- Home
- BACnet points lists
- Cleaver-Brooks
- ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
Boiler feedwater deaerator and surge tank controller via BACnet gateway · BACnet points list
Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) BACnet points list
Updated 7 November 2026Unofficial source
The ProtoNode maps the ADAC 1000 control to BACnet over EtherNet/IP: deaerator and surge tank pressure, temperature and level, valve signals, feedwater header pressure and setpoint, pump run times, lead/lag order and faults, plus a BMS heartbeat. Writable objects set pump lead/lag order and the feedwater header pressure setpoint.
This page lists 338 BACnet objects for the Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) — 62 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.
- Manufacturer
- Cleaver-Brooks
- Model
- ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
- Equipment
- Boiler feedwater deaerator and surge tank controller via BACnet gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 338 (62 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + Modbus Node-ID
- Also known as
- ADAC 1000, ADAC_1000, ProtoNode RER, 750-426
- Source document
- Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.
BMS integration notes: Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
Keep the BV 1 heartbeat updated and write the feedwater header pressure setpoint if the BMS owns it. Read deaerator pressure, level and temperature, header pressure and the no-alarm relays and heartbeat fault.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | BMS Heartbeat bit | Heartbeat written by the BMS | Write |
| AV 21 | FW Header Pressure Setpoint | Feedwater header pressure setpoint | Write |
| AI 17 | Deaerator Tank Pressure | Deaerator tank pressure | Read |
| AI 18 | Deaerator Tank Wtr Lvl | Deaerator tank water level | Read |
| AI 16 | Deaerator Temp | Deaerator temperature | Read |
| AI 21 | Boiler Feed Wtr Header Pressure | Boiler feedwater header pressure | Read |
| BI 61 | Deaerator No Alarms Relay OK | Deaerator no-alarms relay OK | Read |
| BI 47 | BMS Heartbeat Fault | BMS heartbeat fault | Read |
Heartbeat & communication loss
BV 1 BMS Heartbeat bit is written by the BMS and BI 47 BMS Heartbeat Fault reports a loss; the guide does not state the timeout.
Network setup
- BACnet Device Instance = the controller's Modbus Node-ID + Node_Offset (default 50,000), so Node-ID 1 = 50001. Change Node_Offset in the ProtoNode web configurator to pick other instances.
- The ProtoNode RER does BACnet MS/TP or BACnet IP, selected on its S bank DIP switches.
- BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on the A bank DIP switches; baud on B0-B3 (38400 factory default).
- BACnet IP: default ProtoNode address 192.168.1.24; change it in the web configurator.
Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 1 | Deaerator Lvl BAD QUALITY | Read | |||
| BI | 2 | Deaerator Lvl Hi | Read | |||
| BI | 3 | Deaerator Lvl Lo | Read | |||
| BI | 4 | Deaerator Lvl Lo-Lo (LWCO) | Read | |||
| BI | 5 | Feed Pump 1 Flt | Read | |||
| BI | 6 | Feed Pump 2 Flt | Read | |||
| BI | 7 | Feed Pump 3 Flt | Read | |||
| BI | 8 | Feed Pump 4 Flt | Read | |||
| BI | 9 | Feed Pump 5 Flt | Read | |||
| BI | 10 | Feed Pump 6 Flt | Read | |||
| BI | 11 | Feed Pump 1 OVERLOAD | Read | |||
| BI | 12 | Feed Pump 2 OVERLOAD | Read | |||
| BI | 13 | Feed Pump 3 OVERLOAD | Read | |||
| BI | 14 | Feed Pump 4 OVERLOAD | Read | |||
| BI | 15 | Feed Pump 5 OVERLOAD | Read | |||
| BI | 16 | Feed Pump 6 OVERLOAD | Read | |||
| BI | 17 | Spare | Read | |||
| BI | 18 | Spare | Read | |||
| BI | 19 | Spare | Read | |||
| BI | 20 | Deaerator Temperature BAD QUALITY | Read | |||
| BI | 21 | Deaerator Temperature LOW | Read | |||
| BI | 22 | Deaerator Temperature HIGH | Read | |||
| BI | 23 | Deaerator Pressure BAD QUALITY | Read | |||
| BI | 24 | Deaerator Pressure LOW | Read | |||
| BI | 25 | Deaerator Pressure HIGH | Read | |||
| BI | 26 | Boiler Feed Water Header Pressure BQ | Read | |||
| BI | 27 | Boiler Feed Water Header Pressure LOW | Read | |||
| BI | 28 | Boiler Feed Water Header Pressure HIGH | Read | |||
