Steam boiler control via BACnet gateway · BACnet points list
Cleaver-Brooks Falcon Steam boiler control (ProtoNode) BACnet points list
Updated 7 November 2026Unofficial source
The ProtoNode maps the Falcon steam control's Modbus RTU registers to a fixed set of BACnet objects: safety and limit inputs, steam pressure and setpoints, firing rate, flame signal, burner state, lockout and hold codes and lead/lag data. The BMS can enable the burner and lead/lag and write the steam pressure and lead/lag setpoints.
This page lists 62 BACnet objects for the Cleaver-Brooks Falcon Steam boiler control (ProtoNode) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.
- Manufacturer
- Cleaver-Brooks
- Model
- Falcon Steam boiler control (ProtoNode)
- Equipment
- Steam boiler control via BACnet gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 62 (5 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + Modbus Node-ID
- Also known as
- Falcon Steam, CB Falcon steam, ProtoNode RER, 750-426
- Source document
- Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.
BMS integration notes: Cleaver-Brooks Falcon Steam boiler control (ProtoNode)
Enable the burner and write the steam pressure setpoint; use the lead/lag enable and setpoint if the boilers run lead/lag. Read burner state, steam pressure, firing rate, the alarm input and the lockout code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 1 | BURNER ENABLE | Burner enable from the BMS | Write |
| AV 21 | STEAM_PRESSURE_SETPOINT | Steam pressure setpoint | Write |
| AV 11 | LEAD/LAG_ENABLE | Lead/lag enable | Write |
| AV 31 | LEAD/LAG_SETPOINT | Lead/lag setpoint | Write |
| AI 9 | BURN_CTL_STATE | Burner control state code | Read |
| AI 5 | STEAM_PRESSURE | Steam pressure | Read |
| AI 20 | FIRING_RATE_PERCENT | Firing rate, % | Read |
| BI 8 | Alarm | Alarm | Read |
| AI 10 | LOCKOUT_CODE | Lockout code | Read |
Enable & remote start
AV 1 BURNER ENABLE and AV 11 LEAD/LAG_ENABLE are the BMS enables; AV 21 writes the steam pressure setpoint.
Network setup
- BACnet Device Instance = the controller's Modbus Node-ID + Node_Offset (default 50,000), so Node-ID 1 = 50001. Change Node_Offset in the ProtoNode web configurator to pick other instances.
- The ProtoNode RER does BACnet MS/TP or BACnet IP, selected on its S bank DIP switches.
- BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on the A bank DIP switches; baud on B0-B3 (38400 factory default).
- BACnet IP: default ProtoNode address 192.168.1.24; change it in the web configurator.
Cleaver-Brooks Falcon Steam boiler control (ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 1 | PumpA | Modbus 30003, bit 0 | Read | ||
| BI | 2 | PumpB | Modbus 30003, bit 1 | Read | ||
| BI | 3 | PumpC | Modbus 30003, bit 2 | Read | ||
| BI | 4 | Blower_Mtr | Modbus 30003, bit 3 | Read | ||
| BI | 5 | Ext_Ignition | Modbus 30003, bit 4 | Read | ||
| BI | 6 | Pilot_Valve | Modbus 30003, bit 5 | Read | ||
| BI | 7 | Main_Valve | Modbus 30003, bit 6 | Read | ||
| BImin | 8 | Alarm | Modbus 30003, bit 7 | Read | ||
| BI | 9 | Interlock | Modbus 30003, bit 8 | Read | ||
