Boiler flame safeguard via BACnet gateway · BACnet points list

Cleaver-Brooks CB120 flame safeguard (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

A read-only ProtoNode profile for the CB120 flame safeguard: terminal inputs and outputs, status and message codes, flame signal, lockout count, burner minutes and cycles, the last ten lockouts with their burner hours and cycles, and limit/interlock inputs.

This page lists 94 BACnet objects for the Cleaver-Brooks CB120 flame safeguard (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
CB120 flame safeguard (ProtoNode)
Equipment
Boiler flame safeguard via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
94 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
CB120, CB 120, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 94 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks CB120 flame safeguard (ProtoNode)

Integration in brief

Read-only. Map the status code, blower and main valve outputs, flame signal and the alarm output, plus the latest lockout message.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1StatusBurner status codeRead
BI 17Blower_OutBlower output onRead
BI 18Main_Valve_OutMain valve output onRead
AI 5FlameFlame signalRead
BI 24Alarm_OutAlarm outputRead
AI 11LOCKOUT1_MSGLockout 1 message codeRead

Network setup

Cleaver-Brooks CB120 flame safeguard (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

94 of 94 shown
Type
AnalogBinary
Show
Cleaver-Brooks CB120 flame safeguard (ProtoNode) BACnet Points List
DescriptionStates
BI1Safety_RelayModbus 40007, bit 0Read
BI2Main_Valve_InModbus 40007, bit 1Read
BI3Delayed_Valve_InModbus 40007, bit 2Read
BI4Pilot_Valve_InModbus 40007, bit 3Read
BI5Ignition_InModbus 40007, bit 4Read
BI6Blower_InModbus 40007, bit 5Read
BI7Op_CntrlModbus 40007, bit 6Read
BI8Run_IntlckModbus 40007, bit 7Read
BI9LAG1Modbus 40007, bit 8Read
BI10LAG2Modbus 40007, bit 11Read
BI11Fuel_Vlv_POCModbus 40007, bit 12Read
BI12High_Fire_IntlckModbus 40007, bit 13Read
BI13Low_Fire_StartModbus 40007, bit 14Read
BI14Ref_AC_LineModbus 40007, bit 15Read
BI15Ignition_OutModbus 40008, bit 1Read
BI16Pilot_Valve_OutModbus 40008, bit 2Read
BImin17Blower_OutModbus 40008, bit 3Read
BImin18Main_Valve_OutModbus 40008, bit 4Read
BI19Delayed_Valve_OutModbus 40008, bit 5Read
BI20Internal_Safety_OutModbus 40008, bit 6Read
BI21LowFireOutModbus 40008, bit 8Read
BI22HighFireOutModbus 40008, bit 9Read
BI23Rel_to_ModOutModbus 40008, bit 10Read
BImin24Alarm_OutModbus 40008, bit 11Read
AImin1StatusModbus 40001Read
AI2MsgnModbus 40002Read
AI3GstatModbus 40003Read
AI4TimerModbus 40004Read
AImin5FlameModbus 40005Read
AI6LogstatModbus 40006Read
AI7Lockout_CountModbus 40015Read
AI8SysminsModbus 40009-10Read
AI9BnrminsModbus 40011-12Read
AI10CyclesModbus 40013-14Read
AImin11LOCKOUT1_MSGModbus 40016Read
AI12LOCKOUT1_MODULEModbus 40017Read
AI13LOCKOUT2_MSGModbus 40022Read
AI14LOCKOUT2_MODULEModbus 40023Read
AI15LOCKOUT3_MSGModbus 40028Read
AI16LOCKOUT3_MODULEModbus 40029Read