| BI | 29 | Tray Temperature/User Def 0 Bad Quality | Read | |||
| BI | 30 | Tray Temperature/User Def 0 LOW | Read | |||
| BI | 31 | Tray Temperature/User Def 0 HIGH | Read | |||
| BI | 32 | Reserved for CB - ADAC 1000 Single | Read | |||
| BI | 33 | Feed Pump 1 VSD Bypass | Read | |||
| BI | 34 | Feed Pump 2 VSD Bypass | Read | |||
| BI | 35 | Feed Pump 3 VSD Bypass | Read | |||
| BI | 36 | Feed Pump 4 VSD Bypass | Read | |||
| BI | 37 | Feed Pump 5 VSD Bypass | Read | |||
| BI | 38 | Feed Pump 6 VSD Bypass | Read | |||
| BI | 39 | Tray Pressure/User Def 1 Bad Quality | Read | |||
| BI | 40 | Tray Pressure/User Def 1 LOW | Read | |||
| BI | 41 | Tray Pressure/User Def 1 HIGH | Read | |||
| BI | 42 | Transfer Pump 1 VSD Bypass | Read | |||
| BI | 43 | Transfer Pump 2 VSD Bypass | Read | |||
| BI | 44 | Transfer Pump 3 VSD Bypass | Read | |||
| BI | 45 | Feed Pump Lead Lag Write Permissive | Read | |||
| BI | 46 | Spare | Read | |||
| BImin | 47 | BMS Heartbeat Fault | Read | |||
| BI | 48 | ADAC PLC Heartbeat to BMS | Read | |||
| BI | 49 | Feed Pump 1 ON | Read | |||
| BI | 50 | Feed Pump 2 ON | Read | |||
| BI | 51 | Feed Pump 3 ON | Read | |||
| BI | 52 | Feed Pump 4 ON | Read | |||
| BI | 53 | Feed Pump 5 ON | Read | |||
| BI | 54 | Feed Pump 6 ON/DA Bypass | Read | |||
| BI | 55 | Feed Pump 1 In AUTO | Read | |||
| BI | 56 | Feed Pump 2 In AUTO | Read | |||
| BI | 57 | Feed Pump 3 In AUTO | Read | |||
| BI | 58 | Feed Pump 4 In AUTO | Read | |||
| BI | 59 | Feed Pump 5 In AUTO | Read | |||
| BI | 60 | Feed Pump 6 In AUTO | Read | |||
| BImin | 61 | Deaerator No Alarms Relay OK | Read | |||
| BI | 62 | Yellow Stack Light ON | Read | |||
| BI | 63 | Green Stack Light ON | Read | |||
| BI | 64 | Red Stack Light ON | Read | |||
| BI | 65 | Chemical Feed ON | Read | |||
| BI | 66 | Deaerator Feed Wtr Valve Open | Read | |||
| BI | 67 | Feed Pumps ALT MODE ON | Read | |||
| BI | 68 | DA Lo-Lo Wtr Cutoff Relay Energized | Read | |||
| BI | 69 | Deaerator 2nd Feed Wtr Valve Open | Read | |||
| BI | 70 | Boiler Feed Pump 1 Flow Fault | Read | |||
| BI | 71 | Boiler Feed Pump 2 Flow Fault | Read | |||
| BI | 72 | Boiler Feed Pump 3 Flow Fault | Read | |||
| BI | 73 | Boiler Feed Pump 4 Flow Fault | Read | |||
| BI | 74 | Boiler Feed Pump 5 Flow Fault | Read | |||
| BI | 75 | Boiler Feed Pump 6 Flow Fault | Read | |||
| BI | 76 | PLC Battery Low. Replace Battery | Read | |||
| BI | 77 | Feed Pump 1 VSD Speed Feedback Bad Q | Read | |||
| BI | 78 | Feed Pump 2 VSD Speed Feedback Bad Q | Read | |||
| BI | 79 | Feed Pump 3 VSD Speed Feedback Bad Q | Read | |||
| BI | 80 | Feed Pump 4 VSD Speed Feedback Bad Q | Read | |||
| BI | 81 | Feed Pump 5 VSD Speed Feedback Bad Q | Read | |||
| BI | 82 | Feed Pump 6 VSD Speed Feedback Bad Q | Read | |||
| BI | 83 | Recirculation Valve Close | Read | |||
| BI | 84 | Feed Pumps Lead Lag Enabled | Read | |||
| BI | 85 | Feed Pumps Auto Restart Enabled | Read | |||
| BI | 86 | Remote Set Point Active | Read | |||
| BI | 87 | User Def Ch2 Bad Quality | Read | |||
| BI | 88 | User Def Ch2 LOW | Read | |||
| BI | 89 | User Def Ch2 HIGH | Read | |||
| BI | 90 | User Def Ch3 Bad Quality | Read | |||
| BI | 91 | User Def Ch3 LOW | Read | |||
| BI | 92 | User Def Ch3 HIGH | Read | |||
| BI | 93 | Spare45 | Read | |||
| BI | 94 | Spare46 | Read | |||
| BI | 95 | Spare47 | Read | |||
| BI | 96 | Reserved for CB - ADAC 1000 Dual | Read | |||
| BI | 97 | Surge Tank Level BAD QUALITY | Read | |||
| BI | 98 | Surge Tank Level HIGH | Read | |||
| BI | 99 | Surge Tank Level LOW | Read | |||
| BI | 100 | Surge Tank Temperature BAD QUALITY | Read | |||
| BI | 101 | Surge Tank Temperature LOW | Read | |||
| BI | 102 | Surge Tank Temperature HIGH | Read | |||
| BI | 103 | Transfer Pump 1 FAULT | Read | |||
| BI | 104 | Transfer Pump 2 FAULT | Read | |||
| BI | 105 | Transfer Pump 3 FAULT | Read | |||
| BI | 106 | Transfer Pump 1 OVERLOAD | Read | |||
| BI | 107 | Transfer Pump 2OVERLOAD | Read | |||
| BI | 108 | Transfer Pump 3OVERLOAD | Read | |||
| BI | 109 | Surge Tank LOW-LOW (LWCO) | Read | |||
| BI | 110 | Surge Tank Header Pressure HIGH | Read | |||
