Boiler feedwater deaerator and surge tank controller via BACnet gateway · BACnet points list

Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The ProtoNode maps the ADAC 1000 control to BACnet over EtherNet/IP: deaerator and surge tank pressure, temperature and level, valve signals, feedwater header pressure and setpoint, pump run times, lead/lag order and faults, plus a BMS heartbeat. Writable objects set pump lead/lag order and the feedwater header pressure setpoint.

This page lists 338 BACnet objects for the Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) — 62 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
Equipment
Boiler feedwater deaerator and surge tank controller via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
338 (62 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
ADAC 1000, ADAC_1000, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 338 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)

Integration in brief

Keep the BV 1 heartbeat updated and write the feedwater header pressure setpoint if the BMS owns it. Read deaerator pressure, level and temperature, header pressure and the no-alarm relays and heartbeat fault.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1BMS Heartbeat bitHeartbeat written by the BMSWrite
AV 21FW Header Pressure SetpointFeedwater header pressure setpointWrite
AI 17Deaerator Tank PressureDeaerator tank pressureRead
AI 18Deaerator Tank Wtr LvlDeaerator tank water levelRead
AI 16Deaerator TempDeaerator temperatureRead
AI 21Boiler Feed Wtr Header PressureBoiler feedwater header pressureRead
BI 61Deaerator No Alarms Relay OKDeaerator no-alarms relay OKRead
BI 47BMS Heartbeat FaultBMS heartbeat faultRead

Heartbeat & communication loss

BV 1 BMS Heartbeat bit is written by the BMS and BI 47 BMS Heartbeat Fault reports a loss; the guide does not state the timeout.

