Hot water boiler control via BACnet gateway · BACnet points list
Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) BACnet points list
Updated 7 November 2026Unofficial source
The ProtoNode maps the Falcon hydronic control's Modbus RTU registers to a fixed set of BACnet objects: safety and limit inputs, water and stack temperatures, firing rate, flame signal, burner state, lockout and hold codes, pump status and lead/lag data. The BMS can enable the burner and lead/lag and write the CH and lead/lag setpoints in °F or °C.
This page lists 90 BACnet objects for the Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.
- Manufacturer
- Cleaver-Brooks
- Model
- Falcon Hydronic boiler control (ProtoNode)
- Equipment
- Hot water boiler control via BACnet gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 90 (7 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + Modbus Node-ID
- Also known as
- Falcon Hydronic, ClearFire Falcon, CB Falcon, ProtoNode RER, 750-426
- Source document
- Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.
BMS integration notes: Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)
Enable the burner, write the CH setpoint (°F or °C object), and use the lead/lag enable and setpoint if the boilers run lead/lag. Read burner state, outlet temperature, firing rate, the alarm input and the lockout code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 1 | BOILER BURNER ENABLE | Burner enable from the BMS | Write |
| AV 21 | BOILER CH SETPOINT DEG F | Central heat setpoint, °F | Write |
| AV 11 | BOILER LEAD/LAG ENABLE | Lead/lag enable | Write |
| AV 31 | BOILER LEAD/LAG SETPOINT DEG F | Lead/lag setpoint, °F | Write |
| AI 16 | BURN_CTL_STATE | Burner control state code | Read |
| AI 2 | OUTLET WATER TEMP DEG F | Outlet water temperature, °F | Read |
| AI 74 | FIRING_RATE_PERCENT | Firing rate, % | Read |
| BI 8 | Alarm | Alarm | Read |
| AI 17 | LOCKOUT_CODE | Lockout code | Read |
Enable & remote start
AV 1 BOILER BURNER ENABLE and AV 11 BOILER LEAD/LAG ENABLE are the BMS enables; AV 21 / AV 41 write the CH setpoint in °F / °C.
Network setup
- BACnet Device Instance = the controller's Modbus Node-ID + Node_Offset (default 50,000), so Node-ID 1 = 50001. Change Node_Offset in the ProtoNode web configurator to pick other instances.
- The ProtoNode RER does BACnet MS/TP or BACnet IP, selected on its S bank DIP switches.
- BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on the A bank DIP switches; baud on B0-B3 (38400 factory default).
- BACnet IP: default ProtoNode address 192.168.1.24; change it in the web configurator.
Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 3 | PumpC | Modbus 30003, bit 2 | Read | ||
| BI | 4 | Blower_Mtr | Modbus 30003, bit 3 | Read | ||
| BI | 5 | Ext_Ignition | Modbus 30003, bit 4 | Read | ||
| BI | 6 | Pilot-MainDBI_Valve | Modbus 30003, bit 5 | Read | ||
| BI | 7 | Main_Valve | Modbus 30003, bit 6 | Read | ||
| BImin | 8 | Alarm | Modbus 30003, bit 7 | Read | ||
| BI | 9 | Interlock | Modbus 30003, bit 8 | Read | ||
| BI | 10 | PreIgn_Interlock | Modbus 30003, bit 9 | Read | ||
