Power and energy meter (BACnet IP) · BACnet points list
Schneider Electric PowerLogic PM5300 power meter (BACnet IP) BACnet points list
Updated 6 November 2026
The PM5300 Ethernet models have a fixed, read-only BACnet IP object list: about 110 Analog Inputs for current, voltage, unbalance, power, power factor, energy (including 4 tariffs), demand, THD and meter setup values, plus Binary Inputs for two digital inputs and outputs and Multi-State Inputs for power system type, VT connection, demand methods and I/O modes. Object instances match the meter register numbers.
This page lists 127 BACnet objects for the Schneider Electric PowerLogic PM5300 power meter (BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- PowerLogic PM5300 power meter (BACnet IP)
- Equipment
- Power and energy meter (BACnet IP)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 127 (0 writable)
- Transport
- BACnet IP
- Firmware
- 2.00 or later (BACnet IP support)
- Also known as
- PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Enable BACnet IP on the meter and set a unique Device ID, then read total power, energy, demand, power factor, average voltage and current. The meter is monitoring-only over BACnet.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 3060 | Active Power - Total | Total active power, kW | Read |
| AI 2700 | Active Energy Delvd | Active energy delivered, kWh | Read |
| AI 3766 | Dmd - Active Power Present | Present active power demand, kW | Read |
| AI 3084 | Power Factor - Total | Total power factor | Read |
| AI 3026 | Voltage - Avg L-L | Average line-to-line voltage | Read |
| AI 3010 | Current - Avg | Average phase current | Read |
| AI 3110 | Frequency | System frequency, Hz | Read |
Network setup
- Enable BACnet IP and set the Device ID, UDP port (default 47808) and BBMD/foreign-device settings on the display (Maint > Setup > Comm > BACnet) or the meter webpages.
- The Device ID ships as the last 6 digits of the serial number; it must be unique on the network.
- Up to 20 COV subscriptions are supported on AI, BI and MSI objects; no segmentation, max APDU 1476 bytes.
Watch out for
- All configuration objects are read-only over BACnet; change meter settings on the display, webpages or ION Setup.
- Out_Of_Service is writable for testing; set it back to false or the BMS sees the test value instead of the measurement.
- Digital input and output status BIs read 0 = on, 1 = off as printed in the manual; check the polarity on site.
Schneider Electric PowerLogic PM5300 power meter (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 3000 | Current - Ph A | Current phase A | A | Read | |
| AI | 3002 | Current - Ph B | Current phase B | A | Read | |
| AI | 3004 | Current - Ph C | Current phase C | A | Read | |
| AI | 3006 | Current - Neutral | Neutral current | A | Read | |
| AI | 3008 | Current - Ground | Ground current | A | Read | |
| AImin | 3010 | Current - Avg | Current average | A | Read | |
| AI | 3012 | Current Unb - Ph A | Current unbalance phase A | % | Read | |
| AI | 3014 | Current Unb - Ph B | Current unbalance phase B | % | Read | |
| AI | 3016 | Current Unb - Ph C | Current unbalance phase C | % | Read | |
| AI | 3018 | Current Unb - Worst | Current unbalance worst | % | Read | |
| AI | 3020 | Voltage - A-B | Voltage A-B | V | Read | |
| AI | 3022 | Voltage - B-C | Voltage B-C | V | Read | |
| AI | 3024 | Voltage - C-A | Voltage C-A | V | Read | |