Network setup

Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

338 of 338 shown
Type
Access
Show
Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) BACnet Points List
DescriptionStates
BI1Deaerator Lvl BAD QUALITYRead
BI2Deaerator Lvl HiRead
BI3Deaerator Lvl LoRead
BI4Deaerator Lvl Lo-Lo (LWCO)Read
BI5Feed Pump 1 FltRead
BI6Feed Pump 2 FltRead
BI7Feed Pump 3 FltRead
BI8Feed Pump 4 FltRead
BI9Feed Pump 5 FltRead
BI10Feed Pump 6 FltRead
BI11Feed Pump 1 OVERLOADRead
BI12Feed Pump 2 OVERLOADRead
BI13Feed Pump 3 OVERLOADRead
BI14Feed Pump 4 OVERLOADRead
BI15Feed Pump 5 OVERLOADRead
BI16Feed Pump 6 OVERLOADRead
BI17SpareRead
BI18SpareRead
BI19SpareRead
BI20Deaerator Temperature BAD QUALITYRead
BI21Deaerator Temperature LOWRead
BI22Deaerator Temperature HIGHRead
BI23Deaerator Pressure BAD QUALITYRead
BI24Deaerator Pressure LOWRead
BI25Deaerator Pressure HIGHRead
BI26Boiler Feed Water Header Pressure BQRead
BI27Boiler Feed Water Header Pressure LOWRead
BI28Boiler Feed Water Header Pressure HIGHRead
BI29Tray Temperature/User Def 0 Bad QualityRead
BI30Tray Temperature/User Def 0 LOWRead
BI31Tray Temperature/User Def 0 HIGHRead
BI32Reserved for CB - ADAC 1000 SingleRead
BI33Feed Pump 1 VSD BypassRead
BI34Feed Pump 2 VSD BypassRead
BI35Feed Pump 3 VSD BypassRead
BI36Feed Pump 4 VSD BypassRead
BI37Feed Pump 5 VSD BypassRead
BI38Feed Pump 6 VSD BypassRead
BI39Tray Pressure/User Def 1 Bad QualityRead
BI40Tray Pressure/User Def 1 LOWRead
BI41Tray Pressure/User Def 1 HIGHRead
BI42Transfer Pump 1 VSD BypassRead
BI43Transfer Pump 2 VSD BypassRead
BI44Transfer Pump 3 VSD BypassRead
BI45Feed Pump Lead Lag Write PermissiveRead
BI46SpareRead
BImin47BMS Heartbeat FaultRead
BI48ADAC PLC Heartbeat to BMSRead
BI49Feed Pump 1 ONRead
BI50Feed Pump 2 ONRead
BI51Feed Pump 3 ONRead
BI52Feed Pump 4 ONRead
BI53Feed Pump 5 ONRead
BI54Feed Pump 6 ON/DA BypassRead
BI55Feed Pump 1 In AUTORead
BI56Feed Pump 2 In AUTORead
BI57Feed Pump 3 In AUTORead
BI58Feed Pump 4 In AUTORead
BI59Feed Pump 5 In AUTORead
BI60Feed Pump 6 In AUTORead
BImin61Deaerator No Alarms Relay OKRead
BI62Yellow Stack Light ONRead
BI63Green Stack Light ONRead
BI64Red Stack Light ONRead
BI65Chemical Feed ONRead
BI66Deaerator Feed Wtr Valve OpenRead
BI67Feed Pumps ALT MODE ONRead
BI68DA Lo-Lo Wtr Cutoff Relay EnergizedRead
BI69Deaerator 2nd Feed Wtr Valve OpenRead
BI70Boiler Feed Pump 1 Flow FaultRead
BI71Boiler Feed Pump 2 Flow FaultRead
BI72Boiler Feed Pump 3 Flow FaultRead
BI73Boiler Feed Pump 4 Flow FaultRead
BI74Boiler Feed Pump 5 Flow FaultRead
BI75Boiler Feed Pump 6 Flow FaultRead
BI76PLC Battery Low. Replace BatteryRead
BI77Feed Pump 1 VSD Speed Feedback Bad QRead
BI78Feed Pump 2 VSD Speed Feedback Bad QRead
BI79Feed Pump 3 VSD Speed Feedback Bad QRead
BI80Feed Pump 4 VSD Speed Feedback Bad QRead
BI81Feed Pump 5 VSD Speed Feedback Bad QRead
BI82Feed Pump 6 VSD Speed Feedback Bad QRead
BI83Recirculation Valve CloseRead
BI84Feed Pumps Lead Lag EnabledRead
BI85Feed Pumps Auto Restart EnabledRead
BI86Remote Set Point ActiveRead
BI87User Def Ch2 Bad QualityRead
BI88User Def Ch2 LOWRead
BI89User Def Ch2 HIGHRead
BI90User Def Ch3 Bad QualityRead
BI91User Def Ch3 LOWRead
BI92User Def Ch3 HIGHRead
BI93Spare45Read
BI94Spare46Read
BI95Spare47Read
BI96Reserved for CB - ADAC 1000 DualRead
BI97Surge Tank Level BAD QUALITYRead