| BI | 11 | Load_Control_In | Modbus 30003, bit 10 | Read | ||
| BI | 12 | Low_Fire_Switch | Modbus 30003, bit 11 | Read | ||
| BI | 13 | High_Fire_Switch | Modbus 30003, bit 12 | Read | ||
| BI | 14 | Stat_Demand | Modbus 30003, bit 13 | Read | ||
| BI | 15 | TimeOfDay | Modbus 30003, bit 14 | Read | ||
| BI | 16 | Safety_Relay | Modbus 30003, bit 15 | Read | ||
| BI | 17 | Int_Air_Switch | Modbus 30004, bit 0 | Read | ||
| BI | 18 | Low_Water | Modbus 30004, bit 1 | Read | ||
| BI | 19 | Aux_Low_Water | Modbus 30004, bit 2 | Read | ||
| BI | 20 | High_Limit | Modbus 30004, bit 3 | Read | ||
| BI | 21 | High_Gas_Press | Modbus 30004, bit 4 | Read | ||
| BI | 22 | Low_Gas_Press | Modbus 30004, bit 5 | Read | ||
| BI | 23 | Natural_Gas | Modbus 30004, bit 6 | Read | ||
| BI | 24 | Propane_Gas | Modbus 30004, bit 7 | Read | ||
| AI | 1 | DEMAND SOURCE | Modbus 30007 | Read | ||
| AImin | 2 | OUTLET WATER TEMP DEG F | Modbus 30008 | °F | Read | |
| AI | 3 | FIRING_RATE | Modbus 30009 | Read | ||
| AI | 4 | FAN_SPEED | Modbus 30010 | Read | ||
| AI | 5 | FLAME_SIGNAL | Modbus 30011 | Read | ||
| AI | 6 | INLET WATER TEMP DEG F | Modbus 30012 | °F | Read | |
| AI | 7 | DHW WATER TEMP DEG F | Modbus 30013 | °F | Read | |
| AI | 8 | HEADER or ODT DEG F | Modbus 30014 | °F | Read | |
| AI | 9 | STACK TEMP DEG F | Modbus 30015 | °F | Read | |
| AI | 11 | CH SETPOINT DEG F | Modbus 30017 | °F | Read | |
| AI | 12 | DHW SETPOINT DEG F | Modbus 30018 | °F | Read | |
| AI | 14 | ANALOG_INPUT | Modbus 30022 | Read | ||
| AI | 15 | BURN_CTL_STATUS | Modbus 30033 | Read | ||
| AImin | 16 | BURN_CTL_STATE | Modbus 30034 | Read | ||
| AImin | 17 | LOCKOUT_CODE | Modbus 30035 | Read | ||
| AI | 18 | HOLD_CODE | Modbus 30041 | Read | ||
| AI | 20 | CH STATUS | Modbus 30063 | Read | ||
| AI | 21 | CH SETPOINT SOURCE | Modbus 30066 | Read | ||
| AI | 22 | CH HEAT DEMAND | Modbus 30067 | Read | ||
| AI | 23 | CH BURNER DEMAND | Modbus 30068 | Read | ||
| AI | 24 | CH REQUESTED RATE | Modbus 30069 | Read | ||
| AI | 25 | CH FROST HEAT DEMAND | Modbus 30070 | Read | ||
| AI | 26 | CH FROST BURNER DEMAND | Modbus 30071 | Read | ||
| AI | 29 | DHW STATUS | Modbus 30081 | Read | ||
| AI | 30 | DHW SETPOINT SOURCE | Modbus 30082 | Read | ||
| AI | 32 | DHW HEAT DEMAND | Modbus 30084 | Read | ||
| AI | 33 | DHW BURNER DEMAND | Modbus 30085 | Read | ||
| AI | 34 | DHW REQUESTED RATE | Modbus 30086 | Read | ||
| AI | 39 | CH PUMP STATUS | Modbus 30097 | Read | ||
| AI | 43 | DHW PUMP STATUS | Modbus 30101 | Read | ||
| AI | 48 | SYSTEM PUMP STATUS | Modbus 30106 | Read | ||
| AI | 51 | BOILER PUMP STATUS | Modbus 30109 | Read | ||
| AI | 54 | AUXILIARY1 PUMP STATUS | Modbus 30112 | Read | ||
| AI | 55 | AUXILIARY2 PUMP STATUS | Modbus 30114 | Read | ||
| AI | 57 | BURNER_ENABLE | Modbus 30204 | Read | ||
| AI | 60 | LEAD/LAG SETPOINT DEG F | Modbus 30547 | °F | Read | |
| AI | 61 | LEAD/LAG_ENABLE | Modbus 30556 | Read | ||
| AI | 58 | CYCLE_COUNT | Modbus 30129-30 | Read | ||
| AI | 59 | BURNER RUN_TIME | Modbus 30131-32 | Read | ||
| AVmin | 1 | BOILER BURNER ENABLE | Modbus 40204; write point | Write | ||
