- Hawk Master Panel lead/lag (ProtoNode)
Boiler lead/lag master panel via BACnet gateway · BACnet points list
Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode) BACnet points list
Updated 7 November 2026Unofficial source
The ProtoNode maps the Hawk master panel to BACnet: per-boiler communication, power, ready and start-output bits, sequence status, run time since last rotation, lead/lag order and control output, plus plant pressure or temperature, on/off points and setpoint limits. Writable AVs set lag start/stop points and timers, the boiler order and the setpoint.
This page lists 196 BACnet objects for the Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode) — 52 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.
- Manufacturer
- Cleaver-Brooks
- Model
- Hawk Master Panel lead/lag (ProtoNode)
- Equipment
- Boiler lead/lag master panel via BACnet gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 196 (52 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + Modbus Node-ID
- Also known as
- Hawk Master Panel, Hawk Master, CB Master Panel, ProtoNode RER, 750-426
- Source document
- Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.
BMS integration notes: Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode)
Write the plant setpoint with AV 51 and read operating pressure or temperature, each boiler's sequence status and start output, and the sensor and low pressure alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 51 | Setpoint Value Write | Setpoint value written by the BMS | Write |
| AI 404 | Operating Pressure/Temp | Operating pressure or temperature | Read |
| AI 419 | Steam Pressure (Water Temp) SP | Steam pressure (water temperature) setpoint | Read |
| AI 614 | Boiler A Sequence Status | Boiler A sequence status | Read |
| BI 1305 | Boiler A Start Output | Boiler A start output | Read |
| BI 1291 | Steam/Water Sensor Fail | Steam/water sensor failure | Read |
| BI 1292 | Low Steam Pressure | Low steam pressure | Read |
| BI 1323 | I/O Module Failure | I/O module failure | Read |
Network setup
- BACnet Device Instance = the controller's Modbus Node-ID + Node_Offset (default 50,000), so Node-ID 1 = 50001. Change Node_Offset in the ProtoNode web configurator to pick other instances.
- The ProtoNode RER does BACnet MS/TP or BACnet IP, selected on its S bank DIP switches.
- BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on the A bank DIP switches; baud on B0-B3 (38400 factory default).
- BACnet IP: default ProtoNode address 192.168.1.24; change it in the web configurator.
Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 1287 | Boiler A Ethernet Comm Error | Read | |||
| BI | 1288 | Boiler B Ethernet Comm Error | Read | |||
| BI | 1289 | Boiler C Ethernet Comm Error | Read | |||
| BI | 1290 | Boiler D Ethernet Comm Error | Read | |||
| BImin | 1291 | Steam/Water Sensor Fail | Read | |||
| BImin | 1292 | Low Steam Pressure | Read | |||
| BI | 1293 | Boiler A Power Failure | Read | |||
| BI | 1294 | Boiler B Power Failure | Read | |||
| BI | 1295 | Boiler C Power Failure | Read | |||
| BI | 1296 | Boiler D Power Failure | Read | |||