| AImin | 3026 | Voltage - Avg L-L | Voltage L-L Avg | V | Read | |
| AI | 3028 | Voltage - A-N | Voltage A-N | V | Read | |
| AI | 3030 | Voltage - B-N | Voltage B-N | V | Read | |
| AI | 3032 | Voltage - C-N | Voltage C-N | V | Read | |
| AI | 3036 | Voltage - Avg L-N | Voltage L-N Avg | V | Read | |
| AI | 3038 | Voltage Unb - A-B | Voltage unbalance A-B | % | Read | |
| AI | 3040 | Voltage Unb - B-C | Voltage unbalance B-C | % | Read | |
| AI | 3042 | Voltage Unb - C-A | Voltage unbalance C-A | % | Read | |
| AI | 3044 | Voltage Unb - Worst L-L | Voltage unbalance L-L worst | % | Read | |
| AI | 3046 | Voltage Unb - A-N | Voltage unbalance A-N | % | Read | |
| AI | 3048 | Voltage Unb - B-N | Voltage unbalance B-N | % | Read | |
| AI | 3050 | Voltage Unb - C-N | Voltage unbalance C-N | % | Read | |
| AI | 3052 | Voltage Unb - Worst L-N | Voltage unbalance L-N worst | % | Read | |
| AImin | 3110 | Frequency | Frequency | Hz | Read | |
| AI | 3054 | Active Power - Ph A | Active power phase A | kW | Read | |
| AI | 3056 | Active Power - Ph B | Active power phase B | kW | Read | |
| AI | 3058 | Active Power - Ph C | Active power phase C | kW | Read | |
| AImin | 3060 | Active Power - Total | Active power total | kW | Read | |
| AI | 3062 | Reactive Power - Ph A | Reactive power phase A | kVAR | Read | |
| AI | 3064 | Reactive Power - Ph B | Reactive power phase B | kVAR | Read | |
| AI | 3066 | Reactive Power - Ph C | Reactive power phase C | kVAR | Read | |
| AI | 3068 | Reactive Power - Total | Reactive power total | kVAR | Read | |
| AI | 3070 | Apparent Power - Ph A | Apparent power phase A | kVA | Read | |
| AI | 3072 | Apparent Power - Ph B | Apparent power phase B | kVA | Read | |
| AI | 3074 | Apparent Power - Ph C | Apparent power phase C | kVA | Read | |
| AI | 3076 | Apparent Power - Total | Apparent power total | kVA | Read | |
| AI | 3078 | Power Factor - Ph A | Power factor phase A | Read | ||
| AI | 3080 | Power Factor - Ph B | Power factor phase B | Read | ||
| AI | 3082 | Power Factor - Ph C | Power factor phase C | Read | ||
| AImin | 3084 | Power Factor - Total | Power Factor Total | Read | ||
| AImin | 2700 | Active Energy Delvd | Active energy delivered | kWh | Read | |
| AI | 2702 | Active Energy Rcvd | Active energy received | kWh | Read | |
| AI | 2704 | Active Energy Delvd + Rcvd | Active energy delivered + received | kWh | Read | |
| AI | 2706 | Active Energy Delvd - Rcvd | Active energy delivered – received | kWh | Read | |
| AI | 2708 | Reactive Energy Delvd | Reactive energy delivered | kVARh | Read | |
| AI | 2710 | Reactive Energy Rcvd | Reactive energy received | kVARh | Read | |
| AI | 2712 | Reactive Energy Delvd + Rcvd | Reactive energy delivered + received | kVARh | Read | |
| AI | 2714 | Reactive Energy Delvd - Rcvd | Reactive energy delivered – received | kVARh | Read | |
| AI | 2716 | Apparent Energy Delvd | Apparent energy delivered | kVAh | Read | |
| AI | 2718 | Apparent Energy Rcvd | Apparent energy received | kVAh | Read | |
| AI | 2720 | Apparent Energy Delvd + Rcvd | Apparent energy delivered + received | kVAh | Read | |
| AI | 2722 | Apparent Energy Delvd - Rcvd | Apparent energy delivered – received | kVAh | Read | |
| AI | 4191 | Applicable Tariff Energy Rate | Active tariff: 0 = multi-tariff off, 1-8 = tariff number | Read | ||
| AI | 4800 | Active Energy Delvd (Tariff 1) | Tariff 1 active energy import | kWh | Read | |