| AVmin | 11 | BOILER LEAD/LAG ENABLE | Modbus 40556; write point | Write | ||
| AVmin | 21 | BOILER CH SETPOINT DEG F | Modbus 40212; write point | °F | Write | |
| AVmin | 31 | BOILER LEAD/LAG SETPOINT DEG F | Modbus 40547; write point | °F | Write | |
| AI | 62 | OUTLET WATER TEMP DEG C | Modbus 30008 | °C | Read | |
| AI | 66 | INLET WATER TEMP DEG C | Modbus 30012 | °C | Read | |
| AI | 67 | DHW WATER TEMP DEG C | Modbus 30013 | °C | Read | |
| AI | 68 | HEADER or ODT DEG C | Modbus 30014 | °C | Read | |
| AI | 69 | STACK TEMP DEG C | Modbus 30015 | °C | Read | |
| AI | 71 | CH SETPOINT DEG C | Modbus 30017 | °C | Read | |
| AI | 72 | DHW SETPOINT DEG C | Modbus 30018 | °C | Read | |
| AI | 73 | LEAD/LAG SETPOINT DEG C | Modbus 30547 | °C | Read | |
| AV | 41 | BOILER CH SETPOINT DEG C | Modbus 40212; write point | °C | Write | |
| AV | 51 | BOILER LEAD/LAG SETPOINT DEG C | Modbus 40547; write point | °C | Write | |
| AImin | 74 | FIRING_RATE_PERCENT | Modbus 30074 | Read | ||
| AI | 75 | 4-20Ma Remote Ctl Input | Modbus 40016 | Read | ||
| AI | 76 | Active LL Setpoint | Modbus 40019 | Read | ||
| AI | 77 | Alarm Reason | Modbus 40036 | Read | ||
| AI | 78 | Annunciator First Out | Modbus 40037 | Read | ||
| AI | 79 | Annunciator Hold | Modbus 40038 | Read | ||
| AI | 80 | Outdoor Temperature | Modbus 40171 | Read | ||
| AV | 61 | CH Pump Cycle Count | Modbus 40133-34; write point | Write | ||
| AI | 81 | Lead Boiler Address | Modbus 40802 | Read | ||
| AI | 82 | Firing Rate Type | Modbus 30193 | Read | ||
| AI | 83 | Master ID | Modbus 30546 | Read | ||
| AI | 84 | Slave Setpoint | Modbus 30030 | Read | ||
| AI | 85 | Master OAT | Modbus 30171 | Read | ||
| AI | 86 | Max Firing Rate | Modbus 30194 | Read | ||
| AI | 87 | Min Firing Rate | Modbus 30196 | Read |
No points match these filters.
Object ID lookup: Cleaver-Brooks Falcon Hydronic boiler control point IDs by name
BI3PumpCBI4Blower_MtrBI5Ext_IgnitionBI6Pilot-MainDBI_ValveBI7Main_ValveBI8AlarmBI9InterlockBI10PreIgn_InterlockBI11Load_Control_InBI12Low_Fire_SwitchBI13High_Fire_SwitchBI14Stat_DemandBI15TimeOfDayBI16Safety_RelayBI17Int_Air_SwitchBI18Low_WaterBI19Aux_Low_WaterBI20High_LimitBI21High_Gas_PressBI22Low_Gas_PressBI23Natural_GasBI24Propane_GasAI1DEMAND SOURCEAI2OUTLET WATER TEMP DEG FAI3FIRING_RATEAI4FAN_SPEEDAI5FLAME_SIGNALAI6INLET WATER TEMP DEG FAI7DHW WATER TEMP DEG FAI8HEADER or ODT DEG FAI9STACK TEMP DEG FAI11CH SETPOINT DEG FAI12DHW SETPOINT DEG FAI14ANALOG_INPUTAI15BURN_CTL_STATUSAI16BURN_CTL_STATEAI17LOCKOUT_CODEAI18HOLD_CODEAI20CH STATUSAI21CH SETPOINT SOURCEAI22CH HEAT DEMANDAI23CH BURNER DEMANDAI24CH REQUESTED RATEAI25CH FROST HEAT DEMANDAI26CH FROST BURNER DEMANDAI29DHW STATUSAI30DHW SETPOINT SOURCEAI32DHW HEAT DEMANDAI33DHW BURNER DEMANDAI34DHW REQUESTED RATEAI39CH PUMP STATUSAI43DHW PUMP STATUSAI48SYSTEM PUMP STATUSAI51BOILER PUMP STATUSAI54AUXILIARY1 PUMP STATUSAI55AUXILIARY2 PUMP STATUSAI57BURNER_ENABLEAI60LEAD/LAG SETPOINT DEG FAI61LEAD/LAG_ENABLEAI58CYCLE_COUNTAI59BURNER RUN_TIMEAV1BOILER BURNER ENABLEAV11BOILER LEAD/LAG ENABLEAV21BOILER CH SETPOINT DEG FAV31BOILER