| BI | 1297 | Boiler A Ready | Read | |||
| BI | 1298 | Boiler B Ready | Read | |||
| BI | 1299 | Boiler C Ready | Read | |||
| BI | 1300 | Boiler D Ready | Read | |||
| BI | 1301 | Power To Boiler A | Read | |||
| BI | 1302 | Power To Boiler B | Read | |||
| BI | 1303 | Power To Boiler C | Read | |||
| BI | 1304 | Power To Boiler D | Read | |||
| BImin | 1305 | Boiler A Start Output | Read | |||
| BI | 1306 | Boiler B Start Output | Read | |||
| BI | 1307 | Boiler C Start Output | Read | |||
| BI | 1308 | Boiler D Start Output | Read | |||
| BI | 1309 | Unison Modulation | Read | |||
| BI | 1310 | L/Lag Modulation | Read | |||
| BI | 1311 | English System | Read | |||
| BI | 1312 | Metric System | Read | |||
| BI | 1313 | Auto Rotation On | Read | |||
| BI | 1314 | AMB[1]11 | Read | |||
| BI | 1315 | AMB[1]12 | Read | |||
| BI | 1316 | AMB[1]13 | Read | |||
| BI | 1317 | AMB[1]14 | Read | |||
| BI | 1318 | AMB[1]15 | Read | |||
| BI | 1319 | Boiler E Ethernet Comm Error | Read | |||
| BI | 1320 | Boiler F Ethernet Comm Error | Read | |||
| BI | 1321 | Boiler G Ethernet Comm Error | Read | |||
| BI | 1322 | Boiler H Ethernet Comm Error | Read | |||
| BImin | 1323 | I/O Module Failure | Read | |||
| BI | 1324 | AMB[2]5 | Read | |||
| BI | 1325 | Boiler E Power Failure | Read | |||
| BI | 1326 | Boiler F Power Failure | Read | |||
| BI | 1327 | Boiler G Power Failure | Read | |||
| BI | 1328 | Boiler H Power Failure | Read | |||
| BI | 1329 | Boiler E Ready | Read | |||
| BI | 1330 | Boiler F Ready | Read | |||
| BI | 1331 | Boiler G Ready | Read | |||
| BI | 1332 | Boiler H Ready | Read | |||
| BI | 1333 | Power To Boiler E | Read | |||
| BI | 1334 | Power To Boiler F | Read | |||
| BI | 1335 | Power To Boiler G | Read | |||
| BI | 1336 | Power To Boiler H | Read | |||
| BI | 1337 | Boiler E Start Output | Read | |||
| BI | 1338 | Boiler F Start Output | Read | |||
| BI | 1339 | Boiler G Start Output | Read | |||
| BI | 1340 | Boiler H Start Output | Read | |||
| BI | 1341 | AMB[3]6 | Read | |||
| BI | 1342 | AMB[3]7 | Read | |||
| BI | 1343 | AMB[3]8 | Read | |||
| BI | 1344 | AMB[3]9 | Read | |||
| BI | 1345 | AMB[3]10 | Read | |||
| BI | 1346 | AMB[3]11 | Read | |||
| BI | 1347 | AMB[3]12 | Read | |||
| BI | 1348 | AMB[3]13 | Read | |||
| BI | 1349 | AMB[3]14 | Read | |||
| BI | 1350 | AMB[3]15 | Read | |||
| AI | 613 | Number of units | Modbus 31105 | Read | ||
| AImin | 614 | Boiler A Sequence Status | Modbus 31106 | Read | ||
| AI | 615 | Boiler B Sequence Status | Modbus 31107 | Read | ||
| AI | 616 | Boiler C Sequence Status | Modbus 31108 | Read | ||
| AI | 617 | Boiler D Sequence Status | Modbus 31109 | Read | ||
| AI | 618 | Auto Sequence Rotation Days Set | Modbus 31110 | Read | ||
| AI | 619 | Blr A Run Time Since Last Rot (Days) | Modbus 31111 | Read | ||
| AI | 620 | Blr A Run Time Since Last Rot (Hrs) | Modbus 31112 | Read | ||
| AI | 621 | Blr A Run Time Since Last Rot (Min) | Modbus 31113 | Read | ||
| AI | 622 | Blr B Run Time Since Last Rot (Days) | Modbus 31114 | Read | ||
| AI | 623 | Blr B Run Time Since Last Rot (Hrs) | Modbus 31115 | Read | ||
