Boiler flame safeguard and fuel-air ratio control via BACnet gateway · BACnet points list

Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

A read-only ProtoNode profile combining the CB780/CB783 burner control (sequence state, run mode, flame signal, alarm, lockout, fault history, annunciator inputs) with the FARC fuel-air ratio control (program mode, fault code, operating status, air, fuel and FGR positions and endpoints, firing rate input and fault info words).

This page lists 178 BACnet objects for the Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
FARC with CB780 / CB783 burner control (ProtoNode)
Equipment
Boiler flame safeguard and fuel-air ratio control via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
178 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
FARC, CB 780/783, CB783, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 178 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)

Integration in brief

Read-only. Map burner sequence state, run mode, firing rate input, air and fuel positions, and the alarm, lockout and fault codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3BC_Sequence_StateBurner sequence stateRead
BI 6BC_Run_ModeBurner in runRead
AI 73Firing Rate InputFiring rate inputRead
AI 68Air PositionAir actuator positionRead
AI 69Active Fuel PositionActive fuel actuator positionRead
BI 9BC_Alarm_OutAlarm outputRead
BI 10BC_LockoutLockoutRead
AI 1BC_Fault_CodeBurner control fault codeRead
AI 66Fault CodeFARC fault codeRead

Network setup

Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

178 of 178 shown
Type
AnalogBinary
Show
Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode) BACnet Points List
DescriptionStates
BI1BC_InitiateRead
BI2BC_StandbyRead
BI3BC_PurgeRead
BI4BC_Pilot_IgnitionRead
BI5BC_Main_IgnitionRead
BImin6BC_Run_ModeRead
BI7BC_PostpurgeRead
BI8BC_PreignitionRead
BImin9BC_Alarm_OutRead
BImin10BC_LockoutRead
BI11EA_Valve_POCRead
BI12EA_Burner_SwitchRead
BI13EA_Oper_ControlRead
BI14EA_Aux_Limit_1Read
BI15EA_Aux_Limit_2Read
BI16EA_LWCORead
BI17EA_High_LimitRead
BI18EA_Aux_Limit_3Read
BI19EA_Oil_SelectRead
BI20EA_High_Oil_PressRead
BI21EA_Low_Oil_PressRead
BI22EA_High_Oil_TempRead
BI23EA_Low_Oil_TempRead
BI24EA_Gas_SelectRead
BI25EA_High_Gas_PressRead
BI26EA_Low_Gas_PressRead
BI27EA_Air_Flow_SwitchRead
BI28EA_Aux_Limit_4Read
BI29EA_Aux_Limit_5Read
AImin1BC_Fault_CodeModbus 40001Read
AI2BC_Fault_String_CodeModbus 40002Read
AImin3BC_Sequence_StateModbus 40003Read
AI4BC_State_String_Code_L1Modbus 40004Read
AI5BC_State_String_Code_L2Modbus 40005Read
AI6BC_Sequence_TimeModbus 40006Read
AI7BC_Flame_Signal_StrengthModbus 40011Read
AI8BC_State_BitsModbus 40012Read
AI9BC_Flt_Hist_Code_Rec1Modbus 40017Read
AI10BC_Flt_Hist_String_Rec1Modbus 40018Read
AI11BC_Flt_Hist_State_Rec1Modbus 40019Read
AI12BC_Flt_Hist_Line1_Rec1Modbus 40020Read
AI13BC_Flt_Hist_Line2_Rec1Modbus 40021Read
AI14BC_Flt_Hist_Time_Rec1Modbus 40022Read
AI15BC_Flt_Hist_Code_Rec2Modbus 40027Read
AI16BC_Flt_Hist_String_Rec2Modbus 40028Read
AI17BC_Flt_Hist_State_Rec2Modbus 40029Read
AI18BC_Flt_Hist_Line1_Rec2Modbus 40030Read
AI19BC_Flt_Hist_Line2_Rec2Modbus 40031Read
AI20BC_Flt_Hist_Time_Rec2Modbus 40032Read
