration | Read | 0=1PH2W L-N, 1=1PH2W L-L, 2=1PH3W L-L with N, 3=3PH3W, 11=3PH4W, 13=1PH4 wire multi L-N | |
| AI | 48 | AI48 - Nominal frequency | 50 or 60 | Hz | Read | |
| AI | 49 | AI49 - Number of VTs | 0-10; iEM3265 only | Read | ||
| AI | 50 | AI50 - VT Primary | iEM3265 only | V | Read | |
| AI | 51 | AI51 - VT Secondary | iEM3265 only | V | Read | |
| AI | 52 | AI52 - Number of CTs | 1, 2 or 3; iEM3265 only | Read | ||
| AI | 53 | AI53 - CT Primary | iEM3265 only | A | Read | |
| AI | 54 | AI54 - CT Secondary | iEM3265 only | A | Read | |
| AI | 55 | AI55 - VT connection type | iEM3265 only | Read | 0=Direct connection, no VTs, 1=3PH3W (2 VTs), 2=3PH4W (3 VTs) | |
| AV | 0 | AV00 - Command | Write a command code to the meter | Write | 20001=Acknowledge overload alarm, 2020=Reset partial energy counters, 2023=Reset input metering counter | |
| BI | 0 | BI00 - Digital Output Enable | Digital output used as active energy pulse output | Read | 0=Disabled, 1=Energy pulse output | |
| BI | 1 | BI01 - Digital Input Association Enable | Digital input used for input metering | Read | 0=Not associated, 1=Associated | |
| BI | 2 | BI02 - Digital Input Status | Digital input contact state (input status mode) | Read | 0=Relay open, 1=Relay closed | |
| BI | 3 | BI03 - Alarm Enable | Overload alarm enabled | Read | 0=Disabled, 1=Enabled | |
| BI | 4 | BI04 - Digital Output Association Enable | Digital output used for the overload alarm | Read | 0=Disabled, 1=Alarm | |
| BImin | 5 | BI05 - Alarm Status | Overload alarm active | Read | 0=Inactive, 1=Active | |
| BI | 6 | BI06 - Unacknowledged status | Historic alarm not yet acknowledged | Read | 0=Acknowledged, 1=Unacknowledged |
No points match these filters.
Integration notes
- Configuration readbacks (AI 0-6, AI 44-55) can't be changed over BACnet; set them at the front panel.
- Energy values are in Wh and survive power loss.
- AV00 Command accepts 20001 (acknowledge overload alarm), 2020 (reset partial energy) and 2023 (reset input metering).
- Up to 14 COV subscriptions on AI and BI objects.
- Object names follow the manual's 'AIxx - name' form.
- Source is user manual DOCA0005EN-16, chapter 'Communications using BACnet'.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
How many BACnet points does the Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP) have?
This list has 64 BACnet objects: 56 analog inputs, 1 analog value, 7 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP) BACnet points are writable?
1 of the 64 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP) BACnet documentation?
The source is iEM3100 / iEM3200 / iEM3300 series User Manual (DOCA0005EN-16), revision 05/2026, published free by Schneider Electric at https://download.schneider-electric.com/files?p_Doc_Ref=DOCA0005EN.
What are the minimum BACnet points to integrate the Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)?
Start with AI 27 AI27 - Total active energy import (Imported active energy, Wh); AI 22 AI22 - Active Power Total (Total active power, kW); AI 25 AI25 - Power Factor Total (Total power factor); AI 10 AI10 - Current Average (Average phase current, A); AI 18 AI18 - Voltage Average L-N (Average line-to-neutral voltage); AI 26 AI26 - Frequency (Supply frequency); BI 5 BI05 - Alarm Status (Overload alarm active).
How do I check these points on the real Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP
Source: iEM3100 / iEM3200 / iEM3300 series User Manual · DOCA0005EN-16 · rev. 05/2026. Object names, instances and units are reproduced as published; descriptions are our own.