| AI | 624 | Blr B Run Time Since Last Rot (Min) | Modbus 31116 | Read | ||
| AI | 625 | Blr C Run Time Since Last Rot (Days) | Modbus 31117 | Read | ||
| AI | 626 | Blr C Run Time Since Last Rot (Hrs) | Modbus 31118 | Read | ||
| AI | 627 | Blr C Run Time Since Last Rot (Min) | Modbus 31119 | Read | ||
| AI | 628 | Blr D Run Time Since Last Rot (Days) | Modbus 31120 | Read | ||
| AI | 629 | Blr D Run Time Since Last Rot (Hrs) | Modbus 31121 | Read | ||
| AI | 630 | Blr D Run Time Since Last Rot (Min) | Modbus 31122 | Read | ||
| AI | 631 | AMI[18] | Modbus 31123 | Read | ||
| AI | 632 | AMI[19] | Modbus 31124 | Read | ||
| AI | 633 | AMI[20] | Modbus 31125 | Read | ||
| AI | 634 | Boiler E Sequence Status | Modbus 31126 | Read | ||
| AI | 635 | Boiler F Sequence Status | Modbus 31127 | Read | ||
| AI | 636 | Boiler G Sequence Status | Modbus 31128 | Read | ||
| AI | 637 | Boiler H Sequence Status | Modbus 31129 | Read | ||
| AI | 638 | AMI[25] | Modbus 31130 | Read | ||
| AI | 639 | Blr E Run Time Since Last Rot (Days) | Modbus 31131 | Read | ||
| AI | 640 | Blr E Run Time Since Last Rot (Hrs) | Modbus 31132 | Read | ||
| AI | 641 | Blr E Run Time Since Last Rot (Min) | Modbus 31133 | Read | ||
| AI | 642 | Blr F Run Time Since Last Rot (Days) | Modbus 31134 | Read | ||
| AI | 643 | Blr F Run Time Since Last Rot (Hrs) | Modbus 31135 | Read | ||
| AI | 644 | Blr F Run Time Since Last Rot (Min) | Modbus 31136 | Read | ||
| AI | 645 | Blr G Run Time Since Last Rot (Days) | Modbus 31137 | Read | ||
| AI | 646 | Blr G Run Time Since Last Rot (Hrs) | Modbus 31138 | Read | ||
| AI | 647 | Blr G Run Time Since Last Rot (Min) | Modbus 31139 | Read | ||
| AI | 648 | Blr H Run Time Since Last Rot (Days) | Modbus 31140 | Read | ||
| AI | 649 | Blr H Run Time Since Last Rot (Hrs) | Modbus 31141 | Read | ||
| AI | 650 | Blr H Run Time Since Last Rot (Min) | Modbus 31142 | Read | ||
| AI | 651 | Blr A Lead Lag Entered Seq | Modbus 31143 | Read | ||
| AI | 652 | Blr B Lead Lag Entered Seq | Modbus 31144 | Read | ||
| AI | 653 | Blr C Lead Lag Entered Seq | Modbus 31145 | Read | ||
| AI | 654 | Blr D Lead Lag Entered Seq | Modbus 31146 | Read | ||
| AI | 655 | Blr E Lead Lag Entered Seq | Modbus 31147 | Read | ||
| AI | 656 | Blr F Lead Lag Entered Seq | Modbus 31148 | Read | ||
| AI | 657 | Blr G Lead Lag Entered Seq | Modbus 31149 | Read | ||
| AI | 658 | Blr H Lead Lag Entered Seq | Modbus 31150 | Read | ||
| AI | 659 | Blr A Lead Lag Working Seq | Modbus 31151 | Read | ||
| AI | 660 | Blr B Lead Lag Working Seq | Modbus 31152 | Read | ||
| AI | 661 | Blr C Lead Lag Working Seq | Modbus 31153 | Read | ||
| AI | 662 | Blr D Lead Lag Working Seq | Modbus 31154 | Read | ||
| AI | 663 | Blr E Lead Lag Working Seq | Modbus 31155 | Read | ||
| AI | 664 | Blr F Lead Lag Working Seq | Modbus 31156 | Read | ||
| AI | 665 | Blr G Lead Lag Working Seq | Modbus 31157 | Read | ||
| AI | 666 | Blr H Lead Lag Working Seq | Modbus 31158 | Read | ||
| AI | 401 | Max Pressure/Temp | Modbus 30801 | Read | ||
| AI | 402 | Lead Boiler On Point | Modbus 30803 | Read | ||
