Boiler feedwater deaerator and surge tank controller via BACnet gateway · BACnet points list
Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) BACnet points list
Updated 7 November 2026Unofficial source
A read-only ProtoNode profile for the ADAC control: deaerator temperature, pressure and level, make-up and steam valve signals, feedwater header pressure, surge tank pressure, temperature and level, feed and transfer pump run times and lead/lag status, pump alarms and stack-light states.
This page lists 265 BACnet objects for the Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.
- Manufacturer
- Cleaver-Brooks
- Model
- ADAC deaerator / surge tank control (ProtoNode)
- Equipment
- Boiler feedwater deaerator and surge tank controller via BACnet gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 265 (0 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + Modbus Node-ID
- Also known as
- ADAC, CB deaerator control, ProtoNode RER, 750-426
- Source document
- Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.
BMS integration notes: Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)
Read-only. Map deaerator pressure, level and temperature, feedwater header pressure, surge tank level and the no-alarm relay states.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 16 | Deaerator Tank Pressure | Deaerator tank pressure | Read |
| AI 17 | Deaerator Tank Wtr Lvl | Deaerator tank water level | Read |
| AI 15 | Deaerator Temp | Deaerator temperature | Read |
| AI 20 | Boiler Feed Wtr Header Pressure | Boiler feedwater header pressure | Read |
| AI 41 | Surge Tank Wtr Lvl | Surge tank water level | Read |
| BI 61 | Deaerator No Alarms Relay OK | Deaerator no-alarms relay OK | Read |
| BI 129 | Surge Tank No Alarms Relay OK | Surge tank no-alarms relay OK | Read |
Network setup
- BACnet Device Instance = the controller's Modbus Node-ID + Node_Offset (default 50,000), so Node-ID 1 = 50001. Change Node_Offset in the ProtoNode web configurator to pick other instances.
- The ProtoNode RER does BACnet MS/TP or BACnet IP, selected on its S bank DIP switches.
- BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on the A bank DIP switches; baud on B0-B3 (38400 factory default).
- BACnet IP: default ProtoNode address 192.168.1.24; change it in the web configurator.
Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 1 | Deaerator Lvl BAD QUALITY | Read | |||
| BI | 2 | Deaerator Lvl Hi | Read | |||
| BI | 3 | Deaerator Lvl Lo | Read | |||
| BI | 4 | Deaerator Lvl Lo-Lo (LWCO) | Read | |||
| BI | 5 | Feed Pump 1 Flt | Read | |||
| BI | 6 | Feed Pump 2 Flt | Read | |||
| BI | 7 | Feed Pump 3 Flt | Read | |||
| BI | 8 | Feed Pump 4 Flt | Read | |||
| BI | 9 | Feed Pump 5 Flt | Read | |||
| BI | 10 | Feed Pump 6 Flt | Read | |||
| BI | 11 | Feed Pump 1 OVERLOAD | Read | |||
| BI | 12 | Feed Pump 2 OVERLOAD | Read | |||
| BI | 13 | Feed Pump 3 OVERLOAD | Read | |||
| BI | 14 | Feed Pump 4 OVERLOAD | Read | |||
| BI | 15 | Feed Pump 5 OVERLOAD | Read | |||
