Fan coil unit controller (room thermostat) · BACnet points list

Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller BACnet points list

Updated 4 November 2026

Short answer

The SER7300 series are line-voltage PIR-ready fan coil room controllers. With the BACnet module they are BACnet MS/TP application specific controllers (B-ASC). The object list covers room, outdoor and supply temperature, setpoints, system and fan mode, occupancy, PI demands, fan and valve status, alarms and the SER configuration objects (CPH, NO/NC valves, demand limits); humidity objects exist only on the SER7350/SER7355.

This page lists 73 BACnet objects for the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.

Manufacturer
Schneider Electric
Model
SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Equipment
Fan coil unit controller (room thermostat)
Equipment type
VAV boxes & fan coils
BACnet objects
73 (48 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B
Source document
BACnet Integration Manual: PIR Ready SE7200, SE7300 & SER7300 Series (24 Vac zoning, fan coil and line-voltage fan coil controllers) · IG-SE7000-BNET24VAC-A4.EN.4.2013.v1 · rev. April 2013
Download CSV 73 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.

BMS integration notes: Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller

Integration in brief

Command occupancy with MV 18 and the mode with MV 16, fan mode with MV 17, and write the occupied setpoints AV 39/AV 40. Read AV 7 room temperature, MV 33 effective occupancy and MV 28 fan status. The BMS can also send outdoor temperature to AV 9.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 18Occupancy CommandBMS occupancy: local, occupied or unoccupiedCommand
MV 16System ModeOff / auto / cool / heatCommand
MV 17Fan ModeFan mode commandCommand
AV 39Occupied Heat SetpointOccupied heating setpointCommand
AV 40Occupied Cool SetpointOccupied cooling setpointCommand
MV 33Effective OccupancyActual occupancy stateRead
AV 7Room TemperatureSpace temperatureCommand
MV 28Fan StatusFan speed status: off / low / med / highRead
BI 37Service AlarmService alarm from an input set to ServiceRead

Enable & remote start

BACnet stays off until the MAC address is changed from the factory 254 to 0-127. MV 18 Occupancy Command: 1 = Local Occupancy, 2 = Occupied, 3 = Unoccupied.

Sensors & values from the BMS

The BMS can write Outdoor Temperature (AV 9) and, for testing or override, Room Temperature (AV 7); AV 7 only accepts writes while BV 8 Room Temp Override is set to Override. On the humidity models, Room Humidity (AV 10) likewise needs BV 11 Room Humid Override. Written room temperature, outdoor temperature and occupancy are released if the controller goes offline.

