Room humidity and temperature sensor (wall) · BACnet points list

Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The SpaceLogic SLP humidity/temperature sensor reports room temperature and humidity over BACnet MS/TP (or Modbus). It has the same object layout as the Veris HW2 plus two writable offset values for the temperature and humidity readings.

This page lists 15 BACnet objects for the Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.

Manufacturer
Schneider Electric
Model
SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Equipment
Room humidity and temperature sensor (wall)
Equipment type
Thermostats, sensors & meters
BACnet objects
15 (13 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Vendor ID + MS/TP address (nnn)
Also known as
SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903
Source document
SpaceLogic Sensors, SLP Series Humidity and Temperature Sensors - BACnet and Modbus Installation Instructions · Z207903-0J · rev. 2024-06
Download CSV 15 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.

BMS integration notes: Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)

Integration in brief

Set the MS/TP address and BACnet mode on the DIP switches, then read room temperature and humidity; use AV 7/AV 8 to trim the readings once.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Room TemperatureRoom temperatureRead
AI 2Room HumidityRoom relative humidity, %Read
AV 1Temperature Setpoint*Occupant temperature setpoint, 0-50Write
BV 5Occupancy OverrideOverride button state: active = not occupiedWrite
MV 2Fan Speed*Occupant fan speed selection, 1-5Write

Network setup

Watch out for

Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

15 of 15 shown
Type
BinaryMulti-state
Access
Show
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1Room TemperatureRoom temperature°C or °FRead
AImin2Room HumidityRoom relative humidity%RHRead
AVmin1Temperature Setpoint*Temperature setpoint, 0-50°CWrite
AV2Humidity Setpoint*Humidity setpoint, 0-100%RHWrite
AV7Temperature Offset*Offset added to temperature reading, -5 to 5Write
AV8Humidity Offset*Offset added to humidity reading, -10 to 10Write
BV2Touch Disable*Disables touch response when activeWrite0=Touch enabled, 1=Touch disabled
BV4Temperature Units*Display unitsWrite0=Celsius, 1=Fahrenheit
BVmin5Occupancy OverrideOccupancy override (active = room not occupied)Write0=Occupied, 1=Not occupied
BV6Screen Timeout*Enables screen timeoutWrite0=Disabled, 1=Enabled
BV7Display Humidity*Shows humidity on the screenWrite0=Hidden, 1=Shown
BV11Select Temperature Display*Main screen shows setpoint (active) or room temperatureWrite0=Room temp on main screen, 1=Setpoint on main screen
BV13Display Setpoint*Shows temperature setpoint on home screenWrite0=Hidden, 1=Shown
MV1Screen Color Set*Screen color theme, 1-4Write
MVmin2Fan Speed*Fan speed selection, 1-5Write
Object ID lookup: Schneider Electric SpaceLogic SLP Series humidity and temperature sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)

How many BACnet points does the Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) have?

This list has 15 BACnet objects: 2 analog inputs, 4 analog values, 7 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) BACnet points are writable?

13 of the 15 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP) BACnet documentation?

The source is SpaceLogic Sensors, SLP Series Humidity and Temperature Sensors - BACnet and Modbus Installation Instructions (Z207903-0J), revision 2024-06, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=Z207903.

What are the minimum BACnet points to integrate the Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)?

Start with AI 1 Room Temperature (Room temperature); AI 2 Room Humidity (Room relative humidity, %); AV 1 Temperature Setpoint* (Occupant temperature setpoint, 0-50); BV 5 Occupancy Override (Override button state: active = not occupied); MV 2 Fan Speed* (Occupant fan speed selection, 1-5).

How do I check these points on the real SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Schneider Electric BACnet points lists

Source: SpaceLogic Sensors, SLP Series Humidity and Temperature Sensors - BACnet and Modbus Installation Instructions · Z207903-0J · rev. 2024-06. Object names, instances and units are reproduced as published; descriptions are our own.