Boiler water level controller via BACnet gateway · BACnet points list
Cleaver-Brooks LCS Level Control System (ProtoNode) BACnet points list
Updated 7 November 2026Unofficial source
A read-only ProtoNode profile for the LCS level controller: tank 1 and 2 levels and setpoints, primary and secondary valve positions, alarm word and a common alarm, low-water-cutoff and high/low water alarms and contacts per tank, and the state of each digital input and output.
This page lists 59 BACnet objects for the Cleaver-Brooks LCS Level Control System (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.
- Manufacturer
- Cleaver-Brooks
- Model
- LCS Level Control System (ProtoNode)
- Equipment
- Boiler water level controller via BACnet gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 59 (0 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + Modbus Node-ID
- Also known as
- LCS, Level Control System, ProtoNode RER, 750-426
- Source document
- Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.
BMS integration notes: Cleaver-Brooks LCS Level Control System (ProtoNode)
Read-only. Map tank levels and setpoints, valve position, the common alarm and the alarm word.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 101 | Tank 1 Level | Tank 1 water level | Read |
| AI 108 | Tank 1 Level Setpoint | Tank 1 level setpoint | Read |
| AI 103 | Primary Valve Postion | Primary valve position | Read |
| BI 230 | Common Alarm | Common alarm | Read |
| AI 107 | Alarm Word | Alarm word | Read |
Network setup
- BACnet Device Instance = the controller's Modbus Node-ID + Node_Offset (default 50,000), so Node-ID 1 = 50001. Change Node_Offset in the ProtoNode web configurator to pick other instances.
- The ProtoNode RER does BACnet MS/TP or BACnet IP, selected on its S bank DIP switches.
- BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on the A bank DIP switches; baud on B0-B3 (38400 factory default).
- BACnet IP: default ProtoNode address 192.168.1.24; change it in the web configurator.
Cleaver-Brooks LCS Level Control System (ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 101 | Tank 1 Level | Modbus 40050 | Read | ||
| AI | 102 | Tank 2 Level | Modbus 40051 | Read | ||
| AImin | 103 | Primary Valve Postion | Modbus 40052 | Read | ||
| AI | 104 | Secondary Valve Postion | Modbus 40053 | Read | ||
| AI | 105 | Digital Inputs | Modbus 40054 | Read | ||
| AI | 106 | Digital Outputs | Modbus 40055 | Read | ||
| AImin | 107 | Alarm Word | Modbus 40056 | Read | ||
| AImin | 108 | Tank 1 Level Setpoint | Modbus 40057 | Read | ||
| AI | 109 | Tank 2 Level Setpoint | Modbus 40058 | Read | ||
| BImin | 230 | Common Alarm | Read | |||
| BI | 231 | Tank 1 LWCO Alarm | Read | |||
| BI | 232 | Tank 1 LLW Alarm | Read | |||
| BI | 233 | Tank 1 LW Alarm | Read | |||
| BI | 234 | Tank 1 HW Alarm | Read | |||
| BI | 235 | Tank 1 HHW Alarm | Read | |||
| BI | 236 | Tank 2 LWCO Alarm | Read | |||
| BI | 237 | Tank 2 LLW Alarm | Read | |||
| BI | 238 | Tank 2 LW Alarm | Read | |||
| BI | 239 | Tank 2 HW Alarm | Read | |||
| BI | 240 | Tank 2 HHW Alarm | Read | |||
| BI | 241 | Analog In Failure | Read | |||
| BI | 242 | Spare Alarm Bit 40056_12 | Read | |||
| BI | 243 | Spare Alarm Bit 40056_13 | Read | |||
| BI | 244 | Spare Alarm Bit 40056_14 | Read | |||
| BI | 245 | Spare Alarm Bit 40056_15 | Read | |||
| BI | 246 | Tank 1 LWCO Contacts | Read | |||
| BI | 247 | Tank 1 LLW Contacts | Read | |||
| BI | 248 | Tank 1 LW Contacts | Read | |||
| BI | 249 | Tank 1 HW Contacts | Read | |||
| BI | 250 | Tank 1 HHW Contacts | Read | |||
| BI | 251 | Tank 2 LWCO Contacts | Read | |||
| BI | 252 | Tank 2 LLW Contacts | Read | |||
| BI | 253 | Tank 2 LW Contacts | Read | |||
| BI | 254 | Tank 2 HW Contacts | Read | |||
| BI | 255 | Tank 2 HHW Contacts | Read | |||
| BI | 256 | Digital Input 1 Status | Read | |||
| BI | 257 | Digital Input 2 Status | Read | |||