| AI | 4802 | Active Energy Delvd (Tariff 2) | Tariff 2 active energy import | kWh | Read | |
| AI | 4804 | Active Energy Delvd (Tariff 3) | Tariff 3 active energy import | kWh | Read | |
| AI | 4806 | Active Energy Delvd (Tariff 4) | Tariff 4 active energy import | kWh | Read | |
| AI | 3764 | Dmd - Active Power Last | Demand - Active power last | kW | Read | |
| AImin | 3766 | Dmd - Active Power Present | Demand - Active power present | kW | Read | |
| AI | 3768 | Dmd - Active Power Pred | Demand - Active power predicted | kW | Read | |
| AI | 3770 | Dmd - Active Power Peak | Demand - Active power peak | kW | Read | |
| AI | 3780 | Dmd - Reactive Power Last | Demand - Reactive power last | kVAR | Read | |
| AI | 3782 | Dmd - Reactive Power Present | Demand - Reactive power present | kVAR | Read | |
| AI | 3784 | Dmd - Reactive Power Pred | Demand - Reactive power predicted | kVAR | Read | |
| AI | 3786 | Dmd - Reactive Power Peak | Demand - Reactive power peak | kVAR | Read | |
| AI | 3796 | Dmd - Apparent Power Last | Demand - Apparent power last | kVA | Read | |
| AI | 3798 | Dmd - Apparent Power Present | Demand - Apparent power present | kVA | Read | |
| AI | 3800 | Dmd - Apparent Power Pred | Demand - Apparent power predicted | kVA | Read | |
| AI | 3802 | Dmd - Apparent Power Peak | Demand - Apparent power peak | kVA | Read | |
| AI | 3876 | Dmd - Average Current Last | Demand - Average current last | A | Read | |
| AI | 3878 | Dmd - Avg Current Present | Demand - Average current present | A | Read | |
| AI | 3880 | Dmd - Average Current Pred | Demand - Average current predicted | A | Read | |
| AI | 3882 | Dmd - Average Current Peak | Demand - Average current peak | A | Read | |
| AI | 21300 | THD Current - Ph A | THD Current A | % | Read | |
| AI | 21302 | THD Current - Ph B | THD Current B | % | Read | |
| AI | 21304 | THD Current - Ph C | THD Current C | % | Read | |
| AI | 21306 | THD Current - Ph N | THD Current N | % | Read | |
| AI | 21308 | THD Current - Ph G | THD Current G | % | Read | |
| AI | 21310 | thd Current - Ph A | thd Current A | % | Read | |
| AI | 21312 | thd Current - Ph B | thd Current B | % | Read | |
| AI | 21314 | thd Current - Ph C | thd Current C | % | Read | |
| AI | 21316 | thd Current - Ph N | thd Current N | % | Read | |
| AI | 21318 | thd Current - Ph G | thd Current G | % | Read | |
| AI | 21320 | Total Dmd Distortion | Total Demand Distortion | % | Read | |
| AI | 21322 | THD Voltage - A-B | THD Voltage A-B | % | Read | |
| AI | 21324 | THD Voltage - B-C | THD Voltage B-C | % | Read | |
| AI | 21326 | THD Voltage - C-A | THD Voltage C-A | % | Read | |
| AI | 21328 | THD Voltage - Avg L-L | THD Voltage L-L | % | Read | |
| AI | 21330 | THD Voltage - A-N | THD Voltage A-N | % | Read | |
| AI | 21332 | THD Voltage - B–N | THD Voltage B-N | % | Read | |
| AI | 21334 | THD Voltage - C-N | THD Voltage C-N | % | Read | |
| AI | 21338 | THD Voltage - Avg L-N | THD Voltage L-N | % | Read | |
| AI | 21340 | thd Voltage - A-B | thd Voltage A-B | % | Read | |
| AI | 21342 | thd Voltage - B-C | thd Voltage B-C | % | Read | |
| AI | 21344 | thd Voltage - C-A | thd Voltage C-A | % | Read | |
| AI | 21346 | thd Voltage - Avg L-L | thd Voltage L-L | % | Read | |
| AI | 21348 | thd Voltage - A-N | thd Voltage A-N | % | Read | |
| AI | 21350 | thd Voltage - B-N | thd Voltage B-N | % | Read | |
| AI | 21352 | thd Voltage - C-N | thd Voltage C-N | % | Read | |