| AI | 403 | Lead Boiler Off Point | Modbus 30805 | Read | ||
| AImin | 404 | Operating Pressure/Temp | Modbus 30807 | Read | ||
| AI | 405 | Low SP Limit | Modbus 30809 | Read | ||
| AI | 406 | High SP Limit | Modbus 30811 | Read | ||
| AI | 407 | Days Till Auto Seq Rotation | Modbus 30813 | Read | ||
| AI | 408 | Hours Till Auto Seq Rotation | Modbus 30815 | Read | ||
| AI | 409 | Minutes Till Auto Seq Rotation | Modbus 30817 | Read | ||
| AI | 410 | Seconds Till Auto Seq Rotation | Modbus 30819 | Read | ||
| AI | 411 | Control Output Boiler A | Modbus 30821 | Read | ||
| AI | 412 | Control Output Boiler B | Modbus 30823 | Read | ||
| AI | 413 | Control Output Boiler C | Modbus 30825 | Read | ||
| AI | 414 | Control Output Boiler D | Modbus 30827 | Read | ||
| AI | 415 | Control Output Boiler E | Modbus 30829 | Read | ||
| AI | 416 | Control Output Boiler F | Modbus 30831 | Read | ||
| AI | 417 | Control Output Boiler G | Modbus 30833 | Read | ||
| AI | 418 | Control Output Boiler H | Modbus 30835 | Read | ||
| AImin | 419 | Steam Pressure (Water Temp) SP | Modbus 30837 | Read | ||
| AI | 420 | AMR[19] | Modbus 30839 | Read | ||
| AI | 421 | AMR[20] | Modbus 30841 | Read | ||
| AI | 422 | AMR[21] | Modbus 30843 | Read | ||
| AI | 423 | AMR[22] | Modbus 30845 | Read | ||
| AI | 424 | AMR[23] | Modbus 30847 | Read | ||
| AI | 425 | AMR[24] | Modbus 30849 | Read | ||
| AI | 426 | AMR[25] | Modbus 30851 | Read | ||
| BV | 1 | Master Write Bit | write point | Write | ||
| AVmin | 51 | Setpoint Value Write | Modbus 40051; write point | Write | ||
| AV | 1 | N510[0] | Modbus 40001; write point | Write | ||
| AV | 2 | Lag 1 Start Timer Set | Modbus 40002; write point | Write | ||
| AV | 3 | Lag 1 Start Point | Modbus 40003; write point | Write | ||
| AV | 4 | Lag 1 Stop Point | Modbus 40004; write point | Write | ||
| AV | 5 | Lag 1 Stop Timer Set | Modbus 40005; write point | Write | ||
| AV | 6 | N510[5] | Modbus 40006; write point | Write | ||
| AV | 7 | Lag 2 Start Timer Set | Modbus 40007; write point | Write | ||
| AV | 8 | Lag 2 Start Point | Modbus 40008; write point | Write | ||
| AV | 9 | Lag 2 Stop Point | Modbus 40009; write point | Write | ||
| AV | 10 | Lag 2 Stop Timer Set | Modbus 40010; write point | Write | ||
| AV | 11 | N510[10] | Modbus 40011; write point | Write | ||
| AV | 12 | Lag 3 Start Timer Set | Modbus 40012; write point | Write | ||
| AV | 13 | Lag 3 Start Point | Modbus 40013; write point | Write | ||
| AV | 14 | Lag 3 Stop Point | Modbus 40014; write point | Write | ||
| AV | 15 | Lag 3 Stop Timer Set | Modbus 40015; write point | Write | ||
| AV | 16 | Lead Boiler Selection | Modbus 40016; write point | Write | ||
| AV | 17 | Lag 1 Boiler Selection | Modbus 40017; write point | Write | ||
| AV | 18 | Lag 2 Boiler Selection | Modbus 40018; write point | Write | ||
| AV | 19 | Lag 3 Boiler Selection | Modbus 40019; write point | Write | ||
| AV | 20 | Lag 4 Boiler Selection | Modbus 40020; write point | Write | ||
| AV | 21 | Lag 5 Boiler Selection | Modbus 40021; write point | Write | ||
| AV | 22 | Lag 6 Boiler Selection | Modbus 40022; write point | Write | ||
