  4. ADAC deaerator / surge tank control (ProtoNode)

Boiler feedwater deaerator and surge tank controller via BACnet gateway · BACnet points list

Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

A read-only ProtoNode profile for the ADAC control: deaerator temperature, pressure and level, make-up and steam valve signals, feedwater header pressure, surge tank pressure, temperature and level, feed and transfer pump run times and lead/lag status, pump alarms and stack-light states.

This page lists 265 BACnet objects for the Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
ADAC deaerator / surge tank control (ProtoNode)
Equipment
Boiler feedwater deaerator and surge tank controller via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
265 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
ADAC, CB deaerator control, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 265 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)

Integration in brief

Read-only. Map deaerator pressure, level and temperature, feedwater header pressure, surge tank level and the no-alarm relay states.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 16Deaerator Tank PressureDeaerator tank pressureRead
AI 17Deaerator Tank Wtr LvlDeaerator tank water levelRead
AI 15Deaerator TempDeaerator temperatureRead
AI 20Boiler Feed Wtr Header PressureBoiler feedwater header pressureRead
AI 41Surge Tank Wtr LvlSurge tank water levelRead
BI 61Deaerator No Alarms Relay OKDeaerator no-alarms relay OKRead
BI 129Surge Tank No Alarms Relay OKSurge tank no-alarms relay OKRead