BI98Surge Tank Level HIGHRead
BI99Surge Tank Level LOWRead
BI100Surge Tank Temperature BAD QUALITYRead
BI101Surge Tank Temperature LOWRead
BI102Surge Tank Temperature HIGHRead
BI103Transfer Pump 1 FAULTRead
BI104Transfer Pump 2 FAULTRead
BI105Transfer Pump 3 FAULTRead
BI106Transfer Pump 1 OVERLOADRead
BI107Transfer Pump 2OVERLOADRead
BI108Transfer Pump 3OVERLOADRead
BI109Surge Tank LOW-LOW (LWCO)Read
BI110Surge Tank Header Pressure HIGHRead
BI111Surge Tank Header Pressure LOWRead
BI112Surge Tank Header Pressure BAD QUALITYRead
BI113Transfer Pump Lead Lag Write PermissiveRead
BI114PLC IO Module FaultRead
BI115SpareRead
BI116Surge 2nd Feed Water Valve OpenRead
BI117Transfer Pump 1 Flow FaultRead
BI118Transfer Pump 2 Flow FaultRead
BI119Transfer Pump 3 Flow FaultRead
BI120Transfer Pump 1 VSD Speed Feedback BQRead
BI121Transfer Pump 2 VSD Speed Feedback BQRead
BI122Transfer Pump 3 VSD Speed Feedback BQRead
BI123Spare62Read
BI124Spare63Read
BI125Spare64Read
BI126Transfer Pump 1 VSD BypassRead
BI127Transfer Pump 2 VSD BypassRead
BI128Transfer Pump 3 VSD BypassRead
BI129Surge Tank No Alarms Relay OKRead
BI130Yellow Stack Light ONRead
BI131Green Stack Light ONRead
BI132RED Stack Light ONRead
BI133Surge Tank Feed Water Valve OpenRead
BI134ST Low Low Water Cutoff Relay EnergizedRead
BI135Transfer Pump 1 ONRead
BI136Transfer Pump 2 ONRead
BI137Transfer Pump 3 ONRead
BI138Transfer Pump 1 In AUTORead
BI139Transfer Pump 2 In AUTORead
BI140Transfer Pump 3 In AUTORead
BI141Transfer Pumps ALT MODE ONRead
BI142Transfer Pumps Lead Lag EnabledRead
BI143Transfer Pumps Auto Restart EnabledRead
BI144Spare70Read
BI145DAB1[9]0Read
BI146DAB1[9]1Read
BI147DAB1[9]2Read
BI148DAB1[9]3Read
BI149DAB1[9]4Read
BI150DAB1[9]5Read
BI151DAB1[9]6Read
BI152DAB1[9]7Read
BI153DAB1[9]8Read
BI154DAB1[9]9Read
BI155DAB1[9]10Read
BI156DAB1[9]11Read
BI157DAB1[9]12Read
BI158DAB1[9]13Read
BI159DAB1[9]14Read
BI160DAB1[9]15Read
AI1Feed Pump 1 Run TimeModbus 30001Read
AI2Feed Pump 2 Run TimeModbus 30003Read
AI3Feed Pump 3 Run TimeModbus 30005Read
AI4Feed Pump 4 Run TimeModbus 30007Read
AI5Feed Pump 5 Run TimeModbus 30009Read
AI6Feed Pump 6 Run TimeModbus 30011Read
AI7DAR1[6]Modbus 30013Read
AI8DAR1[7]Modbus 30015Read
AI9DAR1[8]Modbus 30017Read
AI10DAR1[9]Modbus 30019Read
AI11Stop Lag Feed Pump LimitModbus 30021Read
AI12Alternate Feed PumpsModbus 30023Read
AI13Start Chemical Feed Time DelayModbus 30025Read
AI14Stop Chemical Feed Time DelayModbus 30027Read
AI15DAR1[14]Modbus 30029Read
AImin16Deaerator TempModbus 30031Read
AImin17Deaerator Tank PressureModbus 30033Read
AImin18Deaerator Tank Wtr LvlModbus 30035Read
AI19Deaerator Feed Wtr (MUV) SignalModbus 30037Read
AI20Deaerator Steam PRValve SignalModbus 30039Read
AImin21Boiler Feed Wtr Header PressureModbus 30041Read
AI222nd Feed Water (MUV) SignalModbus 30043Read
AI23Start Lag Feed Pump LimitModbus 30045Read
AI24DA Level - Pump Auto-Restart LevelModbus 30047Read
AI25Boiler Feed Water Header Pressure SetPtModbus 30049Read
AI26Over Flow Valve SignalModbus 30051Read
AI27User Cfg 0 EU/Tray TemperatureModbus 30053Read
AI28User Cfg 1 EU/Tray PressureModbus 30055Read
AI29User Cfg 2 EUModbus 30057Read
AI30User Cfg 3 EUModbus 30059Read
AI31SpareModbus 30061Read
AI32User Cfg 0 Flow TotalModbus 30063Read
AI33User Cfg 1 Flow TotalModbus 30065Read
AI34User Cfg 2 Flow TotalModbus 30067Read
