Power and energy meter (BACnet IP) · BACnet points list

Schneider Electric PowerLogic PM5300 power meter (BACnet IP) BACnet points list

Updated 6 November 2026

Short answer

The PM5300 Ethernet models have a fixed, read-only BACnet IP object list: about 110 Analog Inputs for current, voltage, unbalance, power, power factor, energy (including 4 tariffs), demand, THD and meter setup values, plus Binary Inputs for two digital inputs and outputs and Multi-State Inputs for power system type, VT connection, demand methods and I/O modes. Object instances match the meter register numbers.

This page lists 127 BACnet objects for the Schneider Electric PowerLogic PM5300 power meter (BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.

Manufacturer
Schneider Electric
Model
PowerLogic PM5300 power meter (BACnet IP)
Equipment
Power and energy meter (BACnet IP)
Equipment type
Thermostats, sensors & meters
BACnet objects
127 (0 writable)
Transport
BACnet IP
Firmware
2.00 or later (BACnet IP support)
Also known as
PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340
Source document
PowerLogic PM5300 series User manual (BACnet objects section) · EAV15107-EN11 · rev. 10/2023
Download CSV 127 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.

BMS integration notes: Schneider Electric PowerLogic PM5300 power meter (BACnet IP)

Integration in brief

Enable BACnet IP on the meter and set a unique Device ID, then read total power, energy, demand, power factor, average voltage and current. The meter is monitoring-only over BACnet.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3060Active Power - TotalTotal active power, kWRead
AI 2700Active Energy DelvdActive energy delivered, kWhRead
AI 3766Dmd - Active Power PresentPresent active power demand, kWRead
AI 3084Power Factor - TotalTotal power factorRead
AI 3026Voltage - Avg L-LAverage line-to-line voltageRead
AI 3010Current - AvgAverage phase currentRead
AI 3110FrequencySystem frequency, HzRead

Network setup

Watch out for

Schneider Electric PowerLogic PM5300 power meter (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