| BI | 10 | PreIgn_Interlock | Modbus 30003, bit 9 | Read | ||
| BI | 11 | Load_Control_In | Modbus 30003, bit 10 | Read | ||
| BI | 12 | Low_Fire_Switch | Modbus 30003, bit 11 | Read | ||
| BI | 13 | High_Fire_Switch | Modbus 30003, bit 12 | Read | ||
| BI | 14 | Stat_Demand | Modbus 30003, bit 13 | Read | ||
| BI | 15 | TimeOfDay | Modbus 30003, bit 14 | Read | ||
| BI | 16 | Safety_Relay | Modbus 30003, bit 15 | Read | ||
| BI | 17 | Int_Air_Switch | Modbus 30004, bit 0 | Read | ||
| BI | 18 | Low_Water | Modbus 30004, bit 1 | Read | ||
| BI | 19 | Aux_Low_Water | Modbus 30004, bit 2 | Read | ||
| BI | 20 | High_Limit | Modbus 30004, bit 3 | Read | ||
| BI | 21 | High_Gas_Press | Modbus 30004, bit 4 | Read | ||
| BI | 22 | Low_Gas_Press | Modbus 30004, bit 5 | Read | ||
| BI | 23 | High_Water | Modbus 30004, bit 6 | Read | ||
| BI | 24 | Feed_Water | Modbus 30004, bit 7 | Read | ||
| AI | 1 | DEMAND SOURCE | Modbus 30007 | Read | ||
| AI | 2 | FIRING_RATE | Modbus 30009 | Read | ||
| AI | 3 | FAN_SPEED | Modbus 30010 | Read | ||
| AI | 4 | FLAME_SIGNAL | Modbus 30011 | Read | ||
| AImin | 5 | STEAM_PRESSURE | Modbus 30021 | Read | ||
| AI | 6 | ANALOG_INPUT | Modbus 30022 | Read | ||
| AI | 7 | ACTIVE_STEAM_SP | Modbus 30023 | Read | ||
| AI | 8 | BURN_CTL_STATUS | Modbus 30033 | Read | ||
| AImin | 9 | BURN_CTL_STATE | Modbus 30034 | Read | ||
| AImin | 10 | LOCKOUT_CODE | Modbus 30035 | Read | ||
| AI | 11 | HOLD_CODE | Modbus 30041 | Read | ||
| AI | 12 | CYCLE_COUNT | Read | |||
| AI | 13 | RUN_TIME | Read | |||
| AI | 16 | BURNER_ENABLE | Modbus 30204 | Read | ||
| AI | 14 | STEAM_PRESSURE_SETPOINT | Modbus 30221 | Read | ||
| AI | 15 | LEAD/LAG_STEAM_PRESS_SET POINT | Modbus 30739 | Read | ||
| AI | 17 | LEAD/LAG_HEADER_STEAM_PRESS | Modbus 30807 | Read | ||
| AI | 18 | VESSEL WATER TEMP (Deg C) | Modbus 30008 | °C | Read | |
| AI | 19 | VESSEL WATER TEMP (Deg F) | Modbus 30008 | °F | Read | |
| AVmin | 1 | BURNER ENABLE | Modbus 40204; write point | Write | ||
| AVmin | 21 | STEAM_PRESSURE_SETPOINT | Modbus 40221; write point | Write | ||
| AVmin | 11 | LEAD/LAG_ENABLE | Modbus 40556; write point | Write | ||
| AVmin | 31 | LEAD/LAG_SETPOINT | Modbus 40739; write point | Write | ||
| AImin | 20 | FIRING_RATE_PERCENT | Modbus 30074 | Read | ||
| AI | 21 | 4-20Ma Remote Ctl Input | Modbus 40016 | Read | ||
| AI | 22 | Active LL Setpoint | Modbus 40019 | Read | ||
| AI | 23 | Alarm Reason | Modbus 40036 | Read | ||
| AI | 24 | Annunciator First Out | Modbus 40037 | Read | ||
| AI | 25 | Annunciator Hold | Modbus 40038 | Read | ||
| AI | 26 | Outdoor Temperature | Modbus 40171 | Read | ||
| AV | 41 | CH Pump Cycle Count | write point | Write | ||
| AI | 27 | Lead Boiler Address | Modbus 40802 | Read | ||
| AI | 28 | Firing Rate Type | Modbus 30193 | Read | ||
| AI | 29 | Master ID | Modbus 30546 | Read | ||
| AI | 30 | Slave Setpoint | Modbus 30030 | Read | ||
| AI | 31 | Master OAT | Modbus 30171 | Read | ||
| AI | 32 | Max Firing Rate | Modbus 30194 | Read | ||
| AI | 33 | Min Firing Rate | Modbus 30196 | Read |
No points match these filters.