| BI | 111 | Surge Tank Header Pressure LOW | Read | |||
| BI | 112 | Surge Tank Header Pressure BAD QUALITY | Read | |||
| BI | 113 | Transfer Pump Lead Lag Write Permissive | Read | |||
| BI | 114 | PLC IO Module Fault | Read | |||
| BI | 115 | Spare | Read | |||
| BI | 116 | Surge 2nd Feed Water Valve Open | Read | |||
| BI | 117 | Transfer Pump 1 Flow Fault | Read | |||
| BI | 118 | Transfer Pump 2 Flow Fault | Read | |||
| BI | 119 | Transfer Pump 3 Flow Fault | Read | |||
| BI | 120 | Transfer Pump 1 VSD Speed Feedback BQ | Read | |||
| BI | 121 | Transfer Pump 2 VSD Speed Feedback BQ | Read | |||
| BI | 122 | Transfer Pump 3 VSD Speed Feedback BQ | Read | |||
| BI | 123 | Spare62 | Read | |||
| BI | 124 | Spare63 | Read | |||
| BI | 125 | Spare64 | Read | |||
| BI | 126 | Transfer Pump 1 VSD Bypass | Read | |||
| BI | 127 | Transfer Pump 2 VSD Bypass | Read | |||
| BI | 128 | Transfer Pump 3 VSD Bypass | Read | |||
| BI | 129 | Surge Tank No Alarms Relay OK | Read | |||
| BI | 130 | Yellow Stack Light ON | Read | |||
| BI | 131 | Green Stack Light ON | Read | |||
| BI | 132 | RED Stack Light ON | Read | |||
| BI | 133 | Surge Tank Feed Water Valve Open | Read | |||
| BI | 134 | ST Low Low Water Cutoff Relay Energized | Read | |||
| BI | 135 | Transfer Pump 1 ON | Read | |||
| BI | 136 | Transfer Pump 2 ON | Read | |||
| BI | 137 | Transfer Pump 3 ON | Read | |||
| BI | 138 | Transfer Pump 1 In AUTO | Read | |||
| BI | 139 | Transfer Pump 2 In AUTO | Read | |||
| BI | 140 | Transfer Pump 3 In AUTO | Read | |||
| BI | 141 | Transfer Pumps ALT MODE ON | Read | |||
| BI | 142 | Transfer Pumps Lead Lag Enabled | Read | |||
| BI | 143 | Transfer Pumps Auto Restart Enabled | Read | |||
| BI | 144 | Spare70 | Read | |||
| BI | 145 | DAB1[9]0 | Read | |||
| BI | 146 | DAB1[9]1 | Read | |||
| BI | 147 | DAB1[9]2 | Read | |||
| BI | 148 | DAB1[9]3 | Read | |||
| BI | 149 | DAB1[9]4 | Read | |||
| BI | 150 | DAB1[9]5 | Read | |||
| BI | 151 | DAB1[9]6 | Read | |||
| BI | 152 | DAB1[9]7 | Read | |||
| BI | 153 | DAB1[9]8 | Read | |||
| BI | 154 | DAB1[9]9 | Read | |||
| BI | 155 | DAB1[9]10 | Read | |||
| BI | 156 | DAB1[9]11 | Read | |||
| BI | 157 | DAB1[9]12 | Read | |||
| BI | 158 | DAB1[9]13 | Read | |||
| BI | 159 | DAB1[9]14 | Read | |||
| BI | 160 | DAB1[9]15 | Read | |||
| AI | 1 | Feed Pump 1 Run Time | Modbus 30001 | Read | ||
| AI | 2 | Feed Pump 2 Run Time | Modbus 30003 | Read | ||
| AI | 3 | Feed Pump 3 Run Time | Modbus 30005 | Read | ||
| AI | 4 | Feed Pump 4 Run Time | Modbus 30007 | Read | ||
| AI | 5 | Feed Pump 5 Run Time | Modbus 30009 | Read | ||
| AI | 6 | Feed Pump 6 Run Time | Modbus 30011 | Read | ||
| AI | 7 | DAR1[6] | Modbus 30013 | Read | ||
| AI | 8 | DAR1[7] | Modbus 30015 | Read | ||
| AI | 9 | DAR1[8] | Modbus 30017 | Read | ||
| AI | 10 | DAR1[9] | Modbus 30019 | Read | ||
| AI | 11 | Stop Lag Feed Pump Limit | Modbus 30021 | Read | ||
| AI | 12 | Alternate Feed Pumps | Modbus 30023 | Read | ||
| AI | 13 | Start Chemical Feed Time Delay | Modbus 30025 | Read | ||
| AI | 14 | Stop Chemical Feed Time Delay | Modbus 30027 | Read | ||
| AI | 15 | DAR1[14] | Modbus 30029 | Read | ||
| AImin | 16 | Deaerator Temp | Modbus 30031 | Read | ||
| AImin | 17 | Deaerator Tank Pressure | Modbus 30033 | Read | ||
| AImin | 18 | Deaerator Tank Wtr Lvl | Modbus 30035 | Read | ||
| AI | 19 | Deaerator Feed Wtr (MUV) Signal | Modbus 30037 | Read | ||
| AI | 20 | Deaerator Steam PRValve Signal | Modbus 30039 | Read | ||
| AImin | 21 | Boiler Feed Wtr Header Pressure | Modbus 30041 | Read | ||
| AI | 22 | 2nd Feed Water (MUV) Signal | Modbus 30043 | Read | ||
| AI | 23 | Start Lag Feed Pump Limit | Modbus 30045 | Read | ||
| AI | 24 | DA Level - Pump Auto-Restart Level | Modbus 30047 | Read | ||
| AI | 25 | Boiler Feed Water Header Pressure SetPt | Modbus 30049 | Read | ||
| AI | 26 | Over Flow Valve Signal | Modbus 30051 | Read | ||
| AI | 27 | User Cfg 0 EU/Tray Temperature | Modbus 30053 | Read | ||
| AI | 28 | User Cfg 1 EU/Tray Pressure | Modbus 30055 | Read | ||
| AI | 29 | User Cfg 2 EU | Modbus 30057 | Read | ||
| AI | 30 | User Cfg 3 EU | Modbus 30059 | Read | ||
