Easy BACnet
  1. Home
  2. BACnet points lists
  3. Cleaver-Brooks
  4. Falcon Steam boiler control (ProtoNode)

Steam boiler control via BACnet gateway · BACnet points list

Cleaver-Brooks Falcon Steam boiler control (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The ProtoNode maps the Falcon steam control's Modbus RTU registers to a fixed set of BACnet objects: safety and limit inputs, steam pressure and setpoints, firing rate, flame signal, burner state, lockout and hold codes and lead/lag data. The BMS can enable the burner and lead/lag and write the steam pressure and lead/lag setpoints.

This page lists 62 BACnet objects for the Cleaver-Brooks Falcon Steam boiler control (ProtoNode) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
Falcon Steam boiler control (ProtoNode)
Equipment
Steam boiler control via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
62 (5 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
Falcon Steam, CB Falcon steam, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 62 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks Falcon Steam boiler control (ProtoNode)

Integration in brief

Enable the burner and write the steam pressure setpoint; use the lead/lag enable and setpoint if the boilers run lead/lag. Read burner state, steam pressure, firing rate, the alarm input and the lockout code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1BURNER ENABLEBurner enable from the BMSWrite
AV 21STEAM_PRESSURE_SETPOINTSteam pressure setpointWrite
AV 11LEAD/LAG_ENABLELead/lag enableWrite
AV 31LEAD/LAG_SETPOINTLead/lag setpointWrite
AI 9BURN_CTL_STATEBurner control state codeRead
AI 5STEAM_PRESSURESteam pressureRead
AI 20FIRING_RATE_PERCENTFiring rate, %Read
BI 8AlarmAlarmRead
AI 10LOCKOUT_CODELockout codeRead

Enable & remote start

AV 1 BURNER ENABLE and AV 11 LEAD/LAG_ENABLE are the BMS enables; AV 21 writes the steam pressure setpoint.

Network setup

Cleaver-Brooks Falcon Steam boiler control (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

62 of 62 shown
Type
Binary
Access
Show
Cleaver-Brooks Falcon Steam boiler control (ProtoNode) BACnet Points List
DescriptionStates
BI1PumpAModbus 30003, bit 0Read
BI2PumpBModbus 30003, bit 1Read
BI3PumpCModbus 30003, bit 2Read
BI4Blower_MtrModbus 30003, bit 3Read
BI5Ext_IgnitionModbus 30003, bit 4Read
BI6Pilot_ValveModbus 30003, bit 5Read
BI7Main_ValveModbus 30003, bit 6Read
BImin8AlarmModbus 30003, bit 7Read
BI9InterlockModbus 30003, bit 8Read
BI10PreIgn_InterlockModbus 30003, bit 9Read
BI11Load_Control_InModbus 30003, bit 10Read
BI12Low_Fire_SwitchModbus 30003, bit 11Read
BI13High_Fire_SwitchModbus 30003, bit 12Read
BI14Stat_DemandModbus 30003, bit 13Read
BI15TimeOfDayModbus 30003, bit 14Read
BI16Safety_RelayModbus 30003, bit 15Read
BI17Int_Air_SwitchModbus 30004, bit 0Read
BI18Low_WaterModbus 30004, bit 1Read
BI19Aux_Low_WaterModbus 30004, bit 2Read
BI20High_LimitModbus 30004, bit 3Read
BI21High_Gas_PressModbus 30004, bit 4Read
BI22Low_Gas_PressModbus 30004, bit 5Read
BI23High_WaterModbus 30004, bit 6Read
BI24Feed_WaterModbus 30004, bit 7Read
AI1DEMAND SOURCEModbus 30007Read
AI2FIRING_RATEModbus 30009Read
AI3FAN_SPEEDModbus 30010Read
AI4FLAME_SIGNALModbus 30011Read
AImin5STEAM_PRESSUREModbus 30021Read
AI6ANALOG_INPUTModbus 30022Read
AI7ACTIVE_STEAM_SPModbus 30023Read
AI8BURN_CTL_STATUSModbus 30033Read
AImin9BURN_CTL_STATEModbus 30034Read
AImin10LOCKOUT_CODEModbus 30035Read
AI11HOLD_CODEModbus 30041Read
AI12CYCLE_COUNTRead
AI13RUN_TIMERead
AI16BURNER_ENABLEModbus 30204Read
AI14STEAM_PRESSURE_SETPOINTModbus 30221Read
AI15LEAD/LAG_STEAM_PRESS_SET POINTModbus 30739Read
AI17LEAD/LAG_HEADER_STEAM_PRESSModbus 30807Read
AI18VESSEL WATER TEMP (Deg C)Modbus 30008°CRead
AI19VESSEL WATER TEMP (Deg F)Modbus 30008°FRead
AVmin1BURNER ENABLEModbus 40204; write pointWrite
AVmin21STEAM_PRESSURE_SETPOINTModbus 40221; write pointWrite
AVmin11LEAD/LAG_ENABLEModbus 40556; write pointWrite
AVmin31LEAD/LAG_SETPOINTModbus 40739; write pointWrite
AImin20FIRING_RATE_PERCENTModbus 30074Read
AI214-20Ma Remote Ctl InputModbus 40016Read
AI22Active LL SetpointModbus 40019Read
AI23Alarm ReasonModbus 40036Read
AI24Annunciator First OutModbus 40037Read
AI25Annunciator HoldModbus 40038Read
AI26Outdoor TemperatureModbus 40171Read
AV41CH Pump Cycle Countwrite pointWrite
AI27Lead Boiler AddressModbus 40802Read
AI28Firing Rate TypeModbus 30193Read
AI29Master IDModbus 30546Read
AI30Slave SetpointModbus 30030Read
AI31Master OATModbus 30171Read
AI32Max Firing RateModbus 30194Read
AI33Min Firing RateModbus 30196Read
Object ID lookup: Cleaver-Brooks Falcon Steam boiler control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Falcon Steam boiler control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks Falcon Steam boiler control (ProtoNode)

How many BACnet points does the Cleaver-Brooks Falcon Steam boiler control (ProtoNode) have?

This list has 62 BACnet objects: 33 analog inputs, 5 analog values, 24 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks Falcon Steam boiler control (ProtoNode) BACnet points are writable?

5 of the 62 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Cleaver-Brooks Falcon Steam boiler control (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks Falcon Steam boiler control (ProtoNode)?

Start with AV 1 BURNER ENABLE (Burner enable from the BMS); AV 21 STEAM_PRESSURE_SETPOINT (Steam pressure setpoint); AV 11 LEAD/LAG_ENABLE (Lead/lag enable); AV 31 LEAD/LAG_SETPOINT (Lead/lag setpoint); AI 9 BURN_CTL_STATE (Burner control state code); AI 5 STEAM_PRESSURE (Steam pressure); AI 20 FIRING_RATE_PERCENT (Firing rate, %); BI 8 Alarm (Alarm); AI 10 LOCKOUT_CODE (Lockout code).

How do I enable BMS control of the Cleaver-Brooks Falcon Steam boiler control (ProtoNode)?

AV 1 BURNER ENABLE and AV 11 LEAD/LAG_ENABLE are the BMS enables; AV 21 writes the steam pressure setpoint.

How do I check these points on the real Falcon Steam boiler control (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.