Electric power meter via BACnet gateway · BACnet points list

Cleaver-Brooks Shark 100 power meter profile (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

A read-only ProtoNode profile for the Shark 100 meter: phase and line voltages, phase and neutral currents, kW, kVAR, kVA, power factor, frequency, energy totals, demand averages and maxima, and voltage and current THD.

This page lists 41 BACnet objects for the Cleaver-Brooks Shark 100 power meter profile (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
Shark 100 power meter profile (ProtoNode)
Equipment
Electric power meter via BACnet gateway
Equipment type
Thermostats, sensors & meters
BACnet objects
41 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
Shark 100, Electro Industries Shark 100, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 41 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks Shark 100 power meter profile (ProtoNode)

Integration in brief

Read-only. Map voltage, current, total kW, power factor, frequency and energy.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Volts A-NVolts A-NRead
AI 7Amps AAmps ARead
AI 10Watts 3-Ph totalTotal watts, 3-phaseRead
AI 13Power Factor 3-Ph totalPower factor, 3-phaseRead
AI 14FrequencyFrequencyRead
AI 17W-hours DeliveredWatt-hours deliveredRead

Network setup

Cleaver-Brooks Shark 100 power meter profile (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

41 of 41 shown
Type
Analog
Show
Cleaver-Brooks Shark 100 power meter profile (ProtoNode) BACnet Points List
DescriptionStates
AImin1Volts A-NModbus 41000Read
AI2Volts B-NModbus 41002Read
AI3Volts C-NModbus 41004Read
AI4Volts A-BModbus 41006Read
AI5Volts B-CModbus 41008Read
AI6Volts C-AModbus 41010Read
AImin7Amps AModbus 41012Read
AI8Amps BModbus 41014Read
AI9Amps CModbus 41016Read
AImin10Watts 3-Ph totalModbus 41018Read
AI11VARs 3-Ph totalModbus 41020Read
AI12VAs 3-Ph totalModbus 41022Read
AImin13Power Factor 3-Ph totalModbus 41024Read
AImin14FrequencyModbus 41026Read
AI15Neutral CurrentModbus 41028Read
AI16W-hours ReceivedModbus 41100Read
AImin17W-hours DeliveredModbus 41102Read
AI18W-hours NetModbus 41104Read
AI19W-hours TotalModbus 41106Read
AI20VAR-hours PositiveModbus 41108Read
AI21VAR-hours NegativeModbus 41110Read
AI22VAR-hours NetModbus 41112Read
AI23VAR-hours TotalModbus 41114Read
AI24VA-hours TotalModbus 41116Read
AI25Positive Watts 3-Ph AvgModbus 42006Read
AI26Positive VARs 3-Ph AvgModbus 42008Read
AI27Negative Watts 3-Ph AvgModbus 42010Read
AI28Negative VARs 3-Ph AvgModbus 42012Read
AI29VAs 3-Ph AvgModbus 42014Read
AI30Positive PF 3-Ph AvgModbus 42016Read
AI31Negative PF 3-PF AvgModbus 42018Read
AI32Positive Watts 3-Ph Max Avg DemandModbus 43118Read
AI33Positive VARs 3-Ph Max Avg DemandModbus 43120Read
AI34Negative Watts 3-Ph Max Avg DemandModbus 43122Read
AI35Negative VARs 3-Ph Max Avg DemandModbus 43124Read
AI36Volts A-N %THDModbus 44000Read
AI37Volts B-N %THDModbus 44001Read
AI38Volts C-N %THDModbus 44002Read
AI39Amps A %THDModbus 44003Read
AI40Amps B %THDModbus 44004Read
AI41Amps C %THDModbus 44005Read
Object ID lookup: Cleaver-Brooks Shark 100 power meter profile point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Shark 100 power meter profile (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks Shark 100 power meter profile (ProtoNode)

How many BACnet points does the Cleaver-Brooks Shark 100 power meter profile (ProtoNode) have?

This list has 41 BACnet objects: 41 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks Shark 100 power meter profile (ProtoNode) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Cleaver-Brooks Shark 100 power meter profile (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks Shark 100 power meter profile (ProtoNode)?

Start with AI 1 Volts A-N (Volts A-N); AI 7 Amps A (Amps A); AI 10 Watts 3-Ph total (Total watts, 3-phase); AI 13 Power Factor 3-Ph total (Power factor, 3-phase); AI 14 Frequency (Frequency); AI 17 W-hours Delivered (Watt-hours delivered).

How do I check these points on the real Shark 100 power meter profile (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.