| BI | 16 | Feed Pump 6 OVERLOAD | Read | |||
| BI | 17 | Spare | Read | |||
| BI | 18 | Spare | Read | |||
| BI | 19 | Spare | Read | |||
| BI | 20 | Deaerator Temp BAD QUALITY | Read | |||
| BI | 21 | Deaerator Temp Lo | Read | |||
| BI | 22 | Deaerator Temp Hi | Read | |||
| BI | 23 | Deaerator Pressure BAD QUALITY | Read | |||
| BI | 24 | Deaerator Pressure Lo | Read | |||
| BI | 25 | Deaerator Pressure Hi | Read | |||
| BI | 26 | Boiler Feed Wtr Header Pressure BQ | Read | |||
| BI | 27 | Boiler Feed Wtr Header Pressure Lo | Read | |||
| BI | 28 | Boiler Feed Wtr Header Pressure Hi | Read | |||
| BI | 29 | DAB1[1]12 | Read | |||
| BI | 30 | DAB1[1]13 | Read | |||
| BI | 31 | DAB1[1]14 | Read | |||
| BI | 32 | DAB1[1]15 | Read | |||
| BI | 33 | DAB1[2]0 | Read | |||
| BI | 34 | DAB1[2]1 | Read | |||
| BI | 35 | DAB1[2]2 | Read | |||
| BI | 36 | DAB1[2]3 | Read | |||
| BI | 37 | DAB1[2]4 | Read | |||
| BI | 38 | DAB1[2]5 | Read | |||
| BI | 39 | DAB1[2]6 | Read | |||
| BI | 40 | DAB1[2]7 | Read | |||
| BI | 41 | DAB1[2]8 | Read | |||
| BI | 42 | DAB1[2]9 | Read | |||
| BI | 43 | DAB1[2]10 | Read | |||
| BI | 44 | DAB1[2]11 | Read | |||
| BI | 45 | DAB1[2]12 | Read | |||
| BI | 46 | DAB1[2]13 | Read | |||
| BI | 47 | DAB1[2]14 | Read | |||
| BI | 48 | DAB1[2]15 | Read | |||
| BI | 49 | Feed Pump 1 ON | Read | |||
| BI | 50 | Feed Pump 2 ON | Read | |||
| BI | 51 | Feed Pump 3 ON | Read | |||
| BI | 52 | Feed Pump 4 ON | Read | |||
| BI | 53 | Feed Pump 5 ON | Read | |||
| BI | 54 | Feed Pump 6 ON | Read | |||
| BI | 55 | Feed Pump 1 In AUTO | Read | |||
| BI | 56 | Feed Pump 2 In AUTO | Read | |||
| BI | 57 | Feed Pump 3 In AUTO | Read | |||
| BI | 58 | Feed Pump 4 In AUTO | Read | |||
| BI | 59 | Feed Pump 5 In AUTO | Read | |||
| BI | 60 | Feed Pump 6 In AUTO | Read | |||
| BImin | 61 | Deaerator No Alarms Relay OK | Read | |||
| BI | 62 | YelLo Stack Light ON | Read | |||
| BI | 63 | Green Stack Light ON | Read | |||
| BI | 64 | Red Stack Light ON | Read | |||
| BI | 65 | Chemical Feed ON | Read | |||
| BI | 66 | Deaerator Feed Wtr Valve Open | Read | |||
| BI | 67 | Feed Pumps ALT MODE ON | Read | |||
| BI | 68 | DA Lo-Lo Wtr Cutoff Relay Energized | Read | |||
| BI | 69 | Deaerator 2nd Feed Wtr Valve Open | Read | |||
| BI | 70 | Boiler Feed Pump 1 FLo Flt | Read | |||
| BI | 71 | Boiler Feed Pump 2 FLo Flt | Read | |||
| BI | 72 | Boiler Feed Pump 3 FLo Flt | Read | |||
| BI | 73 | Boiler Feed Pump 4 FLo Flt | Read | |||
| BI | 74 | Boiler Feed Pump 5 FLo Flt | Read | |||
| BI | 75 | Boiler Feed Pump 6 FLo Flt | Read | |||
| BI | 76 | PLC Battery Lo Replace Battery | Read | |||
| BI | 77 | Feed Pump 1 VSD Speed Feedback Bad Q | Read | |||
| BI | 78 | Feed Pump 2 VSD Speed Feedback Bad Q | Read | |||
| BI | 79 | Feed Pump 3 VSD Speed Feedback Bad Q | Read | |||
| BI | 80 | Feed Pump 4 VSD Speed Feedback Bad Q | Read | |||
| BI | 81 | Feed Pump 5 VSD Speed Feedback Bad Q | Read | |||
| BI | 82 | Feed Pump 6 VSD Speed Feedback Bad Q | Read | |||
| BI | 83 | DAB1[5]2 | Read | |||