AI21BC_Flt_Hist_Code_Rec3Modbus 40037Read
AI22BC_Flt_Hist_String_Rec3Modbus 40038Read
AI23BC_Flt_Hist_State_Rec3Modbus 40039Read
AI24BC_Flt_Hist_Line1_Rec3Modbus 40040Read
AI25BC_Flt_Hist_Line2_Rec3Modbus 40041Read
AI26BC_Flt_Hist_Time_Rec3Modbus 40042Read
AI27BC_Flt_Hist_Code_Rec4Modbus 40047Read
AI28BC_Flt_Hist_String_Rec4Modbus 40048Read
AI29BC_Flt_Hist_State_Rec4Modbus 40049Read
AI30BC_Flt_Hist_Line1_Rec4Modbus 40050Read
AI31BC_Flt_Hist_Line1_Rec5Modbus 40051Read
AI32BC_Flt_Hist_Line2_Rec4Modbus 40052Read
AI33BC_Flt_Hist_Time_Rec4Modbus 40057Read
AI34BC_Flt_Hist_Code_Rec5Modbus 40058Read
AI35BC_Flt_Hist_String_Rec5Modbus 40059Read
AI36BC_Flt_Hist_State_Rec5Modbus 40060Read
AI37BC_Flt_Hist_Line2_Rec5Modbus 40061Read
AI38BC_Flt_Hist_Time_Rec5Modbus 40062Read
AI39BC_Flt_Hist_Code_Rec6Modbus 40067Read
AI40BC_Flt_Hist_String_Rec6Modbus 40068Read
AI41BC_Flt_Hist_State_Rec6Modbus 40069Read
AI42BC_Flt_Hist_Line1_Rec6Modbus 40070Read
AI43BC_Flt_Hist_Line2_Rec6Modbus 40071Read
AI44BC_Flt_Hist_Time_Rec6Modbus 40072Read
AI45BC_Rem_Comd_StatModbus 40085Read
AI46BC_Vlv_Prov_ModeModbus 40104Read
AI47BC_Vlv_Prov_TimeModbus 40106Read
AI48BC_Rem_CommandModbus 40128Read
AI49EA_First_Out_CodeModbus 40014Read
AI50BC_Total_CyclesModbus 40007Read
AI51BC_Total_HoursModbus 40009Read
AI52BC_Flt_Hist_Cyc_Rec1Modbus 40023Read
AI53BC_Flt_Hist_Hrs_Rec1Modbus 40025Read
AI54BC_Flt_Hist_Cyc_Rec2Modbus 40033Read
AI55BC_Flt_Hist_Hrs_Rec2Modbus 40035Read
AI56BC_Flt_Hist_Cyc_Rec3Modbus 40043Read
AI57BC_Flt_Hist_Hrs_Rec3Modbus 40045Read
AI58BC_Flt_Hist_Cyc_Rec4Modbus 40053Read
AI59BC_Flt_Hist_Hrs_Rec4Modbus 40055Read
AI60BC_Flt_Hist_Cyc_Rec5Modbus 40063Read
AI61BC_Flt_Hist_Hrs_Rec5Modbus 40065Read
AI62BC_Flt_Hist_Cyc_Rec6Modbus 40073Read
AI63BC_Flt_Hist_Hrs_Rec6Modbus 40075Read
AI64EA_State_BitsModbus 40015Read
AI65Program ModeModbus 40130Read
AImin66Fault CodeModbus 40131Read
AI67Operational StatusModbus 40132Read
AImin68Air PositionModbus 40133Read
AImin69Active Fuel PositionModbus 40134Read
AI70FGR PositionModbus 40135Read
AI71Fuel IDModbus 40136Read
AI72Diagnostic BitsModbus 40139Read
AImin73Firing Rate InputModbus 40140Read
AI74Manual Pot InputModbus 40141Read
AI75Aux InputModbus 40142Read
AI76HoldModbus 40144Read
AI77Fuel 1 Closed EndpointModbus 40353Read
AI78Fuel 1 Open EndpointModbus 40354Read
AI79Fuel 2 Closed EndpointModbus 40355Read
AI80Fuel 2 Open EndpointModbus 40356Read
AI81Inactive Motor PositionModbus 40357Read
AI82Registers 40353-40357 CurrentModbus 40358Read
AI83Air Closed EndpointModbus 40359Read
AI84Air Open EndpointModbus 40360Read
AI85FGR Closed EndpointModbus 40361Read
AI86FGR Open EndpointModbus 40362Read
AI87Registers 40359-40363 CurrentModbus 40364Read
AI88R7999 Fault Info Word 0Modbus 40365Read
AI89R7999 Fault Info Word 1Modbus 40366Read
AI90R7999 Fault Info Word 2Modbus 40367Read
AI91R7999 Fault Info Word 3Modbus 40368Read
AI92R7999 Fault Info Word 4Modbus 40369Read
AI93R7999 Fault Info Word 5Modbus 40370Read
AI94R7999 Fault Info Word 6Modbus 40371Read
AI95R7999 Fault Info Word 7Modbus 40372Read
AI96R7999 Fault Info Word 8Modbus 40373Read
AI97R7999 Fault Info Word 9Modbus 40374Read
AI98R7999 Fault Info Word 10Modbus 40375Read
AI99R7999 Fault Info Word 11Modbus 40376Read