| AI | 21356 | thd Voltage - Avg L-N | thd Voltage L-N | % | Read | |
| AI | 2000 | Time since last meter power up | Time since the meter was last powered up | s | Read | |
| AI | 2004 | Meter operation timer | Total meter operation time | s | Read | |
| AI | 2014 | Number of phases | Number of phases (1 or 3) | Read | ||
| AI | 2015 | Number of wires | Number of wires (2, 3 or 4) | Read | ||
| AI | 2017 | Nominal frequency | Nominal frequency (50 or 60) | Hz | Read | |
| AI | 2025 | Number of VTs | Number of VTs (0, 2 or 3) | Read | ||
| AI | 2026 | VT primary | VT Primary | V | Read | |
| AI | 2028 | VTsecondary | VT Secondary | V | Read | |
| AI | 2029 | Number of CTs | Number of CTs 1, 2, 3 | Read | ||
| AI | 2030 | CT primary | CT Primary | A | Read | |
| AI | 2031 | CTsecondary | CT Secondary | A | Read | |
| BI | 38416 | Digital Input 1 | Digital input 1 status (status-input mode) | Read | 0=on, 1=off | |
| BI | 38417 | Digital Input 2 | Digital input 2 status (status-input mode) | Read | 0=on, 1=off | |
| BI | 38448 | Digital Output 1 | Digital output 1 status | Read | 0=on, 1=off | |
| BI | 38449 | Digital Output 2 | Digital output 2 status | Read | 0=on, 1=off | |
| MI | 2016 | Power System Type | Power system configuration | Read | 0=1PH2W L-N, 1=1PH2W L-L, 2=1PH3W L-L with N, 3=3PH3W ungrounded delta, 4=3PH3W corner grounded delta, 5=3PH3W ungrounded wye, 6=3PH3W grounded wye, 7=3PH3W resistance grounded wye, 8=3PH4W center-tapped open delta, 9=3PH4W center-tapped delta, 10=3PH4W ungrounded wye, 11=3PH4W grounded wye, 12=3PH4W resistance grounded wye | |
| MI | 2036 | VT Connection Type | VT connection type | Read | 0=Direct connect, 1=Delta (2 VT), 2=Wye (3 VT), 3=L-N (1 VT), 4=L-L (1 VT), 5=L-L with N (2 VT) | |
| MI | 3701 | Demand Method - Power | Power demand method | Read | 0=Thermal demand, 1=Timed interval sliding block, 2=Timed interval block, 3=Timed interval rolling block, 4=Input synchronized block, 5=Input synchronized rolling block, 6=Command synchronized block, 7=Command synchronized rolling block, 8=Clock synchronized block, 9=Clock synchronized rolling block | |
| MI | 3711 | Demand Method - Current | Current demand method | Read | 0=Thermal demand, 1=Timed interval sliding block, 2=Timed interval block, 3=Timed interval rolling block, 4=Input synchronized block, 5=Input synchronized rolling block, 6=Command synchronized block, 7=Command synchronized rolling block, 8=Clock synchronized block, 9=Clock synchronized rolling block | |
| MI | 3721 | Demand Method - Input Metering | Input metering demand method | Read | 0=Thermal demand, 1=Timed interval sliding block, 2=Timed interval block, 3=Timed interval rolling block, 4=Input synchronized block, 5=Input synchronized rolling block, 6=Command synchronized block, 7=Command synchronized rolling block, 8=Clock synchronized block, 9=Clock synchronized rolling block | |
| MI | 7274 | Digital Input 1 Mode | Digital input 1 control mode | Read | 0=Normal (Alarm), 1=Demand Interval Sync Pulse, 2=Multi-tariff Control | |
| MI | 7298 | Digital Input 2 Mode | Digital input 2 control mode | Read | 0=Normal (Alarm), 1=Demand Interval Sync Pulse, 2=Multi-tariff Control | |
| MI | 9673 | Digital Output Mode 1 | Digital output 1 control mode | Read | 0=External, 1=Demand Sync, 2=Alarm, 3=Energy | |
| MI | 9681 | Digital Output Mode 2 | Digital output 2 control mode | Read | 0=External, 1=Demand Sync, 2=Alarm, 3=Energy |
No points match these filters.