| BI | 258 | Digital Input 3 Status | Read | |||
| BI | 259 | Digital Input 4 Status | Read | |||
| BI | 260 | Digital Input 5 Status | Read | |||
| BI | 261 | Digital Input 6 Status | Read | |||
| BI | 262 | Digital Input 7 Status | Read | |||
| BI | 263 | Digital Input 8 Status | Read | |||
| BI | 264 | Digital Input 9 Status | Read | |||
| BI | 265 | Digital Input 10 Status | Read | |||
| BI | 266 | Digital Input 11 Status | Read | |||
| BI | 267 | Digital Input 12 Status | Read | |||
| BI | 268 | Digital Output 1 Status | Read | |||
| BI | 269 | Digital Output 2 Status | Read | |||
| BI | 270 | Digital Output 3 Status | Read | |||
| BI | 271 | Digital Output 4 Status | Read | |||
| BI | 272 | Digital Output 5 Status | Read | |||
| BI | 273 | Digital Output 6 Status | Read | |||
| BI | 274 | Digital Output 7 Status | Read | |||
| BI | 275 | Digital Output 8 Status | Read | |||
| BI | 276 | Digital Output 9 Status | Read | |||
| BI | 277 | Digital Output 10 Status | Read | |||
| BI | 278 | Digital Output 11 Status | Read | |||
| BI | 279 | Digital Output 12 Status | Read |
No points match these filters.
Object ID lookup: Cleaver-Brooks LCS Level Control System point IDs by name
AI101Tank 1 LevelAI102Tank 2 LevelAI103Primary Valve PostionAI104Secondary Valve PostionAI105Digital InputsAI106Digital OutputsAI107Alarm WordAI108Tank 1 Level SetpointAI109Tank 2 Level SetpointBI230Common AlarmBI231Tank 1 LWCO AlarmBI232Tank 1 LLW AlarmBI233Tank 1 LW AlarmBI234Tank 1 HW AlarmBI235Tank 1 HHW AlarmBI236Tank 2 LWCO AlarmBI237Tank 2 LLW AlarmBI238Tank 2 LW AlarmBI239Tank 2 HW AlarmBI240Tank 2 HHW AlarmBI241Analog In FailureBI242Spare Alarm Bit 40056_12BI243Spare Alarm Bit 40056_13BI244Spare Alarm Bit 40056_14BI245Spare Alarm Bit 40056_15BI246Tank 1 LWCO ContactsBI247Tank 1 LLW ContactsBI248Tank 1 LW ContactsBI249Tank 1 HW ContactsBI250Tank 1 HHW ContactsBI251Tank 2 LWCO ContactsBI252Tank 2 LLW ContactsBI253Tank 2 LW ContactsBI254Tank 2 HW ContactsBI255Tank 2 HHW ContactsBI256Digital Input 1 StatusBI257Digital Input 2 StatusBI258Digital Input 3 StatusBI259Digital Input 4 StatusBI260Digital Input 5 StatusBI261Digital Input 6 StatusBI262Digital Input 7 StatusBI263Digital Input 8 StatusBI264Digital Input 9 StatusBI265Digital Input 10 StatusBI266Digital Input 11 StatusBI267Digital Input 12 StatusBI268Digital Output 1 StatusBI269Digital Output 2 StatusBI270Digital Output 3 StatusBI271Digital Output 4 StatusBI272Digital Output 5 StatusBI273Digital Output 6 StatusBI274Digital Output 7 StatusBI275Digital Output 8 StatusBI276Digital Output 9 StatusBI277Digital Output 10 StatusBI278Digital Output 11 StatusBI279Digital Output 12 Status
Integration notes
- Each Cleaver-Brooks controller on the ProtoNode is its own BACnet device; the object instances below are the same on every device.
- The profile has only AI and BI objects and the guide marks none as write points, so all are read-only.
- The guide gives no engineering units or state texts; units appear only where the object name carries them (DEG F / DEG C).
- Where a description is filled in, it gives the register from the guide's Modbus column.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the LCS Level Control System (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Cleaver-Brooks LCS Level Control System (ProtoNode)
How many BACnet points does the Cleaver-Brooks LCS Level Control System (ProtoNode) have?
This list has 59 BACnet objects: 9 analog inputs, 50 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Cleaver-Brooks LCS Level Control System (ProtoNode) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Cleaver-Brooks LCS Level Control System (ProtoNode) BACnet documentation?
Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.
What are the minimum BACnet points to integrate the Cleaver-Brooks LCS Level Control System (ProtoNode)?
