- Home
- BACnet points lists
- Schneider Electric
- EM3570 series DIN Ethernet energy meter (BACnet IP)
Power and energy meter (BACnet IP) · BACnet points list
Schneider Electric EM3570 series DIN Ethernet energy meter (BACnet IP) BACnet points list
Updated 12 November 2026Unofficial source
The EM3570 is a compact three-phase DIN meter with two Ethernet ports, BACnet IP, Modbus TCP and SNMP. Its BACnet object list is read-only: Analog Inputs for current, voltage, per-phase and total power, power factor, frequency, delivered and received energy, and present and peak demand, plus Binary Inputs for its two status inputs and alarm relay. Object instances follow the Modbus register numbers.
This page lists 51 BACnet objects for the Schneider Electric EM3570 series DIN Ethernet energy meter (BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Schneider Electric’s documentation hosted by BACnet International catalog, not by Schneider Electric itself, so treat it as unofficial.
- Manufacturer
- Schneider Electric
- Model
- EM3570 series DIN Ethernet energy meter (BACnet IP)
- Equipment
- Power and energy meter (BACnet IP)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 51 (0 writable)
- Transport
- BACnet IP
- Firmware
- 1.9.0 (application 111.241.298)
- Also known as
- EM3570, METSEEM3570, METSEEM3570A, METSEEM3570X, METSEEM3570AX, EM70, EM3570 BACnet
- Source document
- EM3570 Protocol Implementation Conformance Statement · rev. 2024-08-06 (unofficial copy, hosted by BACnet International catalog)
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric EM3570 series DIN Ethernet energy meter (BACnet IP)
Give the meter an IP address and device ID, then read total power, delivered energy, demand, power factor, voltage and current. Nothing is controlled over BACnet.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 3060 | Active Power - Total | Total active power | Read |
| AI 3204 | Active Energy Delvd | Active energy delivered | Read |
| AI 3766 | Dmd - Active Power Present | Present active power demand | Read |
| AI 3084 | Power Factor - Total | Total power factor | Read |
| AI 3026 | Voltage - Avg L-L | Average line-to-line voltage | Read |
| AI 3010 | Current - Avg | Average phase current | Read |
| AI 3110 | Frequency | System frequency | Read |
Network setup
- BACnet IP only (no MS/TP); dual Ethernet ports allow daisy-chaining.
- Device Object_Identifier, Object_Name and Location are writable.
- No segmentation.
Watch out for
- Out_Of_Service is writable on AIs and BIs; leave it false.
Schneider Electric EM3570 series DIN Ethernet energy meter (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 3000 | Current - Ph A | Current phase A | Read | ||
| AI | 3002 | Current - Ph B | Current phase B | Read | ||
| AI | 3004 | Current - Ph C | Current phase C | Read | ||
| AImin | 3010 | Current - Avg | Current avg | Read | ||
| AI | 3020 | Voltage - A-B | Voltage A-B | Read | ||
| AI | 3022 | Voltage - B-C | Voltage B-C | Read | ||
| AI | 3024 | Voltage - C-A | Voltage C-A | Read | ||
| AImin | 3026 | Voltage - Avg L-L | Voltage avg L-L | Read | ||
| AI | 3028 | Voltage A-N | Voltage A-N | Read | ||
| AI | 3030 | Voltage B-N | Voltage B-N | Read | ||
| AI | 3032 | Voltage C-N | Voltage C-N | Read | ||
| AI | 3036 | Voltage - Avg L-N | Voltage avg L-N | Read | ||
| AI | 3054 | Active Power - Ph A | Active power phase A | Read | ||
| AI | 3056 | Active Power - Ph B | Active power phase B | Read | ||
| AI | 3058 | Active Power - Ph C | Active power phase C | Read | ||
| AImin | 3060 | Active Power - Total | Active power total | Read | ||
| AI | 3062 | Reactive Power - Ph A | Reactive power phase A | Read | ||
| AI | 3064 | Reactive Power - Ph B | Reactive power phase B | Read | ||
| AI | 3066 | Reactive Power - Ph C | Reactive power phase C | Read | ||
| AI | 3068 | Reactive Power - Total | Reactive power total | Read | ||
| AI | 3070 | Apparent Power - Ph A | Apparent power phase A | Read | ||
| AI | 3072 | Apparent Power - Ph B | Apparent power phase B | Read | ||
| AI | 3074 | Apparent Power - Ph C | Apparent power phase C | Read | ||
| AI | 3076 | Apparent Power - Total | Apparent power total | Read | ||
| AI | 3078 | Power Factor - Ph A | Power factor phase A | Read | ||
