- SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Fan coil unit controller (room thermostat) · BACnet points list
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller BACnet points list
Updated 4 November 2026
The SER7300 series are line-voltage PIR-ready fan coil room controllers. With the BACnet module they are BACnet MS/TP application specific controllers (B-ASC). The object list covers room, outdoor and supply temperature, setpoints, system and fan mode, occupancy, PI demands, fan and valve status, alarms and the SER configuration objects (CPH, NO/NC valves, demand limits); humidity objects exist only on the SER7350/SER7355.
This page lists 73 BACnet objects for the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- SER7300 Series PIR Ready Line Voltage Fan Coil Controller
- Equipment
- Fan coil unit controller (room thermostat)
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 73 (48 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Command occupancy with MV 18 and the mode with MV 16, fan mode with MV 17, and write the occupied setpoints AV 39/AV 40. Read AV 7 room temperature, MV 33 effective occupancy and MV 28 fan status. The BMS can also send outdoor temperature to AV 9.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 18 | Occupancy Command | BMS occupancy: local, occupied or unoccupied | Command |
| MV 16 | System Mode | Off / auto / cool / heat | Command |
| MV 17 | Fan Mode | Fan mode command | Command |
| AV 39 | Occupied Heat Setpoint | Occupied heating setpoint | Command |
| AV 40 | Occupied Cool Setpoint | Occupied cooling setpoint | Command |
| MV 33 | Effective Occupancy | Actual occupancy state | Read |
| AV 7 | Room Temperature | Space temperature | Command |
| MV 28 | Fan Status | Fan speed status: off / low / med / high | Read |
| BI 37 | Service Alarm | Service alarm from an input set to Service | Read |
Enable & remote start
BACnet stays off until the MAC address is changed from the factory 254 to 0-127. MV 18 Occupancy Command: 1 = Local Occupancy, 2 = Occupied, 3 = Unoccupied.
Sensors & values from the BMS
The BMS can write Outdoor Temperature (AV 9) and, for testing or override, Room Temperature (AV 7); AV 7 only accepts writes while BV 8 Room Temp Override is set to Override. On the humidity models, Room Humidity (AV 10) likewise needs BV 11 Room Humid Override. Written room temperature, outdoor temperature and occupancy are released if the controller goes offline.
Network setup
- Controllers ship with MAC address 254, which keeps BACnet communication off. Set the MAC address (0-127) at the controller to enable BACnet MS/TP.
- Baud rate auto-detects (9600, 19200, 38400, 76800) at power-up; after a network speed change the device keeps the old speed for 10 minutes unless re-powered.
- Default Device Name is the model number plus the MAC address; Device Name and Device ID are writable.
- No COV support: poll at 5 seconds or slower and write on change ('if once' or every few minutes), not every program scan.
Watch out for
- If the controller goes offline, values the BMS wrote to Room Temperature, Outdoor Temperature and Occupancy are released.
- Segmented requests and responses are not supported; keep Read Property Multiple requests small.
- The device object has no Local_Time or Local_Date, so the controller cannot claim DM-TS-B even though time sync over the network works.
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 7 | Room Temperature | Range -39.9°F (-40°C) to 121.9°F (50°C) | °F/°C | Command | |
| BV | 8 | Room Temp Override | Default Normal | Command | 0=Normal, 1=Override | |
| AV | 9 | Outdoor Temperature | Range -39°F (-40°C) to 121.9°F (50°C) | °F/°C | Command | |
| AV | 10 | Room Humidity | Range 5% to 90%; only SER7350, SER7355 | % | Command | |
| BV | 11 | Room Humid Override | only SER7350, SER7355 | Command | ||
| AI | 12 | Supply Temperature | Range -39.9°F (-40°C) to 121.9°F (50°C) | °F/°C | Read | |