Start with AI 101 Tank 1 Level (Tank 1 water level); AI 108 Tank 1 Level Setpoint (Tank 1 level setpoint); AI 103 Primary Valve Postion (Primary valve position); BI 230 Common Alarm (Common alarm); AI 107 Alarm Word (Alarm word).
How do I check these points on the real LCS Level Control System (ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Cleaver-Brooks BACnet points lists
- Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
Cleaver-Brooks deaerator and surge tank packages with the ADAC 1000 PLC control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: ADAC 1000, ADAC_1000, ProtoNode RER, 750-426 - Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)
Cleaver-Brooks deaerator and surge tank packages with the ADAC control, read through a ProtoNode RER gateway.
Also known as: ADAC, CB deaerator control, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB120 flame safeguard (ProtoNode)
Cleaver-Brooks boilers with the CB120 flame safeguard, read through a ProtoNode RER gateway.
Also known as: CB120, CB 120, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB780 flame safeguard with expanded annunciator (ProtoNode)
Cleaver-Brooks boilers with the CB780 burner management control and expanded annunciator, read through a ProtoNode RER gateway.
Also known as: CB780, CB 780, CB780E, ProtoNode RER, 750-426 - Hot water boiler control via BACnet gateway
Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)
Cleaver-Brooks hot water boilers with the Falcon hydronic burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Hydronic, ClearFire Falcon, CB Falcon, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Falcon Steam boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Falcon steam burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Steam, CB Falcon steam, ProtoNode RER, 750-426 - Boiler flame safeguard and fuel-air ratio control via BACnet gateway
Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)
Cleaver-Brooks boilers with a CB780/CB783 burner control and FARC fuel-air ratio control, read through a ProtoNode RER gateway.
Also known as: FARC, CB 780/783, CB783, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 1000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 1000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 1000, CB Hawk 1000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 2000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 2000, CB Hawk 2000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 4000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 4000, CB Hawk 4000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 V2 boiler control (ProtoNode)
Cleaver-Brooks boilers with the HAWK 4000 V2 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: HAWK 4000 V2, CB HAWK 4000 V2, HAWK_4000_V2, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4500 boiler control (ProtoNode, EtherNet/IP)
Cleaver-Brooks boilers with the Hawk 4500 PLC boiler control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: Hawk 4500, CB Hawk 4500, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Hawk 5000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 5000, CB Hawk 5000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk ICS boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk ICS control, read through a ProtoNode RER gateway.
Also known as: Hawk ICS, CB ICS, ProtoNode RER, 750-426 - Boiler lead/lag master panel via BACnet gateway
Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode)
Cleaver-Brooks Hawk Master Panels sequencing up to eight Hawk boilers (A-H), read through a ProtoNode RER gateway.
Also known as: Hawk Master Panel, Hawk Master, CB Master Panel, ProtoNode RER, 750-426 - Boiler interface module via BACnet gateway
Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)
Cleaver-Brooks HSC boiler interface modules (one boiler each), read through a ProtoNode RER gateway.
Also known as: Boiler Interface Module, HSC Boiler Interface, BIM, ProtoNode RER, 750-426 - Multi-boiler sequencer (hot water boiler plant) via BACnet gateway
Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)
Cleaver-Brooks HSC panels sequencing up to 10 condensing and 10 non-condensing boilers, read through a ProtoNode RER gateway.
Also known as: HSC, Hydronic System Controller, CB HSC, ProtoNode RER, 750-426 - Pump interface module (boiler plant pumps) via BACnet gateway
Cleaver-Brooks HSC Pump Interface Module (ProtoNode)
Cleaver-Brooks HSC pump interface modules (up to four system pumps), read through a ProtoNode RER gateway.
Also known as: Pump Interface Module, HSC Pump Interface, ProtoNode RER, 750-426 - Boiler feed pump controller via BACnet gateway
Cleaver-Brooks PCS Pump Control System (ProtoNode)
Cleaver-Brooks PCS pump controllers (up to four pumps on header pressure or tank level), read through a ProtoNode RER gateway.
Also known as: PCS, Pump Control System, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 100 power meter profile (ProtoNode)
Shark 100 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 100, Electro Industries Shark 100, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 200 power meter profile (ProtoNode)
Shark 200 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 200, Electro Industries Shark 200, ProtoNode RER, 750-426 - Process loop controller via BACnet gateway
Cleaver-Brooks UDC 2500 loop controller profile (ProtoNode)
Honeywell UDC 2500 loop controllers supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: UDC 2500, UDC2500, Honeywell UDC 2500, ProtoNode RER, 750-426
Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.