LEAD/LAG SETPOINT DEG FAI62OUTLET WATER TEMP DEG CAI66INLET WATER TEMP DEG CAI67DHW WATER TEMP DEG CAI68HEADER or ODT DEG CAI69STACK TEMP DEG CAI71CH SETPOINT DEG CAI72DHW SETPOINT DEG CAI73LEAD/LAG SETPOINT DEG CAV41BOILER CH SETPOINT DEG CAV51BOILER LEAD/LAG SETPOINT DEG CAI74FIRING_RATE_PERCENTAI754-20Ma Remote Ctl InputAI76Active LL SetpointAI77Alarm ReasonAI78Annunciator First OutAI79Annunciator HoldAI80Outdoor TemperatureAV61CH Pump Cycle CountAI81Lead Boiler AddressAI82Firing Rate TypeAI83Master IDAI84Slave SetpointAI85Master OATAI86Max Firing RateAI87Min Firing Rate
Integration notes
- Each Cleaver-Brooks controller on the ProtoNode is its own BACnet device; the object instances below are the same on every device.
- Access follows the guide's write-point stars: the starred AV/BV objects are writable, everything else is read-only.
- The guide gives no engineering units or state texts; units appear only where the object name carries them (DEG F / DEG C).
- Where a description is filled in, it gives the register from the guide's Modbus column.
- Temperature setpoints come as separate °F and °C objects (AV 21 / AV 41, AV 31 / AV 51); write one or the other.
- The table starts at BI 3; BI 1 and BI 2 are not printed for this control.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Falcon Hydronic boiler control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)
How many BACnet points does the Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) have?
This list has 90 BACnet objects: 61 analog inputs, 7 analog values, 22 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) BACnet points are writable?
7 of the 90 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) BACnet documentation?
Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.
What are the minimum BACnet points to integrate the Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)?
Start with AV 1 BOILER BURNER ENABLE (Burner enable from the BMS); AV 21 BOILER CH SETPOINT DEG F (Central heat setpoint, °F); AV 11 BOILER LEAD/LAG ENABLE (Lead/lag enable); AV 31 BOILER LEAD/LAG SETPOINT DEG F (Lead/lag setpoint, °F); AI 16 BURN_CTL_STATE (Burner control state code); AI 2 OUTLET WATER TEMP DEG F (Outlet water temperature, °F); AI 74 FIRING_RATE_PERCENT (Firing rate, %); BI 8 Alarm (Alarm); AI 17 LOCKOUT_CODE (Lockout code).
How do I enable BMS control of the Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)?
AV 1 BOILER BURNER ENABLE and AV 11 BOILER LEAD/LAG ENABLE are the BMS enables; AV 21 / AV 41 write the CH setpoint in °F / °C.
How do I check these points on the real Falcon Hydronic boiler control (ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Cleaver-Brooks BACnet points lists
- Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
Cleaver-Brooks deaerator and surge tank packages with the ADAC 1000 PLC control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: ADAC 1000, ADAC_1000, ProtoNode RER, 750-426 - Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)
Cleaver-Brooks deaerator and surge tank packages with the ADAC control, read through a ProtoNode RER gateway.