| AI | 3080 | Power Factor - Ph B | Power factor phase B | Read | ||
| AI | 3082 | Power Factor - Ph C | Power factor phase C | Read | ||
| AImin | 3084 | Power Factor - Total | Power factor total | Read | ||
| AImin | 3110 | Frequency | Frequency | Read | ||
| AImin | 3204 | Active Energy Delvd | Active energy delivered | Read | ||
| AI | 3208 | Active Energy Rcvd | Active energy received | Read | ||
| AI | 3220 | Reactive Energy Delvd | Reactive energy delivered | Read | ||
| AI | 3224 | Reactive Energy Rcvd | Reactive energy received | Read | ||
| AI | 3236 | Apparent Energy Delvd | Apparent energy delivered | Read | ||
| AI | 3240 | Apparent Energy Rcvd | Apparent energy received | Read | ||
| AImin | 3766 | Dmd - Active Power Present | Demand: active power present | Read | ||
| AI | 3770 | Dmd - Active Power Peak | Demand: active power peak | Read | ||
| AI | 3782 | Dmd - Reactive Power Present | Demand: reactive power present | Read | ||
| AI | 3786 | Dmd - Reactive Power Peak | Demand: reactive power peak | Read | ||
| AI | 3798 | Dmd - Apparent Power Present | Demand: apparent power present | Read | ||
| AI | 3802 | Dmd - Apparent Power Peak | Demand: apparent power peak | Read | ||
| AI | 3814 | Dmd - Current Ph A Present | Demand: current phase A present | Read | ||
| AI | 3818 | Dmd - Active Current Ph A Peak | Demand: active current phase A peak | Read | ||
| AI | 3830 | Dmd - Current Ph B Present | Demand: current phase B present | Read | ||
| AI | 3834 | Dmd - Active Current Ph B Peak | Demand: active current phase B peak | Read | ||
| AI | 3846 | Dmd - Current Ph C Present | Demand: current phase C present | Read | ||
| AI | 3850 | Dmd - Active Current Ph C Peak | Demand: active current phase C peak | Read | ||
| AI | 3862 | Dmd - Current Neutral Present | Demand: current neutral present | Read | ||
| BI | 38416 | Status Input 1 | Digital input 1 state | Read | ||
| BI | 38417 | Status Input 2 | Digital input 2 state | Read | ||
| BI | 38448 | Relay Output | Alarm relay output state | Read |
No points match these filters.
Object ID lookup: Schneider Electric EM3570 series DIN Ethernet energy meter point IDs by name
AI3000Current - Ph AAI3002Current - Ph BAI3004Current - Ph CAI3010Current - AvgAI3020Voltage - A-BAI3022Voltage - B-CAI3024Voltage - C-AAI3026Voltage - Avg L-LAI3028Voltage A-NAI3030Voltage B-NAI3032Voltage C-NAI3036Voltage - Avg L-NAI3054Active Power - Ph AAI3056Active Power - Ph BAI3058Active Power - Ph CAI3060Active Power - TotalAI3062Reactive Power - Ph AAI3064Reactive Power - Ph BAI3066Reactive Power - Ph CAI3068Reactive Power - TotalAI3070Apparent Power - Ph AAI3072Apparent Power - Ph BAI3074Apparent Power - Ph CAI3076Apparent Power - TotalAI3078Power Factor - Ph AAI3080Power Factor - Ph BAI3082Power Factor - Ph CAI3084Power Factor - TotalAI3110FrequencyAI3204Active Energy DelvdAI3208Active Energy RcvdAI3220Reactive Energy DelvdAI3224Reactive Energy RcvdAI3236Apparent Energy DelvdAI3240Apparent Energy RcvdAI3766Dmd - Active Power PresentAI3770Dmd - Active Power PeakAI3782Dmd - Reactive Power PresentAI3786Dmd - Reactive Power PeakAI3798Dmd - Apparent Power PresentAI3802Dmd - Apparent Power PeakAI3814Dmd - Current Ph A PresentAI3818Dmd - Active Current Ph A PeakAI3830Dmd - Current Ph B PresentAI3834Dmd - Active Current Ph B PeakAI3846Dmd - Current Ph C PresentAI3850Dmd - Active Current Ph C PeakAI3862Dmd - Current Neutral PresentBI38416Status Input 1BI38417Status Input 2BI38448Relay Output
Integration notes
- The PICS lists only object identifiers and names; it gives no units, so units are left blank here.
- Only Out_Of_Service and COV_Increment are writable on the AIs, so all objects are read-only data.
- Instance numbers match the PowerLogic meter register scheme (e.g. AI 3060 Active Power - Total).
- The demand peak current objects are printed as 'Dmd - Active Current Ph x Peak'.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EM3570 series DIN Ethernet energy meter (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric EM3570 series DIN Ethernet energy meter (BACnet IP)
How many BACnet points does the Schneider Electric EM3570 series DIN Ethernet energy meter (BACnet IP) have?