| AI | 31 | Spare | Modbus 30061 | Read | ||
| AI | 32 | User Cfg 0 Flow Total | Modbus 30063 | Read | ||
| AI | 33 | User Cfg 1 Flow Total | Modbus 30065 | Read | ||
| AI | 34 | User Cfg 2 Flow Total | Modbus 30067 | Read | ||
| AI | 35 | User Cfg 3 Flow Total | Modbus 30069 | Read | ||
| AI | 36 | Spare | Modbus 30071 | Read | ||
| AI | 37 | Spare102 | Modbus 30073 | Read | ||
| AI | 38 | Spare103 | Modbus 30075 | Read | ||
| AI | 39 | Spare104 | Modbus 30077 | Read | ||
| AI | 40 | Surge Header Pressure | Modbus 30079 | Read | ||
| AI | 41 | Surge Tank Temperature | Modbus 30081 | Read | ||
| AI | 42 | Surge Tank Water Level | Modbus 30083 | Read | ||
| AI | 43 | Surge Tank Feed Water (MUV) Signal | Modbus 30085 | Read | ||
| AI | 44 | Transfer Pump 1 Run Time | Modbus 30087 | Read | ||
| AI | 45 | Transfer Pump 2 Run Time | Modbus 30089 | Read | ||
| AI | 46 | Transfer Pump 3 Run Time | Modbus 30091 | Read | ||
| AI | 47 | Alternate Transfer Pumps | Modbus 30093 | Read | ||
| AI | 48 | Stop Lag Transfer Pump Limit | Modbus 30095 | Read | ||
| AI | 49 | Surge Tank 2nd Feed Water (MUV) Signal | Modbus 30097 | Read | ||
| AI | 50 | Start Lag Transfer Pump Limit | Modbus 30099 | Read | ||
| AI | 51 | Surge Level - Tr Pump Auto-Restart Level | Modbus 30101 | Read | ||
| AI | 52 | Start Surge Chemical Feed Time Delay | Modbus 30103 | Read | ||
| AI | 53 | Stop Surge Chemical Feed Time Delay | Modbus 30105 | Read | ||
| AI | 54 | Transfer Header Pressure SetPt | Modbus 30107 | Read | ||
| AI | 55 | Surge Level - Transfer Valve Bias Setpoint 1 | Modbus 30109 | Read | ||
| AI | 56 | Surge Level - Transfer Valve Bias Setpoint 2 | Modbus 30111 | Read | ||
| AI | 57 | Spare114 | Modbus 30113 | Read | ||
| AI | 58 | Spare115 | Modbus 30115 | Read | ||
| AI | 59 | Spare116 | Modbus 30117 | Read | ||
| AI | 60 | Spare117 | Modbus 30119 | Read | ||
| AI | 61 | Spare118 | Modbus 30121 | Read | ||
| AI | 62 | Spare119 | Modbus 30123 | Read | ||
| AI | 63 | Spare120 | Modbus 30125 | Read | ||
| AI | 64 | Spare121 | Modbus 30127 | Read | ||
| AI | 65 | Spare122 | Modbus 30129 | Read | ||
| AI | 66 | Spare123 | Modbus 30131 | Read | ||
| AI | 67 | Feed Pump 1 LEAD/LAG Status | Modbus 30133 | Read | ||
| AI | 68 | Feed Pump 2 LEAD/LAG Status | Modbus 30134 | Read | ||
| AI | 69 | Feed Pump 3 LEAD/LAG Status | Modbus 30135 | Read | ||
| AI | 70 | Feed Pump 4 LEAD/LAG Status | Modbus 30136 | Read | ||
| AI | 71 | Feed Pump 5 LEAD/LAG Status | Modbus 30137 | Read | ||
| AI | 72 | Feed Pump 6 LEAD/LAG Status | Modbus 30138 | Read | ||
| AI | 73 | DAI1[6] | Modbus 30139 | Read | ||
| AI | 74 | DAI1[7] | Modbus 30140 | Read | ||
| AI | 75 | DAI1[8] | Modbus 30141 | Read | ||
| AI | 76 | DAI1[9] | Modbus 30142 | Read | ||
| AI | 77 | DAI1[10] | Modbus 30143 | Read | ||
| AI | 78 | DAI1[11] | Modbus 30144 | Read | ||
| AI | 79 | DAI1[12] | Modbus 30145 | Read | ||
| AI | 80 | DAI1[13] | Modbus 30146 | Read | ||
| AI | 81 | DAI1[14] | Modbus 30147 | Read | ||
| AI | 82 | DAI1[15] | Modbus 30148 | Read | ||
| AI | 83 | DAI1[16] | Modbus 30149 | Read | ||
| AI | 84 | DAI1[17] | Modbus 30150 | Read | ||
| AI | 85 | DAI1[18] | Modbus 30151 | Read | ||
| AI | 86 | DAI1[19] | Modbus 30152 | Read | ||
| AI | 87 | Transfer Pump 1 LEAD/LAG Status | Modbus 30153 | Read | ||
| AI | 88 | Transfer Pump 2 LEAD/LAG Status | Modbus 30154 | Read | ||
| AI | 89 | Transfer Pump 3 LEAD/LAG Status | Modbus 30155 | Read | ||
| AI | 90 | DAI1[23] | Modbus 30156 | Read | ||
| AI | 91 | DAI1[24] | Modbus 30157 | Read | ||
| AI | 92 | DAI1[25] | Modbus 30158 | Read | ||
| AI | 93 | DAI1[26] | Modbus 30159 | Read | ||
| AI | 94 | DAI1[27] | Modbus 30160 | Read | ||
| AI | 95 | DAI1[28] | Modbus 30161 | Read | ||
| AI | 96 | DAI1[29] | Modbus 30162 | Read | ||
| AI | 97 | DAI1[30] | Modbus 30163 | Read | ||
| AI | 98 | DAI1[31] | Modbus 30164 | Read | ||
| AI | 99 | DAI1[32] | Modbus 30165 | Read | ||
| AI | 100 | DAI1[33] | Modbus 30166 | Read | ||
| AI | 101 | DAI1[34] | Modbus 30167 | Read | ||
| AI | 102 | DAI1[35] | Modbus 30168 | Read | ||
| AI | 103 | DAI1[36] | Modbus 30169 | Read | ||
| AI | 104 | DAI1[37] | Modbus 30170 | Read | ||