Network setup

Watch out for

Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

73 of 73 shown
Type
Multi-stateOther
Access
Show
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller BACnet Points List
DescriptionStates
AVmin7Room TemperatureRange -39.9°F (-40°C) to 121.9°F (50°C)°F/°CCommand
BV8Room Temp OverrideDefault NormalCommand0=Normal, 1=Override
AV9Outdoor TemperatureRange -39°F (-40°C) to 121.9°F (50°C)°F/°CCommand
AV10Room HumidityRange 5% to 90%; only SER7350, SER7355%Command
BV11Room Humid Overrideonly SER7350, SER7355Command
AI12Supply TemperatureRange -39.9°F (-40°C) to 121.9°F (50°C)°F/°CRead
BV13Dehumidification LockoutDefault Enabled; only SER7350, SER7355Command0=Disabled, 1=Enabled
MV15Sequence of OperationCommand1=Cooling Only, 2=Heating Only, 3=Cooling & Reheat, 4=Heating & Reheat, 5=Cool/Heat4P, 6=Cool/Heat4P&Reht
MVmin16System ModeCommand1=Off, 2=Auto, 3=Cool, 4=Heat
MVmin17Fan ModeCommand
MVmin18Occupancy CommandCommand1=Local Occupancy, 2=Occupied, 3=Unoccupied
MV19Keypad LockoutCommand1=Level 0, 2=Level 1, 3=Level 2, 4=Level 3, 5=Level 4, 6=Level 5
Other20Control OutputGroup object (bundles related objects)Read
AV21PI Heating DemandRange 0% to 100%; default 0%%Read
AV22PI Cooling DemandRange 0% to 100%; default 0%%Read
BI23Dehumidification StatusDefault Off; only SER7350, SER7355Read0=Off, 1=On
Other24Controller StatusGroup object (bundles related objects)Read
MVmin28Fan StatusRead1=Off, 2=Low, 3=Med, 4=High
BI29BI 1 StatusDefault DeactivatedRead0=Deactivated, 1=Activated
BI30BI 2 StatusDefault DeactivatedRead0=Deactivated, 1=Activated
BI32Local MotionDefault No MotionRead0=No Motion, 1=Motion
MVmin33Effective OccupancyRead1=Occupied, 2=Unoccupied, 3=Temporary Occupied, 4=Stand-by
Other34Controller AlarmsGroup object (bundles related objects)Read
BI35Window AlarmDefault OffRead0=Off, 1=On
BI36Filter AlarmDefault OffRead0=Off, 1=On
BImin37Service AlarmDefault OffRead0=Off, 1=On
Other38Temperature SetpointsGroup object (bundles related objects)Read
AVmin39Occupied Heat SetpointRange 40°F (4.5°C) to 90°F (32°C); default 72°F (22°C)°F/°CCommand
AVmin40Occupied Cool SetpointRange 54°F (12°C) to 100°F (37.5°C); default 74°F (24°C)°F/°CCommand
AV41Stand-by Heat SetpointRange 40°F (4.5°C) to 90°F (32°C); default 72°F (22°C)°F/°CCommand
AV42Stand-by Cool SetpointRange 54°F (12°C) to 100°F (37.5°C); default 74°F (24°C)°F/°CCommand
AV43Unoccupied Heat SetpointRange 40°F (4.5°C) to 90°F (32°C); default 62°F (16.5°C)°F/°CCommand
AV44Unoccupied Cool SetpointRange 54°F (12°C) to 100°F (37.5°C); default 80°F (26.5°C)°F/°CCommand
Other45General Options 1Group object (bundles related objects)Read
MV46BI 1 ConfigurationCommand1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window
MV47BI 2 ConfigurationCommand1=None, 2=Door Dry, 3=Override, 4=Filter, 5=Service
BV49Menu ScrollDefault Scroll ActiveCommand0=No Scroll, 1=Scroll Active
BV50Auto Mode EnableDefault EnabledCommand0=Disabled, 1=Enabled
BV51Temperature ScaleDefault °FCommand0=°C, 1=°F
MV52Pipe NumberCommand
Other55General Options 2Group object (bundles related objects)Read
AV56Password ValueRange 0 to 1000Read
MV57Fan Mode SequenceCommand1=Low-Med-High, 2=Low-High, 3=Low-Med-High-Auto, 4=Low-High-Auto, 5=On-Auto
AV58Heating Setpoint LimitRange 40°F (4.5°C) to 90°F (32°C); default 90°F (32°C)°F/°CCommand
AV59Cooling Setpoint LimitRange 54°F (12°C) to 100°F (37.5°C); default 54°F (12°C)°F/°CCommand
BV60Setpoint TypeDefault PermanentCommand0=Permanent, 1=Temporary
BV61Setpoint FunctionDefault Dual SetpointsCommand0=Dual Setpoints, 1=Attached Setpoints
MV62Temporary Occupancy TimeCommand1=0 hour, 2=1 hour, 3=2 hours, 4=3 hours, 5=4 hours, 6=5 hours, 7=6 hours, 8=7 hours, 9=8 hours, 10=9 hours, 11=10 hours, 12=11 hours, 13=12 hours, 14=13 hours, 15=14 hours, 16=15 hours, 17=16 hours, 18=17 hours, 19=18 hours, 20=19 hours, 21=20 hours, 22=21 hours, 23=22 hours, 24=23 hours, 25=24 hours
AV63DeadbandRange 2°F (1°C) to 5°F (2.5°C); default 2°F (1°C)°F/°CCommand
MV65Proportional BandCommand1=3 °F (1.2 °C), 2=4 °F (1.7 °C), 3=5 °F (2.2 °C), 4=6 °F (2.8 °C), 5=7 °F (3.3 °C), 6=8 °F (3.9 °C), 7=9 °F (5.0 °C), 8=10 °F (5.6 °C)
BV66Auto FanCommand
AV67Stand-by TimeRange 0.5 Hours to 24.0 Hours; default 0.5 HourshCommand
AV68Unoccupied TimeRange 0.0 Hours to 24.0 Hours; default 0.0 HourshCommand
Other69Humidity Models Config OptionsGroup object (bundles related objects); only SER7350, SER7355Read
BV70RH DisplayDefault Disabled; only SER7350, SER7355Command0=Disabled, 1=Enabled
AV71RH SetpointRange 30% to 95%; default 50%; only SER7350, SER7355%Command
AV72Dehumidification HysterisysRange 2% to 20%; default 5%; only SER7350, SER7355%Command
AV73Dehumidification MAX CoolingRange 20% to 100%; default 100 %; only SER7350, SER7355%Command
Other81SER models Configuration Options and StatusGroup object (bundles related objects)Read
MV82RUI 1 ConfigurationCommand0=None, 1=Filter, 2=Service, 3=COC/NH, 4=COC/NC, 5=COS
MV83RBI 2 ConfigurationCommand
MV84Heat CPHCommand3=3 CPH, 4=4 CPH, 5=5 CPH, 6=6 CPH, 7=7 CPH, 8=8 CPH
MV85Cool CPHCommand3=3 CPH, 4=4 CPH, 5=5 CPH, 6=6 CPH, 7=7 CPH, 8=8 CPH
BV86Heat NO NCDefault Normally ClosedCommand0=Normally Opened, 1=Normally Closed
BV87Cool NO NCDefault Normally ClosedCommand0=Normally Opened, 1=Normally Closed
AV88Heat Demand LimitRange 0% to 100%%Command
AV89Cool Demand LimitRange 0% to 100%%Command
MV90Pulsed HeatCommand0=Off, 1=On, 2=Occupancy Output
BI91RUI 1 StatusDefault DeactivatedRead0=Deactivated, 1=Activated
BI92RBI 2 StatusDefault DeactivatedRead0=Deactivated, 1=Activated
BI93Cooling Valve StatusDefault OffRead0=Off, 1=On
BI94Heating Valve StatusDefault OffRead0=Off, 1=On
MV95Fan ControlCommand0=None, 1=Filter, 2=Service
Object ID lookup: Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SER7300 Series PIR Ready Line Voltage Fan Coil Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller

