Hot water boiler control via BACnet gateway · BACnet points list

Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The ProtoNode maps the Falcon hydronic control's Modbus RTU registers to a fixed set of BACnet objects: safety and limit inputs, water and stack temperatures, firing rate, flame signal, burner state, lockout and hold codes, pump status and lead/lag data. The BMS can enable the burner and lead/lag and write the CH and lead/lag setpoints in °F or °C.

This page lists 90 BACnet objects for the Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
Falcon Hydronic boiler control (ProtoNode)
Equipment
Hot water boiler control via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
90 (7 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
Falcon Hydronic, ClearFire Falcon, CB Falcon, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 90 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)

Integration in brief

Enable the burner, write the CH setpoint (°F or °C object), and use the lead/lag enable and setpoint if the boilers run lead/lag. Read burner state, outlet temperature, firing rate, the alarm input and the lockout code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1BOILER BURNER ENABLEBurner enable from the BMSWrite
AV 21BOILER CH SETPOINT DEG FCentral heat setpoint, °FWrite
AV 11BOILER LEAD/LAG ENABLELead/lag enableWrite
AV 31BOILER LEAD/LAG SETPOINT DEG FLead/lag setpoint, °FWrite
AI 16BURN_CTL_STATEBurner control state codeRead
AI 2OUTLET WATER TEMP DEG FOutlet water temperature, °FRead
AI 74FIRING_RATE_PERCENTFiring rate, %Read
BI 8AlarmAlarmRead
AI 17LOCKOUT_CODELockout codeRead

Enable & remote start

AV 1 BOILER BURNER ENABLE and AV 11 BOILER LEAD/LAG ENABLE are the BMS enables; AV 21 / AV 41 write the CH setpoint in °F / °C.