| BI | 84 | DAB1[5]3 | Read | |||
| BI | 85 | DAB1[5]4 | Read | |||
| BI | 86 | DAB1[5]5 | Read | |||
| BI | 87 | DAB1[5]6 | Read | |||
| BI | 88 | DAB1[5]7 | Read | |||
| BI | 89 | DAB1[5]8 | Read | |||
| BI | 90 | DAB1[5]9 | Read | |||
| BI | 91 | DAB1[5]10 | Read | |||
| BI | 92 | DAB1[5]11 | Read | |||
| BI | 93 | DAB1[5]12 | Read | |||
| BI | 94 | DAB1[5]13 | Read | |||
| BI | 95 | DAB1[5]14 | Read | |||
| BI | 96 | DAB1[5]15 | Read | |||
| BI | 97 | Surge Tank Lvl BAD QUALITY | Read | |||
| BI | 98 | Surge Tank Lvl Hi | Read | |||
| BI | 99 | Surge Tank Lvl Lo | Read | |||
| BI | 100 | Surge Tank Temp BAD QUALITY | Read | |||
| BI | 101 | Surge Tank Temp Lo | Read | |||
| BI | 102 | Surge Tank Temp Hi | Read | |||
| BI | 103 | Transfer Pump 1 Flt | Read | |||
| BI | 104 | Transfer Pump 2 Flt | Read | |||
| BI | 105 | Transfer Pump 3 Flt | Read | |||
| BI | 106 | Transfer Pump 1 OVERLOAD | Read | |||
| BI | 107 | Transfer Pump 2OVERLOAD | Read | |||
| BI | 108 | Transfer Pump 3OVERLOAD | Read | |||
| BI | 109 | Surge Tank Lo-Lo (LWCO) | Read | |||
| BI | 110 | Surge Tank Header Pressure Hi | Read | |||
| BI | 111 | Surge Tank Header Pressure Lo | Read | |||
| BI | 112 | Surge Tank Header Pressure BAD QUALITY | Read | |||
| BI | 113 | DAB1[7]0 | Read | |||
| BI | 114 | DAB1[7]1 | Read | |||
| BI | 115 | DAB1[7]2 | Read | |||
| BI | 116 | Surge 2nd Feed Wtr Valve Open | Read | |||
| BI | 117 | Transfer Pump 1 FLo Flt | Read | |||
| BI | 118 | Transfer Pump 2 FLo Flt | Read | |||
| BI | 119 | Transfer Pump 3 FLo Flt | Read | |||
| BI | 120 | Transfer Pump 1 VSD Speed Feedback BQ | Read | |||
| BI | 121 | Transfer Pump 2 VSD Speed Feedback BQ | Read | |||
| BI | 122 | Transfer Pump 3 VSD Speed Feedback BQ | Read | |||
| BI | 123 | DAB1[7]10 | Read | |||
| BI | 124 | DAB1[7]11 | Read | |||
| BI | 125 | DAB1[7]12 | Read | |||
| BI | 126 | DAB1[7]13 | Read | |||
| BI | 127 | DAB1[7]14 | Read | |||
| BI | 128 | DAB1[7]15 | Read | |||
| BImin | 129 | Surge Tank No Alarms Relay OK | Read | |||
| BI | 130 | YelLo Stack Light ON | Read | |||
| BI | 131 | Green Stack Light ON | Read | |||
| BI | 132 | RED Stack Light ON | Read | |||
| BI | 133 | Surge Tank Feed Wtr Valve Open | Read | |||
| BI | 134 | ST Lo Lo Wtr Cutoff Relay Energized | Read | |||
| BI | 135 | Transfer Pump 1 ON | Read | |||
| BI | 136 | Transfer Pump 2 ON | Read | |||
| BI | 137 | Transfer Pump 3 ON | Read | |||
| BI | 138 | Transfer Pump 1 In AUTO | Read | |||
| BI | 139 | Transfer Pump 2 In AUTO | Read | |||
| BI | 140 | Transfer Pump 3 In AUTO | Read | |||
| BI | 141 | Transfer Pumps ALT MODE ON | Read | |||
| BI | 142 | DAB1[8]13 | Read | |||
| BI | 143 | DAB1[8]14 | Read | |||
| BI | 144 | DAB1[8]15 | Read | |||
| BI | 145 | DAB1[9]0 | Read | |||
| BI | 146 | DAB1[9]1 | Read | |||
| BI | 147 | DAB1[9]2 | Read | |||
| BI | 148 | DAB1[9]3 | Read | |||
| BI | 149 | DAB1[9]4 | Read | |||
| BI | 150 | DAB1[9]5 | Read | |||
| BI | 151 | DAB1[9]6 | Read | |||
| BI | 152 | DAB1[9]7 | Read | |||
| BI | 153 | DAB1[9]8 | Read | |||