| AI | 105 | DAI1[38] | Modbus 30171 | Read | ||
| AI | 106 | DAI1[39] | Modbus 30172 | Read | ||
| AI | 201 | DAB1[0] | Modbus 30201 | Read | ||
| AI | 202 | DAB1[1] | Modbus 30202 | Read | ||
| AI | 203 | DAB1[2] | Modbus 30203 | Read | ||
| AI | 204 | DAB1[3] | Modbus 30204 | Read | ||
| AI | 205 | DAB1[4] | Modbus 30205 | Read | ||
| AI | 206 | DAB1[5] | Modbus 30206 | Read | ||
| AI | 207 | DAB1[6] | Modbus 30207 | Read | ||
| AI | 208 | DAB1[7] | Modbus 30208 | Read | ||
| AI | 209 | DAB1[8] | Modbus 30209 | Read | ||
| AI | 210 | DAB1[9] | Modbus 30210 | Read | ||
| BVmin | 1 | BMS Heartbeat bit | write point | Write | ||
| BV | 2 | Enter BFP LEAD/LAG Order PB | write point | Write | ||
| BV | 3 | Enter TP LEAD/LAG Order PB | write point | Write | ||
| BV | 4 | DAWB[0]3 | write point | Write | ||
| BV | 5 | DAWB[0]4 | write point | Write | ||
| BV | 6 | DAWB[0]5 | write point | Write | ||
| BV | 7 | DAWB[0]6 | write point | Write | ||
| BV | 8 | DAWB[0]7 | write point | Write | ||
| BV | 9 | DAWB[0]8 | write point | Write | ||
| BV | 10 | DAWB[0]9 | write point | Write | ||
| BV | 11 | DAWB[0]10 | write point | Write | ||
| BV | 12 | DAWB[0]11 | write point | Write | ||
| BV | 13 | DAWB[0]12 | write point | Write | ||
| BV | 14 | DAWB[0]13 | write point | Write | ||
| BV | 15 | DAWB[0]14 | write point | Write | ||
| BV | 16 | DAWB[0]15 | write point | Write | ||
| BV | 17 | DAWB[1]0 | write point | Write | ||
| BV | 18 | DAWB[1]1 | write point | Write | ||
| BV | 19 | DAWB[1]2 | write point | Write | ||
| BV | 20 | DAWB[1]3 | write point | Write | ||
| BV | 21 | DAWB[1]4 | write point | Write | ||
| BV | 22 | DAWB[1]5 | write point | Write | ||
| BV | 23 | DAWB[1]6 | write point | Write | ||
| BV | 24 | DAWB[1]7 | write point | Write | ||
| BV | 25 | DAWB[1]8 | write point | Write | ||
| BV | 26 | DAWB[1]9 | write point | Write | ||
| BV | 27 | DAWB[1]10 | write point | Write | ||
| BV | 28 | DAWB[1]11 | write point | Write | ||
| BV | 29 | DAWB[1]12 | write point | Write | ||
| BV | 30 | DAWB[1]13 | write point | Write | ||
| BV | 31 | DAWB[1]14 | write point | Write | ||
| BV | 32 | DAWB[1]15 | write point | Write | ||
| AV | 1 | BFP 1 LEAD/LAG Order | Modbus 40001; write point | Write | ||
| AV | 2 | BFP 2 LEAD/LAG Order | Modbus 40002; write point | Write | ||
| AV | 3 | BFP 3 LEAD/LAG Order | Modbus 40003; write point | Write | ||
| AV | 4 | BFP 4 LEAD/LAG Order | Modbus 40004; write point | Write | ||
| AV | 5 | BFP 5 LEAD/LAG Order | Modbus 40005; write point | Write | ||
| AV | 6 | DAWI[5] | Modbus 40006; write point | Write | ||
| AV | 7 | TP 1 LEAD/LAG Order | Modbus 40007; write point | Write | ||
| AV | 8 | TP 2 LEAD/LAG Order | Modbus 40008; write point | Write | ||
| AV | 9 | TP 2 LEAD/LAG Order | Modbus 40009; write point | Write | ||
| AV | 10 | DAWI[9] | Modbus 40010; write point | Write | ||
| AV | 11 | DAWI[10] | Modbus 40011; write point | Write | ||
| AV | 12 | DAWI[11] | Modbus 40012; write point | Write | ||
| AV | 13 | DAWI[12] | Modbus 40013; write point | Write | ||
| AV | 14 | DAWI[13] | Modbus 40014; write point | Write | ||
| AV | 15 | DAWI[14] | Modbus 40015; write point | Write | ||
| AV | 16 | DAWI[15] | Modbus 40016; write point | Write | ||
| AV | 17 | DAWI[16] | Modbus 40017; write point | Write | ||
| AV | 18 | DAWI[17] | Modbus 40018; write point | Write | ||
| AV | 19 | DAWI[18] | Modbus 40019; write point | Write | ||
| AV | 20 | DAWI[19] | Modbus 40020; write point | Write | ||
| AVmin | 21 | FW Header Pressure Setpoint | Modbus 40030; write point | Write | ||
| AV | 22 | DAWR[1] | Modbus 40032; write point | Write | ||
| AV | 23 | DAWR[2] | Modbus 40034; write point | Write | ||
| AV | 24 | DAWR[3] | Modbus 40036; write point | Write | ||
| AV | 25 | DAWR[4] | Modbus 40038; write point | Write | ||
| AV | 26 | DAWR[5] | Modbus 40040; write point | Write | ||
| AV | 27 | DAWR[6] | Modbus 40042; write point | Write | ||
| AV | 28 | DAWR[7] | Modbus 40044; write point | Write | ||
| AV | 29 | DAWR[8] | Modbus 40046; write point | Write | ||
| AV | 30 | DAWR[9] | Modbus 40048; write point | Write |
No points match these filters.
