Pump interface module (boiler plant pumps) via BACnet gateway · BACnet points list
Cleaver-Brooks HSC Pump Interface Module (ProtoNode) BACnet points list
Updated 7 November 2026Unofficial source
The ProtoNode maps the HSC pump interface module to BACnet: input and output words, pump count, scaled analog inputs, PID process variable, setpoint and output, lead/lag pump numbers and pump run/auto inputs and outputs. Three AVs take a remote setpoint, a modulation override and a heartbeat.
This page lists 47 BACnet objects for the Cleaver-Brooks HSC Pump Interface Module (ProtoNode) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.
- Manufacturer
- Cleaver-Brooks
- Model
- HSC Pump Interface Module (ProtoNode)
- Equipment
- Pump interface module (boiler plant pumps) via BACnet gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 47 (3 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + Modbus Node-ID
- Also known as
- Pump Interface Module, HSC Pump Interface, ProtoNode RER, 750-426
- Source document
- Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.
BMS integration notes: Cleaver-Brooks HSC Pump Interface Module (ProtoNode)
Write the remote setpoint (AV 1) and keep the heartbeat (AV 3) updated. Read the run request, pump run outputs, PID process variable and the alarm output.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 1 | Remote Setpoint Write | Remote setpoint | Write |
| AV 3 | Heartbeat Write Tag | Heartbeat written by the BMS | Write |
| BI 9 | Pump Run Request | Pump run request | Read |
| BI 17 | Pump 1 Run Output | Pump 1 run output | Read |
| AI 7 | PID PV Scaled Value | PID process variable | Read |
| BI 21 | Alarm Output | Alarm output | Read |
Heartbeat & communication loss
AV 3 Heartbeat Write Tag is written by the BMS; the guide does not state the timeout.
Network setup
- BACnet Device Instance = the controller's Modbus Node-ID + Node_Offset (default 50,000), so Node-ID 1 = 50001. Change Node_Offset in the ProtoNode web configurator to pick other instances.
- The ProtoNode RER does BACnet MS/TP or BACnet IP, selected on its S bank DIP switches.
- BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on the A bank DIP switches; baud on B0-B3 (38400 factory default).
- BACnet IP: default ProtoNode address 192.168.1.24; change it in the web configurator.
Cleaver-Brooks HSC Pump Interface Module (ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Input Word | Modbus 30021 | Read | ||
| AI | 2 | Output Word | Modbus 30022 | Read | ||
| AI | 3 | Number of Pumps | Modbus 30023 | Read | ||
| AI | 4 | Analog In 1 Scaled Value | Modbus 30024-25 | Read | ||
| AI | 5 | Analog In 2 Scaled Value | Modbus 30026-27 | Read | ||
| AI | 6 | PID Output Scaled Value | Modbus 30028-29 | Read | ||
| AImin | 7 | PID PV Scaled Value | Modbus 30030-31 | Read | ||
| AI | 8 | PID SP Scaled Value | Modbus 30032-33 | Read | ||
| AI | 9 | Lead Pump Number | Modbus 30034 | Read | ||
| AI | 10 | Lag1 Pump Number | Modbus 30035 | Read | ||
| AI | 11 | Lag2 Pump Number | Modbus 30036 | Read | ||
| AI | 12 | Lag3 Pump Number | Modbus 30037 | Read | ||
| BI | 1 | Pump 1 Run Input | Read | |||
| BI | 2 | Pump 2 Run Input | Read | |||
| BI | 3 | Pump 3 Run Input | Read | |||
| BI | 4 | Pump 4 Run Input | Read | |||
| BI | 5 | Pump 1 Auto Input | Read | |||
| BI | 6 | Pump 2 Auto Input | Read | |||
| BI | 7 | Pump 3 Auto Input | Read | |||
| BI | 8 | Pump 4 Auto Input | Read | |||
| BImin | 9 | Pump Run Request | Read | |||
| BI | 10 | 30021_9 | Read | |||
| BI | 11 | 30021_10 | Read | |||
| BI | 12 | 30021_11 | Read | |||
| BI | 13 | 30021_12 | Read | |||
| BI | 14 | 30021_13 | Read | |||
| BI | 15 | 30021_14 | Read | |||
| BI | 16 | 30021_15 | Read | |||
| BImin | 17 | Pump 1 Run Output | Read | |||
| BI | 18 | Pump 2 Run Output | Read | |||
| BI | 19 | Pump 3 Run Output | Read | |||
| BI | 20 | Pump 4 Run Output | Read | |||
| BImin | 21 | Alarm Output | Read | |||
| BI | 22 | Alarm Blinker | Read | |||
| BI | 23 | Pumps Off | Read | |||
| BI | 24 | 30022_7 | Read | |||
| BI | 25 | 30022_8 | Read | |||
| BI | 26 | 30022_9 | Read | |||
| BI | 27 | 30022_10 | Read | |||
| BI | 28 | 30022_11 | Read | |||
| BI | 29 | 30022_12 | Read | |||
| BI | 30 | 30022_13 | Read | |||
| BI | 31 | 30022_14 | Read | |||
| BI | 32 | OAT Pumps Off | Read | |||
| AVmin | 1 | Remote Setpoint Write | Modbus 40021-22 | Write | ||
| AV | 2 | Modulation Output Override | Modbus 40029-30 | Write | ||
| AVmin | 3 | Heartbeat Write Tag | Modbus 40025 | Write |
No points match these filters.