| AV | 23 | Lag 7 Boiler Selection | Modbus 40023; write point | Write | ||
| AV | 24 | Lag 4 Start Timer Set | Modbus 40024; write point | Write | ||
| AV | 25 | Lag 4 Start Point | Modbus 40025; write point | Write | ||
| AV | 26 | Lag 4 Stop Point | Modbus 40026; write point | Write | ||
| AV | 27 | Lag 4 Stop Timer Set | Modbus 40027; write point | Write | ||
| AV | 28 | Lag 5 Start Timer Set | Modbus 40028; write point | Write | ||
| AV | 29 | Lag 5 Start Point | Modbus 40029; write point | Write | ||
| AV | 30 | Lag 5 Stop Point | Modbus 40030; write point | Write | ||
| AV | 31 | Lag 5 Stop Timer Set | Modbus 40031; write point | Write | ||
| AV | 32 | Lag 6 Start Timer Set | Modbus 40032; write point | Write | ||
| AV | 33 | Lag 6 Start Point | Modbus 40033; write point | Write | ||
| AV | 34 | Lag 6 Stop Point | Modbus 40034; write point | Write | ||
| AV | 35 | Lag 6 Stop Timer Set | Modbus 40035; write point | Write | ||
| AV | 36 | Lag 7 Start Timer Set | Modbus 40036; write point | Write | ||
| AV | 37 | Lag 7 Start Point | Modbus 40037; write point | Write | ||
| AV | 38 | Lag 7 Stop Point | Modbus 40038; write point | Write | ||
| AV | 39 | Lag 7 Stop Timer Set | Modbus 40039; write point | Write | ||
| AV | 40 | N510[39] | Modbus 40040; write point | Write | ||
| AV | 41 | N510[40] | Modbus 40041; write point | Write | ||
| AV | 42 | N510[41] | Modbus 40042; write point | Write | ||
| AV | 43 | N510[42] | Modbus 40043; write point | Write | ||
| AV | 44 | N510[43] | Modbus 40044; write point | Write | ||
| AV | 45 | N510[44] | Modbus 40045; write point | Write | ||
| AV | 46 | N510[45] | Modbus 40046; write point | Write | ||
| AV | 47 | N510[46] | Modbus 40047; write point | Write | ||
| AV | 48 | N510[47] | Modbus 40048; write point | Write | ||
| AV | 49 | N510[48] | Modbus 40049; write point | Write | ||
| AV | 50 | N510[49] | Modbus 40050; write point | Write |
No points match these filters.
Object ID lookup: Cleaver-Brooks Hawk Master Panel lead/lag point IDs by name
BI1287Boiler A Ethernet Comm ErrorBI1288Boiler B Ethernet Comm ErrorBI1289Boiler C Ethernet Comm ErrorBI1290Boiler D Ethernet Comm ErrorBI1291Steam/Water Sensor FailBI1292Low Steam PressureBI1293Boiler A Power FailureBI1294Boiler B Power FailureBI1295Boiler C Power FailureBI1296Boiler D Power FailureBI1297Boiler A ReadyBI1298Boiler B ReadyBI1299Boiler C ReadyBI1300Boiler D ReadyBI1301Power To Boiler ABI1302Power To Boiler BBI1303Power To Boiler CBI1304Power To Boiler DBI1305Boiler A Start OutputBI1306Boiler B Start OutputBI1307Boiler C Start OutputBI1308Boiler D Start OutputBI1309Unison ModulationBI1310L/Lag ModulationBI1311English SystemBI1312Metric SystemBI1313Auto Rotation OnBI1314AMB[1]11BI1315AMB[1]12BI1316AMB[1]13BI1317AMB[1]14BI1318AMB[1]15BI1319Boiler E Ethernet Comm ErrorBI1320Boiler F Ethernet Comm ErrorBI1321Boiler G Ethernet Comm ErrorBI1322Boiler H Ethernet Comm ErrorBI1323I/O Module FailureBI1324AMB[2]5BI1325Boiler E Power FailureBI1326Boiler F Power FailureBI1327Boiler G Power FailureBI1328Boiler H Power FailureBI1329Boiler E ReadyBI1330Boiler