Object ID lookup: Cleaver-Brooks Falcon Steam boiler control point IDs by name
BI1PumpABI2PumpBBI3PumpCBI4Blower_MtrBI5Ext_IgnitionBI6Pilot_ValveBI7Main_ValveBI8AlarmBI9InterlockBI10PreIgn_InterlockBI11Load_Control_InBI12Low_Fire_SwitchBI13High_Fire_SwitchBI14Stat_DemandBI15TimeOfDayBI16Safety_RelayBI17Int_Air_SwitchBI18Low_WaterBI19Aux_Low_WaterBI20High_LimitBI21High_Gas_PressBI22Low_Gas_PressBI23High_WaterBI24Feed_WaterAI1DEMAND SOURCEAI2FIRING_RATEAI3FAN_SPEEDAI4FLAME_SIGNALAI5STEAM_PRESSUREAI6ANALOG_INPUTAI7ACTIVE_STEAM_SPAI8BURN_CTL_STATUSAI9BURN_CTL_STATEAI10LOCKOUT_CODEAI11HOLD_CODEAI12CYCLE_COUNTAI13RUN_TIMEAI16BURNER_ENABLEAI14STEAM_PRESSURE_SETPOINTAI15LEAD/LAG_STEAM_PRESS_SET POINTAI17LEAD/LAG_HEADER_STEAM_PRESSAI18VESSEL WATER TEMP (Deg C)AI19VESSEL WATER TEMP (Deg F)AV1BURNER ENABLEAV21STEAM_PRESSURE_SETPOINTAV11LEAD/LAG_ENABLEAV31LEAD/LAG_SETPOINTAI20FIRING_RATE_PERCENTAI214-20Ma Remote Ctl InputAI22Active LL SetpointAI23Alarm ReasonAI24Annunciator First OutAI25Annunciator HoldAI26Outdoor TemperatureAV41CH Pump Cycle CountAI27Lead Boiler AddressAI28Firing Rate TypeAI29Master IDAI30Slave SetpointAI31Master OATAI32Max Firing RateAI33Min Firing Rate
Integration notes
- Each Cleaver-Brooks controller on the ProtoNode is its own BACnet device; the object instances below are the same on every device.
- Access follows the guide's write-point stars: the starred AV/BV objects are writable, everything else is read-only.
- The guide gives no engineering units or state texts; units appear only where the object name carries them (DEG F / DEG C).
- Where a description is filled in, it gives the register from the guide's Modbus column.
- The source prints the PumpA row (BI 1) twice; it is listed once here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Falcon Steam boiler control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Cleaver-Brooks Falcon Steam boiler control (ProtoNode)
How many BACnet points does the Cleaver-Brooks Falcon Steam boiler control (ProtoNode) have?
This list has 62 BACnet objects: 33 analog inputs, 5 analog values, 24 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Cleaver-Brooks Falcon Steam boiler control (ProtoNode) BACnet points are writable?
5 of the 62 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Cleaver-Brooks Falcon Steam boiler control (ProtoNode) BACnet documentation?
Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.
What are the minimum BACnet points to integrate the Cleaver-Brooks Falcon Steam boiler control (ProtoNode)?
Start with AV 1 BURNER ENABLE (Burner enable from the BMS); AV 21 STEAM_PRESSURE_SETPOINT (Steam pressure setpoint); AV 11 LEAD/LAG_ENABLE (Lead/lag enable); AV 31 LEAD/LAG_SETPOINT (Lead/lag setpoint); AI 9 BURN_CTL_STATE (Burner control state code); AI 5 STEAM_PRESSURE (Steam pressure); AI 20 FIRING_RATE_PERCENT (Firing rate, %); BI 8 Alarm (Alarm); AI 10 LOCKOUT_CODE (Lockout code).
How do I enable BMS control of the Cleaver-Brooks Falcon Steam boiler control (ProtoNode)?
AV 1 BURNER ENABLE and AV 11 LEAD/LAG_ENABLE are the BMS enables; AV 21 writes the steam pressure setpoint.
How do I check these points on the real Falcon Steam boiler control (ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Cleaver-Brooks BACnet points lists
- Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
Cleaver-Brooks deaerator and surge tank packages with the ADAC 1000 PLC control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: ADAC 1000, ADAC_1000, ProtoNode RER, 750-426 - Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)
Cleaver-Brooks deaerator and surge tank packages with the ADAC control, read through a ProtoNode RER gateway.