Object ID lookup: Cleaver-Brooks ADAC 1000 deaerator / surge tank control point IDs by name
BI1Deaerator Lvl BAD QUALITYBI2Deaerator Lvl HiBI3Deaerator Lvl LoBI4Deaerator Lvl Lo-Lo (LWCO)BI5Feed Pump 1 FltBI6Feed Pump 2 FltBI7Feed Pump 3 FltBI8Feed Pump 4 FltBI9Feed Pump 5 FltBI10Feed Pump 6 FltBI11Feed Pump 1 OVERLOADBI12Feed Pump 2 OVERLOADBI13Feed Pump 3 OVERLOADBI14Feed Pump 4 OVERLOADBI15Feed Pump 5 OVERLOADBI16Feed Pump 6 OVERLOADBI17SpareBI18SpareBI19SpareBI20Deaerator Temperature BAD QUALITYBI21Deaerator Temperature LOWBI22Deaerator Temperature HIGHBI23Deaerator Pressure BAD QUALITYBI24Deaerator Pressure LOWBI25Deaerator Pressure HIGHBI26Boiler Feed Water Header Pressure BQBI27Boiler Feed Water Header Pressure LOWBI28Boiler Feed Water Header Pressure HIGHBI29Tray Temperature/User Def 0 Bad QualityBI30Tray Temperature/User Def 0 LOWBI31Tray Temperature/User Def 0 HIGHBI32Reserved for CB - ADAC 1000 SingleBI33Feed Pump 1 VSD BypassBI34Feed Pump 2 VSD BypassBI35Feed Pump 3 VSD BypassBI36Feed Pump 4 VSD BypassBI37Feed Pump 5 VSD BypassBI38Feed Pump 6 VSD BypassBI39Tray Pressure/User Def 1 Bad QualityBI40Tray Pressure/User Def 1 LOWBI41Tray Pressure/User Def 1 HIGHBI42Transfer Pump 1 VSD BypassBI43Transfer Pump 2 VSD BypassBI44Transfer Pump 3 VSD BypassBI45Feed Pump Lead Lag Write PermissiveBI46SpareBI47BMS Heartbeat FaultBI48ADAC PLC Heartbeat to BMSBI49Feed Pump 1 ONBI50Feed Pump 2 ONBI51Feed Pump 3 ONBI52Feed Pump 4 ONBI53Feed Pump 5 ONBI54Feed Pump 6 ON/DA BypassBI55Feed Pump 1 In AUTOBI56Feed Pump 2 In AUTOBI57Feed Pump 3 In AUTOBI58Feed Pump 4 In AUTOBI59Feed Pump 5 In AUTOBI60Feed Pump 6 In AUTOBI61Deaerator No Alarms Relay OKBI62Yellow Stack Light ONBI63Green Stack Light ONBI64Red Stack Light ONBI65Chemical Feed ONBI66Deaerator Feed Wtr Valve OpenBI67Feed Pumps ALT MODE ONBI68DA Lo-Lo Wtr Cutoff Relay EnergizedBI69Deaerator 2nd Feed Wtr Valve OpenBI70Boiler Feed Pump 1 Flow FaultBI71Boiler Feed Pump 2 Flow FaultBI72Boiler Feed Pump 3 Flow FaultBI73Boiler Feed Pump 4 Flow FaultBI74Boiler Feed Pump 5 Flow FaultBI75Boiler Feed Pump 6 Flow FaultBI76PLC Battery Low. Replace BatteryBI77Feed Pump 1 VSD Speed Feedback Bad QBI78Feed Pump 2 VSD Speed Feedback Bad QBI79Feed Pump 3 VSD Speed Feedback Bad QBI80Feed Pump 4 VSD Speed Feedback Bad QBI81Feed Pump 5 VSD Speed Feedback Bad QBI82Feed Pump 6 VSD Speed Feedback Bad QBI83Recirculation Valve CloseBI84Feed Pumps Lead Lag EnabledBI85Feed Pumps Auto Restart EnabledBI86Remote Set Point ActiveBI87User Def Ch2 Bad QualityBI88User Def Ch2 LOWBI89User Def Ch2 HIGHBI90User Def Ch3 Bad QualityBI91User Def Ch3 LOWBI92User Def Ch3 HIGHBI93Spare45BI94Spare46BI95Spare47BI96Reserved for CB - ADAC 1000 DualBI97Surge Tank Level BAD QUALITYBI98Surge Tank Level HIGHBI99Surge Tank Level LOWBI100Surge Tank Temperature BAD QUALITYBI101Surge Tank Temperature LOWBI102Surge Tank Temperature HIGHBI103Transfer Pump 1 FAULTBI104Transfer Pump 2 FAULTBI105Transfer Pump 3 FAULTBI106Transfer Pump 1 OVERLOADBI107Transfer Pump 2OVERLOADBI108Transfer Pump 3OVERLOADBI109Surge Tank LOW-LOW (LWCO)BI110Surge Tank Header Pressure HIGHBI111Surge Tank Header Pressure LOWBI112Surge Tank Header Pressure BAD QUALITYBI113Transfer Pump Lead Lag Write PermissiveBI114PLC IO Module FaultBI115SpareBI116Surge 2nd Feed Water Valve OpenBI117Transfer Pump 1 Flow FaultBI118Transfer Pump 2 Flow FaultBI119Transfer Pump 3 Flow FaultBI120Transfer Pump 1 VSD Speed Feedback BQBI121Transfer Pump 2 VSD Speed Feedback BQBI122Transfer Pump 3 VSD Speed Feedback BQBI123Spare62BI124Spare63BI125Spare64BI126Transfer Pump 1 VSD BypassBI127Transfer Pump 2 VSD BypassBI128Transfer Pump 3 VSD BypassBI129Surge Tank No Alarms Relay OKBI130Yellow Stack Light ONBI131Green Stack Light ONBI132RED Stack Light ONBI133Surge Tank Feed Water Valve OpenBI134ST Low Low Water Cutoff Relay EnergizedBI135Transfer Pump 1 ONBI136Transfer Pump 2 