Easy BACnet
  1. Home
  2. BACnet points lists
  3. Schneider Electric
  4. Altivar Process ATV600 (BACnet MS/TP)

Variable frequency drive · BACnet points list

Schneider Electric Altivar Process ATV600 (BACnet MS/TP) BACnet points list

Updated 28 October 2026

Short answer

The Altivar Process ATV600 drives talk BACnet MS/TP as a B-ASC with a fixed object list. It covers relay and logic input status, run/stop, direction and fault reset commands, a speed reference, motor measurements, the last three faults, two analog outputs, eight read and eight write comm-scanner values, and a mailbox (MBOX) for reading or writing any drive parameter.

This page lists 74 BACnet objects for the Schneider Electric Altivar Process ATV600 (BACnet MS/TP) — 29 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.

Manufacturer
Schneider Electric
Model
Altivar Process ATV600 (BACnet MS/TP)
Equipment
Variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
74 (29 writable)
Transport
BACnet MS/TP
Firmware
v1.7 (application software v1.1)
Also known as
ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx
Source document
BACnet Protocol Implementation Conformance Statement, Altivar Process ATV630/ATV650/ATV660/ATV690 · rev. 2018-03-07
Download CSV 74 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Schneider Electric Altivar Process ATV600 (BACnet MS/TP)

Integration in brief

Write BV 10 RUN/STOP CMD and AV 16 INPUT REF 1 (%), and read BV 0, BV 2, BV 4 and AV 1/AV 4/AV 6 for status, fault, hand/auto, frequency, current and power. BV 14 resets a fault on a rising edge; AV 18-20 hold the current and two previous faults. Any other drive parameter can be read or written through the MBOX objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10RUN/STOP CMDStart/stop from the BMSCommand
AV 16INPUT REF 1Speed reference in %Command
BV 14FAULT RESETReset a tripped drive (rising edge)Write
BV 0RUN/STOP ACTRunning statusRead
BV 4HAND/AUTO ACTShows if the drive is in HandRead
AV 1OUTPUT FREQOutput frequency in HzRead
AV 4CURRENTMotor ampsRead
AV 6POWERMotor power in %Read
BV 2FAULT ACTAny active drive faultRead
AV 18LAST FAULTWhich fault is activeRead

Sensors & values from the BMS

The BMS can write the process PID setpoint to AV 27 EXT PID STPT. The document lists no BMS-written PID feedback object; COM SCAN OUT1-8 can carry other values into mapped drive registers.

Network setup

Watch out for

Schneider Electric Altivar Process ATV600 (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

