Easy BACnet
  1. Home
  2. BACnet points lists
  3. Cleaver-Brooks
  4. Hawk 4000 boiler control (ProtoNode)

Steam or hot water boiler control via BACnet gateway · BACnet points list

Cleaver-Brooks Hawk 4000 boiler control (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The ProtoNode maps the Hawk 4000 boiler control to BACnet: a long list of alarm and status bits (limits, actuators, sensors, flame safeguard), steam pressure or water temperature, setpoints, firing rate, stack and economizer temperatures, burner control status lines, run time and cycles. The BMS can start the boiler, write a remote setpoint or firing rate, and must keep a heartbeat bit updated.

This page lists 283 BACnet objects for the Cleaver-Brooks Hawk 4000 boiler control (ProtoNode) — 42 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
Hawk 4000 boiler control (ProtoNode)
Equipment
Steam or hot water boiler control via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
283 (42 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
Hawk 4000, CB Hawk 4000, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 283 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)

Integration in brief

Start the boiler with BV 2 and keep BV 1 heartbeat toggling; write the operating setpoint (AV 1) or a remote firing rate (AV 2). Read load demand, steam pressure or water temperature, firing rate and the alarm output.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2Rem Start From BMSRemote start from the BMSWrite
BV 1Heart Beat From BMSHeartbeat written by the BMSWrite
AV 1Rem Op SP BoilerRemote operating setpointWrite
AV 2Rem Firing RateRemote firing rateWrite
BI 57Boiler Load DemandBoiler load demandRead
AI 9Steam Pressure or Hot Water TempSteam pressure or hot water temperatureRead
AI 7SP Steam Pressure/Water TempActive setpointRead
AI 5Firing RateFiring rateRead
BI 55Alm OutputAlarm outputRead

Enable & remote start

BV 2 Remote Start From BMS; BI 47 shows the boiler's remote enable input. The firing-rate mode bits (BI 58-60) show whether remote, manual or auto modulation is active.

Heartbeat & communication loss

BV 1 Heart Beat From BMS is written by the BMS; the guide does not state the timeout.

Network setup

Watch out for

Cleaver-Brooks Hawk 4000 boiler control (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