Also known as: ADAC, CB deaerator control, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB120 flame safeguard (ProtoNode)
Cleaver-Brooks boilers with the CB120 flame safeguard, read through a ProtoNode RER gateway.
Also known as: CB120, CB 120, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB780 flame safeguard with expanded annunciator (ProtoNode)
Cleaver-Brooks boilers with the CB780 burner management control and expanded annunciator, read through a ProtoNode RER gateway.
Also known as: CB780, CB 780, CB780E, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Falcon Steam boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Falcon steam burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Steam, CB Falcon steam, ProtoNode RER, 750-426 - Boiler flame safeguard and fuel-air ratio control via BACnet gateway
Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)
Cleaver-Brooks boilers with a CB780/CB783 burner control and FARC fuel-air ratio control, read through a ProtoNode RER gateway.
Also known as: FARC, CB 780/783, CB783, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 1000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 1000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 1000, CB Hawk 1000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 2000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 2000, CB Hawk 2000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 4000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 4000, CB Hawk 4000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 V2 boiler control (ProtoNode)
Cleaver-Brooks boilers with the HAWK 4000 V2 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: HAWK 4000 V2, CB HAWK 4000 V2, HAWK_4000_V2, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4500 boiler control (ProtoNode, EtherNet/IP)
Cleaver-Brooks boilers with the Hawk 4500 PLC boiler control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: Hawk 4500, CB Hawk 4500, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Hawk 5000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 5000, CB Hawk 5000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk ICS boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk ICS control, read through a ProtoNode RER gateway.
Also known as: Hawk ICS, CB ICS, ProtoNode RER, 750-426 - Boiler lead/lag master panel via BACnet gateway
Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode)
Cleaver-Brooks Hawk Master Panels sequencing up to eight Hawk boilers (A-H), read through a ProtoNode RER gateway.
Also known as: Hawk Master Panel, Hawk Master, CB Master Panel, ProtoNode RER, 750-426 - Boiler interface module via BACnet gateway
Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)
Cleaver-Brooks HSC boiler interface modules (one boiler each), read through a ProtoNode RER gateway.
Also known as: Boiler Interface Module, HSC Boiler Interface, BIM, ProtoNode RER, 750-426 - Multi-boiler sequencer (hot water boiler plant) via BACnet gateway
Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)
Cleaver-Brooks HSC panels sequencing up to 10 condensing and 10 non-condensing boilers, read through a ProtoNode RER gateway.
Also known as: HSC, Hydronic System Controller, CB HSC, ProtoNode RER, 750-426 - Pump interface module (boiler plant pumps) via BACnet gateway
Cleaver-Brooks HSC Pump Interface Module (ProtoNode)
Cleaver-Brooks HSC pump interface modules (up to four system pumps), read through a ProtoNode RER gateway.
Also known as: Pump Interface Module, HSC Pump Interface, ProtoNode RER, 750-426 - Boiler water level controller via BACnet gateway
Cleaver-Brooks LCS Level Control System (ProtoNode)
Cleaver-Brooks LCS water level controllers (one or two tanks), read through a ProtoNode RER gateway.
Also known as: LCS, Level Control System, ProtoNode RER, 750-426 - Boiler feed pump controller via BACnet gateway
Cleaver-Brooks PCS Pump Control System (ProtoNode)
Cleaver-Brooks PCS pump controllers (up to four pumps on header pressure or tank level), read through a ProtoNode RER gateway.
Also known as: PCS, Pump Control System, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 100 power meter profile (ProtoNode)
Shark 100 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 100, Electro Industries Shark 100, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 200 power meter profile (ProtoNode)
Shark 200 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 200, Electro Industries Shark 200, ProtoNode RER, 750-426 - Process loop controller via BACnet gateway
Cleaver-Brooks UDC 2500 loop controller profile (ProtoNode)
Honeywell UDC 2500 loop controllers supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: UDC 2500, UDC2500, Honeywell UDC 2500, ProtoNode RER, 750-426
Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.