AI100R7999 Fault Info Word 12Modbus 40377Read
AI101R7999 Fault Info Word 13Modbus 40378Read
AI102R7999 Fault Info Word 14Modbus 40379Read
AI103R7999 Fault Info Word 15Modbus 40380Read
AI104R7999 Fault Info Word 16Modbus 40381Read
AI105R7999 Fault Info Word 17Modbus 40382Read
AI106R7999 Fault Info Word 18Modbus 40383Read
AI107R7999 Fault Info Word 19Modbus 40384Read
AI108R7999 Fault Info Word 20Modbus 40385Read
AI109R7999 Fault Info Word 21Modbus 40386Read
AI110R7999 Fault Info Word 22Modbus 40387Read
AI111R7999 Fault Info Word 23Modbus 40388Read
AI112R7999 Fault Info Word 24Modbus 40389Read
AI113R7999 Fault Info Word 25Modbus 40390Read
AI114R7999 Fault Info Word 26Modbus 40391Read
AI115R7999 Fault Info Word 27Modbus 40392Read
AI116R7999 Fault Info Word 28Modbus 40393Read
AI117R7999 Fault Info Word 29Modbus 40394Read
AI118R7999 Fault Info Word 30Modbus 40395Read
AI119R7999 Fault Info Word 31Modbus 40396Read
AI120R7999 Fault Info Word 32Modbus 40397Read
AI121R7999 Fault Info Word 33Modbus 40398Read
AI122R7999 Fault Info Word 34Modbus 40399Read
AI123R7999 Fault Info Word 35Modbus 40400Read
AI124Air Total ResistanceModbus 40401Read
AI125Fuel 1 Total ResistanceModbus 40402Read
AI126Fuel 2 Total ResistanceModbus 40403Read
AI127FGR Total ResistanceModbus 40404Read
AI128Air Resistance ChangeModbus 40405Read
AI129Registers 40401-40405 CurrentModbus 40406Read
AI130Fuel 1 Resistance ChangeModbus 40407Read
AI131Fuel 2 Resistance ChangeModbus 40408Read
AI132FGR Resistance ChangeModbus 40409Read
AI133Registers 40407-40411 CurrentModbus 40412Read
AI134Air Purge Preset PositionModbus 40413Read
AI135Fuel Purge Preset PositionModbus 40414Read
AI136FGR Purge Preset PositionModbus 40415Read
AI137Air Lightoff Preset PositionModbus 40416Read
AI138Fuel Lightoff Preset PositionModbus 40417Read
AI139Registers 40413-40417 CurrentModbus 40418Read
AI140Lightoff Preset FGRModbus 40419Read
AI141Air Standby PositionModbus 40420Read
AI142Fuel Standby PositionModbus 40421Read
AI143FGR Standby PositionModbus 40422Read
AI144Non-Sel. Fuel Standby Pos.Modbus 40423Read
AI145Registers 40419-40423 CurrentModbus 40424Read
AI146CyclesModbus 40137Read
AI147LCO Cycle CountModbus 40410Read
AI148Running Time HoursModbus 40437Read
AI149Running Time MinutesModbus 40438Read
Object ID lookup: Cleaver-Brooks FARC with CB780 / CB783 burner control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FARC with CB780 / CB783 burner control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)

How many BACnet points does the Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode) have?

This list has 178 BACnet objects: 149 analog inputs, 29 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)?

Start with AI 3 BC_Sequence_State (Burner sequence state); BI 6 BC_Run_Mode (Burner in run); AI 73 Firing Rate Input (Firing rate input); AI 68 Air Position (Air actuator position); AI 69 Active Fuel Position (Active fuel actuator position); BI 9 BC_Alarm_Out (Alarm output); BI 10 BC_Lockout (Lockout); AI 1 BC_Fault_Code (Burner control fault code); AI 66 Fault Code (FARC fault code).

How do I check these points on the real FARC with CB780 / CB783 burner control (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.