283 of 283 shown
Type
Access
Show
Cleaver-Brooks Hawk 4000 boiler control (ProtoNode) BACnet Points List
DescriptionStates
BI1Drive FaultRead
BI2Modbus Comm ErrorRead
BI3Lo WaterRead
BI4Burner Control AlmRead
BI5Boiler Limits OpenRead
BI6Hi Stack Temp AlmRead
BI7Hi Stack Temp ShutdownRead
BI8External InterlockRead
BI9I/O module faultRead
BI10Steam Sensor FailRead
BI11Air Actuator Out Of Pos AlmRead
BI12NG Actuator Out Of Pos AlmRead
BI13F/A Ratio Controller FaultRead
BI14No Fuel SelectedRead
BI15Lo ControlLogix BatteryRead
BI16Non Recycle Limit Relay FailRead
BI17Recyle Limit Relay FailRead
BI18Rem Modulation Signal FailRead
BI19Header Pressure Sensor FailRead
BI20Temp Channel 0-5 FailRead
BI21Lo O2 AlmRead
BI22Hi Limit AlmRead
BI23ALWCORead
BI24Lo Gas Pressure/Lo Oil TempRead
BI25Hi Gas Pressure/Hi Oil TempRead
BI26Lo Oil PressureRead
BI27Hi Oil PressureRead
BI28Oil Drawer Switch Not MadeRead
BI29Lo Atomizing Air PressureRead
BI30Lo Combustion Air PressureRead
BI31AUX Alm 1Read
BI32AUX Alm 2Read
BI33Blower OnRead
BI34Purge InputRead
BI35Release To Modulate InputRead
BI36Lo Fire SwitchRead
BI37Hi Fire SwitchRead
BI38Ready to start/Limits ClosedRead
BI39External Start InterlockRead
BI40ALFCORead
BI41PilotRead
BI42Main Fuel Valve OpenRead
BI43Fuel 1 SelectedRead
BI44Fuel 2 SelectedRead
BI45Heart Beat To BMSRead
BI46LWCO ShutdownRead
BI47Rem Enable InputRead
BI48Burner SwitchRead
BI49Recycle Limit RelayRead
BI50External Device StartRead
BI51Non Recycle Limit RelayRead
BI52Drive to Lo Fire (FARC)Read
BI53Start Slave Blr (2 Blr LL)Read
BI54Load Demand OutputRead
BImin55Alm OutputRead
BI56Boiler Ready (LL)Read
BImin57Boiler Load DemandRead
BI58Firing Rate Rem/LlagRead
BI59Firing Rate ManualRead
BI60Firing Rate AutoRead
BI61Hot Stand ByRead
BI62Warm UpRead
BI63Fuel 3 SelectedRead
BI64Aux Alm 3Read
BI65Steam or Hot Water 1 = SteamRead
BI66Level Master PresentRead
BI67Variable Speed Drive PresentRead
BI68Economizer PresentRead
BI69Combustion Air Temp PresentRead
BI70Economizer Inlet FW Sensor PresentRead
BI71O2 Analyzer PresentRead
BI72Feedwater or Return Temp PresentRead
BI73Outdoor Reset SelectedRead
BI74Parallel Posing SelectedRead
BI75Two Boiler Lead Lag Master SelectRead
BI76Two Boiler Lead Lag Slave SelectRead
BI77Master Panel SelectRead
BI78Hot Stand By SelectRead
BI79Dual Setpoint SelectRead
BI80Slot 8 Ch 0 AI SelectedRead
BI81Slot 8 Ch 1 AI SelectedRead
BI82Slot 8 Ch 2 AI SelectedRead
BI83Slot 8 Ch 3 AI SelectedRead
BI84Honeywell or Fireye 1 = FireyeRead
BI85Hi Water AlmRead
BI86Oil Actuator Out Of Pos AlmRead
BI87FGR Actuator Out Of Pos AlmRead
BI88Air Actuator Feedback Fail Lo AlmRead
BI89Air Actuator Feedback Fail Hi AlmRead
BI90NG Actuator Feedback Fail Lo AlmRead
BI91NG Actuator Feedback Fail Hi AlmRead
BI92Oil Actuator Feedback Fail Lo AlmRead
BI93Oil Actuator Feedback Fail Hi AlmRead
BI94FGR Actuator Feedback Fail Lo AlmRead
BI95FGR Actuator Feedback Fail Hi AlmRead
BI96VSD Deviation AlmRead
BI97Increase MSG Reg Size Bit (CB Only)Read
BI98Air/Fuel Deviation AlmRead
BI992nd Stage CEC Economizer SelectedRead
BI100Fuel3 Actuator Out Of Pos AlmRead
BI101Fuel3 Actuator Feedback Fail Lo AlmRead
BI102Fuel3 Actuator Feedback Fail Hi AlmRead
BI103Stack Pressure Input FailRead
BI104Hi Stack Pressure AlmRead
BI105Stack Damper Not Open AlmRead
BI106O2 Calibration FailedRead
BI107Lo Steam Pressure/Water Temp AlmRead
BI108Processor Test Fail AlmRead
BI109O2 Trim Internal AlmRead
BI110Firetube or Flextube 1 = FlextubeRead
BI111Reserved for Cleaver BrooksRead
BI112VSD Limits Internal AlmRead
BI113Gas Actuator 2 Out Of Pos AlmRead
BI114Gas Actuator 2 Feedback Fail Lo AlmRead
BI115Gas Actuator 2 Feedback Fail Hi AlmRead
BI116Actuator Modbus Communication ErrorRead
BI117Air Actuator Modbus Comm Error Node 1Read
BI118Gas Actuator Modbus Comm Error Node 2Read
BI119Gas Act 2 Modbus Comm Error Node 3Read
BI120Oil Actuator Modbus Comm Error Node 5Read
BI121FGR Actuator Modbus Comm Error Node 7Read
BI122ReservedRead
BI123ReservedRead
BI1242nd Stage Outlet Wtr Temp Sensor FailRead
BI125Water Temp Second Stage Out HiRead
BI126Air Actuator Man Override Btn PressRead
BI127Gas Actuator 1 Man Override Btn PressRead
BI128Gas Actuator 2 Man Override Btn PressRead
BI129Oil Actuator Man Override Btn PressRead
BI130FGR Actuator Man Override Btn PressRead
BI131Fuel 3 Act 1 Man Override Btn PressRead
BI132Fuel 3 Act 2 Man Override Btn PressRead
BI133Communication from BMS FailedRead
BI134Low O2 ShutdownRead
BI135AB[8]6Read
BI136AB[8]7Read
BI137AB[8]8Read
BI138AB[8]9Read
BI139AB[8]10Read
BI140AB[8]11Read
BI141AB[8]12Read
BI142AB[8]13Read
BI143AB[8]14Read
BI144AB[8]15Read
BI145AB[9]0Read
BI146AB[9]1Read
BI147AB[9]2Read
BI148AB[9]3Read
BI149AB[9]4Read
BI150AB[9]5Read