| BI | 154 | DAB1[9]9 | Read | |||
| BI | 155 | DAB1[9]10 | Read | |||
| BI | 156 | DAB1[9]11 | Read | |||
| BI | 157 | DAB1[9]12 | Read | |||
| BI | 158 | DAB1[9]13 | Read | |||
| BI | 159 | DAB1[9]14 | Read | |||
| BI | 160 | DAB1[9]15 | Read | |||
| AI | 1 | Feed Pump 1 Run Time | Modbus 30853 | Read | ||
| AI | 2 | Feed Pump 2 Run Time | Modbus 30855 | Read | ||
| AI | 3 | Feed Pump 3 Run Time | Modbus 30857 | Read | ||
| AI | 4 | Feed Pump 4 Run Time | Modbus 30859 | Read | ||
| AI | 5 | Feed Pump 5 Run Time | Modbus 30861 | Read | ||
| AI | 6 | Feed Pump 6 Run Time | Modbus 30863 | Read | ||
| AI | 7 | DAR1[6] | Modbus 30865 | Read | ||
| AI | 8 | DAR1[7] | Modbus 30867 | Read | ||
| AI | 9 | DAR1[8] | Modbus 30869 | Read | ||
| AI | 10 | Stop Lag Feed Pump Limit | Modbus 30871 | Read | ||
| AI | 11 | Alternate Feed Pumps | Modbus 30873 | Read | ||
| AI | 12 | Start Chemical Feed Time Delay | Modbus 30875 | Read | ||
| AI | 13 | Stop Chemical Feed Time Delay | Modbus 30877 | Read | ||
| AI | 14 | DAR1[14] | Modbus 30879 | Read | ||
| AImin | 15 | Deaerator Temp | Modbus 30881 | Read | ||
| AImin | 16 | Deaerator Tank Pressure | Modbus 30883 | Read | ||
| AImin | 17 | Deaerator Tank Wtr Lvl | Modbus 30885 | Read | ||
| AI | 18 | Deaerator Feed Wtr (MUV) Signal | Modbus 30887 | Read | ||
| AI | 19 | Deaerator Steam PRValve Signal | Modbus 30889 | Read | ||
| AImin | 20 | Boiler Feed Wtr Header Pressure | Modbus 30891 | Read | ||
| AI | 21 | Deaerator 2nd Feed Wtr (MUV) Signal | Modbus 30893 | Read | ||
| AI | 22 | Start Lag Feed Pump Limit | Modbus 30895 | Read | ||
| AI | 23 | DA Lvl - Pump Auto-Restart Lvl | Modbus 30897 | Read | ||
| AI | 24 | DAR1[24] | Modbus 30899 | Read | ||
| AI | 25 | DAR1[25] | Modbus 30901 | Read | ||
| AI | 26 | DAR1[26] | Modbus 30903 | Read | ||
| AI | 27 | DAR1[27] | Modbus 30905 | Read | ||
| AI | 28 | DAR1[28] | Modbus 30907 | Read | ||
| AI | 29 | DAR1[29] | Modbus 30909 | Read | ||
| AI | 30 | DAR1[30] | Modbus 30911 | Read | ||
| AI | 31 | DAR1[31] | Modbus 30913 | Read | ||
| AI | 32 | DAR1[32] | Modbus 30915 | Read | ||
| AI | 33 | DAR1[33] | Modbus 30917 | Read | ||
| AI | 34 | DAR1[34] | Modbus 30919 | Read | ||
| AI | 35 | DAR1[35] | Modbus 30921 | Read | ||
| AI | 36 | DAR1[36] | Modbus 30923 | Read | ||
| AI | 37 | DAR1[37] | Modbus 30925 | Read | ||
| AI | 38 | DAR1[38] | Modbus 30927 | Read | ||
| AI | 39 | Surge Header Pressure | Modbus 30929 | Read | ||
| AI | 40 | Surge Tank Temp | Modbus 30931 | Read | ||
| AImin | 41 | Surge Tank Wtr Lvl | Modbus 30933 | Read | ||
| AI | 42 | Surge Tank Feed Wtr (MUV) Signal | Modbus 30935 | Read | ||
| AI | 43 | Transfer Pump 1 Run Time | Modbus 30937 | Read | ||
| AI | 44 | Transfer Pump 2 Run Time | Modbus 30939 | Read | ||
| AI | 45 | Transfer Pump 3 Run Time | Modbus 30941 | Read | ||
| AI | 46 | Alternate Transfer Pumps | Modbus 30943 | Read | ||
| AI | 47 | Stop Transfer Lag Feed Pump Limit | Modbus 30945 | Read | ||
| AI | 48 | Surge Tank 2nd Feed Wtr (MUV) Signal | Modbus 30947 | Read | ||
