Room humidity and temperature sensor (wall) · BACnet points list
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) BACnet points list
Updated 6 November 2026
The SpaceLogic SLP humidity/temperature sensor reports room temperature and humidity over BACnet MS/TP (or Modbus). It has the same object layout as the Veris HW2 plus two writable offset values for the temperature and humidity readings.
This page lists 15 BACnet objects for the Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
- Equipment
- Room humidity and temperature sensor (wall)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 15 (13 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Vendor ID + MS/TP address (nnn)
- Also known as
- SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Set the MS/TP address and BACnet mode on the DIP switches, then read room temperature and humidity; use AV 7/AV 8 to trim the readings once.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Room Temperature | Room temperature | Read |
| AI 2 | Room Humidity | Room relative humidity, % | Read |
| AV 1 | Temperature Setpoint* | Occupant temperature setpoint, 0-50 | Write |
| BV 5 | Occupancy Override | Override button state: active = not occupied | Write |
| MV 2 | Fan Speed* | Occupant fan speed selection, 1-5 | Write |
Network setup
- BACnet MS/TP on RS-485: DIP switch ADDRESS positions 1-7 set the MAC (0-127 for BACnet), position 8 selects BACnet or Modbus.
- Baud rates for BACnet: 9600, 19200, 38400, 76800, set on the CONFIG DIP switch.
- Device instance = Vendor_ID followed by the MS/TP address (e.g. 133nnn); it can be rewritten in the device object.
Watch out for
- Occupancy Override logic is inverted: active means not occupied.
- Offsets (AV 7/AV 8) are preserved settings; write them once.
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Room Temperature | Room temperature | °C or °F | Read | |
| AImin | 2 | Room Humidity | Room relative humidity | %RH | Read | |
| AVmin | 1 | Temperature Setpoint* | Temperature setpoint, 0-50 | °C | Write | |
| AV | 2 | Humidity Setpoint* | Humidity setpoint, 0-100 | %RH | Write | |
| AV | 7 | Temperature Offset* | Offset added to temperature reading, -5 to 5 | Write | ||
| AV | 8 | Humidity Offset* | Offset added to humidity reading, -10 to 10 | Write | ||
| BV | 2 | Touch Disable* | Disables touch response when active | Write | 0=Touch enabled, 1=Touch disabled | |
| BV | 4 | Temperature Units* | Display units | Write | 0=Celsius, 1=Fahrenheit | |
| BVmin | 5 | Occupancy Override | Occupancy override (active = room not occupied) | Write | 0=Occupied, 1=Not occupied | |
| BV | 6 | Screen Timeout* | Enables screen timeout | Write | 0=Disabled, 1=Enabled | |
| BV | 7 | Display Humidity* | Shows humidity on the screen | Write | 0=Hidden, 1=Shown | |
| BV | 11 | Select Temperature Display* | Main screen shows setpoint (active) or room temperature | Write | 0=Room temp on main screen, 1=Setpoint on main screen | |
| BV | 13 | Display Setpoint* | Shows temperature setpoint on home screen | Write | 0=Hidden, 1=Shown | |
| MV | 1 | Screen Color Set* | Screen color theme, 1-4 | Write | ||
| MVmin | 2 | Fan Speed* | Fan speed selection, 1-5 | Write |
No points match these filters.
Object ID lookup: Schneider Electric SpaceLogic SLP Series humidity and temperature sensor point IDs by name
AI1Room TemperatureAI2Room HumidityAV1Temperature Setpoint*AV2Humidity Setpoint*AV7Temperature Offset*AV8Humidity Offset*BV2Touch Disable*BV4Temperature Units*BV5Occupancy OverrideBV6Screen Timeout*BV7Display Humidity*BV11Select Temperature Display*BV13Display Setpoint*MV1Screen Color Set*MV2Fan Speed*
Integration notes
- Names with * are preserved through power outages; avoid writing them cyclically.
- Touchscreen setpoint, fan speed, display and color objects only matter on touchscreen models.
- Same object set as the Veris HW2 Protocol Series sensor plus AV 7/AV 8 offsets.
- Source: SpaceLogic SLP Series Humidity and Temperature Sensors installation instructions Z207903-0J (June 2024).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
How many BACnet points does the Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) have?
This list has 15 BACnet objects: 2 analog inputs, 4 analog values, 7 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) BACnet points are writable?
13 of the 15 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) BACnet documentation?
The source is SpaceLogic Sensors, SLP Series Humidity and Temperature Sensors - BACnet and Modbus Installation Instructions (Z207903-0J), revision 2024-06, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=Z207903.
What are the minimum BACnet points to integrate the Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)?
Start with AI 1 Room Temperature (Room temperature); AI 2 Room Humidity (Room relative humidity, %); AV 1 Temperature Setpoint* (Occupant temperature setpoint, 0-50); BV 5 Occupancy Override (Override button state: active = not occupied); MV 2 Fan Speed* (Occupant fan speed selection, 1-5).
How do I check these points on the real SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Multi-circuit branch power meter (high density)
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Schneider Electric (ex-Veris) PowerLogic HDPM6000 head units with busway, strip or retrofit measurement modules, on BACnet IP over Ethernet.
Also known as: HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Schneider Electric PowerLogic PM5300 series power meters with the Ethernet port (PM5320, PM5340, PM5341) using BACnet IP.
Also known as: PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Zone controller (room thermostat)
Schneider Electric SE7200 Series PIR Ready Zoning Controller
Schneider Electric PIR-ready SE7200 series 24 Vac zoning controllers (SE7200C5x45B, SE7200F5x45B).
Also known as: SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Schneider Electric PIR-ready SER7300 series line-voltage fan coil controllers: SER7300, SER7305, SER7350 and SER7355 (A versions).
Also known as: SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B - Pressure-dependent VAV zone controller
Schneider Electric SEZ7260 Zoning System Zone Controller
Schneider Electric SEZ7260 zone controllers (F model with floating damper and AO2, C model) used with SEZ7656 rooftop controllers in pressure-dependent zoning systems.
Also known as: SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B - Rooftop unit controller for zoning systems
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Schneider Electric SEZ7656 rooftop controllers (R conventional, H heat pump, F modulating heat, E economizer) that run a rooftop unit for a group of SEZ7260 zone controllers.
Also known as: SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Schneider Electric SpaceLogic SE8000-series SER8350 room controllers for line-voltage fan coil units.
Also known as: SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil - Rooftop unit controller (room thermostat, rooftop or heat-pump units)
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 6500 (rooftop unit / heat pump) version.
Also known as: SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump
Source: SpaceLogic Sensors, SLP Series Humidity and Temperature Sensors - BACnet and Modbus Installation Instructions · Z207903-0J · rev. 2024-06. Object names, instances and units are reproduced as published; descriptions are our own.