BI151AB[9]6Read
BI152AB[9]7Read
BI153AB[9]8Read
BI154AB[9]9Read
BI155AB[9]10Read
BI156AB[9]11Read
BI157AB[9]12Read
BI158AB[9]13Read
BI159AB[9]14Read
BI160AB[9]15Read
AI1Flame Strength HoneywellModbus 30001Read
AI2Combustion Air Fan SpeedModbus 30003Read
AI3AR[2]Modbus 30005Read
AI4Boiler EfficiencyModbus 30007Read
AImin5Firing RateModbus 30009Read
AI6O2 LevelModbus 30011Read
AImin7SP Steam Pressure/Water TempModbus 30013Read
AI8Water LevelModbus 30015Read
AImin9Steam Pressure or Hot Water TempModbus 30017Read
AI10AR[9]Modbus 30019Read
AI11Stack Temp Before EconomizerModbus 30021Read
AI12Combustion Air TempModbus 30023Read
AI13Water Temp Shell/Outdoor TempModbus 30025Read
AI14Feedwater Temp/Econ Water Out TempModbus 30027Read
AI15Stack Temp After Econ/Return HWModbus 30029Read
AI16Economizer Water In TempModbus 30031Read
AI17AI Slot8Ch0 Value/2Stg Econ Temp INModbus 30033Read
AI18AI Slot8Ch1 Value/2Stg Econ Temp OUTModbus 30035Read
AI19AI Slot8 Ch2 Value (EU)Modbus 30037Read
AI20AI Slot8 Ch3 Value (EU)Modbus 30039Read
AI21Safety Valve Setting or Max Water TempModbus 30041Read
AI22Header Pressure or Temp 2 Boiler LLModbus 30043Read
AI23SP 2 Boiler LLModbus 30045Read
AI24Boiler Off PointModbus 30047Read
AI25Boiler On PointModbus 30049Read
AI26Condensate Return Valve Output CommandModbus 30051Read
AI27Makeup Bypass Valve Output CommandModbus 30053Read
AI28Slot8 Ch0 FLo TotalModbus 30055Read
AI29Slot8 Ch1 FLo TotalModbus 30057Read
AI30Slot8 Ch2 FLo TotalModbus 30059Read
AI31Slot8 Ch3 FLo TotalModbus 30061Read
AI32AR[31]Modbus 30063Read
AI33AR[32]Modbus 30065Read
AI34AR[33]Modbus 30067Read
AI35AR[34]Modbus 30069Read
AI36AR[35]Modbus 30071Read
AI37AR[36]Modbus 30073Read
AI38AR[37]Modbus 30075Read
AI39AR[38]Modbus 30077Read
AI40AR[39]Modbus 30079Read
AI41AR[40]Modbus 30081Read
AI42AR[41]Modbus 30083Read
AI43AR[42]Modbus 30085Read
AI44AR[43]Modbus 30087Read
AI45AR[44]Modbus 30089Read
AI46AR[45]Modbus 30091Read
AI47AR[46]Modbus 30093Read
AI48AR[47]Modbus 30095Read
AI49AR[48]Modbus 30097Read
AI50AR[49]Modbus 30099Read
AI52Burner Control Status Line 1 HoneywellModbus 30102Read
AI53Burner Control Status Line 2 HoneywellModbus 30103Read
AI54Burner Control Status Line 1 FireyeModbus 30104Read
AI55Burner Control Status Line 2 FireyeModbus 30105Read
AI56Flame Signal FireyeModbus 30106Read
AI57Fuel 1TypeModbus 30107Read
AI58Fuel 2 TypeModbus 30108Read
AI59Fuel 3 TypeModbus 30109Read
AI61Elapsed Time (First 16 Bits)Modbus 30111Read
AI62Elapsed Time (Second 16 Bits)Modbus 30112Read
AI63Number Of Cycles (First 16 Bits)Modbus 30113Read
AI64Number Of Cycles (Second 16 Bits)Modbus 30114Read
AI65AI[13]Modbus 30115Read
AI66AI[14]Modbus 30116Read
AI67AI[15]Modbus 30117Read
AI68AI[16]Modbus 30118Read
AI69AI[17]Modbus 30119Read
AI70AI[18]Modbus 30120Read
AI71AI[19]Modbus 30121Read
AI72AI[20]Modbus 30122Read
AI73AI[21]Modbus 30123Read
AI74AI[22]Modbus 30124Read
AI75AI[23]Modbus 30125Read
AI76AI[24]Modbus 30126Read
AI77AI[25]Modbus 30127Read
AI78AI[26]Modbus 30128Read
AI79AI[27]Modbus 30129Read
AI80AI[28]Modbus 30130Read
AI81AI[29]Modbus 30131Read
AI82Elapsed TimeModbus 30132Read
AI83Number Of CyclesModbus 30134Read
BVmin1Heart Beat From BMSwrite pointWrite
BVmin2Rem Start From BMSwrite pointWrite
BV3AWB[0]2write pointWrite
BV4AWB[0]3write pointWrite
BV5AWB[0]4write pointWrite
BV6AWB[0]5write pointWrite
BV7AWB[0]6write pointWrite
BV8AWB[0]7write pointWrite
BV9AWB[0]8write pointWrite
BV10AWB[0]9write pointWrite
BV11AWB[0]10write pointWrite
BV12AWB[0]11write pointWrite
BV13AWB[0]12write pointWrite
BV14AWB[0]13write pointWrite
BV15AWB[0]14write pointWrite
BV16AWB[0]15write pointWrite
BV17AWB[1]0write pointWrite
BV18AWB[1]1write pointWrite
BV19AWB[1]2write pointWrite
BV20AWB[1]3write pointWrite
BV21AWB[1]4write pointWrite
BV22AWB[1]5write pointWrite
BV23AWB[1]6write pointWrite
BV24AWB[1]7write pointWrite
BV25AWB[1]8write pointWrite
BV26AWB[1]9write pointWrite
BV27AWB[1]10write pointWrite
BV28AWB[1]11write pointWrite
BV29AWB[1]12write pointWrite
BV30AWB[1]13write pointWrite
BV31AWB[1]14write pointWrite
BV32AWB[1]15write pointWrite
AVmin1Rem Op SP BoilerModbus 40001; write pointWrite
AVmin2Rem Firing RateModbus 40003; write pointWrite
AV3Rem Op SP 2 boiler Lead/LagModbus 40005; write pointWrite
AV4AWR[3]Modbus 40007; write pointWrite
AV5AWR[4]Modbus 40009; write pointWrite
AV6AWR[5]Modbus 40011; write pointWrite
AV7AWR[6]Modbus 40013; write pointWrite
AV8AWR[7]Modbus 40015; write pointWrite
AV9AWR[8]Modbus 40017; write pointWrite
AV10AWR[9]Modbus 40019; write pointWrite
Object ID lookup: Cleaver-Brooks Hawk 4000 boiler control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hawk 4000 boiler control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)