Network setup

Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

265 of 265 shown
Type
AnalogBinary
Show
Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) BACnet Points List
DescriptionStates
BI1Deaerator Lvl BAD QUALITYRead
BI2Deaerator Lvl HiRead
BI3Deaerator Lvl LoRead
BI4Deaerator Lvl Lo-Lo (LWCO)Read
BI5Feed Pump 1 FltRead
BI6Feed Pump 2 FltRead
BI7Feed Pump 3 FltRead
BI8Feed Pump 4 FltRead
BI9Feed Pump 5 FltRead
BI10Feed Pump 6 FltRead
BI11Feed Pump 1 OVERLOADRead
BI12Feed Pump 2 OVERLOADRead
BI13Feed Pump 3 OVERLOADRead
BI14Feed Pump 4 OVERLOADRead
BI15Feed Pump 5 OVERLOADRead
BI16Feed Pump 6 OVERLOADRead
BI17SpareRead
BI18SpareRead
BI19SpareRead
BI20Deaerator Temp BAD QUALITYRead
BI21Deaerator Temp LoRead
BI22Deaerator Temp HiRead
BI23Deaerator Pressure BAD QUALITYRead
BI24Deaerator Pressure LoRead
BI25Deaerator Pressure HiRead
BI26Boiler Feed Wtr Header Pressure BQRead
BI27Boiler Feed Wtr Header Pressure LoRead
BI28Boiler Feed Wtr Header Pressure HiRead
BI29DAB1[1]12Read
BI30DAB1[1]13Read
BI31DAB1[1]14Read
BI32DAB1[1]15Read
BI33DAB1[2]0Read
BI34DAB1[2]1Read
BI35DAB1[2]2Read
BI36DAB1[2]3Read
BI37DAB1[2]4Read
BI38DAB1[2]5Read
BI39DAB1[2]6Read
BI40DAB1[2]7Read
BI41DAB1[2]8Read
BI42DAB1[2]9Read
BI43DAB1[2]10Read
BI44DAB1[2]11Read
BI45DAB1[2]12Read
BI46DAB1[2]13Read
BI47DAB1[2]14Read
BI48DAB1[2]15Read
BI49Feed Pump 1 ONRead
BI50Feed Pump 2 ONRead
BI51Feed Pump 3 ONRead
BI52Feed Pump 4 ONRead
BI53Feed Pump 5 ONRead
BI54Feed Pump 6 ONRead
BI55Feed Pump 1 In AUTORead
BI56Feed Pump 2 In AUTORead
BI57Feed Pump 3 In AUTORead
BI58Feed Pump 4 In AUTORead
BI59Feed Pump 5 In AUTORead
BI60Feed Pump 6 In AUTORead
BImin61Deaerator No Alarms Relay OKRead
BI62YelLo Stack Light ONRead
BI63Green Stack Light ONRead
BI64Red Stack Light ONRead
BI65Chemical Feed ONRead
BI66Deaerator Feed Wtr Valve OpenRead
BI67Feed Pumps ALT MODE ONRead
BI68DA Lo-Lo Wtr Cutoff Relay EnergizedRead
BI69Deaerator 2nd Feed Wtr Valve OpenRead
BI70Boiler Feed Pump 1 FLo FltRead
BI71Boiler Feed Pump 2 FLo FltRead
BI72Boiler Feed Pump 3 FLo FltRead
BI73Boiler Feed Pump 4 FLo FltRead
BI74Boiler Feed Pump 5 FLo FltRead
BI75Boiler Feed Pump 6 FLo FltRead
BI76PLC Battery Lo Replace BatteryRead
BI77Feed Pump 1 VSD Speed Feedback Bad QRead
BI78Feed Pump 2 VSD Speed Feedback Bad QRead
BI79Feed Pump 3 VSD Speed Feedback Bad QRead
BI80Feed Pump 4 VSD Speed Feedback Bad QRead
BI81Feed Pump 5 VSD Speed Feedback Bad QRead
BI82Feed Pump 6 VSD Speed Feedback Bad QRead
BI83DAB1[5]2Read
BI84DAB1[5]3Read
BI85DAB1[5]4Read
BI86DAB1[5]5Read
BI87DAB1[5]6Read
BI88DAB1[5]7Read
BI89DAB1[5]8Read
BI90DAB1[5]9Read
BI91DAB1[5]10Read
BI92DAB1[5]11Read
BI93DAB1[5]12Read
BI94DAB1[5]13Read
BI95DAB1[5]14Read
BI96DAB1[5]15Read
BI97Surge Tank Lvl BAD QUALITYRead
BI98Surge Tank Lvl HiRead
BI99Surge Tank Lvl LoRead
BI100Surge Tank Temp BAD QUALITYRead
BI101Surge Tank Temp LoRead
BI102Surge Tank Temp HiRead
BI103Transfer Pump 1 FltRead
BI104Transfer Pump 2 FltRead
BI105Transfer Pump 3 FltRead
BI106Transfer Pump 1 OVERLOADRead
BI107Transfer Pump 2OVERLOADRead
BI108Transfer Pump 3OVERLOADRead