Object ID lookup: Schneider Electric PowerLogic PM5300 power meter point IDs by name
AI3000Current - Ph AAI3002Current - Ph BAI3004Current - Ph CAI3006Current - NeutralAI3008Current - GroundAI3010Current - AvgAI3012Current Unb - Ph AAI3014Current Unb - Ph BAI3016Current Unb - Ph CAI3018Current Unb - WorstAI3020Voltage - A-BAI3022Voltage - B-CAI3024Voltage - C-AAI3026Voltage - Avg L-LAI3028Voltage - A-NAI3030Voltage - B-NAI3032Voltage - C-NAI3036Voltage - Avg L-NAI3038Voltage Unb - A-BAI3040Voltage Unb - B-CAI3042Voltage Unb - C-AAI3044Voltage Unb - Worst L-LAI3046Voltage Unb - A-NAI3048Voltage Unb - B-NAI3050Voltage Unb - C-NAI3052Voltage Unb - Worst L-NAI3110FrequencyAI3054Active Power - Ph AAI3056Active Power - Ph BAI3058Active Power - Ph CAI3060Active Power - TotalAI3062Reactive Power - Ph AAI3064Reactive Power - Ph BAI3066Reactive Power - Ph CAI3068Reactive Power - TotalAI3070Apparent Power - Ph AAI3072Apparent Power - Ph BAI3074Apparent Power - Ph CAI3076Apparent Power - TotalAI3078Power Factor - Ph AAI3080Power Factor - Ph BAI3082Power Factor - Ph CAI3084Power Factor - TotalAI2700Active Energy DelvdAI2702Active Energy RcvdAI2704Active Energy Delvd + RcvdAI2706Active Energy Delvd - RcvdAI2708Reactive Energy DelvdAI2710Reactive Energy RcvdAI2712Reactive Energy Delvd + RcvdAI2714Reactive Energy Delvd - RcvdAI2716Apparent Energy DelvdAI2718Apparent Energy RcvdAI2720Apparent Energy Delvd + RcvdAI2722Apparent Energy Delvd - RcvdAI4191Applicable Tariff Energy RateAI4800Active Energy Delvd (Tariff 1)AI4802Active Energy Delvd (Tariff 2)AI4804Active Energy Delvd (Tariff 3)AI4806Active Energy Delvd (Tariff 4)AI3764Dmd - Active Power LastAI3766Dmd - Active Power PresentAI3768Dmd - Active Power PredAI3770Dmd - Active Power PeakAI3780Dmd - Reactive Power LastAI3782Dmd - Reactive Power PresentAI3784Dmd - Reactive Power PredAI3786Dmd - Reactive Power PeakAI3796Dmd - Apparent Power LastAI3798Dmd - Apparent Power PresentAI3800Dmd - Apparent Power PredAI3802Dmd - Apparent Power PeakAI3876Dmd - Average Current LastAI3878Dmd - Avg Current PresentAI3880Dmd - Average Current PredAI3882Dmd - Average Current PeakAI21300THD Current - Ph AAI21302THD Current - Ph BAI21304THD Current - Ph CAI21306THD Current - Ph NAI21308THD Current - Ph GAI21310thd Current - Ph AAI21312thd Current - Ph BAI21314thd Current - Ph CAI21316thd Current - Ph NAI21318thd Current - Ph GAI21320Total Dmd DistortionAI21322THD Voltage - A-BAI21324THD Voltage - B-CAI21326THD Voltage - C-AAI21328THD Voltage - Avg L-LAI21330THD Voltage - A-NAI21332THD Voltage - B–NAI21334THD Voltage - C-NAI21338THD Voltage - Avg L-NAI21340thd Voltage - A-BAI21342thd Voltage - B-CAI21344thd Voltage - C-AAI21346thd Voltage - Avg L-LAI21348thd Voltage - A-NAI21350thd Voltage - B-NAI21352thd Voltage - C-NAI21356thd Voltage - Avg L-NAI2000Time since last meter power upAI2004Meter operation timerAI2014Number of phasesAI2015Number of wiresAI2017Nominal frequencyAI2025Number of VTsAI2026VT primaryAI2028VTsecondaryAI2029Number of CTsAI2030CT primaryAI2031CTsecondaryBI38416Digital Input 1BI38417Digital Input 2BI38448Digital Output 1BI38449Digital Output 2MI2016Power System TypeMI2036VT Connection TypeMI3701Demand Method - PowerMI3711Demand Method - CurrentMI3721Demand Method - Input MeteringMI7274Digital Input 1 ModeMI7298Digital Input 2 ModeMI9673Digital Output Mode 1MI9681Digital Output Mode 2
Integration notes
- Points from the BACnet objects section (pages 50-57) of user manual EAV15107-EN11.