| BV | 13 | Dehumidification Lockout | Default Enabled; only SER7350, SER7355 | Command | 0=Disabled, 1=Enabled | |
| MV | 15 | Sequence of Operation | Command | 1=Cooling Only, 2=Heating Only, 3=Cooling & Reheat, 4=Heating & Reheat, 5=Cool/Heat4P, 6=Cool/Heat4P&Reht | ||
| MVmin | 16 | System Mode | Command | 1=Off, 2=Auto, 3=Cool, 4=Heat | ||
| MVmin | 17 | Fan Mode | Command | |||
| MVmin | 18 | Occupancy Command | Command | 1=Local Occupancy, 2=Occupied, 3=Unoccupied | ||
| MV | 19 | Keypad Lockout | Command | 1=Level 0, 2=Level 1, 3=Level 2, 4=Level 3, 5=Level 4, 6=Level 5 | ||
| Other | 20 | Control Output | Group object (bundles related objects) | Read | ||
| AV | 21 | PI Heating Demand | Range 0% to 100%; default 0% | % | Read | |
| AV | 22 | PI Cooling Demand | Range 0% to 100%; default 0% | % | Read | |
| BI | 23 | Dehumidification Status | Default Off; only SER7350, SER7355 | Read | 0=Off, 1=On | |
| Other | 24 | Controller Status | Group object (bundles related objects) | Read | ||
| MVmin | 28 | Fan Status | Read | 1=Off, 2=Low, 3=Med, 4=High | ||
| BI | 29 | BI 1 Status | Default Deactivated | Read | 0=Deactivated, 1=Activated | |
| BI | 30 | BI 2 Status | Default Deactivated | Read | 0=Deactivated, 1=Activated | |
| BI | 32 | Local Motion | Default No Motion | Read | 0=No Motion, 1=Motion | |
| MVmin | 33 | Effective Occupancy | Read | 1=Occupied, 2=Unoccupied, 3=Temporary Occupied, 4=Stand-by | ||
| Other | 34 | Controller Alarms | Group object (bundles related objects) | Read | ||
| BI | 35 | Window Alarm | Default Off | Read | 0=Off, 1=On | |
| BI | 36 | Filter Alarm | Default Off | Read | 0=Off, 1=On | |
| BImin | 37 | Service Alarm | Default Off | Read | 0=Off, 1=On | |
| Other | 38 | Temperature Setpoints | Group object (bundles related objects) | Read | ||
| AVmin | 39 | Occupied Heat Setpoint | Range 40°F (4.5°C) to 90°F (32°C); default 72°F (22°C) | °F/°C | Command | |
| AVmin | 40 | Occupied Cool Setpoint | Range 54°F (12°C) to 100°F (37.5°C); default 74°F (24°C) | °F/°C | Command | |
| AV | 41 | Stand-by Heat Setpoint | Range 40°F (4.5°C) to 90°F (32°C); default 72°F (22°C) | °F/°C | Command | |
| AV | 42 | Stand-by Cool Setpoint | Range 54°F (12°C) to 100°F (37.5°C); default 74°F (24°C) | °F/°C | Command | |
| AV | 43 | Unoccupied Heat Setpoint | Range 40°F (4.5°C) to 90°F (32°C); default 62°F (16.5°C) | °F/°C | Command | |
| AV | 44 | Unoccupied Cool Setpoint | Range 54°F (12°C) to 100°F (37.5°C); default 80°F (26.5°C) | °F/°C | Command | |
| Other | 45 | General Options 1 | Group object (bundles related objects) | Read | ||
| MV | 46 | BI 1 Configuration | Command | 1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window | ||
| MV | 47 | BI 2 Configuration | Command | 1=None, 2=Door Dry, 3=Override, 4=Filter, 5=Service | ||
| BV | 49 | Menu Scroll | Default Scroll Active | Command | 0=No Scroll, 1=Scroll Active | |
| BV | 50 | Auto Mode Enable | Default Enabled | Command | 0=Disabled, 1=Enabled | |
| BV | 51 | Temperature Scale | Default °F | Command | 0=°C, 1=°F | |
| MV | 52 | Pipe Number | Command | |||
| Other | 55 | General Options 2 | Group object (bundles related objects) | Read | ||
| AV | 56 | Password Value | Range 0 to 1000 | Read | ||
| MV | 57 | Fan Mode Sequence | Command | 1=Low-Med-High, 2=Low-High, 3=Low-Med-High-Auto, 4=Low-High-Auto, 5=On-Auto | ||
| AV | 58 | Heating Setpoint Limit | Range 40°F (4.5°C) to 90°F (32°C); default 90°F (32°C) | °F/°C | Command | |
| AV | 59 | Cooling Setpoint Limit | Range 54°F (12°C) to 100°F (37.5°C); default 54°F (12°C) | °F/°C | Command | |
| BV | 60 | Setpoint Type | Default Permanent | Command | 0=Permanent, 1=Temporary | |
| BV | 61 | Setpoint Function | Default Dual Setpoints | Command | 0=Dual Setpoints, 1=Attached Setpoints | |
| MV | 62 | Temporary Occupancy Time | Command | 1=0 hour, 2=1 hour, 3=2 hours, 4=3 hours, 5=4 hours, 6=5 hours, 7=6 hours, 8=7 hours, 9=8 hours, 10=9 hours, 11=10 hours, 12=11 hours, 13=12 hours, 14=13 hours, 15=14 hours, 16=15 hours, 17=16 hours, 18=17 hours, 19=18 hours, 20=19 hours, 21=20 hours, 22=21 hours, 23=22 hours, 24=23 hours, 25=24 hours | ||