127 of 127 shown
Type
AnalogBinaryMulti-state
Show
Schneider Electric PowerLogic PM5300 power meter (BACnet IP) BACnet Points List
DescriptionStates
AI3000Current - Ph ACurrent phase AARead
AI3002Current - Ph BCurrent phase BARead
AI3004Current - Ph CCurrent phase CARead
AI3006Current - NeutralNeutral currentARead
AI3008Current - GroundGround currentARead
AImin3010Current - AvgCurrent averageARead
AI3012Current Unb - Ph ACurrent unbalance phase A%Read
AI3014Current Unb - Ph BCurrent unbalance phase B%Read
AI3016Current Unb - Ph CCurrent unbalance phase C%Read
AI3018Current Unb - WorstCurrent unbalance worst%Read
AI3020Voltage - A-BVoltage A-BVRead
AI3022Voltage - B-CVoltage B-CVRead
AI3024Voltage - C-AVoltage C-AVRead
AImin3026Voltage - Avg L-LVoltage L-L AvgVRead
AI3028Voltage - A-NVoltage A-NVRead
AI3030Voltage - B-NVoltage B-NVRead
AI3032Voltage - C-NVoltage C-NVRead
AI3036Voltage - Avg L-NVoltage L-N AvgVRead
AI3038Voltage Unb - A-BVoltage unbalance A-B%Read
AI3040Voltage Unb - B-CVoltage unbalance B-C%Read
AI3042Voltage Unb - C-AVoltage unbalance C-A%Read
AI3044Voltage Unb - Worst L-LVoltage unbalance L-L worst%Read
AI3046Voltage Unb - A-NVoltage unbalance A-N%Read
AI3048Voltage Unb - B-NVoltage unbalance B-N%Read
AI3050Voltage Unb - C-NVoltage unbalance C-N%Read
AI3052Voltage Unb - Worst L-NVoltage unbalance L-N worst%Read
AImin3110FrequencyFrequencyHzRead
AI3054Active Power - Ph AActive power phase AkWRead
AI3056Active Power - Ph BActive power phase BkWRead
AI3058Active Power - Ph CActive power phase CkWRead
AImin3060Active Power - TotalActive power totalkWRead
AI3062Reactive Power - Ph AReactive power phase AkVARRead
AI3064Reactive Power - Ph BReactive power phase BkVARRead
AI3066Reactive Power - Ph CReactive power phase CkVARRead
AI3068Reactive Power - TotalReactive power totalkVARRead
AI3070Apparent Power - Ph AApparent power phase AkVARead
AI3072Apparent Power - Ph BApparent power phase BkVARead
AI3074Apparent Power - Ph CApparent power phase CkVARead
AI3076Apparent Power - TotalApparent power totalkVARead
AI3078Power Factor - Ph APower factor phase ARead
AI3080Power Factor - Ph BPower factor phase BRead
AI3082Power Factor - Ph CPower factor phase CRead
AImin3084Power Factor - TotalPower Factor TotalRead
AImin2700Active Energy DelvdActive energy deliveredkWhRead
AI2702Active Energy RcvdActive energy receivedkWhRead
AI2704Active Energy Delvd + RcvdActive energy delivered + receivedkWhRead
AI2706Active Energy Delvd - RcvdActive energy delivered – receivedkWhRead
AI2708Reactive Energy DelvdReactive energy deliveredkVARhRead
AI2710Reactive Energy RcvdReactive energy receivedkVARhRead
AI2712Reactive Energy Delvd + RcvdReactive energy delivered + receivedkVARhRead
AI2714Reactive Energy Delvd - RcvdReactive energy delivered – receivedkVARhRead
AI2716Apparent Energy DelvdApparent energy deliveredkVAhRead
AI2718Apparent Energy RcvdApparent energy receivedkVAhRead
AI2720Apparent Energy Delvd + RcvdApparent energy delivered + receivedkVAhRead
AI2722Apparent Energy Delvd - RcvdApparent energy delivered – receivedkVAhRead
AI4191Applicable Tariff Energy RateActive tariff: 0 = multi-tariff off, 1-8 = tariff numberRead
AI4800Active Energy Delvd (Tariff 1)Tariff 1 active energy importkWhRead
AI4802Active Energy Delvd (Tariff 2)Tariff 2 active energy importkWhRead
AI4804Active Energy Delvd (Tariff 3)Tariff 3 active energy importkWhRead
AI4806Active Energy Delvd (Tariff 4)Tariff 4 active energy importkWhRead
AI3764Dmd - Active Power LastDemand - Active power lastkWRead
AImin3766Dmd - Active Power PresentDemand - Active power presentkWRead
AI3768Dmd - Active Power PredDemand - Active power predictedkWRead
AI3770Dmd - Active Power PeakDemand - Active power peakkWRead
AI3780Dmd - Reactive Power LastDemand - Reactive power lastkVARRead
AI3782Dmd - Reactive Power PresentDemand - Reactive power presentkVARRead
AI3784Dmd - Reactive Power PredDemand - Reactive power predictedkVARRead
AI3786Dmd - Reactive Power PeakDemand - Reactive power peakkVARRead
AI3796Dmd - Apparent Power LastDemand - Apparent power lastkVARead
AI3798Dmd - Apparent Power PresentDemand - Apparent power presentkVARead
AI3800Dmd - Apparent Power PredDemand - Apparent power predictedkVARead
AI3802Dmd - Apparent Power PeakDemand - Apparent power peakkVARead
AI3876Dmd - Average Current LastDemand - Average current lastARead
AI3878Dmd - Avg Current PresentDemand - Average current presentARead
AI3880Dmd - Average Current PredDemand - Average current predictedARead
AI3882Dmd - Average Current PeakDemand - Average current peakARead
AI21300THD Current - Ph ATHD Current A%Read
AI21302THD Current - Ph BTHD Current B%Read
AI21304THD Current - Ph CTHD Current C%Read
AI21306THD Current - Ph NTHD Current N%Read
AI21308THD Current - Ph GTHD Current G%Read
AI21310thd Current - Ph Athd Current A%Read
AI21312thd Current - Ph Bthd Current B%Read
AI21314thd Current - Ph Cthd Current C%Read
AI21316thd Current - Ph Nthd Current N%Read
AI21318thd Current - Ph Gthd Current G%Read
AI21320Total Dmd DistortionTotal Demand Distortion%Read
AI21322THD Voltage - A-BTHD Voltage A-B%Read
AI21324THD Voltage - B-CTHD Voltage B-C%Read
AI21326THD Voltage - C-ATHD Voltage C-A%Read
AI21328THD Voltage - Avg L-LTHD Voltage L-L%Read
AI21330THD Voltage - A-NTHD Voltage A-N%Read
AI21332THD Voltage - B–NTHD Voltage B-N%Read
AI21334THD Voltage - C-NTHD Voltage C-N%Read
AI21338THD Voltage - Avg L-NTHD Voltage L-N%Read
AI21340thd Voltage - A-Bthd Voltage A-B%Read
AI21342thd Voltage - B-Cthd Voltage B-C%Read
AI21344thd Voltage - C-Athd Voltage C-A%Read
AI21346thd Voltage - Avg L-Lthd Voltage L-L%Read
AI21348thd Voltage - A-Nthd Voltage A-N%Read
AI21350thd Voltage - B-Nthd Voltage B-N%Read
AI21352thd Voltage - C-Nthd Voltage C-N%Read
AI21356thd Voltage - Avg L-Nthd Voltage L-N%Read
AI2000Time since last meter power upTime since the meter was last powered upsRead
AI2004Meter operation timerTotal meter operation timesRead
AI2014Number of phasesNumber of phases (1 or 3)Read
AI2015Number of wiresNumber of wires (2, 3 or 4)Read
AI2017Nominal frequencyNominal frequency (50 or 60)HzRead
AI2025Number of VTsNumber of VTs (0, 2 or 3)Read
AI2026VT primaryVT PrimaryVRead
AI2028VTsecondaryVT SecondaryVRead
AI2029Number of CTsNumber of CTs 1, 2, 3Read
AI2030CT primaryCT PrimaryARead
AI2031CTsecondaryCT SecondaryARead
BI38416Digital Input 1Digital input 1 status (status-input mode)Read0=on, 1=off
BI38417Digital Input 2Digital input 2 status (status-input mode)Read0=on, 1=off
BI38448Digital Output 1Digital output 1 statusRead0=on, 1=off
BI38449Digital Output 2Digital output 2 statusRead0=on, 1=off
MI2016Power System TypePower system configurationRead0=1PH2W L-N, 1=1PH2W L-L, 2=1PH3W L-L with N, 3=3PH3W ungrounded delta, 4=3PH3W corner grounded delta, 5=3PH3W ungrounded wye, 6=3PH3W grounded wye, 7=3PH3W resistance grounded wye, 8=3PH4W center-tapped open delta, 9=3PH4W center-tapped delta, 10=3PH4W ungrounded wye, 11=3PH4W grounded wye, 12=3PH4W resistance grounded wye
MI2036VT Connection TypeVT connection typeRead0=Direct connect, 1=Delta (2 VT), 2=Wye (3 VT), 3=L-N (1 VT), 4=L-L (1 VT), 5=L-L with N (2 VT)
MI3701Demand Method - PowerPower demand methodRead0=Thermal demand, 1=Timed interval sliding block, 2=Timed interval block, 3=Timed interval rolling block, 4=Input synchronized block, 5=Input synchronized rolling block, 6=Command synchronized block, 7=Command synchronized rolling block, 8=Clock synchronized block, 9=Clock synchronized rolling block
MI3711Demand Method - CurrentCurrent demand methodRead0=Thermal demand, 1=Timed interval sliding block, 2=Timed interval block, 3=Timed interval rolling block, 4=Input synchronized block, 5=Input synchronized rolling block, 6=Command synchronized block, 7=Command synchronized rolling block, 8=Clock synchronized block, 9=Clock synchronized rolling block
MI3721Demand Method - Input MeteringInput metering demand methodRead0=Thermal demand, 1=Timed interval sliding block, 2=Timed interval block, 3=Timed interval rolling block, 4=Input synchronized block, 5=Input synchronized rolling block, 6=Command synchronized block, 7=Command synchronized rolling block, 8=Clock synchronized block, 9=Clock synchronized rolling block
MI7274Digital Input 1 ModeDigital input 1 control modeRead0=Normal (Alarm), 1=Demand Interval Sync Pulse, 2=Multi-tariff Control
MI7298Digital Input 2 ModeDigital input 2 control modeRead0=Normal (Alarm), 1=Demand Interval Sync Pulse, 2=Multi-tariff Control
MI9673Digital Output Mode 1Digital output 1 control modeRead0=External, 1=Demand Sync, 2=Alarm, 3=Energy
MI9681Digital Output Mode 2Digital output 2 control modeRead0=External, 1=Demand Sync, 2=Alarm, 3=Energy
Object ID lookup: Schneider Electric PowerLogic PM5300 power meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PowerLogic PM5300 power meter (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Schneider Electric PowerLogic PM5300 power meter (BACnet IP)