| AI | 49 | Start Lag Feed Pump Limit | Modbus 30949 | Read | ||
| AI | 50 | Surge Lvl - Pump Auto-Restart Lvl | Modbus 30951 | Read | ||
| AI | 51 | DAR1[51] | Modbus 30953 | Read | ||
| AI | 52 | DAR1[52] | Modbus 30955 | Read | ||
| AI | 53 | DAR1[53] | Modbus 30957 | Read | ||
| AI | 54 | DAR1[54] | Modbus 30959 | Read | ||
| AI | 55 | DAR1[55] | Modbus 30961 | Read | ||
| AI | 56 | DAR1[56] | Modbus 30963 | Read | ||
| AI | 57 | DAR1[57] | Modbus 30965 | Read | ||
| AI | 58 | DAR1[58] | Modbus 30967 | Read | ||
| AI | 59 | DAR1[59] | Modbus 30969 | Read | ||
| AI | 60 | DAR1[60] | Modbus 30971 | Read | ||
| AI | 61 | DAR1[61] | Modbus 30973 | Read | ||
| AI | 62 | DAR1[62] | Modbus 30975 | Read | ||
| AI | 63 | DAR1[63] | Modbus 30977 | Read | ||
| AI | 64 | DAR1[64] | Modbus 30979 | Read | ||
| AI | 65 | DAR1[65] | Modbus 30981 | Read | ||
| AI | 66 | Feed Pump 1 LEAD/LAG Status | Modbus 30983 | Read | ||
| AI | 67 | Feed Pump 2 LEAD/LAG Status | Modbus 31159 | Read | ||
| AI | 68 | Feed Pump 3 LEAD/LAG Status | Modbus 31160 | Read | ||
| AI | 69 | Feed Pump 4 LEAD/LAG Status | Modbus 31161 | Read | ||
| AI | 70 | Feed Pump 5 LEAD/LAG Status | Modbus 31162 | Read | ||
| AI | 71 | Feed Pump 6 LEAD/LAG Status | Modbus 31163 | Read | ||
| AI | 72 | DAI1[6] | Modbus 31164 | Read | ||
| AI | 73 | DAI1[7] | Modbus 31165 | Read | ||
| AI | 74 | DAI1[8] | Modbus 31166 | Read | ||
| AI | 75 | DAI1[9] | Modbus 31167 | Read | ||
| AI | 76 | DAI1[10] | Modbus 31168 | Read | ||
| AI | 77 | DAI1[11] | Modbus 31169 | Read | ||
| AI | 78 | DAI1[12] | Modbus 31170 | Read | ||
| AI | 79 | DAI1[13] | Modbus 31171 | Read | ||
| AI | 80 | DAI1[14] | Modbus 31172 | Read | ||
| AI | 81 | DAI1[15] | Modbus 31173 | Read | ||
| AI | 82 | DAI1[16] | Modbus 31174 | Read | ||
| AI | 83 | DAI1[17] | Modbus 31175 | Read | ||
| AI | 84 | DAI1[18] | Modbus 31176 | Read | ||
| AI | 85 | DAI1[19] | Modbus 31177 | Read | ||
| AI | 86 | Transfer Pump 1 LEAD/LAG Status | Modbus 31178 | Read | ||
| AI | 87 | Transfer Pump 2 LEAD/LAG Status | Modbus 31179 | Read | ||
| AI | 88 | Transfer Pump 3 LEAD/LAG Status | Modbus 31180 | Read | ||
| AI | 89 | DAI1[23] | Modbus 31181 | Read | ||
| AI | 90 | DAI1[24] | Modbus 31182 | Read | ||
| AI | 91 | DAI1[25] | Modbus 31183 | Read | ||
| AI | 92 | DAI1[26] | Modbus 31184 | Read | ||
| AI | 93 | DAI1[27] | Modbus 31185 | Read | ||
| AI | 94 | DAI1[28] | Modbus 31186 | Read | ||
| AI | 95 | DAI1[29] | Modbus 31187 | Read | ||
| AI | 96 | DAI1[30] | Modbus 31188 | Read | ||
| AI | 97 | DAI1[31] | Modbus 31189 | Read | ||
| AI | 98 | DAI1[32] | Modbus 31190 | Read | ||
| AI | 99 | DAI1[33] | Modbus 31191 | Read | ||
| AI | 100 | DAI1[34] | Modbus 31192 | Read | ||
| AI | 101 | DAI1[35] | Modbus 31193 | Read | ||
| AI | 102 | DAI1[36] | Modbus 31194 | Read | ||
| AI | 103 | DAI1[37] | Modbus 31195 | Read | ||
| AI | 104 | DAI1[38] | Modbus 31196 | Read | ||
| AI | 105 | DAI1[39] | Modbus 31197 | Read |
No points match these filters.