BI109Surge Tank Lo-Lo (LWCO)Read
BI110Surge Tank Header Pressure HiRead
BI111Surge Tank Header Pressure LoRead
BI112Surge Tank Header Pressure BAD QUALITYRead
BI113DAB1[7]0Read
BI114DAB1[7]1Read
BI115DAB1[7]2Read
BI116Surge 2nd Feed Wtr Valve OpenRead
BI117Transfer Pump 1 FLo FltRead
BI118Transfer Pump 2 FLo FltRead
BI119Transfer Pump 3 FLo FltRead
BI120Transfer Pump 1 VSD Speed Feedback BQRead
BI121Transfer Pump 2 VSD Speed Feedback BQRead
BI122Transfer Pump 3 VSD Speed Feedback BQRead
BI123DAB1[7]10Read
BI124DAB1[7]11Read
BI125DAB1[7]12Read
BI126DAB1[7]13Read
BI127DAB1[7]14Read
BI128DAB1[7]15Read
BImin129Surge Tank No Alarms Relay OKRead
BI130YelLo Stack Light ONRead
BI131Green Stack Light ONRead
BI132RED Stack Light ONRead
BI133Surge Tank Feed Wtr Valve OpenRead
BI134ST Lo Lo Wtr Cutoff Relay EnergizedRead
BI135Transfer Pump 1 ONRead
BI136Transfer Pump 2 ONRead
BI137Transfer Pump 3 ONRead
BI138Transfer Pump 1 In AUTORead
BI139Transfer Pump 2 In AUTORead
BI140Transfer Pump 3 In AUTORead
BI141Transfer Pumps ALT MODE ONRead
BI142DAB1[8]13Read
BI143DAB1[8]14Read
BI144DAB1[8]15Read
BI145DAB1[9]0Read
BI146DAB1[9]1Read
BI147DAB1[9]2Read
BI148DAB1[9]3Read
BI149DAB1[9]4Read
BI150DAB1[9]5Read
BI151DAB1[9]6Read
BI152DAB1[9]7Read
BI153DAB1[9]8Read
BI154DAB1[9]9Read
BI155DAB1[9]10Read
BI156DAB1[9]11Read
BI157DAB1[9]12Read
BI158DAB1[9]13Read
BI159DAB1[9]14Read
BI160DAB1[9]15Read
AI1Feed Pump 1 Run TimeModbus 30853Read
AI2Feed Pump 2 Run TimeModbus 30855Read
AI3Feed Pump 3 Run TimeModbus 30857Read
AI4Feed Pump 4 Run TimeModbus 30859Read
AI5Feed Pump 5 Run TimeModbus 30861Read
AI6Feed Pump 6 Run TimeModbus 30863Read
AI7DAR1[6]Modbus 30865Read
AI8DAR1[7]Modbus 30867Read
AI9DAR1[8]Modbus 30869Read
AI10Stop Lag Feed Pump LimitModbus 30871Read
AI11Alternate Feed PumpsModbus 30873Read
AI12Start Chemical Feed Time DelayModbus 30875Read
AI13Stop Chemical Feed Time DelayModbus 30877Read
AI14DAR1[14]Modbus 30879Read
AImin15Deaerator TempModbus 30881Read
AImin16Deaerator Tank PressureModbus 30883Read
AImin17Deaerator Tank Wtr LvlModbus 30885Read
AI18Deaerator Feed Wtr (MUV) SignalModbus 30887Read
AI19Deaerator Steam PRValve SignalModbus 30889Read
AImin20Boiler Feed Wtr Header PressureModbus 30891Read
AI21Deaerator 2nd Feed Wtr (MUV) SignalModbus 30893Read
AI22Start Lag Feed Pump LimitModbus 30895Read
AI23DA Lvl - Pump Auto-Restart LvlModbus 30897Read
AI24DAR1[24]Modbus 30899Read
AI25DAR1[25]Modbus 30901Read
AI26DAR1[26]Modbus 30903Read
AI27DAR1[27]Modbus 30905Read
AI28DAR1[28]Modbus 30907Read
AI29DAR1[29]Modbus 30909Read
AI30DAR1[30]Modbus 30911Read
AI31DAR1[31]Modbus 30913Read
AI32DAR1[32]Modbus 30915Read
AI33DAR1[33]Modbus 30917Read
AI34DAR1[34]Modbus 30919Read
AI35DAR1[35]Modbus 30921Read
AI36DAR1[36]Modbus 30923Read
AI37DAR1[37]Modbus 30925Read
AI38DAR1[38]Modbus 30927Read
AI39Surge Header PressureModbus 30929Read
AI40Surge Tank TempModbus 30931Read
AImin41Surge Tank Wtr LvlModbus 30933Read
AI42Surge Tank Feed Wtr (MUV) SignalModbus 30935Read
AI43Transfer Pump 1 Run TimeModbus 30937Read
AI44Transfer Pump 2 Run TimeModbus 30939Read