How many BACnet points does the Schneider Electric PowerLogic PM5300 power meter (BACnet IP) have?

This list has 127 BACnet objects: 114 analog inputs, 4 binary inputs, 9 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Schneider Electric PowerLogic PM5300 power meter (BACnet IP) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Schneider Electric PowerLogic PM5300 power meter (BACnet IP) BACnet documentation?

The source is PowerLogic PM5300 series User manual (BACnet objects section) (EAV15107-EN11), revision 10/2023, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=EAV15107-EN.

What are the minimum BACnet points to integrate the Schneider Electric PowerLogic PM5300 power meter (BACnet IP)?

Start with AI 3060 Active Power - Total (Total active power, kW); AI 2700 Active Energy Delvd (Active energy delivered, kWh); AI 3766 Dmd - Active Power Present (Present active power demand, kW); AI 3084 Power Factor - Total (Total power factor); AI 3026 Voltage - Avg L-L (Average line-to-line voltage); AI 3010 Current - Avg (Average phase current); AI 3110 Frequency (System frequency, Hz).

How do I check these points on the real PowerLogic PM5300 power meter (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Schneider Electric BACnet points lists

Source: PowerLogic PM5300 series User manual (BACnet objects section) · EAV15107-EN11 · rev. 10/2023. Object names, instances and units are reproduced as published; descriptions are our own.