Object ID lookup: Cleaver-Brooks ADAC deaerator / surge tank control point IDs by name
BI1Deaerator Lvl BAD QUALITYBI2Deaerator Lvl HiBI3Deaerator Lvl LoBI4Deaerator Lvl Lo-Lo (LWCO)BI5Feed Pump 1 FltBI6Feed Pump 2 FltBI7Feed Pump 3 FltBI8Feed Pump 4 FltBI9Feed Pump 5 FltBI10Feed Pump 6 FltBI11Feed Pump 1 OVERLOADBI12Feed Pump 2 OVERLOADBI13Feed Pump 3 OVERLOADBI14Feed Pump 4 OVERLOADBI15Feed Pump 5 OVERLOADBI16Feed Pump 6 OVERLOADBI17SpareBI18SpareBI19SpareBI20Deaerator Temp BAD QUALITYBI21Deaerator Temp LoBI22Deaerator Temp HiBI23Deaerator Pressure BAD QUALITYBI24Deaerator Pressure LoBI25Deaerator Pressure HiBI26Boiler Feed Wtr Header Pressure BQBI27Boiler Feed Wtr Header Pressure LoBI28Boiler Feed Wtr Header Pressure HiBI29DAB1[1]12BI30DAB1[1]13BI31DAB1[1]14BI32DAB1[1]15BI33DAB1[2]0BI34DAB1[2]1BI35DAB1[2]2BI36DAB1[2]3BI37DAB1[2]4BI38DAB1[2]5BI39DAB1[2]6BI40DAB1[2]7BI41DAB1[2]8BI42DAB1[2]9BI43DAB1[2]10BI44DAB1[2]11BI45DAB1[2]12BI46DAB1[2]13BI47DAB1[2]14BI48DAB1[2]15BI49Feed Pump 1 ONBI50Feed Pump 2 ONBI51Feed Pump 3 ONBI52Feed Pump 4 ONBI53Feed Pump 5 ONBI54Feed Pump 6 ONBI55Feed Pump 1 In AUTOBI56Feed Pump 2 In AUTOBI57Feed Pump 3 In AUTOBI58Feed Pump 4 In AUTOBI59Feed Pump 5 In AUTOBI60Feed Pump 6 In AUTOBI61Deaerator No Alarms Relay OKBI62YelLo Stack Light ONBI63Green Stack Light ONBI64Red Stack Light ONBI65Chemical Feed ONBI66Deaerator Feed Wtr Valve OpenBI67Feed Pumps ALT MODE ONBI68DA Lo-Lo Wtr Cutoff Relay EnergizedBI69Deaerator 2nd Feed Wtr Valve OpenBI70Boiler Feed Pump 1 FLo FltBI71Boiler Feed Pump 2 FLo FltBI72Boiler Feed Pump 3 FLo FltBI73Boiler Feed Pump 4 FLo FltBI74Boiler Feed Pump 5 FLo FltBI75Boiler Feed Pump 6 FLo FltBI76PLC Battery Lo Replace BatteryBI77Feed Pump 1 VSD Speed Feedback Bad QBI78Feed Pump 2 VSD Speed Feedback Bad QBI79Feed Pump 3 VSD Speed Feedback Bad QBI80Feed Pump 4 VSD Speed Feedback Bad QBI81Feed Pump 5 VSD Speed Feedback Bad QBI82Feed Pump 6 VSD Speed Feedback Bad QBI83DAB1[5]2BI84DAB1[5]3BI85DAB1[5]4BI86DAB1[5]5BI87DAB1[5]6BI88DAB1[5]7BI89DAB1[5]8BI90DAB1[5]9BI91DAB1[5]10BI92DAB1[5]11BI93DAB1[5]12BI94DAB1[5]13BI95DAB1[5]14BI96DAB1[5]15BI97Surge Tank Lvl BAD QUALITYBI98Surge Tank Lvl HiBI99Surge Tank Lvl LoBI100Surge Tank Temp BAD QUALITYBI101Surge Tank Temp LoBI102Surge Tank Temp HiBI103Transfer Pump 1 FltBI104Transfer Pump 2 FltBI105Transfer Pump 3 FltBI106Transfer Pump 1 OVERLOADBI107Transfer Pump 2OVERLOADBI108Transfer Pump 3OVERLOADBI109Surge Tank Lo-Lo (LWCO)BI110Surge Tank Header Pressure HiBI111Surge Tank Header Pressure LoBI112Surge Tank Header Pressure BAD QUALITYBI113DAB1[7]0BI114DAB1[7]1BI115DAB1[7]2BI116Surge 2nd Feed Wtr Valve OpenBI117Transfer Pump 1 FLo FltBI118Transfer Pump 2 FLo FltBI119Transfer Pump 3 FLo FltBI120Transfer Pump 1 VSD Speed Feedback BQBI121Transfer Pump 2 VSD Speed Feedback BQBI122Transfer Pump 3 VSD Speed Feedback BQBI123DAB1[7]10BI124DAB1[7]11BI125DAB1[7]12BI126DAB1[7]13BI127DAB1[7]14BI128DAB1[7]15BI129Surge Tank No Alarms Relay OKBI130YelLo Stack Light ONBI131Green Stack Light ONBI132RED Stack Light ONBI133Surge Tank Feed Wtr Valve OpenBI134ST Lo Lo Wtr Cutoff Relay EnergizedBI135Transfer Pump 1 ONBI136Transfer Pump 2 ONBI137Transfer Pump 3 ONBI138Transfer Pump 1 In AUTOBI139Transfer Pump 2 In AUTOBI140Transfer Pump 3 In AUTOBI141Transfer Pumps ALT MODE