Also known as: ADAC, CB deaerator control, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB120 flame safeguard (ProtoNode)
Cleaver-Brooks boilers with the CB120 flame safeguard, read through a ProtoNode RER gateway.
Also known as: CB120, CB 120, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB780 flame safeguard with expanded annunciator (ProtoNode)
Cleaver-Brooks boilers with the CB780 burner management control and expanded annunciator, read through a ProtoNode RER gateway.
Also known as: CB780, CB 780, CB780E, ProtoNode RER, 750-426 - Hot water boiler control via BACnet gateway
Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)
Cleaver-Brooks hot water boilers with the Falcon hydronic burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Hydronic, ClearFire Falcon, CB Falcon, ProtoNode RER, 750-426 - Boiler flame safeguard and fuel-air ratio control via BACnet gateway
Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)
Cleaver-Brooks boilers with a CB780/CB783 burner control and FARC fuel-air ratio control, read through a ProtoNode RER gateway.
Also known as: FARC, CB 780/783, CB783, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 1000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 1000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 1000, CB Hawk 1000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 2000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 2000, CB Hawk 2000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 4000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 4000, CB Hawk 4000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 V2 boiler control (ProtoNode)
Cleaver-Brooks boilers with the HAWK 4000 V2 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: HAWK 4000 V2, CB HAWK 4000 V2, HAWK_4000_V2, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4500 boiler control (ProtoNode, EtherNet/IP)
Cleaver-Brooks boilers with the Hawk 4500 PLC boiler control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: Hawk 4500, CB Hawk 4500, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Hawk 5000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 5000, CB Hawk 5000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk ICS boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk ICS control, read through a ProtoNode RER gateway.
Also known as: Hawk ICS, CB ICS, ProtoNode RER, 750-426 - Boiler lead/lag master panel via BACnet gateway
Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode)
Cleaver-Brooks Hawk Master Panels sequencing up to eight Hawk boilers (A-H), read through a ProtoNode RER gateway.
Also known as: Hawk Master Panel, Hawk Master, CB Master Panel, ProtoNode RER, 750-426 - Boiler interface module via BACnet gateway
Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)
Cleaver-Brooks HSC boiler interface modules (one boiler each), read through a ProtoNode RER gateway.
Also known as: Boiler Interface Module, HSC Boiler Interface, BIM, ProtoNode RER, 750-426 - Multi-boiler sequencer (hot water boiler plant) via BACnet gateway
Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)
Cleaver-Brooks HSC panels sequencing up to 10 condensing and 10 non-condensing boilers, read through a ProtoNode RER gateway.
Also known as: HSC, Hydronic System Controller, CB HSC, ProtoNode RER, 750-426 - Pump interface module (boiler plant pumps) via BACnet gateway
Cleaver-Brooks HSC Pump Interface Module (ProtoNode)
Cleaver-Brooks HSC pump interface modules (up to four system pumps), read through a ProtoNode RER gateway.
Also known as: Pump Interface Module, HSC Pump Interface, ProtoNode RER, 750-426 - Boiler water level controller via BACnet gateway
Cleaver-Brooks LCS Level Control System (ProtoNode)
Cleaver-Brooks LCS water level controllers (one or two tanks), read through a ProtoNode RER gateway.
Also known as: LCS, Level Control System, ProtoNode RER, 750-426 - Boiler feed pump controller via BACnet gateway
Cleaver-Brooks PCS Pump Control System (ProtoNode)
Cleaver-Brooks PCS pump controllers (up to four pumps on header pressure or tank level), read through a ProtoNode RER gateway.
Also known as: PCS, Pump Control System, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 100 power meter profile (ProtoNode)
Shark 100 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 100, Electro Industries Shark 100, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 200 power meter profile (ProtoNode)
Shark 200 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 200, Electro Industries Shark 200, ProtoNode RER, 750-426 - Process loop controller via BACnet gateway
Cleaver-Brooks UDC 2500 loop controller profile (ProtoNode)
Honeywell UDC 2500 loop controllers supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: UDC 2500, UDC2500, Honeywell UDC 2500, ProtoNode RER, 750-426
Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.