Object ID lookup: Cleaver-Brooks HSC Pump Interface Module point IDs by name
AI1Input WordAI2Output WordAI3Number of PumpsAI4Analog In 1 Scaled ValueAI5Analog In 2 Scaled ValueAI6PID Output Scaled ValueAI7PID PV Scaled ValueAI8PID SP Scaled ValueAI9Lead Pump NumberAI10Lag1 Pump NumberAI11Lag2 Pump NumberAI12Lag3 Pump NumberBI1Pump 1 Run InputBI2Pump 2 Run InputBI3Pump 3 Run InputBI4Pump 4 Run InputBI5Pump 1 Auto InputBI6Pump 2 Auto InputBI7Pump 3 Auto InputBI8Pump 4 Auto InputBI9Pump Run RequestBI1030021_9BI1130021_10BI1230021_11BI1330021_12BI1430021_13BI1530021_14BI1630021_15BI17Pump 1 Run OutputBI18Pump 2 Run OutputBI19Pump 3 Run OutputBI20Pump 4 Run OutputBI21Alarm OutputBI22Alarm BlinkerBI23Pumps OffBI2430022_7BI2530022_8BI2630022_9BI2730022_10BI2830022_11BI2930022_12BI3030022_13BI3130022_14BI32OAT Pumps OffAV1Remote Setpoint WriteAV2Modulation Output OverrideAV3Heartbeat Write Tag
Integration notes
- Each Cleaver-Brooks controller on the ProtoNode is its own BACnet device; the object instances below are the same on every device.
- The guide prints no write-point stars for this profile; the AV/BV objects map to Metasys N2 outputs and Modbus output registers or coils, so they are taken as writable. Access is inferred from object type.
- The guide gives no engineering units or state texts; units appear only where the object name carries them (DEG F / DEG C).
- Where a description is filled in, it gives the register from the guide's Modbus column.
- BIs named after a register and bit (e.g. 30021_9) are spare bits in the profile.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HSC Pump Interface Module (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Cleaver-Brooks HSC Pump Interface Module (ProtoNode)
How many BACnet points does the Cleaver-Brooks HSC Pump Interface Module (ProtoNode) have?
This list has 47 BACnet objects: 12 analog inputs, 3 analog values, 32 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Cleaver-Brooks HSC Pump Interface Module (ProtoNode) BACnet points are writable?
3 of the 47 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Cleaver-Brooks HSC Pump Interface Module (ProtoNode) BACnet documentation?
Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.
What are the minimum BACnet points to integrate the Cleaver-Brooks HSC Pump Interface Module (ProtoNode)?
Start with AV 1 Remote Setpoint Write (Remote setpoint); AV 3 Heartbeat Write Tag (Heartbeat written by the BMS); BI 9 Pump Run Request (Pump run request); BI 17 Pump 1 Run Output (Pump 1 run output); AI 7 PID PV Scaled Value (PID process variable); BI 21 Alarm Output (Alarm output).
Does the Cleaver-Brooks HSC Pump Interface Module (ProtoNode) need a BACnet heartbeat or have a communication timeout?
AV 3 Heartbeat Write Tag is written by the BMS; the guide does not state the timeout.