ONBI142DAB1[8]13BI143DAB1[8]14BI144DAB1[8]15BI145DAB1[9]0BI146DAB1[9]1BI147DAB1[9]2BI148DAB1[9]3BI149DAB1[9]4BI150DAB1[9]5BI151DAB1[9]6BI152DAB1[9]7BI153DAB1[9]8BI154DAB1[9]9BI155DAB1[9]10BI156DAB1[9]11BI157DAB1[9]12BI158DAB1[9]13BI159DAB1[9]14BI160DAB1[9]15AI1Feed Pump 1 Run TimeAI2Feed Pump 2 Run TimeAI3Feed Pump 3 Run TimeAI4Feed Pump 4 Run TimeAI5Feed Pump 5 Run TimeAI6Feed Pump 6 Run TimeAI7DAR1[6]AI8DAR1[7]AI9DAR1[8]AI10Stop Lag Feed Pump LimitAI11Alternate Feed PumpsAI12Start Chemical Feed Time DelayAI13Stop Chemical Feed Time DelayAI14DAR1[14]AI15Deaerator TempAI16Deaerator Tank PressureAI17Deaerator Tank Wtr LvlAI18Deaerator Feed Wtr (MUV) SignalAI19Deaerator Steam PRValve SignalAI20Boiler Feed Wtr Header PressureAI21Deaerator 2nd Feed Wtr (MUV) SignalAI22Start Lag Feed Pump LimitAI23DA Lvl - Pump Auto-Restart LvlAI24DAR1[24]AI25DAR1[25]AI26DAR1[26]AI27DAR1[27]AI28DAR1[28]AI29DAR1[29]AI30DAR1[30]AI31DAR1[31]AI32DAR1[32]AI33DAR1[33]AI34DAR1[34]AI35DAR1[35]AI36DAR1[36]AI37DAR1[37]AI38DAR1[38]AI39Surge Header PressureAI40Surge Tank TempAI41Surge Tank Wtr LvlAI42Surge Tank Feed Wtr (MUV) SignalAI43Transfer Pump 1 Run TimeAI44Transfer Pump 2 Run TimeAI45Transfer Pump 3 Run TimeAI46Alternate Transfer PumpsAI47Stop Transfer Lag Feed Pump LimitAI48Surge Tank 2nd Feed Wtr (MUV) SignalAI49Start Lag Feed Pump LimitAI50Surge Lvl - Pump Auto-Restart LvlAI51DAR1[51]AI52DAR1[52]AI53DAR1[53]AI54DAR1[54]AI55DAR1[55]AI56DAR1[56]AI57DAR1[57]AI58DAR1[58]AI59DAR1[59]AI60DAR1[60]AI61DAR1[61]AI62DAR1[62]AI63DAR1[63]AI64DAR1[64]AI65DAR1[65]AI66Feed Pump 1 LEAD/LAG StatusAI67Feed Pump 2 LEAD/LAG StatusAI68Feed Pump 3 LEAD/LAG StatusAI69Feed Pump 4 LEAD/LAG StatusAI70Feed Pump 5 LEAD/LAG StatusAI71Feed Pump 6 LEAD/LAG StatusAI72DAI1[6]AI73DAI1[7]AI74DAI1[8]AI75DAI1[9]AI76DAI1[10]AI77DAI1[11]AI78DAI1[12]AI79DAI1[13]AI80DAI1[14]AI81DAI1[15]AI82DAI1[16]AI83DAI1[17]AI84DAI1[18]AI85DAI1[19]AI86Transfer Pump 1 LEAD/LAG StatusAI87Transfer Pump 2 LEAD/LAG StatusAI88Transfer Pump 3 LEAD/LAG StatusAI89DAI1[23]AI90DAI1[24]AI91DAI1[25]AI92DAI1[26]AI93DAI1[27]AI94DAI1[28]AI95DAI1[29]AI96DAI1[30]AI97DAI1[31]AI98DAI1[32]AI99DAI1[33]AI100DAI1[34]AI101DAI1[35]AI102DAI1[36]AI103DAI1[37]AI104DAI1[38]AI105DAI1[39]
Integration notes
- Each Cleaver-Brooks controller on the ProtoNode is its own BACnet device; the object instances below are the same on every device.
- The profile has only AI and BI objects and the guide marks none as write points, so all are read-only.
- The guide gives no engineering units or state texts; units appear only where the object name carries them (DEG F / DEG C).
- Where a description is filled in, it gives the register from the guide's Modbus column.
- Objects named DAR1[..] or DAI1[..] are spare tags in the profile with no stated use.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ADAC deaerator / surge tank control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)
How many BACnet points does the Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) have?
This list has 265 BACnet objects: 105 analog inputs, 160 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode) BACnet documentation?
Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.
What are the minimum BACnet points to integrate the Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)?
