Boiler feed pump controller via BACnet gateway · BACnet points list

Cleaver-Brooks PCS Pump Control System (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

A read-only ProtoNode profile for the PCS pump controller: header pressure or tank level, VSD PID setpoint and output, lead/lag pump assignment, pump hours, pump run and fault states, manual-mode flags and the alarm words with each bit broken out.

This page lists 57 BACnet objects for the Cleaver-Brooks PCS Pump Control System (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
PCS Pump Control System (ProtoNode)
Equipment
Boiler feed pump controller via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
57 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
PCS, Pump Control System, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 57 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks PCS Pump Control System (ProtoNode)

Integration in brief

Read-only. Map the controlled pressure or level and its setpoint, VSD speed, pump run states and pump faults.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Header Pressure/Tank LevelHeader pressure or tank levelRead
AI 2VSD Speed PID Loop SetpointVSD PID setpointRead
AI 21VSD Speed Output SignalVSD speed outputRead
BI 33Pump 1 RunPump 1 runningRead
BI 34Pump 2 RunPump 2 runningRead
BI 1Pump 1 FaultPump 1 faultRead
BI 2Pump 2 FaultPump 2 faultRead
AI 7Alarm Word 1Alarm word 1Read

Network setup

Cleaver-Brooks PCS Pump Control System (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

57 of 57 shown
Type
AnalogBinary
Show
Cleaver-Brooks PCS Pump Control System (ProtoNode) BACnet Points List
DescriptionStates
AImin1Header Pressure/Tank LevelModbus 40050Read
AImin2VSD Speed PID Loop SetpointModbus 40051Read
AI3ReservedModbus 40052Read
AI4VSD Speed PID Loop OutputModbus 40053Read
AI5Digital Input WordModbus 40054Read
AI6Digital Output WordModbus 40055Read
AImin7Alarm Word 1Modbus 40056Read
AI8Alarm Word 2Modbus 40057Read
AI9Lead PumpModbus 40058Read
AI10Lag 1 PumpModbus 40059Read
AI11Lag 2 PumpModbus 40060Read
AI12Standby PumpModbus 40061Read
AI13Pump 1 Hours (10 000s)Modbus 40062Read
AI14Pump 1 Hours (1s)Modbus 40063Read
AI15Pump 2 Hours (10 000s)Modbus 40064Read
AI16Pump 2 Hours (1s)Modbus 40065Read
AI17Pump 3 Hours (10 000s)Modbus 40066Read
AI18Pump 3 Hours (1s)Modbus 40067Read
AI19Pump 4 Hours (10 000s)Modbus 40068Read
AI20Pump 4 Hours (1s)Modbus 40069Read
AImin21VSD Speed Output SignalModbus 40070Read
BImin1Pump 1 FaultRead
BImin2Pump 2 FaultRead
BI3Pump 3 FaultRead
BI4Pump 4 FaultRead
BI5Header Pressure Low AlmRead
BI6Header Pressure High AlmRead
BI7Analog Signal FailureRead
BI8Datalog SD Card FullRead
BI9Pump 1 in Manual ModeRead
BI10Pump 2 in Manual ModeRead
BI11Pump 3 in Manual ModeRead
BI12Pump 4 in Manual ModeRead
BI13Source Tank LWCORead
BI14Low BatteryRead
BI15External AlmRead
BI16Level Low AlmRead
BI17Level High AlmRead
BI18Alarm Word Bit 1Read
BI19Alarm Word Bit 2Read
BI20Alarm Word Bit 3Read
BI21Alarm Word Bit 4Read
BI22Alarm Word Bit 5Read
BI23Alarm Word Bit 6Read
BI24Alarm Word Bit 7Read
BI25Alarm Word Bit 8Read
BI26Alarm Word Bit 9Read
BI27Alarm Word Bit 10Read
BI28Alarm Word Bit 11Read
BI29Alarm Word Bit 12Read
BI30Alarm Word Bit 13Read
BI31Alarm Word Bit 14Read
BI32Alarm Word Bit 15Read
BImin33Pump 1 RunRead
BImin34Pump 2 RunRead
BI35Pump 3 RunRead
BI36Pump 4 RunRead
Object ID lookup: Cleaver-Brooks PCS Pump Control System point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PCS Pump Control System (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks PCS Pump Control System (ProtoNode)

How many BACnet points does the Cleaver-Brooks PCS Pump Control System (ProtoNode) have?

This list has 57 BACnet objects: 21 analog inputs, 36 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks PCS Pump Control System (ProtoNode) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Cleaver-Brooks PCS Pump Control System (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks PCS Pump Control System (ProtoNode)?

Start with AI 1 Header Pressure/Tank Level (Header pressure or tank level); AI 2 VSD Speed PID Loop Setpoint (VSD PID setpoint); AI 21 VSD Speed Output Signal (VSD speed output); BI 33 Pump 1 Run (Pump 1 running); BI 34 Pump 2 Run (Pump 2 running); BI 1 Pump 1 Fault (Pump 1 fault); BI 2 Pump 2 Fault (Pump 2 fault); AI 7 Alarm Word 1 (Alarm word 1).

How do I check these points on the real PCS Pump Control System (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.