ONBI137Transfer Pump 3 ONBI138Transfer Pump 1 In AUTOBI139Transfer Pump 2 In AUTOBI140Transfer Pump 3 In AUTOBI141Transfer Pumps ALT MODE ONBI142Transfer Pumps Lead Lag EnabledBI143Transfer Pumps Auto Restart EnabledBI144Spare70BI145DAB1[9]0BI146DAB1[9]1BI147DAB1[9]2BI148DAB1[9]3BI149DAB1[9]4BI150DAB1[9]5BI151DAB1[9]6BI152DAB1[9]7BI153DAB1[9]8BI154DAB1[9]9BI155DAB1[9]10BI156DAB1[9]11BI157DAB1[9]12BI158DAB1[9]13BI159DAB1[9]14BI160DAB1[9]15AI1Feed Pump 1 Run TimeAI2Feed Pump 2 Run TimeAI3Feed Pump 3 Run TimeAI4Feed Pump 4 Run TimeAI5Feed Pump 5 Run TimeAI6Feed Pump 6 Run TimeAI7DAR1[6]AI8DAR1[7]AI9DAR1[8]AI10DAR1[9]AI11Stop Lag Feed Pump LimitAI12Alternate Feed PumpsAI13Start Chemical Feed Time DelayAI14Stop Chemical Feed Time DelayAI15DAR1[14]AI16Deaerator TempAI17Deaerator Tank PressureAI18Deaerator Tank Wtr LvlAI19Deaerator Feed Wtr (MUV) SignalAI20Deaerator Steam PRValve SignalAI21Boiler Feed Wtr Header PressureAI222nd Feed Water (MUV) SignalAI23Start Lag Feed Pump LimitAI24DA Level - Pump Auto-Restart LevelAI25Boiler Feed Water Header Pressure SetPtAI26Over Flow Valve SignalAI27User Cfg 0 EU/Tray TemperatureAI28User Cfg 1 EU/Tray PressureAI29User Cfg 2 EUAI30User Cfg 3 EUAI31SpareAI32User Cfg 0 Flow TotalAI33User Cfg 1 Flow TotalAI34User Cfg 2 Flow TotalAI35User Cfg 3 Flow TotalAI36SpareAI37Spare102AI38Spare103AI39Spare104AI40Surge Header PressureAI41Surge Tank TemperatureAI42Surge Tank Water LevelAI43Surge Tank Feed Water (MUV) SignalAI44Transfer Pump 1 Run TimeAI45Transfer Pump 2 Run TimeAI46Transfer Pump 3 Run TimeAI47Alternate Transfer PumpsAI48Stop Lag Transfer Pump LimitAI49Surge Tank 2nd Feed Water (MUV) SignalAI50Start Lag Transfer Pump LimitAI51Surge Level - Tr Pump Auto-Restart LevelAI52Start Surge Chemical Feed Time DelayAI53Stop Surge Chemical Feed Time DelayAI54Transfer Header Pressure SetPtAI55Surge Level - Transfer Valve Bias Setpoint 1AI56Surge Level - Transfer Valve Bias Setpoint 2AI57Spare114AI58Spare115AI59Spare116AI60Spare117AI61Spare118AI62Spare119AI63Spare120AI64Spare121AI65Spare122AI66Spare123AI67Feed Pump 1 LEAD/LAG StatusAI68Feed Pump 2 LEAD/LAG StatusAI69Feed Pump 3 LEAD/LAG StatusAI70Feed Pump 4 LEAD/LAG StatusAI71Feed Pump 5 LEAD/LAG StatusAI72Feed Pump 6 LEAD/LAG StatusAI73DAI1[6]AI74DAI1[7]AI75DAI1[8]AI76DAI1[9]AI77DAI1[10]AI78DAI1[11]AI79DAI1[12]AI80DAI1[13]AI81DAI1[14]AI82DAI1[15]AI83DAI1[16]AI84DAI1[17]AI85DAI1[18]AI86DAI1[19]AI87Transfer Pump 1 LEAD/LAG StatusAI88Transfer Pump 2 LEAD/LAG StatusAI89Transfer Pump 3 LEAD/LAG StatusAI90DAI1[23]AI91DAI1[24]AI92DAI1[25]AI93DAI1[26]AI94DAI1[27]AI95DAI1[28]AI96DAI1[29]AI97DAI1[30]AI98DAI1[31]AI99DAI1[32]AI100DAI1[33]AI101DAI1[34]AI102DAI1[35]AI103DAI1[36]AI104DAI1[37]AI105DAI1[38]AI106DAI1[39]AI201DAB1[0]AI202DAB1[1]AI203DAB1[2]AI204DAB1[3]AI205DAB1[4]AI206DAB1[5]AI207DAB1[6]AI208DAB1[7]AI209DAB1[8]AI210DAB1[9]BV1BMS Heartbeat bitBV2Enter BFP LEAD/LAG Order PBBV3Enter TP LEAD/LAG Order PBBV4DAWB[0]3BV5DAWB[0]4BV6DAWB[0]5BV7DAWB[0]6BV8DAWB[0]7BV9DAWB[0]8BV10DAWB[0]9BV11DAWB[0]10BV12DAWB[0]11BV13DAWB[0]12BV14DAWB[0]13BV15DAWB[0]14BV16DAWB[0]15BV17DAWB[1]0BV18DAWB[1]1BV19DAWB[1]2BV20DAWB[1]3BV21DAWB[1]4BV22DAWB[1]5BV23DAWB[1]6BV24DAWB[1]7BV25DAWB[1]8BV26DAWB[1]9BV27DAWB[1]10BV28DAWB[1]11BV29DAWB[1]12BV30DAWB[1]13BV31DAWB[1]14BV32DAWB[1]15AV1BFP 1 LEAD/LAG OrderAV2BFP 2 LEAD/LAG OrderAV3BFP 3 LEAD/LAG OrderAV4BFP 4 LEAD/LAG OrderAV5BFP 5 LEAD/LAG OrderAV6DAWI[5]AV7TP 1 LEAD/LAG OrderAV8TP 2 LEAD/LAG OrderAV9TP 2 LEAD/LAG OrderAV10DAWI[9]AV11DAWI[10]AV12DAWI[11]AV13DAWI[12]AV14DAWI[13]AV15DAWI[14]AV16DAWI[15]AV17DAWI[16]AV18DAWI[17]AV19DAWI[18]AV20DAWI[19]AV21FW Header Pressure SetpointAV22DAWR[1]AV23DAWR[2]AV24DAWR[3]AV25DAWR[4]AV26DAWR[5]AV27DAWR[6]AV28DAWR[7]AV29DAWR[8]AV30DAWR[9]
Integration notes
- Each Cleaver-Brooks controller on the ProtoNode is its own BACnet device; the object instances below are the same on every device.