How many BACnet points does the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller have?

This list has 73 BACnet objects: 1 analog input, 22 analog values, 11 binary inputs, 12 binary values, 19 multi-state values, 8 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller BACnet points are writable?

48 of the 73 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller BACnet documentation?

The source is BACnet Integration Manual: PIR Ready SE7200, SE7300 & SER7300 Series (24 Vac zoning, fan coil and line-voltage fan coil controllers) (IG-SE7000-BNET24VAC-A4.EN.4.2013.v1), revision April 2013, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=IG-SE7000-BNET24VAC-A4.

What are the minimum BACnet points to integrate the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller?

Start with MV 18 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode command); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 33 Effective Occupancy (Actual occupancy state); AV 7 Room Temperature (Space temperature); MV 28 Fan Status (Fan speed status: off / low / med / high); BI 37 Service Alarm (Service alarm from an input set to Service).

How do I enable BMS control of the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller?

BACnet stays off until the MAC address is changed from the factory 254 to 0-127. MV 18 Occupancy Command: 1 = Local Occupancy, 2 = Occupied, 3 = Unoccupied.

Can the BMS supply sensor values to the Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller?

The BMS can write Outdoor Temperature (AV 9) and, for testing or override, Room Temperature (AV 7); AV 7 only accepts writes while BV 8 Room Temp Override is set to Override. On the humidity models, Room Humidity (AV 10) likewise needs BV 11 Room Humid Override. Written room temperature, outdoor temperature and occupancy are released if the controller goes offline.

How do I check these points on the real SER7300 Series PIR Ready Line Voltage Fan Coil Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Schneider Electric BACnet points lists

Source: BACnet Integration Manual: PIR Ready SE7200, SE7300 & SER7300 Series (24 Vac zoning, fan coil and line-voltage fan coil controllers) · IG-SE7000-BNET24VAC-A4.EN.4.2013.v1 · rev. April 2013. Object names, instances and units are reproduced as published; descriptions are our own.