F ReadyBI1331Boiler G ReadyBI1332Boiler H ReadyBI1333Power To Boiler EBI1334Power To Boiler FBI1335Power To Boiler GBI1336Power To Boiler HBI1337Boiler E Start OutputBI1338Boiler F Start OutputBI1339Boiler G Start OutputBI1340Boiler H Start OutputBI1341AMB[3]6BI1342AMB[3]7BI1343AMB[3]8BI1344AMB[3]9BI1345AMB[3]10BI1346AMB[3]11BI1347AMB[3]12BI1348AMB[3]13BI1349AMB[3]14BI1350AMB[3]15AI613Number of unitsAI614Boiler A Sequence StatusAI615Boiler B Sequence StatusAI616Boiler C Sequence StatusAI617Boiler D Sequence StatusAI618Auto Sequence Rotation Days SetAI619Blr A Run Time Since Last Rot (Days)AI620Blr A Run Time Since Last Rot (Hrs)AI621Blr A Run Time Since Last Rot (Min)AI622Blr B Run Time Since Last Rot (Days)AI623Blr B Run Time Since Last Rot (Hrs)AI624Blr B Run Time Since Last Rot (Min)AI625Blr C Run Time Since Last Rot (Days)AI626Blr C Run Time Since Last Rot (Hrs)AI627Blr C Run Time Since Last Rot (Min)AI628Blr D Run Time Since Last Rot (Days)AI629Blr D Run Time Since Last Rot (Hrs)AI630Blr D Run Time Since Last Rot (Min)AI631AMI[18]AI632AMI[19]AI633AMI[20]AI634Boiler E Sequence StatusAI635Boiler F Sequence StatusAI636Boiler G Sequence StatusAI637Boiler H Sequence StatusAI638AMI[25]AI639Blr E Run Time Since Last Rot (Days)AI640Blr E Run Time Since Last Rot (Hrs)AI641Blr E Run Time Since Last Rot (Min)AI642Blr F Run Time Since Last Rot (Days)AI643Blr F Run Time Since Last Rot (Hrs)AI644Blr F Run Time Since Last Rot (Min)AI645Blr G Run Time Since Last Rot (Days)AI646Blr G Run Time Since Last Rot (Hrs)AI647Blr G Run Time Since Last Rot (Min)AI648Blr H Run Time Since Last Rot (Days)AI649Blr H Run Time Since Last Rot (Hrs)AI650Blr H Run Time Since Last Rot (Min)AI651Blr A Lead Lag Entered SeqAI652Blr B Lead Lag Entered SeqAI653Blr C Lead Lag Entered SeqAI654Blr D Lead Lag Entered SeqAI655Blr E Lead Lag Entered SeqAI656Blr F Lead Lag Entered SeqAI657Blr G Lead Lag Entered SeqAI658Blr H Lead Lag Entered SeqAI659Blr A Lead Lag Working SeqAI660Blr B Lead Lag Working SeqAI661Blr C Lead Lag Working SeqAI662Blr D Lead Lag Working SeqAI663Blr E Lead Lag Working SeqAI664Blr F Lead Lag Working SeqAI665Blr G Lead Lag Working SeqAI666Blr H Lead Lag Working SeqAI401Max Pressure/TempAI402Lead Boiler On PointAI403Lead Boiler Off PointAI404Operating Pressure/TempAI405Low SP LimitAI406High SP LimitAI407Days Till Auto Seq RotationAI408Hours Till Auto Seq RotationAI409Minutes Till Auto Seq RotationAI410Seconds Till Auto Seq RotationAI411Control Output Boiler AAI412Control Output Boiler BAI413Control Output Boiler CAI414Control Output Boiler DAI415Control Output Boiler EAI416Control Output Boiler FAI417Control Output Boiler GAI418Control Output Boiler HAI419Steam Pressure (Water Temp) SPAI420AMR[19]AI421AMR[20]AI422AMR[21]AI423AMR[22]AI424AMR[23]AI425AMR[24]AI426AMR[25]BV1Master Write BitAV51Setpoint Value WriteAV1N510[0]AV2Lag 1 Start Timer SetAV3Lag 1 Start PointAV4Lag 1 Stop PointAV5Lag 1 Stop Timer SetAV6N510[5]AV7Lag 2 Start Timer SetAV8Lag 2 Start PointAV9Lag 2 Stop PointAV10Lag 2 Stop Timer SetAV11N510[10]AV12Lag 3 Start Timer SetAV13Lag 3 Start PointAV14Lag 3 Stop