Network setup

Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

90 of 90 shown
Type
Binary
Access
Show
Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) BACnet Points List
DescriptionStates
BI3PumpCModbus 30003, bit 2Read
BI4Blower_MtrModbus 30003, bit 3Read
BI5Ext_IgnitionModbus 30003, bit 4Read
BI6Pilot-MainDBI_ValveModbus 30003, bit 5Read
BI7Main_ValveModbus 30003, bit 6Read
BImin8AlarmModbus 30003, bit 7Read
BI9InterlockModbus 30003, bit 8Read
BI10PreIgn_InterlockModbus 30003, bit 9Read
BI11Load_Control_InModbus 30003, bit 10Read
BI12Low_Fire_SwitchModbus 30003, bit 11Read
BI13High_Fire_SwitchModbus 30003, bit 12Read
BI14Stat_DemandModbus 30003, bit 13Read
BI15TimeOfDayModbus 30003, bit 14Read
BI16Safety_RelayModbus 30003, bit 15Read
BI17Int_Air_SwitchModbus 30004, bit 0Read
BI18Low_WaterModbus 30004, bit 1Read
BI19Aux_Low_WaterModbus 30004, bit 2Read
BI20High_LimitModbus 30004, bit 3Read
BI21High_Gas_PressModbus 30004, bit 4Read
BI22Low_Gas_PressModbus 30004, bit 5Read
BI23Natural_GasModbus 30004, bit 6Read
BI24Propane_GasModbus 30004, bit 7Read
AI1DEMAND SOURCEModbus 30007Read
AImin2OUTLET WATER TEMP DEG FModbus 30008°FRead
AI3FIRING_RATEModbus 30009Read
AI4FAN_SPEEDModbus 30010Read
AI5FLAME_SIGNALModbus 30011Read
AI6INLET WATER TEMP DEG FModbus 30012°FRead
AI7DHW WATER TEMP DEG FModbus 30013°FRead
AI8HEADER or ODT DEG FModbus 30014°FRead
AI9STACK TEMP DEG FModbus 30015°FRead
AI11CH SETPOINT DEG FModbus 30017°FRead
AI12DHW SETPOINT DEG FModbus 30018°FRead
AI14ANALOG_INPUTModbus 30022Read
AI15BURN_CTL_STATUSModbus 30033Read
AImin16BURN_CTL_STATEModbus 30034Read
AImin17LOCKOUT_CODEModbus 30035Read
AI18HOLD_CODEModbus 30041Read
AI20CH STATUSModbus 30063Read
AI21CH SETPOINT SOURCEModbus 30066Read
AI22CH HEAT DEMANDModbus 30067Read
AI23CH BURNER DEMANDModbus 30068Read
AI24CH REQUESTED RATEModbus 30069Read
AI25CH FROST HEAT DEMANDModbus 30070Read
AI26CH FROST BURNER DEMANDModbus 30071Read
AI29DHW STATUSModbus 30081Read
AI30DHW SETPOINT SOURCEModbus 30082Read
AI32DHW HEAT DEMANDModbus 30084Read
AI33DHW BURNER DEMANDModbus 30085Read
AI34DHW REQUESTED RATEModbus 30086Read
AI39CH PUMP STATUSModbus 30097Read
AI43DHW PUMP STATUSModbus 30101Read
AI48SYSTEM PUMP STATUSModbus 30106Read
AI51BOILER PUMP STATUSModbus 30109Read
AI54AUXILIARY1 PUMP STATUSModbus 30112Read
AI55AUXILIARY2 PUMP STATUSModbus 30114Read
AI57BURNER_ENABLEModbus 30204Read
AI60LEAD/LAG SETPOINT DEG FModbus 30547°FRead
AI61LEAD/LAG_ENABLEModbus 30556Read
AI58CYCLE_COUNTModbus 30129-30Read
AI59BURNER RUN_TIMEModbus 30131-32Read
AVmin1BOILER BURNER ENABLEModbus 40204; write pointWrite
AVmin11BOILER LEAD/LAG ENABLEModbus 40556; write pointWrite
AVmin21BOILER CH SETPOINT DEG FModbus 40212; write point°FWrite
AVmin31BOILER LEAD/LAG SETPOINT DEG FModbus 40547; write point°FWrite
AI62OUTLET WATER TEMP DEG CModbus 30008°CRead
AI66INLET WATER TEMP DEG CModbus 30012°CRead
AI67DHW WATER TEMP DEG CModbus 30013°CRead
AI68HEADER or ODT DEG CModbus 30014°CRead
AI69STACK TEMP DEG CModbus 30015°CRead
AI71CH SETPOINT DEG CModbus 30017°CRead
AI72DHW SETPOINT DEG CModbus 30018°CRead
AI73LEAD/LAG SETPOINT DEG CModbus 30547°CRead
AV41BOILER CH SETPOINT DEG CModbus 40212; write point°CWrite
AV51BOILER LEAD/LAG SETPOINT DEG CModbus 40547; write point°CWrite
AImin74FIRING_RATE_PERCENTModbus 30074Read
AI754-20Ma Remote Ctl InputModbus 40016Read
AI76Active LL SetpointModbus 40019Read
AI77Alarm ReasonModbus 40036Read
AI78Annunciator First OutModbus 40037Read
AI79Annunciator HoldModbus 40038Read
AI80Outdoor TemperatureModbus 40171Read
AV61CH Pump Cycle CountModbus 40133-34; write pointWrite
AI81Lead Boiler AddressModbus 40802Read
AI82Firing Rate TypeModbus 30193Read
AI83Master IDModbus 30546Read
AI84Slave SetpointModbus 30030Read
AI85Master OATModbus 30171Read
AI86Max Firing RateModbus 30194Read
AI87Min Firing RateModbus 30196Read
Object ID lookup: Cleaver-Brooks Falcon Hydronic boiler control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Falcon Hydronic boiler control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)

How many BACnet points does the Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) have?

This list has 90 BACnet objects: 61 analog inputs, 7 analog values, 22 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) BACnet points are writable?

7 of the 90 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)?

Start with AV 1 BOILER BURNER ENABLE (Burner enable from the BMS); AV 21 BOILER CH SETPOINT DEG F (Central heat setpoint, °F); AV 11 BOILER LEAD/LAG ENABLE (Lead/lag enable); AV 31 BOILER LEAD/LAG SETPOINT DEG F (Lead/lag setpoint, °F); AI 16 BURN_CTL_STATE (Burner control state code); AI 2 OUTLET WATER TEMP DEG F (Outlet water temperature, °F); AI 74 FIRING_RATE_PERCENT (Firing rate, %); BI 8 Alarm (Alarm); AI 17 LOCKOUT_CODE (Lockout code).

How do I enable BMS control of the Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)?

AV 1 BOILER BURNER ENABLE and AV 11 BOILER LEAD/LAG ENABLE are the BMS enables; AV 21 / AV 41 write the CH setpoint in °F / °C.

How do I check these points on the real Falcon Hydronic boiler control (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.