How many BACnet points does the Cleaver-Brooks Hawk 4000 boiler control (ProtoNode) have?

This list has 283 BACnet objects: 81 analog inputs, 10 analog values, 160 binary inputs, 32 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks Hawk 4000 boiler control (ProtoNode) BACnet points are writable?

42 of the 283 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Cleaver-Brooks Hawk 4000 boiler control (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)?

Start with BV 2 Rem Start From BMS (Remote start from the BMS); BV 1 Heart Beat From BMS (Heartbeat written by the BMS); AV 1 Rem Op SP Boiler (Remote operating setpoint); AV 2 Rem Firing Rate (Remote firing rate); BI 57 Boiler Load Demand (Boiler load demand); AI 9 Steam Pressure or Hot Water Temp (Steam pressure or hot water temperature); AI 7 SP Steam Pressure/Water Temp (Active setpoint); AI 5 Firing Rate (Firing rate); BI 55 Alm Output (Alarm output).

How do I enable BMS control of the Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)?

BV 2 Remote Start From BMS; BI 47 shows the boiler's remote enable input. The firing-rate mode bits (BI 58-60) show whether remote, manual or auto modulation is active.

Does the Cleaver-Brooks Hawk 4000 boiler control (ProtoNode) need a BACnet heartbeat or have a communication timeout?

BV 1 Heart Beat From BMS is written by the BMS; the guide does not state the timeout.

How do I check these points on the real Hawk 4000 boiler control (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.