AI35User Cfg 3 Flow TotalModbus 30069Read
AI36SpareModbus 30071Read
AI37Spare102Modbus 30073Read
AI38Spare103Modbus 30075Read
AI39Spare104Modbus 30077Read
AI40Surge Header PressureModbus 30079Read
AI41Surge Tank TemperatureModbus 30081Read
AI42Surge Tank Water LevelModbus 30083Read
AI43Surge Tank Feed Water (MUV) SignalModbus 30085Read
AI44Transfer Pump 1 Run TimeModbus 30087Read
AI45Transfer Pump 2 Run TimeModbus 30089Read
AI46Transfer Pump 3 Run TimeModbus 30091Read
AI47Alternate Transfer PumpsModbus 30093Read
AI48Stop Lag Transfer Pump LimitModbus 30095Read
AI49Surge Tank 2nd Feed Water (MUV) SignalModbus 30097Read
AI50Start Lag Transfer Pump LimitModbus 30099Read
AI51Surge Level - Tr Pump Auto-Restart LevelModbus 30101Read
AI52Start Surge Chemical Feed Time DelayModbus 30103Read
AI53Stop Surge Chemical Feed Time DelayModbus 30105Read
AI54Transfer Header Pressure SetPtModbus 30107Read
AI55Surge Level - Transfer Valve Bias Setpoint 1Modbus 30109Read
AI56Surge Level - Transfer Valve Bias Setpoint 2Modbus 30111Read
AI57Spare114Modbus 30113Read
AI58Spare115Modbus 30115Read
AI59Spare116Modbus 30117Read
AI60Spare117Modbus 30119Read
AI61Spare118Modbus 30121Read
AI62Spare119Modbus 30123Read
AI63Spare120Modbus 30125Read
AI64Spare121Modbus 30127Read
AI65Spare122Modbus 30129Read
AI66Spare123Modbus 30131Read
AI67Feed Pump 1 LEAD/LAG StatusModbus 30133Read
AI68Feed Pump 2 LEAD/LAG StatusModbus 30134Read
AI69Feed Pump 3 LEAD/LAG StatusModbus 30135Read
AI70Feed Pump 4 LEAD/LAG StatusModbus 30136Read
AI71Feed Pump 5 LEAD/LAG StatusModbus 30137Read
AI72Feed Pump 6 LEAD/LAG StatusModbus 30138Read
AI73DAI1[6]Modbus 30139Read
AI74DAI1[7]Modbus 30140Read
AI75DAI1[8]Modbus 30141Read
AI76DAI1[9]Modbus 30142Read
AI77DAI1[10]Modbus 30143Read
AI78DAI1[11]Modbus 30144Read
AI79DAI1[12]Modbus 30145Read
AI80DAI1[13]Modbus 30146Read
AI81DAI1[14]Modbus 30147Read
AI82DAI1[15]Modbus 30148Read
AI83DAI1[16]Modbus 30149Read
AI84DAI1[17]Modbus 30150Read
AI85DAI1[18]Modbus 30151Read
AI86DAI1[19]Modbus 30152Read
AI87Transfer Pump 1 LEAD/LAG StatusModbus 30153Read
AI88Transfer Pump 2 LEAD/LAG StatusModbus 30154Read
AI89Transfer Pump 3 LEAD/LAG StatusModbus 30155Read
AI90DAI1[23]Modbus 30156Read
AI91DAI1[24]Modbus 30157Read
AI92DAI1[25]Modbus 30158Read
AI93DAI1[26]Modbus 30159Read
AI94DAI1[27]Modbus 30160Read
AI95DAI1[28]Modbus 30161Read
AI96DAI1[29]Modbus 30162Read
AI97DAI1[30]Modbus 30163Read
AI98DAI1[31]Modbus 30164Read
AI99DAI1[32]Modbus 30165Read
AI100DAI1[33]Modbus 30166Read
AI101DAI1[34]Modbus 30167Read
AI102DAI1[35]Modbus 30168Read
AI103DAI1[36]Modbus 30169Read
AI104DAI1[37]Modbus 30170Read
AI105DAI1[38]Modbus 30171Read
AI106DAI1[39]Modbus 30172Read
AI201DAB1[0]Modbus 30201Read
AI202DAB1[1]Modbus 30202Read
AI203DAB1[2]Modbus 30203Read
AI204DAB1[3]Modbus 30204Read
AI205DAB1[4]Modbus 30205Read
AI206DAB1[5]Modbus 30206Read
AI207DAB1[6]Modbus 30207Read
AI208DAB1[7]Modbus 30208Read
AI209DAB1[8]Modbus 30209Read
AI210DAB1[9]Modbus 30210Read
BVmin1BMS Heartbeat bitwrite pointWrite
BV2Enter BFP LEAD/LAG Order PBwrite pointWrite
BV3Enter TP LEAD/LAG Order PBwrite pointWrite
BV4DAWB[0]3write pointWrite
BV5DAWB[0]4write pointWrite
BV6DAWB[0]5write pointWrite
BV7DAWB[0]6write pointWrite
BV8DAWB[0]7write pointWrite
BV9DAWB[0]8write pointWrite
BV10DAWB[0]9write pointWrite
BV11DAWB[0]10write pointWrite