This list has 51 BACnet objects: 48 analog inputs, 3 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric EM3570 series DIN Ethernet energy meter (BACnet IP) BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Schneider Electric EM3570 series DIN Ethernet energy meter (BACnet IP) BACnet documentation?
Schneider Electric does not publish it on its own website. This list comes from EM3570 Protocol Implementation Conformance Statement, revision 2024-08-06, a copy hosted by BACnet International catalog at https://www.bacnetinternational.net/catalog/manu/schneider%20electric/PICS_em3570_pics.pdf. Ask Schneider Electric or its representative for the current revision.
What are the minimum BACnet points to integrate the Schneider Electric EM3570 series DIN Ethernet energy meter (BACnet IP)?
Start with AI 3060 Active Power - Total (Total active power); AI 3204 Active Energy Delvd (Active energy delivered); AI 3766 Dmd - Active Power Present (Present active power demand); AI 3084 Power Factor - Total (Total power factor); AI 3026 Voltage - Avg L-L (Average line-to-line voltage); AI 3010 Current - Avg (Average phase current); AI 3110 Frequency (System frequency).
How do I check these points on the real EM3570 series DIN Ethernet energy meter (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Variable frequency drive
Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Schneider Electric Altivar Process ATV630, ATV650, ATV660 and ATV690 drives on BACnet MS/TP.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx - Power and energy meter (BACnet MS/TP)
Schneider Electric iEM3465 / iEM3565 energy meter (BACnet MS/TP)
Schneider Electric iEM3465 (LVCT inputs) and iEM3565 (Rogowski coil inputs) DIN-rail energy meters, the BACnet MS/TP models of the iEM3400 / iEM3500 series.
Also known as: iEM3465, iEM3565, iEM3400 BACnet, iEM3500 BACnet, iEM3X65, 7EN02-0438 - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Multi-circuit branch power meter (high density)
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Schneider Electric (ex-Veris) PowerLogic HDPM6000 head units with busway, strip or retrofit measurement modules, on BACnet IP over Ethernet.
Also known as: HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Schneider Electric PowerLogic PM5300 series power meters with the Ethernet port (PM5320, PM5340, PM5341) using BACnet IP.
Also known as: PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM7000 series panel meters PM7351DUW, PM7252DUW, PM7151DUW and PM7142DUW with BACnet IP, firmware 1.0.1.
Also known as: PM7000, PM7351DUW, PM7252DUW, PM7151DUW, PM7142DUW, PM7351, PM7252, PM7151, PM7142, PowerLogic Intuitive PM7000 - Zone controller (room thermostat)
Schneider Electric SE7200 Series PIR Ready Zoning Controller
Schneider Electric PIR-ready SE7200 series 24 Vac zoning controllers (SE7200C5x45B, SE7200F5x45B).
Also known as: SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Schneider Electric PIR-ready SER7300 series line-voltage fan coil controllers: SER7300, SER7305, SER7350 and SER7355 (A versions).
Also known as: SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B - Pressure-dependent VAV zone controller
Schneider Electric SEZ7260 Zoning System Zone Controller
Schneider Electric SEZ7260 zone controllers (F model with floating damper and AO2, C model) used with SEZ7656 rooftop controllers in pressure-dependent zoning systems.
Also known as: SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B - Rooftop unit controller for zoning systems
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Schneider Electric SEZ7656 rooftop controllers (R conventional, H heat pump, F modulating heat, E economizer) that run a rooftop unit for a group of SEZ7260 zone controllers.
Also known as: SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Schneider Electric SpaceLogic SE8000-series SER8350 room controllers for line-voltage fan coil units.
Also known as: SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350 - Room humidity and temperature sensor (wall)
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Schneider Electric SpaceLogic SLP Series wall humidity/temperature sensors (with or without touchscreen) set to BACnet MS/TP.
Also known as: SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil - Rooftop unit controller (room thermostat, rooftop or heat-pump units)
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 6500 (rooftop unit / heat pump) version.
Also known as: SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump - Fan coil thermostat
Schneider Electric SpaceLogic TC900 Protocol Series fan coil thermostat (TC903 / TC907)
Schneider Electric SpaceLogic TC903 and TC907 Protocol Series fan coil thermostats (on/off or proportional valves, 3-speed or EC fan, 2-pipe or 4-pipe).
Also known as: TC900, TC903, TC907, TC903-EF4LDPSA, TC903-EF4PDPSA, TC903-3A4LXPXA, TC903-3A4LDPSA, TC903-3A4PDPSA, TC907-EF4LDPSAB, TC907-EF4PDPSAB, TC907-3A4LDPSAB, TC907-3A4PDPSAB, F-28335
Source: EM3570 Protocol Implementation Conformance Statement · rev. 2024-08-06. Object names, instances and units are reproduced as published; descriptions are our own.