PointAV15Lag 3 Stop Timer SetAV16Lead Boiler SelectionAV17Lag 1 Boiler SelectionAV18Lag 2 Boiler SelectionAV19Lag 3 Boiler SelectionAV20Lag 4 Boiler SelectionAV21Lag 5 Boiler SelectionAV22Lag 6 Boiler SelectionAV23Lag 7 Boiler SelectionAV24Lag 4 Start Timer SetAV25Lag 4 Start PointAV26Lag 4 Stop PointAV27Lag 4 Stop Timer SetAV28Lag 5 Start Timer SetAV29Lag 5 Start PointAV30Lag 5 Stop PointAV31Lag 5 Stop Timer SetAV32Lag 6 Start Timer SetAV33Lag 6 Start PointAV34Lag 6 Stop PointAV35Lag 6 Stop Timer SetAV36Lag 7 Start Timer SetAV37Lag 7 Start PointAV38Lag 7 Stop PointAV39Lag 7 Stop Timer SetAV40N510[39]AV41N510[40]AV42N510[41]AV43N510[42]AV44N510[43]AV45N510[44]AV46N510[45]AV47N510[46]AV48N510[47]AV49N510[48]AV50N510[49]
Integration notes
- Each Cleaver-Brooks controller on the ProtoNode is its own BACnet device; the object instances below are the same on every device.
- Access follows the guide's write-point stars: the starred AV/BV objects are writable, everything else is read-only.
- The guide gives no engineering units or state texts; units appear only where the object name carries them (DEG F / DEG C).
- Where a description is filled in, it gives the register from the guide's Modbus column.
- Boilers E-H have their own blocks next to A-D; only boiler A objects are in the minimum list.
- Objects named N510[..], AMB[..], AMI[..] or AMR[..] are spare tags in the profile with no stated use.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hawk Master Panel lead/lag (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode)
How many BACnet points does the Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode) have?
This list has 196 BACnet objects: 80 analog inputs, 51 analog values, 64 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode) BACnet points are writable?
52 of the 196 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode) BACnet documentation?
Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.
What are the minimum BACnet points to integrate the Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode)?
Start with AV 51 Setpoint Value Write (Setpoint value written by the BMS); AI 404 Operating Pressure/Temp (Operating pressure or temperature); AI 419 Steam Pressure (Water Temp) SP (Steam pressure (water temperature) setpoint); AI 614 Boiler A Sequence Status (Boiler A sequence status); BI 1305 Boiler A Start Output (Boiler A start output); BI 1291 Steam/Water Sensor Fail (Steam/water sensor failure); BI 1292 Low Steam Pressure (Low steam pressure); BI 1323 I/O Module Failure (I/O module failure).
How do I check these points on the real Hawk Master Panel lead/lag (ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Cleaver-Brooks BACnet points lists
- Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
Cleaver-Brooks deaerator and surge tank packages with the ADAC 1000 PLC control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: ADAC 1000, ADAC_1000, ProtoNode RER, 750-426 - Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)
Cleaver-Brooks deaerator and surge tank packages with the ADAC control, read through a ProtoNode RER gateway.