Start with AI 16 Deaerator Tank Pressure (Deaerator tank pressure); AI 17 Deaerator Tank Wtr Lvl (Deaerator tank water level); AI 15 Deaerator Temp (Deaerator temperature); AI 20 Boiler Feed Wtr Header Pressure (Boiler feedwater header pressure); AI 41 Surge Tank Wtr Lvl (Surge tank water level); BI 61 Deaerator No Alarms Relay OK (Deaerator no-alarms relay OK); BI 129 Surge Tank No Alarms Relay OK (Surge tank no-alarms relay OK).
How do I check these points on the real ADAC deaerator / surge tank control (ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Cleaver-Brooks BACnet points lists
- Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
Cleaver-Brooks deaerator and surge tank packages with the ADAC 1000 PLC control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: ADAC 1000, ADAC_1000, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB120 flame safeguard (ProtoNode)
Cleaver-Brooks boilers with the CB120 flame safeguard, read through a ProtoNode RER gateway.
Also known as: CB120, CB 120, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB780 flame safeguard with expanded annunciator (ProtoNode)
Cleaver-Brooks boilers with the CB780 burner management control and expanded annunciator, read through a ProtoNode RER gateway.
Also known as: CB780, CB 780, CB780E, ProtoNode RER, 750-426 - Hot water boiler control via BACnet gateway
Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)
Cleaver-Brooks hot water boilers with the Falcon hydronic burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Hydronic, ClearFire Falcon, CB Falcon, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Falcon Steam boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Falcon steam burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Steam, CB Falcon steam, ProtoNode RER, 750-426 - Boiler flame safeguard and fuel-air ratio control via BACnet gateway
Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)
Cleaver-Brooks boilers with a CB780/CB783 burner control and FARC fuel-air ratio control, read through a ProtoNode RER gateway.
Also known as: FARC, CB 780/783, CB783, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 1000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 1000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 1000, CB Hawk 1000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 2000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 2000, CB Hawk 2000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 4000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 4000, CB Hawk 4000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 V2 boiler control (ProtoNode)
Cleaver-Brooks boilers with the HAWK 4000 V2 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: HAWK 4000 V2, CB HAWK 4000 V2, HAWK_4000_V2, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4500 boiler control (ProtoNode, EtherNet/IP)
Cleaver-Brooks boilers with the Hawk 4500 PLC boiler control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: Hawk 4500, CB Hawk 4500, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Hawk 5000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 5000, CB Hawk 5000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk ICS boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk ICS control, read through a ProtoNode RER gateway.
Also known as: Hawk ICS, CB ICS, ProtoNode RER, 750-426 - Boiler lead/lag master panel via BACnet gateway
Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode)
Cleaver-Brooks Hawk Master Panels sequencing up to eight Hawk boilers (A-H), read through a ProtoNode RER gateway.
Also known as: Hawk Master Panel, Hawk Master, CB Master Panel, ProtoNode RER, 750-426 - Boiler interface module via BACnet gateway
Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)
Cleaver-Brooks HSC boiler interface modules (one boiler each), read through a ProtoNode RER gateway.
Also known as: Boiler Interface Module, HSC Boiler Interface, BIM, ProtoNode RER, 750-426 - Multi-boiler sequencer (hot water boiler plant) via BACnet gateway
Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)
Cleaver-Brooks HSC panels sequencing up to 10 condensing and 10 non-condensing boilers, read through a ProtoNode RER gateway.
Also known as: HSC, Hydronic System Controller, CB HSC, ProtoNode RER, 750-426 - Pump interface module (boiler plant pumps) via BACnet gateway
Cleaver-Brooks HSC Pump Interface Module (ProtoNode)
Cleaver-Brooks HSC pump interface modules (up to four system pumps), read through a ProtoNode RER gateway.
Also known as: Pump Interface Module, HSC Pump Interface, ProtoNode RER, 750-426 - Boiler water level controller via BACnet gateway
Cleaver-Brooks LCS Level Control System (ProtoNode)
Cleaver-Brooks LCS water level controllers (one or two tanks), read through a ProtoNode RER gateway.
Also known as: LCS, Level Control System, ProtoNode RER, 750-426 - Boiler feed pump controller via BACnet gateway
Cleaver-Brooks PCS Pump Control System (ProtoNode)
Cleaver-Brooks PCS pump controllers (up to four pumps on header pressure or tank level), read through a ProtoNode RER gateway.
Also known as: PCS, Pump Control System, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 100 power meter profile (ProtoNode)
Shark 100 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 100, Electro Industries Shark 100, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 200 power meter profile (ProtoNode)
Shark 200 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 200, Electro Industries Shark 200, ProtoNode RER, 750-426 - Process loop controller via BACnet gateway
Cleaver-Brooks UDC 2500 loop controller profile (ProtoNode)
Honeywell UDC 2500 loop controllers supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: UDC 2500, UDC2500, Honeywell UDC 2500, ProtoNode RER, 750-426
Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.