- Access follows the guide's write-point stars: the starred AV/BV objects are writable, everything else is read-only.
- The guide gives no engineering units or state texts; units appear only where the object name carries them (DEG F / DEG C).
- Where a description is filled in, it gives the register from the guide's Modbus column.
- The ProtoNode reads this profile from the PLC over EtherNet/IP.
- Objects named DAWB[..], DAWI[..], DAWR[..], DAR1[..] or DAI1[..] are spare tags with no stated use.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
How many BACnet points does the Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) have?
This list has 338 BACnet objects: 116 analog inputs, 30 analog values, 160 binary inputs, 32 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) BACnet points are writable?
62 of the 338 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) BACnet documentation?
Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.
What are the minimum BACnet points to integrate the Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)?
Start with BV 1 BMS Heartbeat bit (Heartbeat written by the BMS); AV 21 FW Header Pressure Setpoint (Feedwater header pressure setpoint); AI 17 Deaerator Tank Pressure (Deaerator tank pressure); AI 18 Deaerator Tank Wtr Lvl (Deaerator tank water level); AI 16 Deaerator Temp (Deaerator temperature); AI 21 Boiler Feed Wtr Header Pressure (Boiler feedwater header pressure); BI 61 Deaerator No Alarms Relay OK (Deaerator no-alarms relay OK); BI 47 BMS Heartbeat Fault (BMS heartbeat fault).
Does the Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) need a BACnet heartbeat or have a communication timeout?
BV 1 BMS Heartbeat bit is written by the BMS and BI 47 BMS Heartbeat Fault reports a loss; the guide does not state the timeout.
How do I check these points on the real ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Cleaver-Brooks BACnet points lists
- Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)
Cleaver-Brooks deaerator and surge tank packages with the ADAC control, read through a ProtoNode RER gateway.
Also known as: ADAC, CB deaerator control, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB120 flame safeguard (ProtoNode)
Cleaver-Brooks boilers with the CB120 flame safeguard, read through a ProtoNode RER gateway.
Also known as: CB120, CB 120, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB780 flame safeguard with expanded annunciator (ProtoNode)
Cleaver-Brooks boilers with the CB780 burner management control and expanded annunciator, read through a ProtoNode RER gateway.
Also known as: CB780, CB 780, CB780E, ProtoNode RER, 750-426 - Hot water boiler control via BACnet gateway
Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)
Cleaver-Brooks hot water boilers with the Falcon hydronic burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Hydronic, ClearFire Falcon, CB Falcon, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Falcon Steam boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Falcon steam burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Steam, CB Falcon steam, ProtoNode RER, 750-426 - Boiler flame safeguard and fuel-air ratio control via BACnet gateway
Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)
Cleaver-Brooks boilers with a CB780/CB783 burner control and FARC fuel-air ratio control, read through a ProtoNode RER gateway.
Also known as: FARC, CB 780/783, CB783, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 1000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 1000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 1000, CB Hawk 1000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 2000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 2000, CB Hawk 2000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 4000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 4000, CB Hawk 4000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 V2 boiler control (ProtoNode)
Cleaver-Brooks boilers with the HAWK 4000 V2 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: HAWK 4000 V2, CB HAWK 4000 V2, HAWK_4000_V2, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4500 boiler control (ProtoNode, EtherNet/IP)
Cleaver-Brooks boilers with the Hawk 4500 PLC boiler control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: Hawk 4500, CB Hawk 4500, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Hawk 5000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 5000, CB Hawk 5000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk ICS boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk ICS control, read through a ProtoNode RER gateway.
Also known as: Hawk ICS, CB ICS, ProtoNode RER, 750-426 - Boiler lead/lag master panel via BACnet gateway
Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode)
Cleaver-Brooks Hawk Master Panels sequencing up to eight Hawk boilers (A-H), read through a ProtoNode RER gateway.
Also known as: Hawk Master Panel, Hawk Master, CB Master Panel, ProtoNode RER, 750-426 - Boiler interface module via BACnet gateway
Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)
Cleaver-Brooks HSC boiler interface modules (one boiler each), read through a ProtoNode RER gateway.
Also known as: Boiler Interface Module, HSC Boiler Interface, BIM, ProtoNode RER, 750-426 - Multi-boiler sequencer (hot water boiler plant) via BACnet gateway
Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)
Cleaver-Brooks HSC panels sequencing up to 10 condensing and 10 non-condensing boilers, read through a ProtoNode RER gateway.
Also known as: HSC, Hydronic System Controller, CB HSC, ProtoNode RER, 750-426 - Pump interface module (boiler plant pumps) via BACnet gateway
Cleaver-Brooks HSC Pump Interface Module (ProtoNode)
Cleaver-Brooks HSC pump interface modules (up to four system pumps), read through a ProtoNode RER gateway.
Also known as: Pump Interface Module, HSC Pump Interface, ProtoNode RER, 750-426 - Boiler water level controller via BACnet gateway
Cleaver-Brooks LCS Level Control System (ProtoNode)
Cleaver-Brooks LCS water level controllers (one or two tanks), read through a ProtoNode RER gateway.
Also known as: LCS, Level Control System, ProtoNode RER, 750-426 - Boiler feed pump controller via BACnet gateway
Cleaver-Brooks PCS Pump Control System (ProtoNode)
Cleaver-Brooks PCS pump controllers (up to four pumps on header pressure or tank level), read through a ProtoNode RER gateway.
Also known as: PCS, Pump Control System, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 100 power meter profile (ProtoNode)
Shark 100 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 100, Electro Industries Shark 100, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 200 power meter profile (ProtoNode)
Shark 200 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 200, Electro Industries Shark 200, ProtoNode RER, 750-426 - Process loop controller via BACnet gateway
Cleaver-Brooks UDC 2500 loop controller profile (ProtoNode)
Honeywell UDC 2500 loop controllers supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: UDC 2500, UDC2500, Honeywell UDC 2500, ProtoNode RER, 750-426
Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.