How do I check these points on the real HSC Pump Interface Module (ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Cleaver-Brooks BACnet points lists
- Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
Cleaver-Brooks deaerator and surge tank packages with the ADAC 1000 PLC control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: ADAC 1000, ADAC_1000, ProtoNode RER, 750-426 - Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)
Cleaver-Brooks deaerator and surge tank packages with the ADAC control, read through a ProtoNode RER gateway.
Also known as: ADAC, CB deaerator control, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB120 flame safeguard (ProtoNode)
Cleaver-Brooks boilers with the CB120 flame safeguard, read through a ProtoNode RER gateway.
Also known as: CB120, CB 120, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB780 flame safeguard with expanded annunciator (ProtoNode)
Cleaver-Brooks boilers with the CB780 burner management control and expanded annunciator, read through a ProtoNode RER gateway.
Also known as: CB780, CB 780, CB780E, ProtoNode RER, 750-426 - Hot water boiler control via BACnet gateway
Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)
Cleaver-Brooks hot water boilers with the Falcon hydronic burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Hydronic, ClearFire Falcon, CB Falcon, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Falcon Steam boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Falcon steam burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Steam, CB Falcon steam, ProtoNode RER, 750-426 - Boiler flame safeguard and fuel-air ratio control via BACnet gateway
Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)
Cleaver-Brooks boilers with a CB780/CB783 burner control and FARC fuel-air ratio control, read through a ProtoNode RER gateway.
Also known as: FARC, CB 780/783, CB783, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 1000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 1000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 1000, CB Hawk 1000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 2000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 2000, CB Hawk 2000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 4000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 4000, CB Hawk 4000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 V2 boiler control (ProtoNode)
Cleaver-Brooks boilers with the HAWK 4000 V2 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: HAWK 4000 V2, CB HAWK 4000 V2, HAWK_4000_V2, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4500 boiler control (ProtoNode, EtherNet/IP)
Cleaver-Brooks boilers with the Hawk 4500 PLC boiler control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: Hawk 4500, CB Hawk 4500, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Hawk 5000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 5000, CB Hawk 5000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk ICS boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk ICS control, read through a ProtoNode RER gateway.
Also known as: Hawk ICS, CB ICS, ProtoNode RER, 750-426 - Boiler lead/lag master panel via BACnet gateway
Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode)
Cleaver-Brooks Hawk Master Panels sequencing up to eight Hawk boilers (A-H), read through a ProtoNode RER gateway.
Also known as: Hawk Master Panel, Hawk Master, CB Master Panel, ProtoNode RER, 750-426 - Boiler interface module via BACnet gateway
Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)
Cleaver-Brooks HSC boiler interface modules (one boiler each), read through a ProtoNode RER gateway.
Also known as: Boiler Interface Module, HSC Boiler Interface, BIM, ProtoNode RER, 750-426 - Multi-boiler sequencer (hot water boiler plant) via BACnet gateway
Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)
Cleaver-Brooks HSC panels sequencing up to 10 condensing and 10 non-condensing boilers, read through a ProtoNode RER gateway.
Also known as: HSC, Hydronic System Controller, CB HSC, ProtoNode RER, 750-426 - Boiler water level controller via BACnet gateway
Cleaver-Brooks LCS Level Control System (ProtoNode)
Cleaver-Brooks LCS water level controllers (one or two tanks), read through a ProtoNode RER gateway.
Also known as: LCS, Level Control System, ProtoNode RER, 750-426 - Boiler feed pump controller via BACnet gateway
Cleaver-Brooks PCS Pump Control System (ProtoNode)
Cleaver-Brooks PCS pump controllers (up to four pumps on header pressure or tank level), read through a ProtoNode RER gateway.
Also known as: PCS, Pump Control System, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 100 power meter profile (ProtoNode)
Shark 100 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 100, Electro Industries Shark 100, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 200 power meter profile (ProtoNode)
Shark 200 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 200, Electro Industries Shark 200, ProtoNode RER, 750-426 - Process loop controller via BACnet gateway
Cleaver-Brooks UDC 2500 loop controller profile (ProtoNode)
Honeywell UDC 2500 loop controllers supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: UDC 2500, UDC2500, Honeywell UDC 2500, ProtoNode RER, 750-426
Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.