74 of 74 shown
Type
Access
Show
Schneider Electric Altivar Process ATV600 (BACnet MS/TP) BACnet Points List
DescriptionStates
BI1RO1 ACTStatus of relay R1ReadON/OFF
BI2RO2 ACTStatus of relay R2ReadON/OFF
BI3RO3 ACTStatus of relay R3ReadON/OFF
BI6DI 1 ACTStatus of logic input LI1ReadON/OFF
BI7DI 2 ACTStatus of logic input LI2ReadON/OFF
BI8DI 3 ACTStatus of logic input LI3ReadON/OFF
BI9DI 4 ACTStatus of logic input 4 (doc prints LI3)ReadON/OFF
BI10DI 5 ACTStatus of logic input LI5ReadON/OFF
BI11DI 6 ACTStatus of logic input LI6ReadON/OFF
BO0RO1 CMDDrives relay R1 when it has no other function assignedCommandON/OFF
BO1RO2 CMDDrives relay R2 when it has no other function assignedCommandON/OFF
BO2RO3 CMDDrives relay R3 when it has no other function assignedCommandON/OFF
BVmin0RUN/STOP ACTDrive running statusReadRUNS/READY
BV1FWD/REV ACTMotor rotation directionReadREV/FWD
BVmin2FAULT ACTDrive fault statusReadFAULTED/NONE
BVmin4HAND/AUTO ACTShows if the drive is under local controlReadHAND/AUTO
BV7DRIVE READYDrive ready and waiting for a start commandReadREADY/NOT READY
BV8AT SETPOINTDrive has reached the target speedReadREACHED/NO
BVmin10RUN/STOP CMDStart/stop commandCommandSTART/STOP
BV11FWD/REV CMDMotor direction commandCommandREV/FWD
BVmin14FAULT RESETFault reset on rising edgeWriteRESET/NO
BV15MBOX READTriggers a read of the parameter in MBOX PARAMWriteREAD/RESET
BV16MBOX WRITETriggers a write of MBOX DATA to MBOX PARAMWriteWRITE/RESET
BV18C311CMDCommand word 3, bit 11CommandON/OFF
BV19C312CMDCommand word 3, bit 12CommandON/OFF
BV20C313CMDCommand word 3, bit 13CommandON/OFF
BV21C314CMDCommand word 3, bit 14CommandON/OFF
BV22C315CMDCommand word 3, bit 15CommandON/OFF
BV23STORE CONFIGStore configuration (doc description only says HELP)ReadINACTIVE/STORE
AI0ANALOG INPUT 1Analog input 1 value%Read
AI1ANALOG INPUT 2Analog input 2 value%Read
AI2ANALOG INPUT 3Analog input 3 value%Read
AI16ANALOG OUTPUT 1Analog output 1 status%Read
AI17ANALOG OUTPUT 2Analog output 2 status%Read
AO0AO1 COMMANDAnalog output 1 value from the BMS%Command
AO1AO2 COMMANDAnalog output 2 value from the BMS%Command
AV0OUTPUT SPEEDMotor speedrpmRead
AVmin1OUTPUT FREQOutput frequencyHzRead
AV2DC BUS VOLTDC bus voltageVRead
AV3OUTPUT VOLTMotor voltageVRead
AVmin4CURRENTMotor currentARead
AV5TORQUEMotor torque%Read
AVmin6POWERMotor power%Read
AV7DRIVE TEMPDrive thermal state%Read
AV8KWH(RResettable energy counterkWhRead
AV10PRC PID FBCKProcess PID feedbackRead
AV11PRC PID DEVProcess PID deviation (doc repeats the feedback text)Read
AV14RUN TIMEOperating timehRead
AV15MOTOR TEMPMotor thermal state%Read
AVmin16INPUT REF 1Speed/frequency reference from the BMS%Command
AVmin18LAST FAULTCurrent faultRead
AV19PREV FLT 1Previous fault (n-1)Read
AV20PREV FLT 2Previous fault (n-2)Read
AV23ACCEL1 TIMEAcceleration ramp timesWrite
AV24DECEL1 TIMEDeceleration ramp timesWrite
AV25MBOX PARAMLogic address of the parameter to read or writeWrite
AV26MBOX DATAParameter value read, or value to writeWrite
AV27EXT PID STPTProcess PID setpoint from the BMSCommand
AV28COM SCAN OUT1General-purpose value written to the drive comm scannerCommand
AV29COM SCAN OUT2General-purpose value written to the drive comm scannerCommand
AV30COM SCAN OUT3General-purpose value written to the drive comm scannerCommand
AV31COM SCAN OUT4General-purpose value written to the drive comm scannerCommand
AV32COM SCAN OUT5General-purpose value written to the drive comm scannerCommand
AV33COM SCAN OUT6General-purpose value written to the drive comm scannerCommand
AV34COM SCAN OUT7General-purpose value written to the drive comm scannerCommand
AV35COM SCAN OUT8General-purpose value written to the drive comm scannerCommand
AV36COM SCAN IN1General-purpose value read from the drive comm scannerRead
AV37COM SCAN IN2General-purpose value read from the drive comm scannerRead
AV38COM SCAN IN3General-purpose value read from the drive comm scannerRead
AV39COM SCAN IN4General-purpose value read from the drive comm scannerRead
AV40COM SCAN IN5General-purpose value read from the drive comm scannerRead
AV41COM SCAN IN6General-purpose value read from the drive comm scannerRead
AV42COM SCAN IN7General-purpose value read from the drive comm scannerRead
AV43COM SCAN IN8General-purpose value read from the drive comm scannerRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Altivar Process ATV600 (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Schneider Electric Altivar Process ATV600 (BACnet MS/TP)

How many BACnet points does the Schneider Electric Altivar Process ATV600 (BACnet MS/TP) have?

This list has 74 BACnet objects: 5 analog inputs, 2 analog outputs, 38 analog values, 9 binary inputs, 3 binary outputs, 17 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Schneider Electric Altivar Process ATV600 (BACnet MS/TP) BACnet points are writable?

29 of the 74 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Schneider Electric Altivar Process ATV600 (BACnet MS/TP) BACnet documentation?

The source is BACnet Protocol Implementation Conformance Statement, Altivar Process ATV630/ATV650/ATV660/ATV690, revision 2018-03-07, published free by Schneider Electric at https://www.bacnetinternational.net/catalog/manu/schneider%20electric/pics_atv6x.pdf.

What are the minimum BACnet points to integrate the Schneider Electric Altivar Process ATV600 (BACnet MS/TP)?

Start with BV 10 RUN/STOP CMD (Start/stop from the BMS); AV 16 INPUT REF 1 (Speed reference in %); BV 14 FAULT RESET (Reset a tripped drive (rising edge)); BV 0 RUN/STOP ACT (Running status); BV 4 HAND/AUTO ACT (Shows if the drive is in Hand); AV 1 OUTPUT FREQ (Output frequency in Hz); AV 4 CURRENT (Motor amps); AV 6 POWER (Motor power in %); BV 2 FAULT ACT (Any active drive fault); AV 18 LAST FAULT (Which fault is active).

Can the BMS supply sensor values to the Schneider Electric Altivar Process ATV600 (BACnet MS/TP)?

The BMS can write the process PID setpoint to AV 27 EXT PID STPT. The document lists no BMS-written PID feedback object; COM SCAN OUT1-8 can carry other values into mapped drive registers.

How do I check these points on the real Altivar Process ATV600 (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Schneider Electric BACnet points lists

Source: BACnet Protocol Implementation Conformance Statement, Altivar Process ATV630/ATV650/ATV660/ATV690 · rev. 2018-03-07. Object names, instances and units are reproduced as published; descriptions are our own.