BV12DAWB[0]11write pointWrite
BV13DAWB[0]12write pointWrite
BV14DAWB[0]13write pointWrite
BV15DAWB[0]14write pointWrite
BV16DAWB[0]15write pointWrite
BV17DAWB[1]0write pointWrite
BV18DAWB[1]1write pointWrite
BV19DAWB[1]2write pointWrite
BV20DAWB[1]3write pointWrite
BV21DAWB[1]4write pointWrite
BV22DAWB[1]5write pointWrite
BV23DAWB[1]6write pointWrite
BV24DAWB[1]7write pointWrite
BV25DAWB[1]8write pointWrite
BV26DAWB[1]9write pointWrite
BV27DAWB[1]10write pointWrite
BV28DAWB[1]11write pointWrite
BV29DAWB[1]12write pointWrite
BV30DAWB[1]13write pointWrite
BV31DAWB[1]14write pointWrite
BV32DAWB[1]15write pointWrite
AV1BFP 1 LEAD/LAG OrderModbus 40001; write pointWrite
AV2BFP 2 LEAD/LAG OrderModbus 40002; write pointWrite
AV3BFP 3 LEAD/LAG OrderModbus 40003; write pointWrite
AV4BFP 4 LEAD/LAG OrderModbus 40004; write pointWrite
AV5BFP 5 LEAD/LAG OrderModbus 40005; write pointWrite
AV6DAWI[5]Modbus 40006; write pointWrite
AV7TP 1 LEAD/LAG OrderModbus 40007; write pointWrite
AV8TP 2 LEAD/LAG OrderModbus 40008; write pointWrite
AV9TP 2 LEAD/LAG OrderModbus 40009; write pointWrite
AV10DAWI[9]Modbus 40010; write pointWrite
AV11DAWI[10]Modbus 40011; write pointWrite
AV12DAWI[11]Modbus 40012; write pointWrite
AV13DAWI[12]Modbus 40013; write pointWrite
AV14DAWI[13]Modbus 40014; write pointWrite
AV15DAWI[14]Modbus 40015; write pointWrite
AV16DAWI[15]Modbus 40016; write pointWrite
AV17DAWI[16]Modbus 40017; write pointWrite
AV18DAWI[17]Modbus 40018; write pointWrite
AV19DAWI[18]Modbus 40019; write pointWrite
AV20DAWI[19]Modbus 40020; write pointWrite
AVmin21FW Header Pressure SetpointModbus 40030; write pointWrite
AV22DAWR[1]Modbus 40032; write pointWrite
AV23DAWR[2]Modbus 40034; write pointWrite
AV24DAWR[3]Modbus 40036; write pointWrite
AV25DAWR[4]Modbus 40038; write pointWrite
AV26DAWR[5]Modbus 40040; write pointWrite
AV27DAWR[6]Modbus 40042; write pointWrite
AV28DAWR[7]Modbus 40044; write pointWrite
AV29DAWR[8]Modbus 40046; write pointWrite
AV30DAWR[9]Modbus 40048; write pointWrite
Object ID lookup: Cleaver-Brooks ADAC 1000 deaerator / surge tank control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)

How many BACnet points does the Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) have?

This list has 338 BACnet objects: 116 analog inputs, 30 analog values, 160 binary inputs, 32 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) BACnet points are writable?

62 of the 338 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)?

Start with BV 1 BMS Heartbeat bit (Heartbeat written by the BMS); AV 21 FW Header Pressure Setpoint (Feedwater header pressure setpoint); AI 17 Deaerator Tank Pressure (Deaerator tank pressure); AI 18 Deaerator Tank Wtr Lvl (Deaerator tank water level); AI 16 Deaerator Temp (Deaerator temperature); AI 21 Boiler Feed Wtr Header Pressure (Boiler feedwater header pressure); BI 61 Deaerator No Alarms Relay OK (Deaerator no-alarms relay OK); BI 47 BMS Heartbeat Fault (BMS heartbeat fault).

Does the Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP) need a BACnet heartbeat or have a communication timeout?

BV 1 BMS Heartbeat bit is written by the BMS and BI 47 BMS Heartbeat Fault reports a loss; the guide does not state the timeout.

How do I check these points on the real ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.