| AV | 63 | Deadband | Range 2°F (1°C) to 5°F (2.5°C); default 2°F (1°C) | °F/°C | Command | |
| MV | 65 | Proportional Band | Command | 1=3 °F (1.2 °C), 2=4 °F (1.7 °C), 3=5 °F (2.2 °C), 4=6 °F (2.8 °C), 5=7 °F (3.3 °C), 6=8 °F (3.9 °C), 7=9 °F (5.0 °C), 8=10 °F (5.6 °C) | ||
| BV | 66 | Auto Fan | Command | |||
| AV | 67 | Stand-by Time | Range 0.5 Hours to 24.0 Hours; default 0.5 Hours | h | Command | |
| AV | 68 | Unoccupied Time | Range 0.0 Hours to 24.0 Hours; default 0.0 Hours | h | Command | |
| Other | 69 | Humidity Models Config Options | Group object (bundles related objects); only SER7350, SER7355 | Read | ||
| BV | 70 | RH Display | Default Disabled; only SER7350, SER7355 | Command | 0=Disabled, 1=Enabled | |
| AV | 71 | RH Setpoint | Range 30% to 95%; default 50%; only SER7350, SER7355 | % | Command | |
| AV | 72 | Dehumidification Hysterisys | Range 2% to 20%; default 5%; only SER7350, SER7355 | % | Command | |
| AV | 73 | Dehumidification MAX Cooling | Range 20% to 100%; default 100 %; only SER7350, SER7355 | % | Command | |
| Other | 81 | SER models Configuration Options and Status | Group object (bundles related objects) | Read | ||
| MV | 82 | RUI 1 Configuration | Command | 0=None, 1=Filter, 2=Service, 3=COC/NH, 4=COC/NC, 5=COS | ||
| MV | 83 | RBI 2 Configuration | Command | |||
| MV | 84 | Heat CPH | Command | 3=3 CPH, 4=4 CPH, 5=5 CPH, 6=6 CPH, 7=7 CPH, 8=8 CPH | ||
| MV | 85 | Cool CPH | Command | 3=3 CPH, 4=4 CPH, 5=5 CPH, 6=6 CPH, 7=7 CPH, 8=8 CPH | ||
| BV | 86 | Heat NO NC | Default Normally Closed | Command | 0=Normally Opened, 1=Normally Closed | |
| BV | 87 | Cool NO NC | Default Normally Closed | Command | 0=Normally Opened, 1=Normally Closed | |
| AV | 88 | Heat Demand Limit | Range 0% to 100% | % | Command | |
| AV | 89 | Cool Demand Limit | Range 0% to 100% | % | Command | |
| MV | 90 | Pulsed Heat | Command | 0=Off, 1=On, 2=Occupancy Output | ||
| BI | 91 | RUI 1 Status | Default Deactivated | Read | 0=Deactivated, 1=Activated | |
| BI | 92 | RBI 2 Status | Default Deactivated | Read | 0=Deactivated, 1=Activated | |
| BI | 93 | Cooling Valve Status | Default Off | Read | 0=Off, 1=On | |
| BI | 94 | Heating Valve Status | Default Off | Read | 0=Off, 1=On | |
| MV | 95 | Fan Control | Command | 0=None, 1=Filter, 2=Service |
No points match these filters.
Object ID lookup: Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller point IDs by name
AV7Room TemperatureBV8Room Temp OverrideAV9Outdoor TemperatureAV10Room HumidityBV11Room Humid OverrideAI12Supply TemperatureBV13Dehumidification LockoutMV15Sequence of OperationMV16System ModeMV17Fan ModeMV18Occupancy CommandMV19Keypad LockoutAV21PI Heating DemandAV22PI Cooling DemandBI23Dehumidification StatusMV28Fan StatusBI29BI 1 StatusBI30BI 2 StatusBI32Local MotionMV33Effective OccupancyBI35Window AlarmBI36Filter AlarmBI37Service AlarmAV39Occupied Heat SetpointAV40Occupied Cool SetpointAV41Stand-by Heat SetpointAV42Stand-by Cool SetpointAV43Unoccupied Heat SetpointAV44Unoccupied Cool SetpointMV46BI 1 ConfigurationMV47BI 2 ConfigurationBV49Menu ScrollBV50Auto Mode EnableBV51Temperature ScaleMV52Pipe NumberAV56Password ValueMV57Fan Mode SequenceAV58Heating Setpoint LimitAV59Cooling Setpoint LimitBV60Setpoint TypeBV61Setpoint FunctionMV62Temporary Occupancy TimeAV63DeadbandMV65Proportional BandBV66Auto FanAV67Stand-by TimeAV68Unoccupied TimeBV70RH DisplayAV71RH SetpointAV72Dehumidification HysterisysAV73Dehumidification MAX CoolingMV82RUI 1 ConfigurationMV83RBI 2 ConfigurationMV84Heat CPHMV85Cool CPHBV86Heat NO NCBV87Cool NO NCAV88Heat Demand LimitAV89Cool Demand LimitMV90Pulsed HeatBI91RUI 1 StatusBI92RBI 2 StatusBI93Cooling Valve StatusBI94Heating Valve StatusMV95Fan Control
Integration notes
- Access comes from the objects table (Present_Value R or R,W). Writable AV, BV and MV objects are marked commandable 'C'.