AI17LOCKOUT4_MSGModbus 40034Read
AI18LOCKOUT4_MODULEModbus 40035Read
AI19LOCKOUT5_MSGModbus 40040Read
AI20LOCKOUT5_MODULEModbus 40041Read
AI21LOCKOUT6_MSGModbus 40046Read
AI22LOCKOUT6_MODULEModbus 40047Read
AI23LOCKOUT7_MSGModbus 40052Read
AI24LOCKOUT7_MODULEModbus 40053Read
AI25LOCKOUT8_MSGModbus 40058Read
AI26LOCKOUT8_MODULEModbus 40059Read
AI27LOCKOUT9_MSGModbus 40064Read
AI28LOCKOUT9_MODULEModbus 40065Read
AI29LOCKOUT10_MSGModbus 40070Read
AI30LOCKOUT10_MODULEModbus 40071Read
AI31LOCKOUT1_BNRHRSModbus 40018-19Read
AI32LOCKOUT1_BNRCYCSModbus 40020-21Read
AI33LOCKOUT2_BNRHRSModbus 40024-25Read
AI34LOCKOUT2_BNRCYCSModbus 40026-27Read
AI35LOCKOUT3_BNRHRSModbus 40030-31Read
AI36LOCKOUT3_BNRCYCSModbus 40032-34Read
AI37LOCKOUT4_BNRHRSModbus 40036-37Read
AI38LOCKOUT4_BNRCYCSModbus 40038-39Read
AI39LOCKOUT5_BNRHRSModbus 40042-43Read
AI40LOCKOUT5_BNRCYCSModbus 40044-45Read
AI41LOCKOUT6_BNRHRSModbus 40048-49Read
AI42LOCKOUT6_BNRCYCSModbus 40050-51Read
AI43LOCKOUT7_BNRHRSModbus 40054-55Read
AI44LOCKOUT7_BNRCYCSModbus 40056-57Read
AI45LOCKOUT8_BNRHRSModbus 40060-61Read
AI46LOCKOUT8_BNRCYCSModbus 40062-63Read
AI47LOCKOUT9_BNRHRSModbus 40066-67Read
AI48LOCKOUT9_BNRCYCSModbus 40068-69Read
AI49LOCKOUT10_BNRHRSModbus 40072-73Read
AI50LOCKOUT10_BNRCYCSModbus 40074-75Read
BI25Op_ControlModbus 40901, bit 0Read
BI26Aux_1Modbus 40901, bit 1Read
BI27Aux_2Modbus 40901, bit 2Read
BI28Aux_3Modbus 40901, bit 3Read
BI29High_waterModbus 40901, bit 4Read
BI30Low_WaterModbus 40901, bit 5Read
BI31High_Oil_TempModbus 40901, bit 6Read
BI32Low_Oil_TempModbus 40901, bit 7Read
BI33Low_Oil_PressModbus 40902, bit 0Read
BI34Low_Atom_MediaModbus 40902, bit 1Read
BI35Low_Gas_PressModbus 40902, bit 2Read
BI36High_Gas_PressModbus 40902, bit 3Read
BI37Aux_GasModbus 40902, bit 4Read
BI38High_PressModbus 40902, bit 5Read
BI39High_TempModbus 40902, bit 6Read
BI40Aux_4Modbus 40902, bit 7Read
BI41Aux_5Modbus 40903, bit 0Read
BI42Aux_6Modbus 40903, bit 1Read
BI43Aux_7Modbus 40903, bit 2Read
BI44Air_FlowModbus 40903, bit 3Read
Object ID lookup: Cleaver-Brooks CB120 flame safeguard point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CB120 flame safeguard (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks CB120 flame safeguard (ProtoNode)

How many BACnet points does the Cleaver-Brooks CB120 flame safeguard (ProtoNode) have?

This list has 94 BACnet objects: 50 analog inputs, 44 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks CB120 flame safeguard (ProtoNode) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Cleaver-Brooks CB120 flame safeguard (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks CB120 flame safeguard (ProtoNode)?

Start with AI 1 Status (Burner status code); BI 17 Blower_Out (Blower output on); BI 18 Main_Valve_Out (Main valve output on); AI 5 Flame (Flame signal); BI 24 Alarm_Out (Alarm output); AI 11 LOCKOUT1_MSG (Lockout 1 message code).

How do I check these points on the real CB120 flame safeguard (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.