Boiler water level controller via BACnet gateway · BACnet points list

Cleaver-Brooks LCS Level Control System (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

A read-only ProtoNode profile for the LCS level controller: tank 1 and 2 levels and setpoints, primary and secondary valve positions, alarm word and a common alarm, low-water-cutoff and high/low water alarms and contacts per tank, and the state of each digital input and output.

This page lists 59 BACnet objects for the Cleaver-Brooks LCS Level Control System (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
LCS Level Control System (ProtoNode)
Equipment
Boiler water level controller via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
59 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
LCS, Level Control System, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 59 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks LCS Level Control System (ProtoNode)

Integration in brief

Read-only. Map tank levels and setpoints, valve position, the common alarm and the alarm word.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 101Tank 1 LevelTank 1 water levelRead
AI 108Tank 1 Level SetpointTank 1 level setpointRead
AI 103Primary Valve PostionPrimary valve positionRead
BI 230Common AlarmCommon alarmRead
AI 107Alarm WordAlarm wordRead

Network setup

Cleaver-Brooks LCS Level Control System (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

59 of 59 shown
Type
AnalogBinary
Show
Cleaver-Brooks LCS Level Control System (ProtoNode) BACnet Points List
DescriptionStates
AImin101Tank 1 LevelModbus 40050Read
AI102Tank 2 LevelModbus 40051Read
AImin103Primary Valve PostionModbus 40052Read
AI104Secondary Valve PostionModbus 40053Read
AI105Digital InputsModbus 40054Read
AI106Digital OutputsModbus 40055Read
AImin107Alarm WordModbus 40056Read
AImin108Tank 1 Level SetpointModbus 40057Read
AI109Tank 2 Level SetpointModbus 40058Read
BImin230Common AlarmRead
BI231Tank 1 LWCO AlarmRead
BI232Tank 1 LLW AlarmRead
BI233Tank 1 LW AlarmRead
BI234Tank 1 HW AlarmRead
BI235Tank 1 HHW AlarmRead
BI236Tank 2 LWCO AlarmRead
BI237Tank 2 LLW AlarmRead
BI238Tank 2 LW AlarmRead
BI239Tank 2 HW AlarmRead
BI240Tank 2 HHW AlarmRead
BI241Analog In FailureRead
BI242Spare Alarm Bit 40056_12Read
BI243Spare Alarm Bit 40056_13Read
BI244Spare Alarm Bit 40056_14Read
BI245Spare Alarm Bit 40056_15Read
BI246Tank 1 LWCO ContactsRead
BI247Tank 1 LLW ContactsRead
BI248Tank 1 LW ContactsRead
BI249Tank 1 HW ContactsRead
BI250Tank 1 HHW ContactsRead
BI251Tank 2 LWCO ContactsRead
BI252Tank 2 LLW ContactsRead
BI253Tank 2 LW ContactsRead
BI254Tank 2 HW ContactsRead
BI255Tank 2 HHW ContactsRead
BI256Digital Input 1 StatusRead
BI257Digital Input 2 StatusRead
BI258Digital Input 3 StatusRead
BI259Digital Input 4 StatusRead
BI260Digital Input 5 StatusRead
BI261Digital Input 6 StatusRead
BI262Digital Input 7 StatusRead
BI263Digital Input 8 StatusRead
BI264Digital Input 9 StatusRead
BI265Digital Input 10 StatusRead
BI266Digital Input 11 StatusRead
BI267Digital Input 12 StatusRead
BI268Digital Output 1 StatusRead
BI269Digital Output 2 StatusRead
BI270Digital Output 3 StatusRead
BI271Digital Output 4 StatusRead
BI272Digital Output 5 StatusRead
BI273Digital Output 6 StatusRead
BI274Digital Output 7 StatusRead
BI275Digital Output 8 StatusRead
BI276Digital Output 9 StatusRead
BI277Digital Output 10 StatusRead
BI278Digital Output 11 StatusRead
BI279Digital Output 12 StatusRead
Object ID lookup: Cleaver-Brooks LCS Level Control System point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the LCS Level Control System (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks LCS Level Control System (ProtoNode)

How many BACnet points does the Cleaver-Brooks LCS Level Control System (ProtoNode) have?

This list has 59 BACnet objects: 9 analog inputs, 50 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks LCS Level Control System (ProtoNode) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Cleaver-Brooks LCS Level Control System (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks LCS Level Control System (ProtoNode)?

Start with AI 101 Tank 1 Level (Tank 1 water level); AI 108 Tank 1 Level Setpoint (Tank 1 level setpoint); AI 103 Primary Valve Postion (Primary valve position); BI 230 Common Alarm (Common alarm); AI 107 Alarm Word (Alarm word).

How do I check these points on the real LCS Level Control System (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.