- BACnet IP is only on the models with an Ethernet port (PM5320, PM5340, PM5341).
- Compared with the PM5500 list, the PM5300 has 4 tariffs instead of 8, no per-phase demand objects and two digital inputs.
- Each AI has a default COV increment in the manual (e.g. 50 A for currents, 10 kW for power, 100 kWh for energy).
- The object list is fixed; nothing is writable except Out_Of_Service and COV_Increment.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PowerLogic PM5300 power meter (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
How many BACnet points does the Schneider Electric PowerLogic PM5300 power meter (BACnet IP) have?
This list has 127 BACnet objects: 114 analog inputs, 4 binary inputs, 9 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric PowerLogic PM5300 power meter (BACnet IP) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Schneider Electric PowerLogic PM5300 power meter (BACnet IP) BACnet documentation?
The source is PowerLogic PM5300 series User manual (BACnet objects section) (EAV15107-EN11), revision 10/2023, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=EAV15107-EN.
What are the minimum BACnet points to integrate the Schneider Electric PowerLogic PM5300 power meter (BACnet IP)?
Start with AI 3060 Active Power - Total (Total active power, kW); AI 2700 Active Energy Delvd (Active energy delivered, kWh); AI 3766 Dmd - Active Power Present (Present active power demand, kW); AI 3084 Power Factor - Total (Total power factor); AI 3026 Voltage - Avg L-L (Average line-to-line voltage); AI 3010 Current - Avg (Average phase current); AI 3110 Frequency (System frequency, Hz).
How do I check these points on the real PowerLogic PM5300 power meter (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Multi-circuit branch power meter (high density)
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Schneider Electric (ex-Veris) PowerLogic HDPM6000 head units with busway, strip or retrofit measurement modules, on BACnet IP over Ethernet.
Also known as: HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Zone controller (room thermostat)
Schneider Electric SE7200 Series PIR Ready Zoning Controller
Schneider Electric PIR-ready SE7200 series 24 Vac zoning controllers (SE7200C5x45B, SE7200F5x45B).
Also known as: SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Schneider Electric PIR-ready SER7300 series line-voltage fan coil controllers: SER7300, SER7305, SER7350 and SER7355 (A versions).
Also known as: SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B - Pressure-dependent VAV zone controller
Schneider Electric SEZ7260 Zoning System Zone Controller
Schneider Electric SEZ7260 zone controllers (F model with floating damper and AO2, C model) used with SEZ7656 rooftop controllers in pressure-dependent zoning systems.
Also known as: SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B - Rooftop unit controller for zoning systems
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Schneider Electric SEZ7656 rooftop controllers (R conventional, H heat pump, F modulating heat, E economizer) that run a rooftop unit for a group of SEZ7260 zone controllers.
Also known as: SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Schneider Electric SpaceLogic SE8000-series SER8350 room controllers for line-voltage fan coil units.
Also known as: SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350 - Room humidity and temperature sensor (wall)
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Schneider Electric SpaceLogic SLP Series wall humidity/temperature sensors (with or without touchscreen) set to BACnet MS/TP.
Also known as: SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil - Rooftop unit controller (room thermostat, rooftop or heat-pump units)
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 6500 (rooftop unit / heat pump) version.
Also known as: SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump
Source: PowerLogic PM5300 series User manual (BACnet objects section) · EAV15107-EN11 · rev. 10/2023. Object names, instances and units are reproduced as published; descriptions are our own.