- Group objects (GRP) are listed as type 'Other'; they only bundle related objects. Schneider suggests removing configuration objects from the BAS after setup to cut polling.
- State texts and ranges come from the guide's enumeration tables where the object name and instance match; a few enumeration rows use different instances than the objects table and were not applied.
- The PIR cover and the humidity sensor are model options: objects marked 'only ...' exist only on the listed part numbers.
- The guide gives default Device ID rules only for the SE7200 (72000 + MAC) and SE73xx (73000 + MAC) models, not for the SER models.
- MV 95 Fan Control is printed with the states None/Filter/Service, which look copied from the input configuration tables; listed as printed.
- MV 83 RBI 2 Configuration's state list is cut off in the guide, so no states are given.
- The guide's sample program writes occupancy to 'MV13' and its GUI list gives Unoccupied Cool Setpoint as 'AV34'; the objects table has MV 18 Occupancy Command and AV 44.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SER7300 Series PIR Ready Line Voltage Fan Coil Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
How many BACnet points does the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller have?
This list has 73 BACnet objects: 1 analog input, 22 analog values, 11 binary inputs, 12 binary values, 19 multi-state values, 8 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller BACnet points are writable?
48 of the 73 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller BACnet documentation?
The source is BACnet Integration Manual: PIR Ready SE7200, SE7300 & SER7300 Series (24 Vac zoning, fan coil and line-voltage fan coil controllers) (IG-SE7000-BNET24VAC-A4.EN.4.2013.v1), revision April 2013, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=IG-SE7000-BNET24VAC-A4.
What are the minimum BACnet points to integrate the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller?
Start with MV 18 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode command); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 33 Effective Occupancy (Actual occupancy state); AV 7 Room Temperature (Space temperature); MV 28 Fan Status (Fan speed status: off / low / med / high); BI 37 Service Alarm (Service alarm from an input set to Service).
How do I enable BMS control of the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller?
BACnet stays off until the MAC address is changed from the factory 254 to 0-127. MV 18 Occupancy Command: 1 = Local Occupancy, 2 = Occupied, 3 = Unoccupied.
Can the BMS supply sensor values to the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller?
The BMS can write Outdoor Temperature (AV 9) and, for testing or override, Room Temperature (AV 7); AV 7 only accepts writes while BV 8 Room Temp Override is set to Override. On the humidity models, Room Humidity (AV 10) likewise needs BV 11 Room Humid Override. Written room temperature, outdoor temperature and occupancy are released if the controller goes offline.
How do I check these points on the real SER7300 Series PIR Ready Line Voltage Fan Coil Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Multi-circuit branch power meter (high density)
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Schneider Electric (ex-Veris) PowerLogic HDPM6000 head units with busway, strip or retrofit measurement modules, on BACnet IP over Ethernet.
Also known as: HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Schneider Electric PowerLogic PM5300 series power meters with the Ethernet port (PM5320, PM5340, PM5341) using BACnet IP.
Also known as: PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Zone controller (room thermostat)
Schneider Electric SE7200 Series PIR Ready Zoning Controller
Schneider Electric PIR-ready SE7200 series 24 Vac zoning controllers (SE7200C5x45B, SE7200F5x45B).
Also known as: SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Pressure-dependent VAV zone controller
Schneider Electric SEZ7260 Zoning System Zone Controller
Schneider Electric SEZ7260 zone controllers (F model with floating damper and AO2, C model) used with SEZ7656 rooftop controllers in pressure-dependent zoning systems.
Also known as: SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B - Rooftop unit controller for zoning systems
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Schneider Electric SEZ7656 rooftop controllers (R conventional, H heat pump, F modulating heat, E economizer) that run a rooftop unit for a group of SEZ7260 zone controllers.
Also known as: SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Schneider Electric SpaceLogic SE8000-series SER8350 room controllers for line-voltage fan coil units.
Also known as: SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350 - Room humidity and temperature sensor (wall)
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Schneider Electric SpaceLogic SLP Series wall humidity/temperature sensors (with or without touchscreen) set to BACnet MS/TP.
Also known as: SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil - Rooftop unit controller (room thermostat, rooftop or heat-pump units)
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 6500 (rooftop unit / heat pump) version.
Also known as: SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump
Source: BACnet Integration Manual: PIR Ready SE7200, SE7300 & SER7300 Series (24 Vac zoning, fan coil and line-voltage fan coil controllers) · IG-SE7000-BNET24VAC-A4.EN.4.2013.v1 · rev. April 2013. Object names, instances and units are reproduced as published; descriptions are our own.