AI45Transfer Pump 3 Run TimeModbus 30941Read
AI46Alternate Transfer PumpsModbus 30943Read
AI47Stop Transfer Lag Feed Pump LimitModbus 30945Read
AI48Surge Tank 2nd Feed Wtr (MUV) SignalModbus 30947Read
AI49Start Lag Feed Pump LimitModbus 30949Read
AI50Surge Lvl - Pump Auto-Restart LvlModbus 30951Read
AI51DAR1[51]Modbus 30953Read
AI52DAR1[52]Modbus 30955Read
AI53DAR1[53]Modbus 30957Read
AI54DAR1[54]Modbus 30959Read
AI55DAR1[55]Modbus 30961Read
AI56DAR1[56]Modbus 30963Read
AI57DAR1[57]Modbus 30965Read
AI58DAR1[58]Modbus 30967Read
AI59DAR1[59]Modbus 30969Read
AI60DAR1[60]Modbus 30971Read
AI61DAR1[61]Modbus 30973Read
AI62DAR1[62]Modbus 30975Read
AI63DAR1[63]Modbus 30977Read
AI64DAR1[64]Modbus 30979Read
AI65DAR1[65]Modbus 30981Read
AI66Feed Pump 1 LEAD/LAG StatusModbus 30983Read
AI67Feed Pump 2 LEAD/LAG StatusModbus 31159Read
AI68Feed Pump 3 LEAD/LAG StatusModbus 31160Read
AI69Feed Pump 4 LEAD/LAG StatusModbus 31161Read
AI70Feed Pump 5 LEAD/LAG StatusModbus 31162Read
AI71Feed Pump 6 LEAD/LAG StatusModbus 31163Read
AI72DAI1[6]Modbus 31164Read
AI73DAI1[7]Modbus 31165Read
AI74DAI1[8]Modbus 31166Read
AI75DAI1[9]Modbus 31167Read
AI76DAI1[10]Modbus 31168Read
AI77DAI1[11]Modbus 31169Read
AI78DAI1[12]Modbus 31170Read
AI79DAI1[13]Modbus 31171Read
AI80DAI1[14]Modbus 31172Read
AI81DAI1[15]Modbus 31173Read
AI82DAI1[16]Modbus 31174Read
AI83DAI1[17]Modbus 31175Read
AI84DAI1[18]Modbus 31176Read
AI85DAI1[19]Modbus 31177Read
AI86Transfer Pump 1 LEAD/LAG StatusModbus 31178Read
AI87Transfer Pump 2 LEAD/LAG StatusModbus 31179Read
AI88Transfer Pump 3 LEAD/LAG StatusModbus 31180Read
AI89DAI1[23]Modbus 31181Read
AI90DAI1[24]Modbus 31182Read
AI91DAI1[25]Modbus 31183Read
AI92DAI1[26]Modbus 31184Read
AI93DAI1[27]Modbus 31185Read
AI94DAI1[28]Modbus 31186Read
AI95DAI1[29]Modbus 31187Read
AI96DAI1[30]Modbus 31188Read
AI97DAI1[31]Modbus 31189Read
AI98DAI1[32]Modbus 31190Read
AI99DAI1[33]Modbus 31191Read
AI100DAI1[34]Modbus 31192Read
AI101DAI1[35]Modbus 31193Read
AI102DAI1[36]Modbus 31194Read
AI103DAI1[37]Modbus 31195Read
AI104DAI1[38]Modbus 31196Read
AI105DAI1[39]Modbus 31197Read
Object ID lookup: Cleaver-Brooks ADAC deaerator / surge tank control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ADAC deaerator / surge tank control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)

How many BACnet points does the Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) have?

This list has 265 BACnet objects: 105 analog inputs, 160 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)?

Start with AI 16 Deaerator Tank Pressure (Deaerator tank pressure); AI 17 Deaerator Tank Wtr Lvl (Deaerator tank water level); AI 15 Deaerator Temp (Deaerator temperature); AI 20 Boiler Feed Wtr Header Pressure (Boiler feedwater header pressure); AI 41 Surge Tank Wtr Lvl (Surge tank water level); BI 61 Deaerator No Alarms Relay OK (Deaerator no-alarms relay OK); BI 129 Surge Tank No Alarms Relay OK (Surge tank no-alarms relay OK).

How do I check these points on the real ADAC deaerator / surge tank control (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.