Also known as: ADAC, CB deaerator control, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB120 flame safeguard (ProtoNode)
Cleaver-Brooks boilers with the CB120 flame safeguard, read through a ProtoNode RER gateway.
Also known as: CB120, CB 120, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB780 flame safeguard with expanded annunciator (ProtoNode)
Cleaver-Brooks boilers with the CB780 burner management control and expanded annunciator, read through a ProtoNode RER gateway.
Also known as: CB780, CB 780, CB780E, ProtoNode RER, 750-426 - Hot water boiler control via BACnet gateway
Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)
Cleaver-Brooks hot water boilers with the Falcon hydronic burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Hydronic, ClearFire Falcon, CB Falcon, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Falcon Steam boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Falcon steam burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Steam, CB Falcon steam, ProtoNode RER, 750-426 - Boiler flame safeguard and fuel-air ratio control via BACnet gateway
Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)
Cleaver-Brooks boilers with a CB780/CB783 burner control and FARC fuel-air ratio control, read through a ProtoNode RER gateway.
Also known as: FARC, CB 780/783, CB783, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 1000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 1000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 1000, CB Hawk 1000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 2000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 2000, CB Hawk 2000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 4000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 4000, CB Hawk 4000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 V2 boiler control (ProtoNode)
Cleaver-Brooks boilers with the HAWK 4000 V2 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: HAWK 4000 V2, CB HAWK 4000 V2, HAWK_4000_V2, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4500 boiler control (ProtoNode, EtherNet/IP)
Cleaver-Brooks boilers with the Hawk 4500 PLC boiler control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: Hawk 4500, CB Hawk 4500, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Hawk 5000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 5000, CB Hawk 5000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk ICS boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk ICS control, read through a ProtoNode RER gateway.
Also known as: Hawk ICS, CB ICS, ProtoNode RER, 750-426 - Boiler interface module via BACnet gateway
Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)
Cleaver-Brooks HSC boiler interface modules (one boiler each), read through a ProtoNode RER gateway.
Also known as: Boiler Interface Module, HSC Boiler Interface, BIM, ProtoNode RER, 750-426 - Multi-boiler sequencer (hot water boiler plant) via BACnet gateway
Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)
Cleaver-Brooks HSC panels sequencing up to 10 condensing and 10 non-condensing boilers, read through a ProtoNode RER gateway.
Also known as: HSC, Hydronic System Controller, CB HSC, ProtoNode RER, 750-426 - Pump interface module (boiler plant pumps) via BACnet gateway
Cleaver-Brooks HSC Pump Interface Module (ProtoNode)
Cleaver-Brooks HSC pump interface modules (up to four system pumps), read through a ProtoNode RER gateway.
Also known as: Pump Interface Module, HSC Pump Interface, ProtoNode RER, 750-426 - Boiler water level controller via BACnet gateway
Cleaver-Brooks LCS Level Control System (ProtoNode)
Cleaver-Brooks LCS water level controllers (one or two tanks), read through a ProtoNode RER gateway.
Also known as: LCS, Level Control System, ProtoNode RER, 750-426 - Boiler feed pump controller via BACnet gateway
Cleaver-Brooks PCS Pump Control System (ProtoNode)
Cleaver-Brooks PCS pump controllers (up to four pumps on header pressure or tank level), read through a ProtoNode RER gateway.
Also known as: PCS, Pump Control System, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 100 power meter profile (ProtoNode)
Shark 100 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 100, Electro Industries Shark 100, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 200 power meter profile (ProtoNode)
Shark 200 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 200, Electro Industries Shark 200, ProtoNode RER, 750-426 - Process loop controller via BACnet gateway
Cleaver-Brooks UDC 2500 loop controller profile (ProtoNode)
Honeywell UDC 2500 loop controllers supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: UDC 2500, UDC2500, Honeywell UDC 2500, ProtoNode RER, 750-426
Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.